You are on page 1of 32

MATERIAL AND DESIGN DATA

Code of Practice fcu (N/mm²) Ec, (N/mm²) fy (N/mm²) fyv (N/mm²) γc γs


BS8110 : 1997 30 24597 460 460 1.5 1.05

Cover (mm) Side Cover (mm) Conc. Unit Weight (kN/m³) Steel Unit Weight (kg/m³)
25 25 24 7860

Beam Design Detail Report


DETAIL CALCULATION FOR BEAM GB9(225x450/600/450)
Beam Located along grid 1/D1-A2
Number of Span within beam = 8
Number of Section defined by user = 8
Number of Supports = 7
Beam Cantilever End = Both

Section Dimension Data


Length Width Begin Depth End Depth
Span Section
(mm) (mm) (mm) (mm)
1 1 1075 225 450 450
2 2 3100 225 450 450
3 3 2000 225 450 450
4 4 3500 225 600 600
5 5 3350 225 450 450
6 6 2300 225 450 450
7 7 4550 225 450 450
8 8 1563 225 450 450

MATERIAL PROPERTIES
Maximum Concrete Strain, Ecc = 0.0035
Average Concrete Stress above Neutral Axis, k1 = 12.12 N/mm²
Concrete Lever Arm Factor, k2 = 0.4518
Limiting Effective Depth Factor, cb = 0.50
k2 / k1 Factor, kkk = 0.0373
Limiting Concrete Moment Capacity Factor, kk1 = cb × k1 × (1 - cb * k2) = 0.50 × 12.12 × (1 - 0.50 × 0.4518) = 4.6911 N/mm²

BEAM GB9(225x450/600/450) SPAN NO. 1

FLEXURAL DESIGN CALCULATION

LOCATION : RIGHT SUPPORT


Design Bending Moment = 13.1 kNm Width, b = 225.0 mm Effective Depth, d = 409.0 mm
Mu / bd² = 13.1 × 1000000 / (225.0 × 409.0²) = 0.349 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.349 <= 4.691

Design as Singly Reinforced Rectangular Beam


Concrete Neutral Axis, x = 11.946 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 11.946 / 1000 = 32.58 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 32.58 × 1000 / (460 / 1.05) = 75 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 32.58 × (409.0 - 0.4518 × 11.946) / 1000 = 13.1 kNm
Maximum Depth of Section = 450.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 450.0 = 132 mm²

Top Tension Steel Area Required = 132 mm²


Bottom Compression Steel Area Required = 132 mm²
Top Reinforcement Provided = 2T12 (226 mm²)
Bottom Reinforcement Provided = 2T12 (226 mm²)

LOCATION : 1/4 SPAN


Design Bending Moment = 6.9 kNm Width, b = 225.0 mm Effective Depth, d = 409.0 mm
Mu / bd² = 6.9 × 1000000 / (225.0 × 409.0²) = 0.184 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.184 <= 4.691

Design as Singly Reinforced Rectangular Beam


Concrete Neutral Axis, x = 6.253 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 6.253 / 1000 = 17.05 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 17.05 × 1000 / (460 / 1.05) = 39 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 17.05 × (409.0 - 0.4518 × 6.253) / 1000 = 6.9 kNm
Maximum Depth of Section = 450.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 450.0 = 132 mm²

Top Tension Steel Area Required = 132 mm²


Bottom Compression Steel Area Required = 132 mm²

Top Reinforcement Provided = 2T12 (226 mm²)


Bottom Reinforcement Provided = 2T12 (226 mm²)

SHEAR & TORSION DESIGN CALCULATION


LOCATION : SECTION 1 (B:-75 mm E:1000 mm from left grid of span)

Maximum Torsion within Zone, T = 0.0 kNm


Shear at Location of Maximum Torsion, V = 16.4 kN
Link Horizontal Dimension, h1 = b - 2 × Side Cover - DiaLink = 225 - 2 × 25 - 10 = 165 mm
Link Vertical Dimension, v1 = h - 2 × Cover - DiaLink = 450 - 2 × 25 - 10 = 390 mm
Dimension x1 = Min (h1, v1) = 165 mm, y1 = Max (h1, v1) = 390 mm

Section Dimension: Dmin = 225.0 mm, Dmax = 450.0 mm


Torsion Stress, νst = 2 × T × 106 / (Dmin² × (Dmax - Dmin / 3)) = 0.00 N/mm²
Effective depth, d = 409.0 mm
Shear Stress, νss = V × 1000 / (b × d) = 16.4 × 1000 / (225.0 × 409.0) = 0.18 N/mm²

Part 2 : Clause 2.4.6 and Table 2.3


Maximum Combined Stress Allowed, νtu = Min (0.8 × √fcu, 5) = 4.38 N/mm²
Total Stress, νTot = νss + νst = 0.18 + 0.00 = 0.18 N/mm² ≤ νtu (4.38 N/mm²)
Checking for Combined Stress Allowed Pass

Part 2: Clause 2.4.5


Additional Checking While Small Cross Section (y1 < 550 mm)
Larger Link Dimension, y1 = 390.0 mm < 550 mm
νtu × y1 / 550 = 4.38 × 390.0 / 550 = 3.11 N/mm²
νst = 0.00 N/mm² ≤ 3.11 N/mm²
Checking for Torsion Stress Allowed Pass

Part 2 : Clause 2.4.6 Table 2.3


Torsion Strength contributed by concrete, νt,min = Min (0.067 × √fcu, 0.4) = 0.37 N/mm²
Torsion Stress, νst = 0.00 N/mm² < νt,min = 0.37 N/mm² -> No Torsion Reinforcement is needed

Maximum Shear within Zone, V = 16.1 kN


Maximum Shear Stress Allowed, νMax = Min (0.8 × √30, 5) = 4.38 N/mm² - Clause 3.4.5.2
Shear Stress, νss = V × 1000 / (b × d) = 16.1 × 1000 / (225.0 × 409.0) = 0.17 N/mm² ≤ νMax (4.38 N/mm²)
Checking for Maximum Shear Stress Allowed Pass

Tension Steel Area Provided, Ast = 226 mm²


- Table 3.8: Values of νc, design concrete shear stress
Steel Percentage, 100 × As / (bv × d) = 0.25 % ≤ 3.0 %
Effective Depth Ratio, edr = 400 / d = 400 / 409.0 = 0.978
(400 / d)^ ¼ = 0.994 < 1, (400 / d)^ ¼ taken as 1
Minimum fcu, fcuMin = 25 N/mm², Concrete Grade Ratio, Min(fcu, 40) / fcuMin = 30 / 25 = 1.200
Concrete Shear Capacity, νc = 0.79 {100 As / (bv d)}⅓ (400 / d)¼ (fcu / 25)⅓ / γm
= 0.79 × {0.25}⅓ × 1.000 × (1.200)⅓ / 1.25 = 0.42 N/mm²
Minimum Design Shear Stress, νMin = 0.40 N/mm²
νss = 0.175 < νc + 0.4, Provides only minimum link
Design for minimum Shear Stress, νd = νmin = 0.40 N/mm²
Shear Link Area / Spacing Ratio, SAsv_Sv = (vd × b) / (fyy × fy) = (0.40 × 225) / (0.95 × 460) = 0.205 mm²/mm

