CEB2083 PROCESS INSTRUMENTATION & CONTROL
MAY 2020 SEMESTER
Chapter 8:
Feedback Controllers
BY
Assoc. Prof. Dr Marappagounder Ramasamy / Dr Serene Lock /
Dr Mohd Hilmi Noh / Dr Nurul Aini Amran
UNIVERSITI TEKNOLOGI PETRONAS (UTP)
Chapter Objectives
End of this chapter, you should be able to:
1. Explain the concept of feedback control
2. Explain P, I and D controllers
Course learning outcomes
CLO1
Develop dynamic models of chemical processes
CLO2
Design feedback control systems using modern IT tools
CLO3
Select appropriate instruments for control systems
Introduction
Consider the following blending process (Fig. 8.1).
Control system
Control objective: To keep the tank exit composition x at the
01
desired setpoint by adjusting w2.
02 Measurement: Composition Analyzer-Transmitter (AT)
03 Feedback controller (AC): Automatic Controller
04 Final control element: Pneumatic control valve
05 Current-to-pneumatic (I/P) transducer
Historical Perspective:
5
1980s
4 Use of digital hardware.
3
1960s
Computer applications.
2 1950s
Electronic counterparts in the market.
1 1940s
Widespread acceptance of pneumatic PID controllers.
1930s
Commercial Three-mode controllers with proportional,
integral and derivative (PID) feedback control action.
A Simple Example of Feedback Control
Figs. 8.2 & 8.3: Flow control system/loop (top) and its block diagram (bottom).
Feedback Control Error
In feedback control, the objective is
to reduce the error signal to zero.
Define an error signal, e, by
e(t ) y SP (t ) y m (t ) (6.1)
where y sp = set point
y m = measured value of the controlled variable
(or equivalent signal from transmitter)
Proportional, Integral and Derivative
Three Mode Controller
Proportional Control
For proportional control, the controller
output is proportional to the error signal,
p(t) p K c e(t) (6.2)
where
p(t) = controller output
p = bias value (adjustable, manual reset)
Kc = controller gain (dimensionless, adjustable, tuning)
Proportional Band, PB:
100% (6.3)
01 Definition : PB
Kc
02 Applies when Kc is dimensionless
03 Small (narrow) PB corresponds to large Kc
04 Large (wide) PB corresponds to small Kc
Proportional controller
In order to derive the transfer function for an ideal
proportional controller, define a deviation variable as
p (t ) p(t ) p (6.4)
Then (6.2) can be written as
p (t ) K c e(t ) (6.5)
Taking Laplace transform of (6.5) and rearranging we
get
P ( s )
Kc (6.6)
E ( s)
Typical Response of Proportional Control
Remarks
An inherent limitation of proportional controller is that a
steady-state error (offset) occurs after a set-point change
or a sustained disturbance.
Offset can be eliminated by manually resetting either the
set-point or bias after an offset occurs – impractical.
Ideal vs. actual
Ideal controller does not
include physical limits
A controller saturates when its
output reaches a physical limit,
either pmax or pmin.
Reverse or Direct Acting Controller
Kc can be made positive or negative
Reverse-Acting (Kc > 0)
Controller output (p) increases as
input signal, ym(t), decreases
p p K c e p K c ( ySP ym )
Direct-Acting (Kc < 0)
Controller output (p) increases as
input signal, ym(t), increases
Integral Control
(reset control, floating control)
For integral action, the controller output depends on the
integral of the error signal over time,
1
e(t)dt
t
p(t) p (6.7)
I 0
where τ1 is an adjustable parameter and referred to as the
integral time constant or reset time, has units of time.
The transfer function: P (s) 1 (6.8)
E(s) I s
Integral Control
01 An important practical advantage: Eliminates offset.
For the process being controlled to be at steady state, the controller
02 output p must be constant so that the manipulated variable is also
constant.
03 Eq. (6.7) implies that p changes with time unless e(t) = 0.
This desirable situation occurs unless the controller output or the final
04 control element saturates.
The control action by the integral controller is very little until the error
05 signal has persisted for sometime.
On the other hand, proportional controller takes immediate corrective
06 action as soon as an error is detected.
Integral Control
PI Controller
Integral control is used in conjunction with proportional
control as the proportional-integral (PI) controller:
1
t
p(t ) p K c e(t ) e(t )dt (6.9)
I 0
The corresponding transfer function is:
P(s) 1
K c 1 (6.10)
E(s) Is
PI Controller
The response of the PI controller to a unit step change
in e(t) is shown in Fig.
Figure 8.6 Response of proportional-integral controller to unit step change in e(t).
1/τ1 – repeats per minute, aka, reset rate.
PI Controller - Disadvantages
Produces oscillatory
response – reduces the
stability of the feedback
control system
Reset windup
When a sustained error occurs, the integral term becomes
quite large and the controller output eventually saturates –
reset windup or integral windup.
Antireset windup : Temporarily halting the integral
action whenever the control output saturates.
Reset windup
SP =setpoint
PV =process
variable to
control
Valve
movement
Anti windup
Derivative control
(Rate action, pre-act, anticipatory control )
Anticipate the future error by considering its rate of
change.
For ideal derivative action,
de(t ) (6.11)
p(t ) p D
dt
where τD is the derivative time, and has units of time.
As long as the error is constant de/dt = 0, the
controller output is equal to p .
Derivative control
Derivative action is never used alone.
Always used in conjunction with P or PI control.
PD controller has the transfer function
P (s)
K c 1 D s (6.12)
E(s)
The derivative control action tends to stabilize the
controlled process.
PID Controller
PID control algorithm is given by
t
de(t )
1 (6.13)
p (t ) p K c e(t )
I e(t )dt D
0
dt
Transfer function of an ideal controller (parallel form)
P (s) 1
K c 1 D s (6.14)
E(s) Is
Transfer function – actual (Series form)
P(s) s 1 D s 1
K c I (6.15)
E(s) I s D s 1
= [0.05 … 0.2] Derivative filter
ON-OFF controllers
(“two-position” or “bang-bang” controllers)
More practical controller
Ideal controller (Dead band)
Special case of proportional controller with very
high gain.
Typical responses of Feedback control systems
Consider response of a controlled system after a sustained
disturbance occurs (e.g. step change in load variable)
No control
New steady state is reached
P control
Offset reduced
PI control
Offset eliminated
Oscillatory response
PID control
Oscillations reduced
Response time reduced
Too small a value of Kc
Sluggish response
Larger deviation
Too large a value of Kc
Exhibit oscillatory or unstable behavior
Intermediate values of Kc is desirable
Increasing τD tends to improve the
response by reducing the maximum
deviation, response time, and degree
of oscillation
If τD is too large, measurement noise is
amplified and the response may
become oscillatory.
Increasing tI makes the controller more sluggish.
Offset will be eliminated for all values of tI.
For large values of tI, it takes very long time to
return to the set-point.
Summary
Inexpensive
Two Position
01
(On-Off):
Extremely simple
Simple
Inherently stable when properly tuned
02 Proportional:
Experiences offset at steady state
Easy to tune
Summary
No offset
Proportional Better dynamic response than reset
03
+ Integral: alone
Possibilities exist for instability due to
lag introduced
Stable
Proportional Less offset than proportional alone
04 + Derivative: (use of higher gain possible).
Faster response time.
Summary
Proportional + Integral + Derivative :
Best control
Most Rapid Difficult to
No offset if properly
complex response tune
tuned
Conclusion
You have been introduced to the:
01 Concept of feedback control
P, I, D controller modes
02 - ON-OFF as a special case of P-controller
03 Advantages and disadvantages
04 Motivation for additional modes