AfDB NGFO PIPED SERVICES BOQ (DEC 12)

African Development Bank


Proposed Nigeria Field Office, Abuja, Nigeria

BILL OF QUANTITIES

MECHANICAL (HVAC) SERVICES INSTALLATION

KOA AfDB BOQ Piped 1


AfDB NGFO PIPED SERVICES BOQ (DEC 12)

MECHANICAL (HVAC) SERVICES INSTALLATION

TENDER SUMMARY Naira

BILL NO. 1 - PLANT AND EQUIPMENT

BILL NO. 2 - VRF Installation

BILL NO. 3 - DUCTWORK

BILL NO. 4 - CHILLED WATER PIPING

BILL NO. 5 - CONDENSATE PIPING

BILL NO. 6 -
INSTRUMENTATIONS&CONTROLS

TOTAL

..

KOA AfDB BOQ Piped 2


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 1 - PLANTS AND EQUIPMENT

ITEM DESCRIPTION SUPPLY FIXED


QTY UNIT TOTAL RATE TOTAL
RATE RATE
Supply, install,test,verify and commission
the following plants and equipment. Further
schedules of some of the items are given at
the end of this bill. Tenderer is expected to
be familiar with the specifed manufacturers
and is to submit appropriate brochures of the
specified items (or an equivalent product of
another acceptable manufacturer as shall be
agreed with the Client and Consultants.

Chillers Unit shall be complete with heat


1 recovery accessories. Allow for anti-
corrosion treatment. Controls shall be
interfaced into a BMS system. E.g. Trane air
cooled helical rotary chillers (RTAD 085) or
approved equal

Chiller 0-1&2 (duty and duty)


cooling cap: 255kW 2 Nos
temp diff: 6.0o
ambient: 40oC DB, 280C WB

2 Chilled Water Circulating Pumps e.g


Pullen, Grundfos or approved equal
Constant flow pimary circuit pumps. Pumps
shall be the vertical type mounted indoors
(IP55 rating)
P 0-1&2 (duty/standby)
20 l/s @ 200kPa 2 no

3 Make-up and pressurisation unit comprising


pumps, tank, pneumatic vessel, accessories
and interconnecting pipework as detailed in 1 set
drawing.

4 Chemical dosing unit comprising of tank,


1 No
dosing pump and all accessories

5 Line pressurisation vessel


- chilled water system 1 No

to bill collection

KOA: 485094200.xls 3
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 1 - PLANTS AND EQUIPMENT

ITEM DESCRIPTION SUPPLY FIXED


QTY UNIT TOTAL RATE TOTAL
RATE RATE

6 Allow for anti-vibration mounting of all


sum
equipment.

Air Handling Units (e.g. Trane CLCP or


approved equal)
Modular double skin chilled water air
handlers, coil shall be copper/aluminum

Air handling configuration shall follow the


following modules:
I - Inlet plenum
M - Mixing box
P - Flat pleated panel filter (rated F7)
B - Bag filter (rated F9)
C - Cooling coil (chilled water)
A - Access Box
F - Centrifugal fan unit
O - Outlet plenum

Air flow rates are nominal values. The AHU


shall be rated an extra 5% to cater for duct
leakage and balancing.

7 AHU 0-1 (Horizontal) 1 No


Config: M-P-B-C-A-F
airflow:- 1360 l/s
cooling load: 43.08kW
ESR: 428 Pa

8 AHU 5-1 & 2 (Vertical) - duty/duty 2 No


Config: I-P-C-A-F
airflow:- 3955 l/s
cooling load: 254.00kW
ESR: 890 Pa

to bill collection

KOA: 485094200.xls 4
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 1 - PLANTS AND EQUIPMENT

ITEM DESCRIPTION SUPPLY FIXED


QTY UNIT TOTAL RATE TOTAL
RATE RATE

Extract Fan e.g Flakt Woods or approved


equal.
In-duct aerofoil fans are to be mounted in
acoustic insulated enclosures (boxes) and
rated IP65. Fans shall be generally selected
for speeds not exceeding 1500rpm except
otherwise agreed with the Consultant. Break
out noise (after allowing for acoustic
insulation) shall not exceed 40dB
Fans shall be duplicate operating on a
duty/standby basis

9 TEF 6-1&2 (duty/standby) - Toilet extract


2562 l/s @ 386 Pa 2 Nos

10 EF 6 - 1&2 - Atrium ventilation


Fans shall be rated 'flame proof'
2500 l/s @ 200 Pa 2 Nos

Staircase pressurisation Fan e.g Flakt


Woods or approved equal.
In-duct aerofoil fans are to be mounted in
acoustic insulated enclosures (boxes) and
rated IP65. Fans shall be generally selected
for speeds not exceeding 1500rpm except
otherwise agreed with the Consultant. Break
out noise (after allowing for acoustic
insulation) shall not exceed 40dB
Fans shall be duplicate operating on a
duty/standby basis