Shear Reinforcement Provided : T10-250 (Link spacing is governed by user setting)


Shear Link Area / Spacing Ratio Provided = 0.628 mm²/mm > 0.205 mm²/mm

DEFLECTION CHECKING FOR SPAN


Basic Span / Effective Depth Ratio, Br = 7.0
Span Length, l = 1075.0 mm, Effective Depth, d = 409.0 mm
Actual Span / Effective Depth Ratio, Ar = 2.6
Ultimate Design Moment, Mu = 13.1 kNm
Design Steel Strength, fy = 460.0 N/mm²
Tension Steel Area Required, AsReq = 132 mm²
Tension Steel Area Provided, AsProv = 226 mm²
Compression Steel Area Provided, AsProv (Comp.) = 226 mm²

- Checking for deflection is based on BS8110: 1997


- Table 3.9: Basic span / effective depth ratio for rectangular or flange beams
- Table 3.10: Modification factor for tension reinforcement
- Table 3.11: Modification factor for compression reinforcement

Design Service Stress in Tension Reinforcement, Equation 8


fs = {(2 × fy × AsReq) / (3 × AsProv)} × (1 / ßb)
= {(2 × 460.0 × 132) / (3 × 226)} × (1 / 1.00) = 178.5 N/mm²

Modification Factor for Tension Reinforcement, Equation 7


MFt = 0.55 + {(477 - fs) / (120 × (0.9 + (M/bd²)))}
= 0.55 + {(477 - 178.5) / (120 × (0.9 + (13.1 × 1000000 / (225 × 409.0²)))}
= 2.54 > 2.0
MFt taken as 2.0

New Modification Factor for Compression Reinforcement, Equation 9


MFc = 1 + {(100 × AsProv / (b × d)) / (3 + (100 × AsProv / (b × d)))}
= 1 + {(100 × 226 / (225.0 × 409.0)) / (3 + (100 × 226 / (225.0 × 409.0)))}
= 1.08 <= 1.5

New Deflection Ratio = (Br × MFt × MFc) / Ar = (7.0 × 2.00 × 1.08) / 2.6 = 5.73
Ratio >= 1.0 : Deflection Checked PASSED

BEAM GB9(225x450/600/450) SPAN NO. 2

FLEXURAL DESIGN CALCULATION


LOCATION : SPAN
Design Bending Moment = 1.4 kNm Width, b = 225.0 mm Effective Depth, d = 409.0 mm
Mu / bd² = 1.4 × 1000000 / (225.0 × 409.0²) = 0.038 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.038 <= 4.691

Design as Singly Reinforced Rectangular Beam


Concrete Neutral Axis, x = 1.287 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 1.287 / 1000 = 3.51 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 3.51 × 1000 / (460 / 1.05) = 9 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 3.51 × (409.0 - 0.4518 × 1.287) / 1000 = 1.4 kNm
Maximum Depth of Section = 450.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 450.0 = 132 mm²

Top Compression Steel Area Required = 132 mm²


Bottom Tension Steel Area Required = 132 mm²

Top Reinforcement Provided = 2T12 (226 mm²)


Bottom Reinforcement Provided = 2T12 (226 mm²)

LOCATION : LEFT SUPPORT


Design Bending Moment = 13.2 kNm Width, b = 225.0 mm Effective Depth, d = 409.0 mm
Mu / bd² = 13.2 × 1000000 / (225.0 × 409.0²) = 0.351 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.351 <= 4.691

Design as Singly Reinforced Rectangular Beam


Concrete Neutral Axis, x = 11.998 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 11.998 / 1000 = 32.72 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 32.72 × 1000 / (460 / 1.05) = 75 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 32.72 × (409.0 - 0.4518 × 11.998) / 1000 = 13.2 kNm
Maximum Depth of Section = 450.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 450.0 = 132 mm²

Top Tension Steel Area Required = 132 mm²


Bottom Compression Steel Area Required = 132 mm²

Top Reinforcement Provided = 2T12 (226 mm²)


Bottom Reinforcement Provided = 2T12 (226 mm²)

LOCATION : RIGHT SUPPORT


Design Bending Moment = 0.8 kNm Width, b = 225.0 mm Effective Depth, d = 409.0 mm
Mu / bd² = 0.8 × 1000000 / (225.0 × 409.0²) = 0.021 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.021 <= 4.691

Design as Singly Reinforced Rectangular Beam


Concrete Neutral Axis, x = 0.713 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 0.713 / 1000 = 1.94 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 1.94 × 1000 / (460 / 1.05) = 5 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 1.94 × (409.0 - 0.4518 × 0.713) / 1000 = 0.8 kNm
Maximum Depth of Section = 450.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 450.0 = 132 mm²

Top Tension Steel Area Required = 132 mm²


Bottom Compression Steel Area Required = 132 mm²

LOCATION : RIGHT SUPPORT SAGGING MOMENT


Design Bending Moment = 1.4 kNm Width, b = 225.0 mm Effective Depth, d = 409.0 mm
Mu / bd² = 1.4 × 1000000 / (225.0 × 409.0²) = 0.038 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.038 <= 4.691

Design as Singly Reinforced Rectangular Beam


Concrete Neutral Axis, x = 1.287 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 1.287 / 1000 = 3.51 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 3.51 × 1000 / (460 / 1.05) = 9 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 3.51 × (409.0 - 0.4518 × 1.287) / 1000 = 1.4 kNm
Maximum Depth of Section = 450.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 450.0 = 132 mm²
Top Compression Steel Area Required = 132 mm²
Bottom Tension Steel Area Required = 132 mm²

Top Reinforcement Provided = 2T12 (226 mm²)


Bottom Reinforcement Provided = 2T12 (226 mm²)

LOCATION : 1/4 SPAN


Design Bending Moment = 6.3 kNm Width, b = 225.0 mm Effective Depth, d = 409.0 mm
Mu / bd² = 6.3 × 1000000 / (225.0 × 409.0²) = 0.168 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.168 <= 4.691

Design as Singly Reinforced Rectangular Beam


Concrete Neutral Axis, x = 5.701 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 5.701 / 1000 = 15.55 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 15.55 × 1000 / (460 / 1.05) = 36 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 15.55 × (409.0 - 0.4518 × 5.701) / 1000 = 6.3 kNm
Maximum Depth of Section = 450.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 450.0 = 132 mm²

