CURRENT TRANSFORMER(CT)
Polarity Test:
Reference Forward
OC 6635 /1/4/16 OC 6635 /1/5/16 OC 6635 /1/6/16
1s1 - 1s3 OK OK OK
2s1 - 2s3 OK OK OK
3s1 - 3s3 OK OK OK
Ratio Test:
Applied Current: 200 A Measured Sec. in values A
Sl no C1 C2 C3
OC 6635 /1/4/16 1.009 1.010 1.010
OC 6635 /1/5/16 0.999 1.005 1.005
OC 6635 /1/6/16 0.998 1.003 1.003