11 SPF 6-1&2 (duty/standby) - escape stair


pressurisation
2880 l/s @ 183 Pa 2 Nos

to bill collection

KOA: 485094200.xls 5
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 1 - PLANTS AND EQUIPMENT

ITEM DESCRIPTION SUPPLY FIXED


QTY UNIT TOTAL RATE TOTAL
RATE RATE

Computer Room Air conditioning units


(CRAC 1-1&2) - duty/standby
Units shall have DX coils and shall be
complete with matching air cooled
condensing units.

Units shall be c/w all integral microprocessor


controls for temperature and humidity,
display unit, alarm indication. Units shall
have auto-restart facility. Provide dry
contacts for connections to fire alarm system
and BMS. Refrigerant shall be R410A or
better (The option for electric reheat and
humidifier shall be quoted seperately and
shall be optional). Eg Airedale Logicool In-
Rak (data centre unit) or approved equal.

12 CRAC 1 - 1&2
cooling cap: 26.20kW total, 25.75kW sens.
2 No

Refrigerant piping for CRAC units. Allow for


lot
insulation and sheating

Condensate piping for CRAC units using


lot
25mmDIA HDPE. Allow for insulation

13 Line pressurisation vessel


- chilled water system 1 No

14 Allow for anti-vibration mounting of all


lot
equipment.

15 Wall Extract Fan e.g Xpelair or approved


equal.
EF 0-1 - Battery extract
36 l/s 1 No

16 EF 0-2 - Disabled Toilet


50 l/s 1 No

COLLECTION

pg 1 - 1

pg 1 - 2

pg 1 - 3

pg 1 - 4

TO SUMMARY

..

KOA: 485094200.xls 6
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/1 - VRF Installation

ITEM DESCRIPTION SUPPLY FIXED


QTY UNIT TOTAL RATE TOTAL
RATE RATE
Supply,install,test,verify and commission the
following plants and equipment. Tenderer is
expected to be familiar with the specifed
manufacturers and is to submit appropriate
brochures of the specified items (or an
equivalent product of another acceptable
manufacturer as shall be agreed with the
Client and Consultants.

Outdoor air-cooled VRF condensing


units, capable of multiple indoor units and
zone, with extended range refrigerant piping.
Operating outdoor temperature is 40oC.
High COP. Refrigerant shall be R410A. E.g.
Daikin, LG, or approved equal. Note that the
capacities stated below are for the combined
floor load and are not additions of the
individual capacities of the indoor units.

1 VRF 6-1 (serving ground floor) cap: 85.23kW 1 no

2 VRF 6-2 (serving first floor) cap: 56.03kW 1 no

3 VRF 6-3 (serving second floor) cap: 1 no

4 VRF 6-4 (serving third floor) cap: 61.69kW 1 no

5 VRF 6-5 (serving fourth floor) cap: 63.58kW 1 no

VRF 6-6 is for the future 5th floor


6 development and is not measured in this
developmental phase.

to bill collection

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 7


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/2 - VRF Installation

ITEM DESCRIPTION SUPPLY FIXED


QTY UNIT TOTAL RATE TOTAL
RATE RATE

Indoor VRF Cassette Units (CAS)


Ceiling mounted cassette coil unit, matched
to outdoor unit, with galvanised sheeting
treated for corrosion, 3-speed fan, integral
condensate pump, easily accessible and
cleanable EU4 filter with anti-bacterial and
mildew treatment, connections for remote
control of fan and space temperature, all
mounting and fixing accessories. Unit shall
have port for BMS signal connection. Include
for unit cabled remote control and wall
mounted thermostat/controller. NOTE:
equipment selection shall be at low fan
speed and entering condition of
23.0/16.4oC (except otherwise indicated in
the drawing schedules)