Top Tension Steel Area Required = 132 mm²


Bottom Compression Steel Area Required = 132 mm²

Top Reinforcement Provided = 2T12 (226 mm²)


Bottom Reinforcement Provided = 2T12 (226 mm²)

SHEAR & TORSION DESIGN CALCULATION


LOCATION : SECTION 1 LEFT SUPPORT
(B:0 mm E:775 mm from left grid of span)

Maximum Torsion within Zone, T = 0.0 kNm


Shear at Location of Maximum Torsion, V = 10.1 kN
Link Horizontal Dimension, h1 = b - 2 × Side Cover - DiaLink = 225 - 2 × 25 - 10 = 165 mm
Link Vertical Dimension, v1 = h - 2 × Cover - DiaLink = 450 - 2 × 25 - 10 = 390 mm
Dimension x1 = Min (h1, v1) = 165 mm, y1 = Max (h1, v1) = 390 mm

Section Dimension: Dmin = 225.0 mm, Dmax = 450.0 mm


Torsion Stress, νst = 2 × T × 106 / (Dmin² × (Dmax - Dmin / 3)) = 0.00 N/mm²
Effective depth, d = 409.0 mm
Shear Stress, νss = V × 1000 / (b × d) = 10.1 × 1000 / (225.0 × 409.0) = 0.11 N/mm²

Part 2 : Clause 2.4.6 and Table 2.3


Maximum Combined Stress Allowed, νtu = Min (0.8 × √fcu, 5) = 4.38 N/mm²
Total Stress, νTot = νss + νst = 0.11 + 0.00 = 0.11 N/mm² ≤ νtu (4.38 N/mm²)
Checking for Combined Stress Allowed Pass

Part 2: Clause 2.4.5


Additional Checking While Small Cross Section (y1 < 550 mm)
Larger Link Dimension, y1 = 390.0 mm < 550 mm
νtu × y1 / 550 = 4.38 × 390.0 / 550 = 3.11 N/mm²
νst = 0.00 N/mm² ≤ 3.11 N/mm²
Checking for Torsion Stress Allowed Pass

Part 2 : Clause 2.4.6 Table 2.3


Torsion Strength contributed by concrete, νt,min = Min (0.067 × √fcu, 0.4) = 0.37 N/mm²
Torsion Stress, νst = 0.00 N/mm² < νt,min = 0.37 N/mm² -> No Torsion Reinforcement is needed

Maximum Shear within Zone, V = 9.7 kN


Maximum Shear Stress Allowed, νMax = Min (0.8 × √30, 5) = 4.38 N/mm² - Clause 3.4.5.2
Shear Stress, νss = V × 1000 / (b × d) = 9.7 × 1000 / (225.0 × 409.0) = 0.11 N/mm² ≤ νMax (4.38 N/mm²)
Checking for Maximum Shear Stress Allowed Pass

Tension Steel Area Provided, Ast = 226 mm²


- Table 3.8: Values of νc, design concrete shear stress
Steel Percentage, 100 × As / (bv × d) = 0.25 % ≤ 3.0 %
Effective Depth Ratio, edr = 400 / d = 400 / 409.0 = 0.978
(400 / d)^ ¼ = 0.994 < 1, (400 / d)^ ¼ taken as 1
Minimum fcu, fcuMin = 25 N/mm², Concrete Grade Ratio, Min(fcu, 40) / fcuMin = 30 / 25 = 1.200
Concrete Shear Capacity, νc = 0.79 {100 As / (bv d)}⅓ (400 / d)¼ (fcu / 25)⅓ / γm
= 0.79 × {0.25}⅓ × 1.000 × (1.200)⅓ / 1.25 = 0.42 N/mm²
Minimum Design Shear Stress, νMin = 0.40 N/mm²
νss = 0.106 < νc + 0.4, Provides only minimum link
Design for minimum Shear Stress, νd = νmin = 0.40 N/mm²
Shear Link Area / Spacing Ratio, SAsv_Sv = (vd × b) / (fyy × fy) = (0.40 × 225) / (0.95 × 460) = 0.205 mm²/mm

Shear Reinforcement Provided : T10-250 (Link spacing is governed by user setting)


Shear Link Area / Spacing Ratio Provided = 0.628 mm²/mm > 0.205 mm²/mm

LOCATION : SECTION 1 MIDDLE ZONE


(B:775 mm E:2325 mm from left grid of span)

Maximum Torsion within Zone, T = 0.0 kNm


Shear at Location of Maximum Torsion, V = 6.5 kN
Link Horizontal Dimension, h1 = b - 2 × Side Cover - DiaLink = 225 - 2 × 25 - 10 = 165 mm
Link Vertical Dimension, v1 = h - 2 × Cover - DiaLink = 450 - 2 × 25 - 10 = 390 mm
Dimension x1 = Min (h1, v1) = 165 mm, y1 = Max (h1, v1) = 390 mm

Section Dimension: Dmin = 225.0 mm, Dmax = 450.0 mm


Torsion Stress, νst = 2 × T × 106 / (Dmin² × (Dmax - Dmin / 3)) = 0.00 N/mm²
Effective depth, d = 409.0 mm
Shear Stress, νss = V × 1000 / (b × d) = 6.5 × 1000 / (225.0 × 409.0) = 0.07 N/mm²

Part 2 : Clause 2.4.6 and Table 2.3


Maximum Combined Stress Allowed, νtu = Min (0.8 × √fcu, 5) = 4.38 N/mm²
Total Stress, νTot = νss + νst = 0.07 + 0.00 = 0.07 N/mm² ≤ νtu (4.38 N/mm²)
Checking for Combined Stress Allowed Pass

Part 2: Clause 2.4.5


Additional Checking While Small Cross Section (y1 < 550 mm)
Larger Link Dimension, y1 = 390.0 mm < 550 mm
νtu × y1 / 550 = 4.38 × 390.0 / 550 = 3.11 N/mm²
νst = 0.00 N/mm² ≤ 3.11 N/mm²
Checking for Torsion Stress Allowed Pass

Part 2 : Clause 2.4.6 Table 2.3


Torsion Strength contributed by concrete, νt,min = Min (0.067 × √fcu, 0.4) = 0.37 N/mm²
Torsion Stress, νst = 0.00 N/mm² < νt,min = 0.37 N/mm² -> No Torsion Reinforcement is needed

Maximum Shear within Zone, V = 6.5 kN


Maximum Shear Stress Allowed, νMax = Min (0.8 × √30, 5) = 4.38 N/mm² - Clause 3.4.5.2
Shear Stress, νss = V × 1000 / (b × d) = 6.5 × 1000 / (225.0 × 409.0) = 0.07 N/mm² ≤ νMax (4.38 N/mm²)
Checking for Maximum Shear Stress Allowed Pass

