ADVANCE VENTILATION PVT. LTD.
Project
REVISION HISTORY
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 02 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
SEL-2/ SEL-3 SELECTION BLOCK FOR WORKING STANDBY ALONG WITH AUTOCHANGEOVER
PV PROCESS VARIABLE
SP SET POINT
ZT FEEDBACK
TR TRACK
O/P OUTPUT
I INTERFACE VALUE
M MAIN VALUE
OR OR LOGIC GATE
AooB A out of B
2oo3 2 out of 3
PERM PERMISSIVE
WT WAIT TIME
Delay = XX sec On Delay Timer ( All timer used in this logic are on delay type)
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 03 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
P&I DIAGRAM FOR WATER COOLED CONDENSING UNIT FOR ESP CONTROL
1 DP-16004-XG02-90SAR01-111001
BUILDING
WRITE UP & CONTROL PHILOSOPHY FOR A/C SYSTEM FOR CCB, ESP control
3 building # 1 & 2 AND DM PLANT BUILDING (INCL. CHEMICAL STORAGE & CPU DP16004‐XS00‐90SAA‐111001
REGEN.)
NOTE: (1) SAME AC LOGIC SHALL BE APPLICABLE FOR PRECISION AC OF ESP CONTROL BUILDING UNIT#2.
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 04 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
3 3
SEL-2
CT-2,FAN Standby Mode
4 DDCMIS 4
10SAR01AN502
Note:- The Configuration 1 X 100%
5 configuration and Autochangeover to be 5
DDCMIS SOFT SELECTION CT-2,FAN ( Main Selected) CT-2,FAN Working Mode Selected taken care.
6 DDCMIS 6
SIGNAL 10SAR01AN502
7 7
11 11
SEL-2
CDWP-2 Standby Mode
12 12
10SAR01AP002 DDCMIS
13 Note:- The Configuration 1 X 100% 13
configuration and Autochangeover to be
DDCMIS SOFT SELECTION CDWP-2 ( Main Selected) CDWP-2 Working Mode Selected taken care.
14 DDCMIS 14
SIGNAL 10SAR01AP002 10SAR01AP002
15 15
17 17
19 19
SEL-2
PAC-2 Standby Mode
20 20
10SAR01AN002 DDCMIS
Note:- The Configuration 1 X 100%
21 21
configuration and Autochangeover to be
DDCMIS SOFT SELECTION PAC-2(Main Selected) PAC-2 Working Mode Selected taken care.
22 DDCMIS 22
SIGNAL 10SAR01AN002 10SAR01AN002
23 23
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 05 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
1 1
START
3 NOT 3
4 4
OR
CLOSE ALL FIRE DAMPER OF AC
5 11 SHEET 06 DDCMIS SOFT SIGNAL FIRE IN ESP BUILDING 08 SHEET 09 5
SYSTEM
STOP
6 6
7 7
8 8
9 9
10 10
05 SHEET 06
05 SHEET 09
FIRE SIGNAL
11 FIELD FEEDBACK FIRE IN ESP BUILDING 11 SHEET 09 11
90AYE19GH001_XG61
05 SHEET 19a
11 SHEET 19a
12 12
FIRE ALARM
13 DDCMIS ANNUNCIATION 13
The same logic shall be applicable for following Fire Dampers. (Fire in ESP Building)
1) FIRE DMPR-1 ------- 10SAR01AA501
2)FIRE DMPR-2 ------ 10SAR01AA502
14 14
15 15
16 16
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 06 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
STEP-1
1 DDCMIS DDCMIS SOFT SIGNAL (AUTO START COMMAND FROM AUTO ON 1
HMI FOR SEQUENCE START)
2 N/A MANUAL ON 2
3 3
OPEN
4 4
PERMISSIVE
OPEN CT-1, I/L VLV
5 FIELD COMMAND 5
10SAR01AA001_YB01
6 6
9 9
CLOSE
10 10
PROTECTION
OFF
CT-1,FAN RUN FBK
10 FIELD FEEDBACK DELA 10
10SAR01AN501_XB01
Y-5s
OR
12
* The same logic shall be applicable for following CT Inlet Valves.