GROUND FLOOR

1 CAS 0-1 1 no
Cooling cap: 2.99kW
Nominal airflow: 186 l/s

2 CAS 0-2 1 no
Cooling cap: 2.99 kW
Nominal airflow: 186 l/s

3 CAS 0-3 1 no
Cooling cap: 2.99kW
Nominal airflow: 186 l/s

4 CAS 0-4 1 no
Cooling cap: 2.99kW
Nominal airflow: 186 l/s

5 CAS 0-5 1 no
Cooling cap: 2.65kW
Nominal airflow: 225 l/s

6 CAS 0-6 1 no
Cooling cap: 2.65kW
Nominal airflow: 225 l/s

7 CAS 0-7 1 no
Cooling cap: 2.65kW
Nominal airflow: 225 l/s

to sub collection

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 8


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/2 - VRF Installation

ITEM DESCRIPTION SUPPLY FIXED


QTY UNIT TOTAL RATE TOTAL
RATE RATE

Indoor VRF Cassette Units (CAS):


ground floor
8 CAS 0-8 1 no
Cooling cap: 2.65kW
Nominal airflow: 225 l/s

9 CAS 0-9 1 no
Cooling cap: 2.65kW
Nominal airflow: 225 l/s

10 CAS 0-10 1 no
Cooling cap: 3.00kW
Nominal airflow: 245 l/s

11 CAS 0-11 1 no
Cooling cap: 3.00kW
Nominal airflow: 245 l/s

12 CAS 0-12 1 no
Cooling cap: 3.00kW
Nominal airflow: 245 l/s

13 CAS 0-13 1 no
Cooling cap: 3.00kW
Nominal airflow: 245 l/s

14 CAS 0-14 1 no
Cooling cap: 3.00kW
Nominal airflow: 245 l/s

15 CAS 0-15 1 no
Cooling cap: 3.00kW
Nominal airflow: 245 l/s

16 CAS 0-16 1 no
Cooling cap: 3.00kW
Nominal airflow: 245 l/s

17 CAS 0-17 1 no
Cooling cap: 3.35kW
Nominal airflow: 260 l/s

18 CAS 0-18 1 no
Cooling cap: 3.35kW
Nominal airflow: 260 l/s

to sub collection

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 9


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/2 - VRF Installation

ITEM DESCRIPTION SUPPLY FIXED


QTY UNIT TOTAL RATE TOTAL
RATE RATE
Indoor VRF Cassette Units (CAS):
ground floor
19 CAS 0-19 1 no
Cooling cap: 3.35kW
Nominal airflow: 260 l/s

20 CAS 0-20 1 no
Cooling cap: 3.35kW
Nominal airflow: 260 l/s

21 CAS 0-21 1 no
Cooling cap: 3.35kW
Nominal airflow: 260 l/s

22 CAS 0-22 1 no
Cooling cap: 3.35kW
Nominal airflow: 260 l/s

23 CAS 0-23 1 no
Cooling cap: 2.15kW
Nominal airflow: 188 l/s

24 CAS 0-24 1 no
Cooling cap: 2.15kW
Nominal airflow: 188 l/s

25 CAS 0-25 1 no
Cooling cap: 2.15kW
Nominal airflow: 188 l/s

26 CAS 0-26 1 no
Cooling cap: 2.32kW
Nominal airflow: 175 l/s

27 CAS 0-27 1 no
Cooling cap: 1.80kW
Nominal airflow: 136 l/s

28 CAS 0-28 1 no
Cooling cap: 2.72kW
Nominal airflow: 252 l/s

29 CAS 0-29 1 no
Cooling cap: 3.00kW
Nominal airflow: 225 l/s

30 CAS 0-30 1 no
Cooling cap: 2.63kW
Nominal airflow: 228 l/s

SUB-COLLECTION

page 2/2- 1

page 2/2- 2

page 2/2- 3

to bill collection (ground floor CAS)

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 10


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/3 - VRF Installation

ITEM DESCRIPTION SUPPLY FIXED


QTY UNIT TOTAL RATE TOTAL
RATE RATE

Indoor VRF Cassette Units (CAS):


first floor

1 CAS 1 -1 1 no
Cooling cap: 2.40kW
Nominal airflow: 200 l/s

2 CAS 1 - 2 1 no
Cooling cap: 2.40kW
Nominal airflow: 200 l/s

3 CAS 1 - 3 1 no
Cooling cap: 3.67kW
Nominal airflow: 335 l/s

4 CAS 1 - 4 1 no
Cooling cap: 3.67kW
Nominal airflow: 335 l/s

5 CAS 1 - 5 1 no
Cooling cap: 2.43kW
Nominal airflow: 220 l/s

6 CAS 1 - 6 1 no
Cooling cap: 2.43kW
Nominal airflow: 220 l/s

7 CAS 1 - 7 1 no
Cooling cap: 2.95kW
Nominal airflow: 258 l/s

8 CAS 1 - 8 1 no
Cooling cap: 2.95kW
Nominal airflow: 258 l/s

9 CAS 1 - 9 1 no
Cooling cap: 1.76kW
Nominal airflow: 165 l/s

10 CAS 1 - 10 1 no
Cooling cap: 4.17kW
Nominal airflow: 345 l/s

11 CAS 1 - 11 1 no
Cooling cap: 4.17kW
Nominal airflow: 345 l/s

to sub collection

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 11


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/3 - VRF Installation

ITEM DESCRIPTION SUPPLY FIXED


QTY UNIT TOTAL RATE TOTAL
RATE RATE

Indoor VRF Cassette Units (CAS):


