You are on page 1of 5

संदभर्/Ref : CC-ENGG-TR201617-1000701-SS1701-AHU-FDN-DES Date : 10/11/2020

From : S J Lahiri To : Shandong Taikai


Senior GM Longteng Road, High-tech Industrica Tai'an
271000
271000

Cc : Ch. GM (NERPSIP)

Subject : Substation Package: SS02 (GIS) for Up-gradation of 132kV Jiribam ,132kV Aizawl, 132kV Kumarghat
and 132kV Haflong Substations of POWERGRID from AIS to GIS under NERSS-VIII
LOA Ref : CC-CS/775-NER/GIS-3814/3/G7/CA-I/8771 Dated 10/01/2019

Please find enclosed following drawings/ documents for necessary action at your end.
Vendor Drg. No. : AHU FOUNDATION DESIGN
Orgn. Drg. No. : TR201617-1000701-SS1701-AHU-FDN-DES
Revision No. : 00
Drg. Title : AIZAWL S/S- GIS BUILDING (PEB) - AHU FOUNDATION DESIGN
App. Category : CAT-I
Release Date : 10/11/2020

Comments : Document is generally in order.

अनुमोिदत श्रेणी/App. Category:

I. फेिब्रकेशन/िनमार्ण/टाइप टेिस्टंग हेतु जारी।


Approved/released for fabrication/construction.
II. फेिब्रकेशन/िनमार्ण/टाइप टेिस्टंग हेतु अनुमोिदत/जारी बशतेर् िदए गए िटप्पिणयाँ एवं आशोधनों की सिम्मिलत िकया जाये। कृपया िरवाइजड दस्तावेज अनुमोदनाथर् प्रस्तुत
करें।
Approved/released for fabrication/ construction subject to incorporation of comments and modification as noted. Revised
drawing required for approval.
III. िटप्पिणयाँ सिम्मिलत करने के उपरांत दस्तावेज को अनुमोदनाथर् प्रस्तुत करें।
To be resubmitted for approval after incorporating the comments.
IV. सूचनाथर् एवं िरकाडर् हेतु।
For information and record.
REL-CON िनमार्ण हेतु जारी।
Released for construction.

नोट/Note:

1. Approval/Comments conveyed herein neither relieve the contractor of his contractual obligations and his responsibilities, weights,
quantities, design details assemble fits, performance particulars and conformity of the supplies with the Indian Statutory Laws as
may be applicable, nor does it limits the purchaser's right under the contract.
2. The approval conveyed vide this letter does not cover the approval of make for sub-vendor items.

केन्द्रीय कायार्लय: “सौदािमनी“, प्लॉट नंबर 2, सेक्टर -29, गुरुग्राम -122001, (हिरयाणा) ,दूरभाष: 0124-2571700-719
Corporate Office: “Saudamini“, Plot No. 2, Sector-29, Gurugram-122001, (Haryana) Tel.: 0124-2571700-719
पंजीकृत कायार्लय: बी -9, कुतुब इं स्टीट्यूशनल एिरया, कटवािरया सराय, नई िदल्ली -110016. दूरभाष: 011-26560112, 26560121, 26564812, 26564892, सीआईएन: L40101DL1989GOI038121
Registered Office: B-9, Qutab Institutional Area, Katwaria Sarai, New Delhi-110016. Tel: 011-26560112, 26560121, 26564812, 26564892, CIN : L40101DL1989GOI038121
Website: www.powergridindia.com
TR201617-1000701-SS1701-AHU-FDN-DES/00/CAT-I/Page: 1 of 4

MVP AVS NMP FOR APPROVAL 23.10.2020 0

DSGND CHKD APPRD DATE REV


REVISIONS

OWNER POWERGRID CORPORATION OF INDIA LIMITED

EPC
GODREJ & BOYCE MFG . CO . LTD .
CONTRACTOR
GIS
SHANDONG TAIKAI HIGH VOLT SWITCHGEAR CO. LTD
SUPPLIER

SUBSTATION PACKAGE - SS02 (GIS) :-NERSS-VIII UPGRADATION OF 132kV AIZAWL


PROJECT
SUBSTATION FROM AIS TO GIS
SUPPLY
LOI.NO. ERECTION CC-CS/775-NER/GIS-3814/3/G7/NOA-111/8773 DATED 13.11.2018
CIVIL

TITLE AIZAWL GIS BUILDING (PEB) - AHU FOUNDATION DESIGN

SHEET DATE REVISION


DRG.NO. SVP010072-AZL-C-DOC-24
1 OF 4 23.10.2020 0
TR201617-1000701-SS1701-AHU-FDN-DES/00/CAT-I/Page: 2 of 4

INDEX

SR NO. DESCRIPTION PAGE NO.


1 DESIGN OF BLOCK FOUNDATION 03
TR201617-1000701-SS1701-AHU-FDN-DES/00/CAT-I/Page: 3 of 4
TR201617-1000701-SS1701-AHU-FDN-DES/00/CAT-I/Page: 4 of 4

BLOCK FOUNDATION FOR AHU ROOM

## GENERAL DATA

** AHU ROOM
→ TOTAL LOAD ON AREA (ASSUME) P1 = 10.50 KN
3
→ Density of Concrete considered = 25.00 KN/M
→ Block Area Considered for Design ( L' x B' ) = 1.33 x 0.81 M
→ Thickness of block considered 300.00 mm

→ Total load on Floor (P1+P2) = 18.57 KN


2
→ gross pressure of block foundation PR= 17.26 KN/M
= Total load / ( L' x B' )
2
→ Assumed safe bearing pressure at SBC = 50.00 KN/M
block foundaiton depth (5 Ton/SQM)
→ block foundation capacity SAFE

→ Min. Ast Required as per clause 5.4.5 = 5.65 sq. cm


of IS 2974 (part-1) is 25 kg per CUM or
5.65 SQCM
→ Provide 10 mm dia @ 125 mm C/C = 6.28 sq. cm
BOTH WAYS HENCE SAFE