12
S.No DESCRIPTION TAG NO.
14 14
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 07 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
2 2
3 3
5 5
6 6
AND
7 7
8 8
9 9
11 11
12 12
13 13
14 14
CLOSE FEEDBACK FIRE DMPR1 Any Fire Damper Closed (All Fire
15 FIELD Feedback 10 SHEET 14 15
10SAR01AA501_XB02 Damper not Opened)
16 16
17 17
OR
18 18
19 19
21 21
22 22
23 23
24 24
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 08 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
3 OPEN 3
4 4
OPEN/CLOSE
6 6
05 SHEET 06 DDCMIS SOFT SIGNAL CLOSE ALL FIRE DAMPER OF AC SYSTEM AUTO OFF
8 8
9 CLOSE 9
10 10
PROTECTION
FIRE IN ESP BUILDING
11 SHEET 06 DDCMIS SOFT SIGNAL
11 11
12 12
* The same logic shall be applicable for following Fire Damper.
13 13
14 14
21 NOTE: THE OPEN COMMAND FOR DAMPER WILL BE OF CONTINOUS TYPE AND DAMPER WILL CLOSE ON REMOVAL OF OPEN COMMAND. 21
22 22
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 09 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
LINE SOURCE TYPE OF INPUT INPUTS START SEQUENCE OUTPUTS DEST. LINE
1 1
2 2
STEP-1
(AUTO START COMMAND FROM HMI FOR
3 DDCMIS DDCMIS SOFT SIGNAL 3
SEQUENCE START)
4 4
6 6
9 NEXT MT: 90Sec WT: 10Sec CMD CDWP-1 AUTO START 01 SHEET 16 9
10 10
13 NEXT MT: 90Sec WT: 10Sec CMD PAC-1 AUTO START 01 SHEET 14 13
18 18
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 10 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
3 3
4 4
8 8
START
PERMISSIVE
AND
CT-1,FAN MCC DIST FBK
9 FIELD FEEDBACK NOT 9
10SAR01AN501_XB48
10 10
11 15 SHEET 12 DDCMIS SOFT SIGNAL CT-1 TANK WATER LEVEL LOW NOT 11
12 12
14 14
15 DDCMIS DDCMIS SOFT COMMAND MANUAL STOP FROM HMI OF AHU ROOM MANUAL OFF 15
STEP-3
16 12 SHEET 18 DDCMIS SOFT COMMAND SEQUENCE OFF 16
(CT-1, FAN AUTO STOP)
17 17
23 23
25 25
26 26
27 27
* The same logic shall be applicable for following CT.
28 28
1) CT-1,FAN ---- TAG NO (10SAR01AN502).
29 29
30 30
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 11 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
1 1
CT-1, FAN RUN FBK
Delay=
2 FIELD FEEDBACK 10SAR01AN501_XB01 NOT 2
10 sec
6 6
8 8
TT AT HEADER OF CONDENSER WATER
FROM PAC TO COOLING TOWER HEADER TEMPERATURE OF CONDENSER
10SAR01CT002_XQ01 Setpoint= 38 DEGREE C DDCMIS ANNUNCIATION 9
WATER FROM PAC TO COOLING TOWER
9 FIELD FEEDBACK
11 11
FS AT CNDSR WTR O/L OF PAC-2
10SAR01CF082_XG01
LOW WATER FLOW AT CNDSR WTR O/L OF
12 FIELD FEEDBACK Setpoint=7CMH DDCMIS ANNUNCIATION 12
PAC-2
13 13
CT TANK-1 LT
CT-1 TANK WATER LEVEL LOW
14 FIELD FEEDBACK 10SAR01CL001_XQ01 LVM < 350 mmWC DDCMIS ANNUNCIATION 14
CT TANK-2 LT
16 FIELD FEEDBACK LVM < 350 mmWC CT-2 TANK WATER LEVEL LOW DDCMIS ANNUNCIATION 16
10SAR01CL002_XQ01
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 12 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
1 1
3 3
5 5
7 7
9 9
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 13 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
STEP-3
1 13 SHEET 10 DDCMIS SOFT SIGNAL DELAY-10s SEQUENCE ON 1
(PAC-1 AUTO START)
2 DDCMIS DDCMIS SOFT COMMAND MANUAL START FROM HMI OF AHU ROOM MANUAL ON 2
OR
AND
PERMISSIVE
OR
7 7
STEP-1
9 5 SHEET 18 DDCMIS SOFT COMMAND SEQUENCE OFF 9
(PAC-1 AUTO STOP)
STOP
11 11
PROTECTION
14 14
The same logic shall be applicable for following PAC.