first floor
12 CAS 1 - 12 1 no
Cooling cap: 2.84kW
Nominal airflow: 243 l/s

13 CAS 1 - 13 1 no
Cooling cap: 3.48kW
Nominal airflow: 307 l/s

14 CAS 1 - 14 1 no
Cooling cap: 3.48kW
Nominal airflow: 307 l/s

15 CAS 1 - 15 1 no
Cooling cap: 3.48kW
Nominal airflow: 307 l/s

16 CAS 1 - 16 1 no
Cooling cap: 3.48kW
Nominal airflow: 307 l/s

17 CAS 1 - 17 1 no
Cooling cap: 3.48kW
Nominal airflow: 307 l/s

18 CAS 1 - 18 1 no
Cooling cap: 1.91kW
Nominal airflow: 172 l/s

19 CAS 1 - 19 1 no
Cooling cap: 0.88kW
Nominal airflow: 76 l/s

SUB-COLLECTION

page 2/3- 1

page 2/3- 2

to bill collection (first floor CAS)

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 12


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/4 - VRF Installation

ITEM DESCRIPTION SUPPLY FIXED


QTY UNIT TOTAL RATE TOTAL
RATE RATE

Indoor VRF Cassette Units (CAS):


second floor

1 CAS 2-1 1 no
Cooling cap: 3.58kW
Nominal airflow: 318 l/s

2 CAS 2-2 1 no
Cooling cap: 3.58kW
Nominal airflow: 318 l/s

3 CAS 2-3 1 no
Cooling cap: 3.58kW
Nominal airflow: 318 l/s

4 CAS 2-4 1 no
Cooling cap: 3.58kW
Nominal airflow: 318 l/s

5 CAS 2-5 1 no
Cooling cap: 3.58kW
Nominal airflow: 318 l/s

6 CAS 2-6 1 no
Cooling cap: 3.58kW
Nominal airflow: 318 l/s

7 CAS 2-7 1 no
Cooling cap: 1.79kW
Nominal airflow: 166 l/s

8 CAS 2-8 1 no
Cooling cap: 1.76kW
Nominal airflow: 165 l/s

9 CAS 2-9 1 no
Cooling cap: 4.17kW
Nominal airflow: 345 l/s

10 CAS 2-10 1 no
Cooling cap: 4.17kW
Nominal airflow: 345 l/s

11 CAS 2-11 1 no
Cooling cap: 3.04kW
Nominal airflow: 278 l/s

to sub collection

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 13


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/4 - VRF Installation

ITEM DESCRIPTION SUPPLY FIXED


QTY UNIT TOTAL RATE TOTAL
RATE RATE

Indoor VRF Cassette Units (CAS):


second floor

12 CAS 2-12 1 no
Cooling cap: 3.04kW
Nominal airflow: 278 l/s

13 CAS 2-13 1 no
Cooling cap: 3.46kW
Nominal airflow: 300 l/s

14 CAS 2-14 1 no
Cooling cap: 3.05kW
Nominal airflow: 271 l/s

15 CAS 2-15 1 no
Cooling cap: 3.05kW
Nominal airflow: 271 l/s

16 CAS 2-16 1 no
Cooling cap: 3.05kW
Nominal airflow: 271 l/s

17 CAS 2-17 1 no
Cooling cap: 3.05kW
Nominal airflow: 271 l/s

18 CAS 2-18 1 no
Cooling cap: 3.05kW
Nominal airflow: 271 l/s

19 CAS 2-19 1 no
Cooling cap: 1.62kW
Nominal airflow: 145 l/s

20 CAS 2-20 1 no
Cooling cap: 1.08kW
Nominal airflow: 90 l/s

SUB-COLLECTION

page 2/4- 1

page 2/4- 2

to bill collection (second floor CAS)