Tension Steel Area Provided, Ast = 226 mm²


- Table 3.8: Values of νc, design concrete shear stress
Steel Percentage, 100 × As / (bv × d) = 0.25 % ≤ 3.0 %
Effective Depth Ratio, edr = 400 / d = 400 / 409.0 = 0.978
(400 / d)^ ¼ = 0.994 < 1, (400 / d)^ ¼ taken as 1
Minimum fcu, fcuMin = 25 N/mm², Concrete Grade Ratio, Min(fcu, 40) / fcuMin = 30 / 25 = 1.200
Concrete Shear Capacity, νc = 0.79 {100 As / (bv d)}⅓ (400 / d)¼ (fcu / 25)⅓ / γm
= 0.79 × {0.25}⅓ × 1.000 × (1.200)⅓ / 1.25 = 0.42 N/mm²
Minimum Design Shear Stress, νMin = 0.40 N/mm²
νss = 0.071 < νc + 0.4, Provides only minimum link
Design for minimum Shear Stress, νd = νmin = 0.40 N/mm²
Shear Link Area / Spacing Ratio, SAsv_Sv = (vd × b) / (fyy × fy) = (0.40 × 225) / (0.95 × 460) = 0.205 mm²/mm

Shear Reinforcement Provided : T10-250 (Link spacing is governed by user setting)


Shear Link Area / Spacing Ratio Provided = 0.628 mm²/mm > 0.205 mm²/mm

LOCATION : SECTION 1 RIGHT SUPPORT


(B:2325 mm E:3100 mm from left grid of span)

Maximum Torsion within Zone, T = 0.0 kNm


Shear at Location of Maximum Torsion, V = 2.6 kN
Link Horizontal Dimension, h1 = b - 2 × Side Cover - DiaLink = 225 - 2 × 25 - 10 = 165 mm
Link Vertical Dimension, v1 = h - 2 × Cover - DiaLink = 450 - 2 × 25 - 10 = 390 mm
Dimension x1 = Min (h1, v1) = 165 mm, y1 = Max (h1, v1) = 390 mm

Section Dimension: Dmin = 225.0 mm, Dmax = 450.0 mm


Torsion Stress, νst = 2 × T × 106 / (Dmin² × (Dmax - Dmin / 3)) = 0.00 N/mm²
Effective depth, d = 409.0 mm
Shear Stress, νss = V × 1000 / (b × d) = 2.6 × 1000 / (225.0 × 409.0) = 0.03 N/mm²

Part 2 : Clause 2.4.6 and Table 2.3


Maximum Combined Stress Allowed, νtu = Min (0.8 × √fcu, 5) = 4.38 N/mm²
Total Stress, νTot = νss + νst = 0.03 + 0.00 = 0.03 N/mm² ≤ νtu (4.38 N/mm²)
Checking for Combined Stress Allowed Pass

Part 2: Clause 2.4.5


Additional Checking While Small Cross Section (y1 < 550 mm)
Larger Link Dimension, y1 = 390.0 mm < 550 mm
νtu × y1 / 550 = 4.38 × 390.0 / 550 = 3.11 N/mm²
νst = 0.00 N/mm² ≤ 3.11 N/mm²
Checking for Torsion Stress Allowed Pass

Part 2 : Clause 2.4.6 Table 2.3


Torsion Strength contributed by concrete, νt,min = Min (0.067 × √fcu, 0.4) = 0.37 N/mm²
Torsion Stress, νst = 0.00 N/mm² < νt,min = 0.37 N/mm² -> No Torsion Reinforcement is needed

Maximum Shear within Zone, V = 2.6 kN


Maximum Shear Stress Allowed, νMax = Min (0.8 × √30, 5) = 4.38 N/mm² - Clause 3.4.5.2
Shear Stress, νss = V × 1000 / (b × d) = 2.6 × 1000 / (225.0 × 409.0) = 0.03 N/mm² ≤ νMax (4.38 N/mm²)
Checking for Maximum Shear Stress Allowed Pass

Tension Steel Area Provided, Ast = 226 mm²


- Table 3.8: Values of νc, design concrete shear stress
Steel Percentage, 100 × As / (bv × d) = 0.25 % ≤ 3.0 %
Effective Depth Ratio, edr = 400 / d = 400 / 409.0 = 0.978
(400 / d)^ ¼ = 0.994 < 1, (400 / d)^ ¼ taken as 1
Minimum fcu, fcuMin = 25 N/mm², Concrete Grade Ratio, Min(fcu, 40) / fcuMin = 30 / 25 = 1.200
Concrete Shear Capacity, νc = 0.79 {100 As / (bv d)}⅓ (400 / d)¼ (fcu / 25)⅓ / γm
= 0.79 × {0.25}⅓ × 1.000 × (1.200)⅓ / 1.25 = 0.42 N/mm²
Minimum Design Shear Stress, νMin = 0.40 N/mm²
νss = 0.028 < νc + 0.4, Provides only minimum link
Design for minimum Shear Stress, νd = νmin = 0.40 N/mm²
Shear Link Area / Spacing Ratio, SAsv_Sv = (vd × b) / (fyy × fy) = (0.40 × 225) / (0.95 × 460) = 0.205 mm²/mm

Shear Reinforcement Provided : T10-250 (Link spacing is governed by user setting)


Shear Link Area / Spacing Ratio Provided = 0.628 mm²/mm > 0.205 mm²/mm
DEFLECTION CHECKING FOR SPAN
Basic Span / Effective Depth Ratio, Br = 26.0
Span Length, l = 3100.0 mm, Effective Depth, d = 409.0 mm
Actual Span / Effective Depth Ratio, Ar = 7.6
Ultimate Design Moment, Mu = 1.4 kNm
Design Steel Strength, fy = 460.0 N/mm²
Tension Steel Area Required, AsReq = 132 mm²
Tension Steel Area Provided, AsProv = 226 mm²
Compression Steel Area Provided, AsProv (Comp.) = 226 mm²

- Checking for deflection is based on BS8110: 1997


- Table 3.9: Basic span / effective depth ratio for rectangular or flange beams
- Table 3.10: Modification factor for tension reinforcement
- Table 3.11: Modification factor for compression reinforcement

Design Service Stress in Tension Reinforcement, Equation 8


fs = {(2 × fy × AsReq) / (3 × AsProv)} × (1 / ßb)
= {(2 × 460.0 × 132) / (3 × 226)} × (1 / 1.00) = 178.5 N/mm²

Modification Factor for Tension Reinforcement, Equation 7


MFt = 0.55 + {(477 - fs) / (120 × (0.9 + (M/bd²)))}
= 0.55 + {(477 - 178.5) / (120 × (0.9 + (1.4 × 1000000 / (225 × 409.0²)))}
= 3.20 > 2.0
MFt taken as 2.0

