You are on page 1of 4

SHORT CIRCUIT CALCULATION MRB1

*From Transformer to MDPP:

(Transformer KVa) x 1000 225 x 1000 =


IFLA = = = 324.7690A
EL-N x 1.732 400 x 1.732

*Transformer Multiplier:

100 100
M= = = 92.5926
0.9 (Worst Case) x %Z 0.9 x 1.12

*Three Phase Short Circuit at Transformer Secondary

ISCA (L-N) = Transformer FLA x Multiplier


= 324.7690 x 92.5926
ISCA (L-N) = 30, 071.2061 A

* Calculate for the "F " Factor:

1.732 x L x I3Ø 1.732 x 65.6168 x 30, 071.2061


f= =
C x n x EL-N 20566 x 2 x 400
f = 0.2077

*Multiplier :

1 1
M= = = 0.8280
1+f 1 + 0.2077

*Three Phase Short Circuit at Fault MDPP:

ISCA (MDPP) = ISCA(L-L) x Multiplier


= 52,297.7542 x 0.2077
ISCA (MDPP) = 10,862.2435 A
*Motor Contribution (All Floors)

ISCA (Motors) = 1247.7 x 4


ISCA (Motors) = 4,990.8 A

*Total Short Circuit Current

Total SCC = 10,862.2435 A + 4,990.8 A


Total SCC = 15,853.0432 A
Use : 42 KAIC
SHORT CIRCUIT CALCULATION MRB2
*From Transformer to MDPP:
(Transformer
(Transformer KVa)
KVa) x 1000
x 1000 300
300 x 1000
x 1000
IFLA
FLA = == == 433.0254
433.0254 A
A EL-N x 1.732 400 x 1.732
EL-N x 1.732 400 x 1.732

*Transformer Multiplier:
100 100
M= = = 100.1001
0.9 (Worst Case) x %Z 0.9 x 1.12

*Three Phase Short Circuit at Transformer Secondary


ISCA (L-N) = Transformer FLA x Multiplier
= 433.0254 x 100.1001
ISCA (L-N) = 43,345.8858 A

* Calculate for the "F " Factor:


1.732 x L x Isc3Ø 1.732 x 65.6168 x 43,345.8858
f= =
C x n x EL-N 20566 x 2 x 400
f = 0.2994

*Multiplier :
1 1
M= = = 0.7696
1+f 1 + 0.2994

*Three Phase Short Circuit at Fault MDPP:


ISCA (MDPP) = ISCA(L-L) x Multiplier
= 43,345.8858 x 0.7696
ISCA (MDPP) = 33,358.9937 A
*Motor Contribution (All Floors)
ISCA (Motors) = 2702.58 x 4
ISCA (Motors) = 10,810.32 A

*Total Short Circuit Current


Total SCC = 33,358.9937 A + 10,810.32 A
Total SCC = 44,169.3187 A
Use : 65 KAIC