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 14


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/5 - VRF Installation

ITEM DESCRIPTION SUPPLY FIXED


QTY UNIT TOTAL RATE TOTAL
RATE RATE

Indoor VRF Cassette Units (CAS):


third floor

1 CAS 3-1 1 no
Cooling cap: 3.35kW
Nominal airflow: 297 l/s

2 CAS 3-2 1 no
Cooling cap: 3.35kW
Nominal airflow: 297 l/s

3 CAS 3-3 1 no
Cooling cap: 3.35kW
Nominal airflow: 297 l/s

4 CAS 3-4 1 no
Cooling cap: 3.35kW
Nominal airflow: 297 l/s

5 CAS 3-5 1 no
Cooling cap: 3.35kW
Nominal airflow: 297 l/s

6 CAS 3-6 1 no
Cooling cap: 3.35kW
Nominal airflow: 297 l/s

7 CAS 3-7 1 no
Cooling cap: 3.35kW
Nominal airflow: 297 l/s

8 CAS 3-8 1 no
Cooling cap: 1.76kW
Nominal airflow: 165 l/s

9 CAS 3-9 1 no
Cooling cap: 4.17kW
Nominal airflow: 345 l/s

10 CAS 3-10 1 no
Cooling cap: 4.17kW
Nominal airflow: 345 l/s

11 CAS 3-11 1 no
Cooling cap: 3.09kW
Nominal airflow: 266 l/s

to sub collection

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 15


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/5 - VRF Installation

ITEM DESCRIPTION SUPPLY FIXED


QTY UNIT TOTAL RATE TOTAL
RATE RATE

Indoor VRF Cassette Units (CAS):


third floor

12 CAS 3-12 1 no
Cooling cap: 3.20kW
Nominal airflow: 283 l/s

13 CAS 3-13 1 no
Cooling cap: 3.20kW
Nominal airflow: 283 l/s

14 CAS 3-14 1 no
Cooling cap: 3.20kW
Nominal airflow: 283 l/s

15 CAS 3-15 1 no
Cooling cap: 3.20kW
Nominal airflow: 283 l/s

16 CAS 3-16 1 no
Cooling cap: 3.20kW
Nominal airflow: 283 l/s

17 CAS 3-17 1 no
Cooling cap: 3.20kW
Nominal airflow: 283 l/s

18 CAS 3-18 1 no
Cooling cap: 3.20kW
Nominal airflow: 283 l/s

19 CAS 3-19 1 no
Cooling cap: 1.57kW
Nominal airflow: 140 l/s

20 CAS 3-20 1 no
Cooling cap: 1.08kW
Nominal airflow: 90 l/s

SUB-COLLECTION

page 2/5- 1

page 2/5- 2

to bill collection (third floor CAS)

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 16


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/6 - VRF Installation

ITEM DESCRIPTION SUPPLY FIXED


QTY UNIT TOTAL RATE TOTAL
RATE RATE

Indoor VRF Cassette Units (CAS):


fourth floor

1 CAS 4-1 1 no
cooling cap: 2.94kW
Nominal airflow: 259 l/s

2 CAS 4 - 2 1 no
cooling cap: 2.94kW
Nominal airflow: 259 l/s

3 CAS 4 -3 1 no
cooling cap: 2.94kW
Nominal airflow: 259 l/s

4 CAS 4-4 1 no
cooling cap: 2.94kW
Nominal airflow: 259 l/s

5 CAS 4-5 1 no
Cooling cap: 3.20kW
Nominal airflow: 288 l/s

6 CAS 4-6 1 no
Cooling cap: 3.20kW
Nominal airflow: 288 l/s

7 CAS 4-7 1 no
Cooling cap: 3.20kW
Nominal airflow: 288 l/s

8 CAS 4-8 1 no
Cooling cap: 3.20kW
Nominal airflow: 288 l/s

9 CAS 4-9 1 no
Cooling cap: 1.99kW
Nominal airflow: 187 l/s

10 CAS 4-10 1 no
Cooling cap: 4.20kW
Nominal airflow: 348 l/s

11 CAS 4-11 1 no
Cooling cap: 4.20kW
Nominal airflow: 348 l/s

to sub collection

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 17


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/6 - VRF Installation

ITEM DESCRIPTION SUPPLY FIXED


QTY UNIT TOTAL RATE TOTAL
RATE RATE

Indoor VRF Cassette Units (CAS):


fourth floor

12 CAS 4-12 1 no
Cooling cap: 3.12kW
Nominal airflow: 269 l/s

13 CAS 4-13 1 no
Cooling cap: 3.24kW
Nominal airflow: 287 l/s

14 CAS 4-14 1 no
Cooling cap: 3.24kW
Nominal airflow: 287 l/s

15 CAS 4-15 1 no
Cooling cap: 3.24kW
Nominal airflow: 287 l/s

16 CAS 4-16 1 no
Cooling cap: 3.24kW
Nominal airflow: 287 l/s

17 CAS 4-17 1 no
Cooling cap: 3.24kW
Nominal airflow: 287 l/s

18 CAS 4 - 18 1 no
Cooling cap: 3.24kW
Nominal airflow: 287 l/s

19 CAS 4-19 1 no
Cooling cap: 3.24kW
Nominal airflow: 287 l/s

20 CAS 4-20 1 no
Cooling cap: 1.59kW
Nominal airflow: 142 l/s

21 CAS 4-21 1 no
Cooling cap: 1.24kW
Nominal airflow: 115 l/s

SUB-COLLECTION

page 2/6- 1

page 2/6- 2

to bill collection (fourth floor CAS)