15 1) PAC-2 ----- TAG NO. (10SAR01AN002). 15
16 16
17 17
18 18
20 20
Rev. 00
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 14 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
1 1
6 6
7 7
9 9
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 15 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
STEP-2
1 09 SHEET 10 DDCMIS SOFT SIGNAL DELAY-10s SEQUENCE ON 1
(CDWP-1 AUTO START)
2 DDCMIS DDCMIS SOFT COMMAND MANUAL START FROM HMI OF AHU ROOM MANUAL ON 2
3 3
4 4
OR
START
7 7
PERMISSIVE
CDWP-1 MCC DIST FBK AND
8 FIELD FEEDBACK NOT 8
10SAR01AP001_XB48
9 9
FIRE SIGNAL
10 FIELD FEEDBACK NOT 10
90AYE19GH001_XG61
11 11
13 13
14 DDCMIS DDCMIS SOFT COMMAND MANUAL STOP FROM HMI OF AHU ROOM MANUAL OFF 14
STEP-2
15 09 SHEET 18 DDCMIS SOFT COMMAND SEQUENCE OFF 15
(CDWP-1 AUTO STOP)
PROTECTION
19 19
OR
03 SHEET 17 CDWP-1 STOP CMD
20 COMMAND CDWP-1 FAILED TO START FIELD COMMAND 20
10SAR01AP001_YB02
21 21
FIRE SIGNAL
22 FIELD FEEDBACK 22
90AYE19GH001_XG61
24 24
25 25
* The same logic shall be applicable for following CDWP.
26 26
1) CDWP-2 ---- TAG NO (10SAR01AP002).
27 27
28 28
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 16 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
LINE SOURCE TYPE OF INPUT INPUTS DDCMIS LOGIC FOR CONDENSER WATER PUMP OUTPUTS DEST. LINE
1 1
6 6
10 10
11 11
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 17 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
LINE SOURCE TYPE OF INPUT INPUTS STOP SEQUENCE OUTPUTS DEST. LINE
1 1
2 2
STEP-1
(AUTO STOP COMMAND FROM HMI FOR
3 DDCMIS DDCMIS SOFT SIGNAL 3
STOP SEQUENCE)
4 4
6 6
9 NEXT MT: 90Sec WT: 10Sec CMD CDWP-1 AUTO STOP 15 SHEET 16 9
10 10
13 13
16 16
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 18 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
STEP-2
1 09 SHEET 10 DDCMIS SOFT SIGNAL AUTO ON 1
(Working CDWP Valve to be opened)
2 N/A MANUAL ON 2
3 3
OPEN
4 4
PERMISSIVE
OPEN CDWP-1, O/L VLV
5 FIELD COMMAND 5
10SAR01AA003_YB01
6 6
9 9
CLOSE
10 10
PROTECTION
AND
12
* The same logic shall be applicable for following Condenser Water Pump O/L Valves.
12
S.No DESCRIPTION TAG NO.