New Modification Factor for Compression Reinforcement, Equation 9


MFc = 1 + {(100 × AsProv / (b × d)) / (3 + (100 × AsProv / (b × d)))}
= 1 + {(100 × 226 / (225.0 × 409.0)) / (3 + (100 × 226 / (225.0 × 409.0)))}
= 1.08 <= 1.5

New Deflection Ratio = (Br × MFt × MFc) / Ar = (26.0 × 2.00 × 1.08) / 7.6 = 7.38
Ratio >= 1.0 : Deflection Checked PASSED

BEAM GB9(225x450/600/450) SPAN NO. 3

FLEXURAL DESIGN CALCULATION


LOCATION : SPAN
Design Bending Moment = 1.7 kNm Width, b = 225.0 mm Effective Depth, d = 409.0 mm
Mu / bd² = 1.7 × 1000000 / (225.0 × 409.0²) = 0.046 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.046 <= 4.691

Design as Singly Reinforced Rectangular Beam


Concrete Neutral Axis, x = 1.554 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 1.554 / 1000 = 4.24 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 4.24 × 1000 / (460 / 1.05) = 10 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 4.24 × (409.0 - 0.4518 × 1.554) / 1000 = 1.7 kNm
Maximum Depth of Section = 450.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 450.0 = 132 mm²

Top Compression Steel Area Required = 132 mm²


Bottom Tension Steel Area Required = 132 mm²

Top Reinforcement Provided = 2T12 (226 mm²)


Bottom Reinforcement Provided = 2T12 (226 mm²)

LOCATION : LEFT SUPPORT


Design Bending Moment = 0.7 kNm Width, b = 225.0 mm Effective Depth, d = 409.0 mm
Mu / bd² = 0.7 × 1000000 / (225.0 × 409.0²) = 0.020 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.020 <= 4.691

Design as Singly Reinforced Rectangular Beam


Concrete Neutral Axis, x = 0.672 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 0.672 / 1000 = 1.83 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 1.83 × 1000 / (460 / 1.05) = 5 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 1.83 × (409.0 - 0.4518 × 0.672) / 1000 = 0.7 kNm
Maximum Depth of Section = 450.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 450.0 = 132 mm²

Top Tension Steel Area Required = 132 mm²


Bottom Compression Steel Area Required = 132 mm²

LOCATION : LEFT SUPPORT SAGGING MOMENT


Design Bending Moment = 1.6 kNm Width, b = 225.0 mm Effective Depth, d = 409.0 mm
Mu / bd² = 1.6 × 1000000 / (225.0 × 409.0²) = 0.043 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.043 <= 4.691

Design as Singly Reinforced Rectangular Beam


Concrete Neutral Axis, x = 1.443 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 1.443 / 1000 = 3.93 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 3.93 × 1000 / (460 / 1.05) = 9 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 3.93 × (409.0 - 0.4518 × 1.443) / 1000 = 1.6 kNm
Maximum Depth of Section = 450.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 450.0 = 132 mm²

Top Compression Steel Area Required = 132 mm²


Bottom Tension Steel Area Required = 132 mm²

Top Reinforcement Provided = 2T12 (226 mm²)


Bottom Reinforcement Provided = 2T12 (226 mm²)

LOCATION : RIGHT SUPPORT


Design Bending Moment = 3.1 kNm Width, b = 225.0 mm Effective Depth, d = 409.0 mm
Mu / bd² = 3.1 × 1000000 / (225.0 × 409.0²) = 0.083 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.083 <= 4.691

Design as Singly Reinforced Rectangular Beam


Concrete Neutral Axis, x = 2.811 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 2.811 / 1000 = 7.67 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 7.67 × 1000 / (460 / 1.05) = 18 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 7.67 × (409.0 - 0.4518 × 2.811) / 1000 = 3.1 kNm
Maximum Depth of Section = 450.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 450.0 = 132 mm²

Top Tension Steel Area Required = 132 mm²


Bottom Compression Steel Area Required = 132 mm²

Top Reinforcement Provided = 2T12 (226 mm²)


Bottom Reinforcement Provided = 2T12 (226 mm²)

LOCATION : 1/4 SPAN


Design Bending Moment = 1.5 kNm Width, b = 225.0 mm Effective Depth, d = 409.0 mm
Mu / bd² = 1.5 × 1000000 / (225.0 × 409.0²) = 0.039 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.039 <= 4.691
Design as Singly Reinforced Rectangular Beam
Concrete Neutral Axis, x = 1.322 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 1.322 / 1000 = 3.60 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 3.60 × 1000 / (460 / 1.05) = 9 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 3.60 × (409.0 - 0.4518 × 1.322) / 1000 = 1.5 kNm
Maximum Depth of Section = 450.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 450.0 = 132 mm²

Top Tension Steel Area Required = 132 mm²


Bottom Compression Steel Area Required = 132 mm²

Top Reinforcement Provided = 2T12 (226 mm²)


Bottom Reinforcement Provided = 2T12 (226 mm²)

SHEAR & TORSION DESIGN CALCULATION


LOCATION : SECTION 1 LEFT SUPPORT
(B:0 mm E:500 mm from left grid of span)

Maximum Torsion within Zone, T = 0.0 kNm


Shear at Location of Maximum Torsion, V = 3.3 kN
Link Horizontal Dimension, h1 = b - 2 × Side Cover - DiaLink = 225 - 2 × 25 - 10 = 165 mm
Link Vertical Dimension, v1 = h - 2 × Cover - DiaLink = 450 - 2 × 25 - 10 = 390 mm
Dimension x1 = Min (h1, v1) = 165 mm, y1 = Max (h1, v1) = 390 mm

Section Dimension: Dmin = 225.0 mm, Dmax = 450.0 mm


Torsion Stress, νst = 2 × T × 106 / (Dmin² × (Dmax - Dmin / 3)) = 0.00 N/mm²
Effective depth, d = 409.0 mm
Shear Stress, νss = V × 1000 / (b × d) = 3.3 × 1000 / (225.0 × 409.0) = 0.04 N/mm²

Part 2 : Clause 2.4.6 and Table 2.3


Maximum Combined Stress Allowed, νtu = Min (0.8 × √fcu, 5) = 4.38 N/mm²
Total Stress, νTot = νss + νst = 0.04 + 0.00 = 0.04 N/mm² ≤ νtu (4.38 N/mm²)
Checking for Combined Stress Allowed Pass

Part 2: Clause 2.4.5


Additional Checking While Small Cross Section (y1 < 550 mm)
Larger Link Dimension, y1 = 390.0 mm < 550 mm
νtu × y1 / 550 = 4.38 × 390.0 / 550 = 3.11 N/mm²
νst = 0.00 N/mm² ≤ 3.11 N/mm²
Checking for Torsion Stress Allowed Pass