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 18


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/7 - VRF Installation

ITEM DESCRIPTION SUPPLY FIXED


QTY UNIT TOTAL RATE TOTAL
RATE RATE
Accessories
Supply and install accessories associated
with the VRF units indicated above

1 Remote control and thermostat unit


incorporating 3-speed fan control. Allow for
cabling
- ground floor units lot

- first floor units lot

- second floor units lot

- third floor units lot

- fourth floor units lot

Instrumentation and controls


2 Supply and install system logic-based
electrical and auto-control panel. Control unit
to include for desktop PC and monitor
(mounted in the 5th floor plant room). Panel
shall allow for all electrical power protections 1 no
- phase failure, under/over current, surge
protection, etc. Include for step down
transformer for controllers all to give a fully
functional system

3 Allow for control cabling from all indoor and


outdoor units to the control panel
- outdoor units lot

- ground floor units lot

- first floor units lot

- second floor units lot

- third floor units lot

- fourth floor units lot

4 Allow for power cabling to outdoor units.


lot
Include for outdoor mounted local isolators.

5 Allow for cable fixing, hangers, conduits,


lot
supports

to bill collection

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 19


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/7 - VRF Installation

ITEM DESCRIPTION SUPPLY FIXED


QTY UNIT TOTAL RATE TOTAL
RATE RATE

Refrigerant piping
6 Supply and install all refrigerant piping using
copper (BS 2871). The tenderer shall submit
computer based pipe sizing calculations
appropriate to the product being tendered
and a breakdown of the costings for each
floor extended and totalled to the figures
inserted in this BOQ. The refrigerant
installation shall be from the roof mounted
outdoor units to the indoor units on each
floor. Rates shall include for all fittings and
accessories

- ground floor units lot

- first floor units lot

- second floor units lot

- third floor units lot

- fourth floor units lot

7 Supply and install insulations to all


refrigerant piping using armaflex tubing (or
approved equivalent) of appropriate
thickness. Rates shall include for all fittings
and accessories

- ground floor units lot

- first floor units lot

- second floor units lot

- third floor units lot

- fourth floor units lot

to bill collection

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 20


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/7 - VRF Installation

ITEM DESCRIPTION SUPPLY FIXED


QTY UNIT TOTAL RATE TOTAL
RATE RATE

8 Condensate piping
Supply and install all condensate piping to
the indoor units using HDPE piping. The
layout shall be as indicated in the design
drawings. Rates shall include for all fittings
and accessories. Rates shall includes for
20mm thick armaflex (or approved equal)
insulation tubing.

ground floor units


25mm dia 62 m
50mm dia 144 m
80mm dia (stack for entire installation and
connection to drain channels) 72 m

first floor units


25mm dia 46 m
50mm dia 96 m

second floor units


25mm dia 46 m
50mm dia 96 m

third floor units


25mm dia 44 m
50mm dia 96 m

fourth floor units


25mm dia 44 m
50mm dia 96 m

9 Allow for pipe fixing, brackets, hangers,


lot
supports

to sub collection

COLLECTION

page 2/7- 1

page 2/7- 2

page 2/7- 3

to bill collection

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 21


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 3 - VRF Installation

ITEM DESCRIPTION SUPPLY FIXED


QTY UNIT TOTAL RATE TOTAL
RATE RATE

BILL COLLECTION

bill 2/1

bill 2/2

bill 2/3

bill 2/4

bill 2/5

bill 2/6

bill 2/7

TO SUMMARY

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 22


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 3 - DUCTWORK

ITEM DESCRIPTION SUPPLY FIXED TOTAL


QTY UNIT TOTAL
RATE RATE RATE

Supply,install,test,verify and commission the


following (refer to drawing and specification
for details).

All air diffusion units shall be extruded


aluminum (except otherwise indicated) and
shall be to RAL colour to be approved by the
architect
Ductwork

1 Galvanised sheet metal ductwork (using


1398 m2
appropriate guages as specified).

2 Provided for insulation to duct using 25mm


foil faced mineral fibre insulation and vapour 978 m2
barrier.
3 Provided for internal thermal and acoustic
duct liner to duct above using 50mm thick
non fibre medical grade insulation and
vapour barrier with anti-bacterial and anti-
fungal treatment e.g. Armaflex/Armacell,
420 m2
KFlexUSA or approved equal. Include for
fasterners, etc
Insulations within plantrooms shall be
internal. Also insulations up to 10m from
(airhandling) AHUs shall be internal.