14 14
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 19 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
2 N/A MANUAL ON 2
3 3
4 OPEN 4
9 9
OFF CLOSE
PAC-1 RUN FBK
10 FIELD FEEDBACK DELAY- 10
10SAR01AN001_XB01
5s PROTECTION
11 11
AND
PAC-1 STOP FBK
12 FIELD FEEDBACK 12
10SAR01AN001_XB02
The same logic shall be applicable for following FIRE DAMPER( DISCH. OF PAC).
13 13
1)FIRE DMPR-4 ( DISCH. OF PAC-2) ------ 10SAR01AA402
14 14
NOTE: THE OPEN COMMAND FOR DAMPER WILL BE OF CONTINOUS TYPE AND DAMPER WILL CLOSE ON REMOVAL OF OPEN COMMAND.
21 21
22 22
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 20 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
SINGLE LINE FLOW DIAGRAM FOR UAF UNIT FOR ESP CONTROL BUILDING FOR
1 DP-16004-XG08-90SAR-111001
UNIT-1 & 2.
WRITE UP & CONTROL PHILOSOPHY FOR A/C SYSTEM FOR CCB, ESP control
3 building # 1 & 2 AND DM PLANT BUILDING (INCL. CHEMICAL STORAGE & CPU DP16004‐XS00‐90SAA‐111001
REGEN.)
NOTE: (1) SAME VENTILATION LOGIC SHALL BE APPLICABLE FOR UAF OF ESP CONTROL BUILDING UNIT#2.
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 21 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
3 3
SEL-2
UAF-1, PUMP-2 Standby Mode
4 4
10SAR01AP101
DDCMIS
5 Note:- The Configuration 1 X 100% configuration and 5
Autochangeover to be taken care.
7 7
8
9 9
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 22 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
1 1
START
3 NOT 3
4 4
OR
5 11 SHEET 22 DDCMIS SOFT SIGNAL FIRE IN ESP BUILDING CLOSE ALL FIRE DAMPERS 08 SHEET 24 5
STOP
6 6
7 7
8 8
9 9
10 10
05 SHEET 22
FIRE SIGNAL
11 FIELD FEEDBACK FIRE IN ESP BUILDING 05 SHEET 24 11
90AYE19GH001_XG61
11 SHEET 24
12 12
FIRE ALARM
13 DDCMIS ANNUNCIATION 13
(Fire in ESP Building)
14 14
15 15
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 23 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
2 2
7 7
8 8
9 9
10 10
11 11
CLOSE FEEDBACK FIRE DMPR6 Any Fire Damper Closed (All Fire
FIELD Feedback 18 SHEET 26
10SAR01AA506_XB02 Damper not Opened)
13 13
16 16
17 17
18 18
19 19
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 24 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
3 OPEN 3
4 4
OPEN/CLOSE
6 6
9 CLOSE 9
10 10
PROTECTION
FIRE IN ESP BUILDING
11 SHEET 22 DDCMIS SOFT SIGNAL
11 11
12 12
* The same logic shall be applicable for following Fire Dampers.
13 S.No DESCRIPTION TAG NO. 13
21 NOTE: THE OPEN COMMAND FOR DAMPER WILL BE OF CONTINOUS TYPE AND DAMPER WILL CLOSE ON REMOVAL OF OPEN COMMAND. 21
22 22
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 25 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
LINE SOURCE TYPE OF INPUT INPUTS START SEQUENCE OUTPUTS DEST. LINE
1 1
2 2
STEP-1
(AUTO START COMMAND FROM HMI FOR
3 DDCMIS DDCMIS SOFT SIGNAL 3
SEQUENCE START)
4 4
6 6
9 NEXT MT: 90Sec WT: 10Sec CMD UAF-1, PUMP-1 AUTO START 01 SHEET 29 9
10 10
14 14
18 18
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 26 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
3 3
4 4
7 7
8 8
START
PERMISSIVE
AND
UAF-1,FAN MCC DIST FBK
9 FIELD FEEDBACK NOT 9
10SAR01AN003_XB48
10 10
11 09 SHEET 27 DDCMIS SOFT SIGNAL UAF-1, TANK WATER LEVEL LOW NOT 11
12 12
14 14
15 DDCMIS DDCMIS SOFT COMMAND MANUAL STOP FROM HMI OF AHU ROOM MANUAL OFF 15
STEP-2
16 09 SHEET 31 DDCMIS SOFT COMMAND SEQUENCE OFF 16
(UAF-1,FAN AUTO STOP)
17 17
18 13 SHEET 23 DDCMIS SOFT SIGNAL Any Fire Damper Closed (All Fire Damper not Opened) 18
23 23
25 25
26 26
27 27
* The same logic shall be applicable for following UAF,FAN.