Part 2 : Clause 2.4.6 Table 2.3


Torsion Strength contributed by concrete, νt,min = Min (0.067 × √fcu, 0.4) = 0.37 N/mm²
Torsion Stress, νst = 0.00 N/mm² < νt,min = 0.37 N/mm² -> No Torsion Reinforcement is needed

Maximum Shear within Zone, V = 2.9 kN


Maximum Shear Stress Allowed, νMax = Min (0.8 × √30, 5) = 4.38 N/mm² - Clause 3.4.5.2
Shear Stress, νss = V × 1000 / (b × d) = 2.9 × 1000 / (225.0 × 409.0) = 0.03 N/mm² ≤ νMax (4.38 N/mm²)
Checking for Maximum Shear Stress Allowed Pass

Tension Steel Area Provided, Ast = 226 mm²


- Table 3.8: Values of νc, design concrete shear stress
Steel Percentage, 100 × As / (bv × d) = 0.25 % ≤ 3.0 %
Effective Depth Ratio, edr = 400 / d = 400 / 409.0 = 0.978
(400 / d)^ ¼ = 0.994 < 1, (400 / d)^ ¼ taken as 1
Minimum fcu, fcuMin = 25 N/mm², Concrete Grade Ratio, Min(fcu, 40) / fcuMin = 30 / 25 = 1.200
Concrete Shear Capacity, νc = 0.79 {100 As / (bv d)}⅓ (400 / d)¼ (fcu / 25)⅓ / γm
= 0.79 × {0.25}⅓ × 1.000 × (1.200)⅓ / 1.25 = 0.42 N/mm²
Minimum Design Shear Stress, νMin = 0.40 N/mm²
νss = 0.032 < νc + 0.4, Provides only minimum link
Design for minimum Shear Stress, νd = νmin = 0.40 N/mm²
Shear Link Area / Spacing Ratio, SAsv_Sv = (vd × b) / (fyy × fy) = (0.40 × 225) / (0.95 × 460) = 0.205 mm²/mm

Shear Reinforcement Provided : T10-250 (Link spacing is governed by user setting)


Shear Link Area / Spacing Ratio Provided = 0.628 mm²/mm > 0.205 mm²/mm

LOCATION : SECTION 1 MIDDLE ZONE


(B:500 mm E:1500 mm from left grid of span)

Maximum Torsion within Zone, T = 0.0 kNm


Shear at Location of Maximum Torsion, V = 1.6 kN
Link Horizontal Dimension, h1 = b - 2 × Side Cover - DiaLink = 225 - 2 × 25 - 10 = 165 mm
Link Vertical Dimension, v1 = h - 2 × Cover - DiaLink = 450 - 2 × 25 - 10 = 390 mm
Dimension x1 = Min (h1, v1) = 165 mm, y1 = Max (h1, v1) = 390 mm

Section Dimension: Dmin = 225.0 mm, Dmax = 450.0 mm


Torsion Stress, νst = 2 × T × 106 / (Dmin² × (Dmax - Dmin / 3)) = 0.00 N/mm²
Effective depth, d = 409.0 mm
Shear Stress, νss = V × 1000 / (b × d) = 1.6 × 1000 / (225.0 × 409.0) = 0.02 N/mm²

Part 2 : Clause 2.4.6 and Table 2.3


Maximum Combined Stress Allowed, νtu = Min (0.8 × √fcu, 5) = 4.38 N/mm²
Total Stress, νTot = νss + νst = 0.02 + 0.00 = 0.02 N/mm² ≤ νtu (4.38 N/mm²)
Checking for Combined Stress Allowed Pass

Part 2: Clause 2.4.5


Additional Checking While Small Cross Section (y1 < 550 mm)
Larger Link Dimension, y1 = 390.0 mm < 550 mm
νtu × y1 / 550 = 4.38 × 390.0 / 550 = 3.11 N/mm²
νst = 0.00 N/mm² ≤ 3.11 N/mm²
Checking for Torsion Stress Allowed Pass

Part 2 : Clause 2.4.6 Table 2.3


Torsion Strength contributed by concrete, νt,min = Min (0.067 × √fcu, 0.4) = 0.37 N/mm²
Torsion Stress, νst = 0.00 N/mm² < νt,min = 0.37 N/mm² -> No Torsion Reinforcement is needed

Maximum Shear within Zone, V = 4.1 kN


Maximum Shear Stress Allowed, νMax = Min (0.8 × √30, 5) = 4.38 N/mm² - Clause 3.4.5.2
Shear Stress, νss = V × 1000 / (b × d) = 4.1 × 1000 / (225.0 × 409.0) = 0.05 N/mm² ≤ νMax (4.38 N/mm²)
Checking for Maximum Shear Stress Allowed Pass

Tension Steel Area Provided, Ast = 226 mm²


- Table 3.8: Values of νc, design concrete shear stress
Steel Percentage, 100 × As / (bv × d) = 0.25 % ≤ 3.0 %
Effective Depth Ratio, edr = 400 / d = 400 / 409.0 = 0.978
(400 / d)^ ¼ = 0.994 < 1, (400 / d)^ ¼ taken as 1
Minimum fcu, fcuMin = 25 N/mm², Concrete Grade Ratio, Min(fcu, 40) / fcuMin = 30 / 25 = 1.200
Concrete Shear Capacity, νc = 0.79 {100 As / (bv d)}⅓ (400 / d)¼ (fcu / 25)⅓ / γm
= 0.79 × {0.25}⅓ × 1.000 × (1.200)⅓ / 1.25 = 0.42 N/mm²
Minimum Design Shear Stress, νMin = 0.40 N/mm²
νss = 0.045 < νc + 0.4, Provides only minimum link
Design for minimum Shear Stress, νd = νmin = 0.40 N/mm²
Shear Link Area / Spacing Ratio, SAsv_Sv = (vd × b) / (fyy × fy) = (0.40 × 225) / (0.95 × 460) = 0.205 mm²/mm

Shear Reinforcement Provided : T10-250 (Link spacing is governed by user setting)


Shear Link Area / Spacing Ratio Provided = 0.628 mm²/mm > 0.205 mm²/mm

LOCATION : SECTION 1 RIGHT SUPPORT


(B:1500 mm E:2000 mm from left grid of span)

Maximum Torsion within Zone, T = 0.0 kNm


Shear at Location of Maximum Torsion, V = 5.8 kN
Link Horizontal Dimension, h1 = b - 2 × Side Cover - DiaLink = 225 - 2 × 25 - 10 = 165 mm
Link Vertical Dimension, v1 = h - 2 × Cover - DiaLink = 450 - 2 × 25 - 10 = 390 mm
Dimension x1 = Min (h1, v1) = 165 mm, y1 = Max (h1, v1) = 390 mm