4 Supply Diffuser (SD) ceiling mounted.


Units shall be square face adjustable multi-
louvre type with round neck (or square neck)
supply. Units shall be complete with iris (or
opposed blade) damper. E.g. GDL, Trox or
approved equivalent. Neck diameters are
indicated below
150 dia 103 nos
200 dia 5
250 dia 1

5 Sidewall Supply Diffuser (SWD) Units shall


have double deflection grilles c/w opposed
blade dampers. E.g. GDL, Trox or approved
equivalent
300 x 100 1 nos
900 x 300 4 "

6 Return Grille (RG) ceiling mounted. Units


shall be rectangular face adjustable egg
crate type. Units shall be complete with
opposed blade damper. E.g. GDL, Trox or
approved equivalent
1200 x 600 1 no

To Conclusions

KOA: 485094200.xls 23
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 3 - DUCTWORK

ITEM DESCRIPTION SUPPLY FIXED TOTAL


QTY UNIT TOTAL
RATE RATE RATE

Sidewall Air Jet Grille (AJG) High capacity


7 supply air jets to have concentric rings
assembled with a pivoting eyeball
adjustment c/w opposed blade dampers.
E.g. GDL J frame, Trox or approved
equivalent
350 x 350 (single jet) 4 nos

8 Extract Grille (EG) ceiling mounted. Units


shall be rectangular face adjustable egg
crate type. Units shall be complete with
opposed blade damper. E.g. GDL, Trox or
approved equivalent
150 x 100 35 nos

10 Flow control / Balancing Dampers single


or multi leaf. E.g GDL, Trox or approved
equivalent
Allow for the provision of balancing dampers
as indicated on drawing and/or specification lot
and/or schedules

11 Door Transfer Grille non-vision


600 x 150 6 Nos

12 Fire Dampers 2hr rating c/w fusible link, .


E.g GDL, Trox or approved equivalent
Allow for the provision of fire dampers as
indicated on drawing and/or specification,
schedules
200 x 150 5 nos
300 x 100 1 "
300 x 150 5 "
400 x 300 4 "
500 x 400 1 "
600 x 400 6 "
800 x 400 1 "
900 x 300 4 "
950 x 400 1 "

150dia 5 nos

To Conclusions

KOA: 485094200.xls 24
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 3 - DUCTWORK

ITEM DESCRIPTION SUPPLY FIXED TOTAL


QTY UNIT TOTAL
RATE RATE RATE

13 Allow for clean outs, test holes and access


lot
doors.

14 Allow for support, brackets, vibration


lot
dampers etc.

15 Allow for flexible duct connectors from duct


lot
to ceiling terminals.

To Conclusions

CONCLUSION

pg 3 - 1

pg 3 - 2

pg 3 - 3

TO SUMMARY

..

..

KOA: 485094200.xls 25
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 4 - CHILLED WATER PIPING

ITEM DESCRIPTION SUPPLY FIXED TOTAL


QTY UNIT TOTAL
RATE RATE RATE

Supply,install,test,verify and commission the


following
Pipework shall be black mild steel to BS
1387 Class C Heavy Grade. Large diameter
pipes shall be grooved.

1 Pipes
25mm 6 m
32mm 6 m
50mm 18 m
100mm 54 m
125mm 216 m

2 900 Bend
25mm 6 nos
32mm 6 "
50mm 10 "
100mm 16 "
125mm 30 "

3 1350 Bend
100mm 4 nos
125mm 14 "

4 Tee
125mm 10 nos

5 Isolating Ball Valve


50mm 2 nos

To Conclusions

KOA: 485094200.xls 26
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 4 - CHILLED WATER PIPING

ITEM DESCRIPTION SUPPLY FIXED TOTAL


QTY UNIT TOTAL
RATE RATE RATE

6 Isolating Butterfly Valve


100mm 6
125mm 8

7 Double Regulating Valve (c/w test points and seals)


50mm 1
100mm 6
125mm 2

9 2-Way Modulating Valves (c/w motor actuator)


50mm 1
100mm 2

10 Check (NRV) Valve


32mm 1
125mm 2

11 Strainer (Line)
50mm 1
100mm 4
125mm 2

To Conclusions

KOA: 485094200.xls 27
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 4 - CHILLED WATER PIPING

