Professional Documents
Culture Documents
FOR
EXISTING 2 (TWO) STORIED BUILDING FOR APEX WEAVING &
FINISHING MILLS Ltd AT EAST CHANDORA, SHAFIPUR, GAZIPUR
.
NAME OF THE CLIENT
APEX WEAVING & FINISHING MILLS LTD
Prepared by
Turbo Engineering ltd
House No#43, Block# E, Banasree, Rampura, Dhaka-1219
All structural elements such as column, beam, footing and slab have been checked.
All members are inadequate according to BNBC standard.
Strengthening has been proposed in case of both situation (Existing and horizontal
extension of the existing building)
A detailed calculation and analysis has been described in the rest of the report.
1.0 INTRODUCTION
Existing 2 storied APEX WEAVING & FINISHING MILLS Ltd AT EAST CHANDORA, SHAFIPUR,
GAZIPUR Has been analyzed for different loading conditions & different load combinations
accordingly. This report summarizes the analysis and design related data
The building has been eight storied RCC building. This is a beam-column RCC
frame. The vertical gravity load & lateral load of the building is carried by RCC
columns to foundations. The lateral load arising from wind & earth quake is taken by
framing action of beam-column system. The beams and columns have not sufficient
capacity to carry the lateral loads arising from wind & earth quake.
1
3.0 LIMITATIONS
To produce the design report of this project we have some limitations. It was unable
to collect all the data from every sections of every member. We have collect data
from some specific locations of specific members.
4.0 METHODOLOGY
The following methodology has been used for the DEA of above
mentioned building.
1. We surveyed the site to collect information. Required
measurements were made to form an accurate as built
drawings.
2. We have performed ferro scan to collect the information
of the existing reinforcement so that we can prepare
accurate structural drawing.
3. We have performed core cutting test to find out the
concrete strength.
4. When the above information collection has been
completed we made a computer based 3d model of the
whole structure to simulate the actions of vertical and
lateral loads on the structure.
5. Depending on the analysis we proposed the required
strengthening of the existing structure.
6. A controlled loading plan has been made considering
column capacity and floor plate capacity
7. We have also collected information of the foundation by
earth excavation.
8. Finally based on the above steps the DEA report has been prepared.
2
5.0 STRUCTURAL DESIGN CONCEPT & CRITERIA
The structural element has been designed and considering the following criteria.
Height of structure=52’
Length=365’Width=310’
No of story= 8
Type of the Structure=Regular
Type of Diaphragm=Rigid
Ground floor height=10'-6"
Typical floor height=Average 24’
Type of frames beam column system
Type of floor used two way slab
On the basis of existing structural detailing Ordinary Moment Resisting Frame (OMRF)
has been adopted.
3
5.3 Material Data:
Compressive strength of concrete for Column (Brick Chips)
4
Compressive strength of concrete for Slab (Brick Chips)
Dead Load:
Dead load is the vertical load due to the self-weight of the permanent structural and
non-structural component of a building, e.g. Foundation, column, beam, walls,
ceilings, permanent partitions and fixed service equipment.
Unit weight of materials and the calculation of design dead loads are according to
section-2.2, Chapter-2, part-6, BNBC-Page6-22
Live Load:
Live load is the load superimposed by the use or occupancy of the building not
including the environmental loads such as wind load, rain load, and earth quake load.
Dead load. (Ref. BNBC, Part-6, Chapter-2, Sec-2.3.2)
But it should be not less than the minimum floor live load. (Ref. BNBC, Part-6,
Chapter-2, Sec-2.3.3)
Storage area 63
Stair 84
Working area 42
Open to sky 30
6
5.5 Load applied on structure.
Wind Load:
The calculation of wind load confirms the sub-clause 2.4, Chapter 2, Part-6 of BNBC.
The following equation has been used to calculate sustained wind pressure of the
structure.
Where,
1.0 Seismic Zone coefficient factor, Z=0.15 for Zone-02
(Ref.Table6.2.22 Sec2.5.6.1, Chap.-2, Part-6, BNBC)
2.0 Importance factor, I = 1.0
(Ref. Table 6.2.23 Sec2.5.6.1, Chap.-2, Part-6, BNBC)
3.0 Numerical Co-efficient, C=0.03
4.0 Response Modification factor, R=5
(Ref. Table 6.2.24 Sec2.5.6.2, Chap.-2, Part-6, BNBC)
Reinforcement concrete structure has been designed with Ultimate Strength Design
(USD) method has been adopted
5.7 Method of Analysis
8
7. Structural Feasibility check -at Column Retrofit condition
Comments: As par NTPA load combination at column retrofit condition all footings
area are adequate.
12
Foundation adequacy check-Punching check at existing condition:
13
14
Comments: As par NTPA load combination at Column Retrofit condition all footings
are adequate in punching
15
8.1 Column Adequacy check (NTPA load combination consider at
Before Retrofit model)
Column has been checked following table is prepared considering 42psf live load.
Grid-A
Grid-B
GRID-C
GRID-D
16
GRID-E
GRID-F
GRID-G
GRID-H
GRID-I
GRID-J
GRID-K
GRID-L
GRID-M
GRID-N
18
GRID-P
GRID-Q
GRID-R
Comment: On the basis of above column PMM value, the columns which are
overstressed (O/S) and exceeded maximum PMM ratio (>1.05) should be retrofitted or
PMM ratio<1.05, so ok.
Comments: At NTPA load combination consider 42 psf floor load, all columns are
inadequate.
The reinforcement and sections of the some existing grade beams & Floor beams are
adequate to resist the forces and
Moments for the loadings considered in the analysis. Adequacies of reinforcement are
calculated in ETABS.
19
8.3. Story Drift (at existing condition)
For both cases the drift is less than the allowable limit. So the building is ok for drift.
For both case the Lateral displacement cross the allowable limit
20
8.3. Story Drift (at Retrofit condition)
For both cases the drift is less than the allowable limit. So the building is ok for drift.
For both case the Lateral displacement within the allowable limit
21
QUALITY CONTROL AGREEMENT
This is to certify that the remedial works of for EXISTING 2 (TWO) STORIED
BUILDING FOR APEX WEAVING & FINISHING MILLS Ltd AT EAST CHANDORA,
SHAFIPUR, GAZIPUR.
Thanking You
9.2 Recommendations
Columns are found inadequate both for gravity load combination and lateral load
combination. Therefore, all Column need to be retrofit.
9.3. CONCLUSION
Following are the conclusion drawn from the results of the above investigative studies:
During model analysis floor live load is consider 42 psf & store live load is 84 consider on all
over area. So the factory can use storage area at mentioned in load diagram but capacity
should be maintained within limit.
From the observations of extracted concrete core samples (i.e., brick aggregates& stone
aggregate), it is evident that the extracted samples are uniform, homogeneous and free from
voids / honeycombs.
From the computer model analysis and design verifications, it is inferred that most of the
existing RCC columns structurally not adequate to resist the loads considered in the
analysis so required to retrofit.
All grade beams & floor beams section and reinforcement for positive & negative moment
are found adequate, so don’t need to retrofit these beams.
All foundation is found adequate in area & punching at NTPA load combination.
22