Section Dimension: Dmin = 225.0 mm, Dmax = 450.0 mm


Torsion Stress, νst = 2 × T × 106 / (Dmin² × (Dmax - Dmin / 3)) = 0.00 N/mm²
Effective depth, d = 409.0 mm
Shear Stress, νss = V × 1000 / (b × d) = 5.8 × 1000 / (225.0 × 409.0) = 0.06 N/mm²

Part 2 : Clause 2.4.6 and Table 2.3


Maximum Combined Stress Allowed, νtu = Min (0.8 × √fcu, 5) = 4.38 N/mm²
Total Stress, νTot = νss + νst = 0.06 + 0.00 = 0.06 N/mm² ≤ νtu (4.38 N/mm²)
Checking for Combined Stress Allowed Pass

Part 2: Clause 2.4.5


Additional Checking While Small Cross Section (y1 < 550 mm)
Larger Link Dimension, y1 = 390.0 mm < 550 mm
νtu × y1 / 550 = 4.38 × 390.0 / 550 = 3.11 N/mm²
νst = 0.00 N/mm² ≤ 3.11 N/mm²
Checking for Torsion Stress Allowed Pass

Part 2 : Clause 2.4.6 Table 2.3


Torsion Strength contributed by concrete, νt,min = Min (0.067 × √fcu, 0.4) = 0.37 N/mm²
Torsion Stress, νst = 0.00 N/mm² < νt,min = 0.37 N/mm² -> No Torsion Reinforcement is needed

Maximum Shear within Zone, V = 5.5 kN


Maximum Shear Stress Allowed, νMax = Min (0.8 × √30, 5) = 4.38 N/mm² - Clause 3.4.5.2
Shear Stress, νss = V × 1000 / (b × d) = 5.5 × 1000 / (225.0 × 409.0) = 0.06 N/mm² ≤ νMax (4.38 N/mm²)
Checking for Maximum Shear Stress Allowed Pass

Tension Steel Area Provided, Ast = 226 mm²


- Table 3.8: Values of νc, design concrete shear stress
Steel Percentage, 100 × As / (bv × d) = 0.25 % ≤ 3.0 %
Effective Depth Ratio, edr = 400 / d = 400 / 409.0 = 0.978
(400 / d)^ ¼ = 0.994 < 1, (400 / d)^ ¼ taken as 1
Minimum fcu, fcuMin = 25 N/mm², Concrete Grade Ratio, Min(fcu, 40) / fcuMin = 30 / 25 = 1.200
Concrete Shear Capacity, νc = 0.79 {100 As / (bv d)}⅓ (400 / d)¼ (fcu / 25)⅓ / γm
= 0.79 × {0.25}⅓ × 1.000 × (1.200)⅓ / 1.25 = 0.42 N/mm²
Minimum Design Shear Stress, νMin = 0.40 N/mm²
νss = 0.060 < νc + 0.4, Provides only minimum link
Design for minimum Shear Stress, νd = νmin = 0.40 N/mm²
Shear Link Area / Spacing Ratio, SAsv_Sv = (vd × b) / (fyy × fy) = (0.40 × 225) / (0.95 × 460) = 0.205 mm²/mm

Shear Reinforcement Provided : T10-250 (Link spacing is governed by user setting)


Shear Link Area / Spacing Ratio Provided = 0.628 mm²/mm > 0.205 mm²/mm

DEFLECTION CHECKING FOR SPAN


Basic Span / Effective Depth Ratio, Br = 26.0
Span Length, l = 2000.0 mm, Effective Depth, d = 409.0 mm
Actual Span / Effective Depth Ratio, Ar = 4.9
Ultimate Design Moment, Mu = 1.7 kNm
Design Steel Strength, fy = 460.0 N/mm²
Tension Steel Area Required, AsReq = 132 mm²
Tension Steel Area Provided, AsProv = 226 mm²
Compression Steel Area Provided, AsProv (Comp.) = 226 mm²

- Checking for deflection is based on BS8110: 1997


- Table 3.9: Basic span / effective depth ratio for rectangular or flange beams
- Table 3.10: Modification factor for tension reinforcement
- Table 3.11: Modification factor for compression reinforcement
Design Service Stress in Tension Reinforcement, Equation 8
fs = {(2 × fy × AsReq) / (3 × AsProv)} × (1 / ßb)
= {(2 × 460.0 × 132) / (3 × 226)} × (1 / 1.00) = 178.5 N/mm²

Modification Factor for Tension Reinforcement, Equation 7


MFt = 0.55 + {(477 - fs) / (120 × (0.9 + (M/bd²)))}
= 0.55 + {(477 - 178.5) / (120 × (0.9 + (1.7 × 1000000 / (225 × 409.0²)))}
= 3.18 > 2.0
MFt taken as 2.0

New Modification Factor for Compression Reinforcement, Equation 9


MFc = 1 + {(100 × AsProv / (b × d)) / (3 + (100 × AsProv / (b × d)))}
= 1 + {(100 × 226 / (225.0 × 409.0)) / (3 + (100 × 226 / (225.0 × 409.0)))}
= 1.08 <= 1.5

New Deflection Ratio = (Br × MFt × MFc) / Ar = (26.0 × 2.00 × 1.08) / 4.9 = 11.44
Ratio >= 1.0 : Deflection Checked PASSED

BEAM GB9(225x450/600/450) SPAN NO. 4

FLEXURAL DESIGN CALCULATION


LOCATION : SPAN
Design Bending Moment = 2.4 kNm Width, b = 225.0 mm Effective Depth, d = 559.0 mm
Mu / bd² = 2.4 × 1000000 / (225.0 × 559.0²) = 0.033 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.033 <= 4.691

Design as Singly Reinforced Rectangular Beam


Concrete Neutral Axis, x = 1.544 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 1.544 / 1000 = 4.21 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 4.21 × 1000 / (460 / 1.05) = 10 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 4.21 × (559.0 - 0.4518 × 1.544) / 1000 = 2.4 kNm
Maximum Depth of Section = 600.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 600.0 = 176 mm²

Top Compression Steel Area Required = 176 mm²


Bottom Tension Steel Area Required = 176 mm²

Top Reinforcement Provided = 2T12 (226 mm²)


Bottom Reinforcement Provided = 2T12 (226 mm²)

LOCATION : LEFT SUPPORT


Design Bending Moment = 3.1 kNm Width, b = 225.0 mm Effective Depth, d = 559.0 mm
Mu / bd² = 3.1 × 1000000 / (225.0 × 559.0²) = 0.044 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.044 <= 4.691

Design as Singly Reinforced Rectangular Beam


Concrete Neutral Axis, x = 2.025 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 2.025 / 1000 = 5.52 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 5.52 × 1000 / (460 / 1.05) = 13 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 5.52 × (559.0 - 0.4518 × 2.025) / 1000 = 3.1 kNm
Maximum Depth of Section = 600.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 600.0 = 176 mm²