28 28
1) UAF-2,FAN ---- TAG NO (10SAR01AN004).
29 29
30 30
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 27 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
1 1
6 6
LO LVL OF TANK OF UAF-1 LVM < 350 UAF-1, TANK WATER LEVEL LOW
7 FIELD FEEDBACK DDCMIS ANNUNCIATION 7
10SAR01CL080_XG52 mmWC
8 8
LO LVL OF TANK OF UAF-2 LVM < 350 UAF-2, TANK WATER LEVEL LOW
10 FIELD FEEDBACK DDCMIS ANNUNCIATION 10
10SAR01CL081_XG52 mmWC
13 13
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 28 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
1 1
3 3
5 5
6 6
7 7
9 9
10 10
11 11
12 12
13 13
14 14
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 29 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
STEP-2
1 09 SHEET 25 DDCMIS SOFT SIGNAL SEQUENCE ON 1
(UAF-1,PUMP-1 AUTO START)
2 DDCMIS DDCMIS SOFT COMMAND MANUAL START FROM HMI OF AHU ROOM MANUAL ON 2
3 3
4 4
START
7 7
PERMISSIVE
UAF-1,PUMP-1 MCC DIST FBK AND
8 FIELD FEEDBACK NOT 8
10SAR01AP101_XB48
9 9
FIRE SIGNAL
10 FIELD FEEDBACK NOT 10
90AYE19GH001_XG61
11 11
13 13
14 DDCMIS DDCMIS SOFT COMMAND MANUAL STOP FROM HMI OF AHU ROOM MANUAL OFF 14
STEP-2
15 05 SHEET 31 DDCMIS SOFT COMMAND SEQUENCE OFF 15
(UAF-1,PUMP-1 AUTO STOP)
17 17
STOP
18 18
PROTECTION
19 19
OR
03 SHEET 30 UAF-1,PUMP-1 STOP CMD
20 COMMAND UAF-1,PUMP-1 FAILED TO START FIELD COMMAND 20
10SAR01AP101_YB02
21 21
FIRE SIGNAL
22 FIELD FEEDBACK 22
90AYE19GH001_XG61
24 24
25 25
* The same logic shall be applicable for following UAF, PUMP.
26 26
1) UAF-1,PUMP-2 ---- TAG NO (10SAR01AP102).
27 27
28 28
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 30 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
LINE SOURCE TYPE OF INPUT INPUTS DDCMIS LOGIC FOR UAF PUMP OUTPUTS DEST. LINE
1 1
6 6
7 7
8 8
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 31 of 32
CONTROL LOOP LOGIC DIAGRAM FOR DDCMIS OF HVAC SYSTEM FOR ESP BUILDING # 1 2
DP16004-YF00-90SAR-115001
LINE SOURCE TYPE OF INPUT INPUTS STOP SEQUENCE OUTPUTS DEST. LINE
1 1
2 2
STEP-1
(AUTO STOP COMMAND FROM HMI FOR
3 DDCMIS DDCMIS SOFT SIGNAL 3
STOP SEQUENCE)
4 4
6 6
9 NEXT MT: 90Sec WT: 2Sec CMD UAF-1,FAN AUTO STOP 16 SHEET 26 9
10 10
11 11
14 14
Rev. 01
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Page 32 of 32