ITEM DESCRIPTION SUPPLY FIXED TOTAL


QTY UNIT TOTAL
RATE RATE RATE

12 Flexible Connector
50mm 2
100mm 8
125mm 4

13 Flange (c/w) gasket


50mm 12
100mm 30
125mm 24

14 End Flange (Cap)


125mm 2

15 Capped Flushing Tee


25mm 5 nos

16 Drain Cock
25mm 5 nos

17 Valved Flushing Inlet


50mm 2 nos

18 Safety Relief Valve


10bar setting 2 nos

19 Automatic Air Valve (AAV) 5 no

20 Flow Switch 1 no

21 Air Eliminator 5 no

22 Test point (sealed) 6 no

23 Pressure guage (0 - 15bar) c/w cock 10 no

To Conclusions

KOA: 485094200.xls 28
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 4 - CHILLED WATER PIPING

ITEM DESCRIPTION SUPPLY FIXED TOTAL


QTY UNIT TOTAL
RATE RATE RATE

24 Thermometer (Dial type 150mm) 10 no

25 Miscellaneous Items
Union, connectors, nipples, 135o bends, etc lot
Bracket, hangers, supports, etc lot

26 Thermal Insulation (using preformed rigid


mineral wool insulation or armaflex tubings.
Allow for vapour seal) - thickness as
specified but minimum 50mm
25mm 6 m
32mm 6 m
50mm 18 m
100mm 54 m
125mm 216 m

27 Carry out resin protective coating on pipes


installed in plantrooms, risers and external.
25mm 6 m
32mm 6 m
50mm 18 m
100mm 54 m
125mm 216 m

To Conclusions

CONCLUSION

pg 4 - 1

pg 4 - 2

pg 4 - 3

pg 4 - 4

TO SUMMARY

,,

KOA: 485094200.xls 29
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 5 - CONDENSATE PIPING (for chilled water)

ITEM DESCRIPTION SUPPLY FIXED TOTAL


QTY UNIT TOTAL
RATE RATE RATE

Supply,install,test,verify and commission the


following
Pipework shall be HDPE. All condnsate
pipes shall be appropriately insulated.

1 Pipe
50mm 12
100mm 48

2 Bend
50mm 6
100mm 2

3 Tee
50mm 2
100mm 1

4 Trap Connections
50mm (for AHUs) 3

5 Turndish
100mm 2 nos

6 Miscellaneous Items
Brackets, anchors, etc lot
Flanges, gaskets, sockets, reducers, etc lot

7 Thermal Insulation
using 20mm armaflex lot

TO SUMMARY

,,

KOA: - 485094200.xls 30
AfDB NGFO HAVC SYSTEM BOQ (APR 13)

BILL No. 6 - INSTRUMENTATIONS AND CONTROL

ITEM DESCRIPTION SUPPLY FIXED TOTAL


QTY UNIT TOTAL
RATE RATE RATE
Supply,install,test,verify and commission the
following. Refer to drawing, design report
and specification for details

1 Thermostat
duct 2 nos

2 Temperature Gauge (pipe mounted) - dial 2 nos

3 Test point with cock 10 nos

5 Flow Switch 1 No

6 Differential Pressure Switch 3 Nos

7 Duct mounted dial thermometer 2 Nos

8 Duct mounted dial pressure gauge 2 Nos

9 Smoke Detector Probe 4 Nos

10 Control cabling, terminator, etc Lot

11 CO2 Monitor (e.g Greystone Energy


1 nos
Systems) - duct mounted

12 Control Panel

The controls shall be fully digital. Allow for


control panel and system as detailed in the
specifications, schedules and drawings.
Include for all electrical control elements
including the step-down transformer, (230/24 1 nos
VAC), relays, switches, contactors, timers,
including all current and voltage protective
devices, e.t.c to give a fully function system.
Note provisions for future upgrade. System
shall be integrated into the building BMS

13 Control cabling
Allow for control cabling to connect all
controlled plants and the control panel. lot
Rates to include for termination items.

14 Electrical Power cabling


Allow for power cabling from the control
panel and/or local distribution panel to all
item of equipment for final connections. lot
Provide appropriate termination devices.
Only wireways shall be provided by others.

15 Local isolators to all items of equipment


lot
(some shall be suitable for outdoor
installation)
to conclusion

KOA: 485094200.xls 31
AfDB NGFO HAVC SYSTEM BOQ (APR 13)

BILL No. 6 - INSTRUMENTATIONS AND CONTROL

ITEM DESCRIPTION SUPPLY FIXED TOTAL


QTY UNIT TOTAL
RATE RATE RATE

16 Allow for equipontential bonding of the lot


equipment

17 Allow for brackets, mountings, pads. lot

18 Allow for linkage to the building BMS lot


including provisions for cabling

19 Allow for linkage to the building fire alarm lot


panel including provisions for cabling

to conclusion
..

CONCLUSION

pg 6 - 1

pg 6 - 2

TO SUMMARY

..

..