Professional Documents
Culture Documents
Power Transformer Inspection and Maintenance Essential: Engr. Iñigo V. Escopete, JR., Pee
Power Transformer Inspection and Maintenance Essential: Engr. Iñigo V. Escopete, JR., Pee
INSPECTION AND
MAINTENANCE
ESSENTIAL
Presented by:
You should know that fans are much, much more efficient
if the blades are clean and rotating in cool air. It’s worth
mention that fans should blow cool air through the radiators
and they not be pulling air through.
How it works? If there is gas inside, the oil will be displaced, and
the gas will be evident as a space on top the oil. If sufficient gas is
found to displace the upper float, the alarm should be activated.
the small valve at the top left is to bleed the gas off and reset the
relay.
If the transformer has been online some time (service aged), and gas
is found in the Buchholz, oil samples must be sent to the lab for DGA
for extensive testing. Consult with the manufacturer or other transformer
experts.
This should activate the alarm. If the alarm does not activate,
test the relay and replace it with new one if it fails to function.
OFF-LINE (DE-ENERGIZED) MAINTENANCE
INSPECTION
1. Insulation Resistance Test – IEEE Standard no.43
R – Vt + 1, R = kV + 1
R= Recommended minimum resistance at 40oC
Vt = rated machine terminal to terminal potential, in rms kilovolts
2. Polarization Index – The steepness of the dielectric absorption curve taken
At a given temperature indicates the relative dryness of the insulation at a
constant voltage
Polarization Index = R10/R1
Values should be 1.3 -1.6 for 60/30 second ratio and 2-4 for 10/1 minute ratio
3.Insulation Power Factor Test – The purpose of this test is to determine the
state of dryness of the winding and insulation system and to determine a power
factor for the overall insulation, including bushing, oil and winding.
The power Factor should not exceed 0.5% at 20oC.
4. Winding resistance test – To check for the loose connection, broken strands,
and high contact resistance in the winding and in the tap changer.
Result are compared to other phases in wye connection or between pairs of
terminal on delta connected winding to determine if a resistance is to high.
Value of 5% of any of the above comparison is consider satisfactory.
5. Transformer Turn Ratio (TTR) – TTR detects shorted turns which indicates
insulation failures by determining if the correct turns ratio exist. Shorted turns
may result from short circuit or dielectric (insulation) failure.
The ratio obtained from the field test should conform with the factory data,
within 0.5%’
New transformer of good quality normally within 0.1%