Top Tension Steel Area Required = 176 mm²


Bottom Compression Steel Area Required = 176 mm²
Top Reinforcement Provided = 2T12 (226 mm²)
Bottom Reinforcement Provided = 2T12 (226 mm²)

LOCATION : RIGHT SUPPORT


Design Bending Moment = 11.3 kNm Width, b = 225.0 mm Effective Depth, d = 559.0 mm
Mu / bd² = 11.3 × 1000000 / (225.0 × 559.0²) = 0.160 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.160 <= 4.691

Design as Singly Reinforced Rectangular Beam


Concrete Neutral Axis, x = 7.441 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 7.441 / 1000 = 20.29 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 20.29 × 1000 / (460 / 1.05) = 47 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 20.29 × (559.0 - 0.4518 × 7.441) / 1000 = 11.3 kNm
Maximum Depth of Section = 600.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 600.0 = 176 mm²

Top Tension Steel Area Required = 176 mm²


Bottom Compression Steel Area Required = 176 mm²

Top Reinforcement Provided = 2T12 (226 mm²)


Bottom Reinforcement Provided = 2T12 (226 mm²)

LOCATION : 1/4 SPAN


Design Bending Moment = 5.4 kNm Width, b = 225.0 mm Effective Depth, d = 559.0 mm
Mu / bd² = 5.4 × 1000000 / (225.0 × 559.0²) = 0.077 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.077 <= 4.691

Design as Singly Reinforced Rectangular Beam


Concrete Neutral Axis, x = 3.559 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 3.559 / 1000 = 9.71 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 9.71 × 1000 / (460 / 1.05) = 23 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 9.71 × (559.0 - 0.4518 × 3.559) / 1000 = 5.4 kNm
Maximum Depth of Section = 600.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 600.0 = 176 mm²

Top Tension Steel Area Required = 176 mm²


Bottom Compression Steel Area Required = 176 mm²

Top Reinforcement Provided = 2T12 (226 mm²)


Bottom Reinforcement Provided = 2T12 (226 mm²)

SHEAR & TORSION DESIGN CALCULATION


LOCATION : SECTION 1 LEFT SUPPORT
(B:0 mm E:875 mm from left grid of span)

Maximum Torsion within Zone, T = 0.0 kNm


Shear at Location of Maximum Torsion, V = 6.9 kN
Link Horizontal Dimension, h1 = b - 2 × Side Cover - DiaLink = 225 - 2 × 25 - 10 = 165 mm
Link Vertical Dimension, v1 = h - 2 × Cover - DiaLink = 600 - 2 × 25 - 10 = 540 mm
Dimension x1 = Min (h1, v1) = 165 mm, y1 = Max (h1, v1) = 540 mm

Section Dimension: Dmin = 225.0 mm, Dmax = 600.0 mm


Torsion Stress, νst = 2 × T × 106 / (Dmin² × (Dmax - Dmin / 3)) = 0.00 N/mm²
Effective depth, d = 559.0 mm
Shear Stress, νss = V × 1000 / (b × d) = 6.9 × 1000 / (225.0 × 559.0) = 0.05 N/mm²

Part 2 : Clause 2.4.6 and Table 2.3


Maximum Combined Stress Allowed, νtu = Min (0.8 × √fcu, 5) = 4.38 N/mm²
Total Stress, νTot = νss + νst = 0.05 + 0.00 = 0.05 N/mm² ≤ νtu (4.38 N/mm²)
Checking for Combined Stress Allowed Pass

Part 2: Clause 2.4.5


Additional Checking While Small Cross Section (y1 < 550 mm)
Larger Link Dimension, y1 = 540.0 mm < 550 mm
νtu × y1 / 550 = 4.38 × 540.0 / 550 = 4.30 N/mm²
νst = 0.00 N/mm² ≤ 4.30 N/mm²
Checking for Torsion Stress Allowed Pass

Part 2 : Clause 2.4.6 Table 2.3


Torsion Strength contributed by concrete, νt,min = Min (0.067 × √fcu, 0.4) = 0.37 N/mm²
Torsion Stress, νst = 0.00 N/mm² < νt,min = 0.37 N/mm² -> No Torsion Reinforcement is needed

Maximum Shear within Zone, V = 6.4 kN


Maximum Shear Stress Allowed, νMax = Min (0.8 × √30, 5) = 4.38 N/mm² - Clause 3.4.5.2
Shear Stress, νss = V × 1000 / (b × d) = 6.4 × 1000 / (225.0 × 559.0) = 0.05 N/mm² ≤ νMax (4.38 N/mm²)
Checking for Maximum Shear Stress Allowed Pass

Tension Steel Area Provided, Ast = 226 mm²


- Table 3.8: Values of νc, design concrete shear stress
Steel Percentage, 100 × As / (bv × d) = 0.18 % ≤ 3.0 %
Effective Depth Ratio, edr = 400 / d = 400 / 559.0 = 0.716
(400 / d)^ ¼ = 0.920 < 1, (400 / d)^ ¼ taken as 1
Minimum fcu, fcuMin = 25 N/mm², Concrete Grade Ratio, Min(fcu, 40) / fcuMin = 30 / 25 = 1.200
Concrete Shear Capacity, νc = 0.79 {100 As / (bv d)}⅓ (400 / d)¼ (fcu / 25)⅓ / γm
= 0.79 × {0.18}⅓ × 1.000 × (1.200)⅓ / 1.25 = 0.38 N/mm²
Minimum Design Shear Stress, νMin = 0.40 N/mm²
νss = 0.051 < νc + 0.4, Provides only minimum link
Design for minimum Shear Stress, νd = νmin = 0.40 N/mm²
Shear Link Area / Spacing Ratio, SAsv_Sv = (vd × b) / (fyy × fy) = (0.40 × 225) / (0.95 × 460) = 0.205 mm²/mm

Shear Reinforcement Provided : T10-250 (Link spacing is governed by user setting)


Shear Link Area / Spacing Ratio Provided = 0.628 mm²/mm > 0.205 mm²/mm

LOCATION : SECTION 1 MIDDLE ZONE


(B:875 mm E:2625 mm from left grid of span)

Maximum Torsion within Zone, T = 0.0 kNm


Shear at Location of Maximum Torsion, V = 2.9 kN
Link Horizontal Dimension, h1 = b - 2 × Side Cover - DiaLink = 225 - 2 × 25 - 10 = 165 mm
Link Vertical Dimension, v1 = h - 2 × Cover - DiaLink = 600 - 2 × 25 - 10 = 540 mm
Dimension x1 = Min (h1, v1) = 165 mm, y1 = Max (h1, v1) = 540 mm

Section Dimension: Dmin = 225.0 mm, Dmax = 600.0 mm


Torsion Stress, νst = 2 × T × 106 / (Dmin² × (Dmax - Dmin / 3)) = 0.00 N/mm²
Effective depth, d = 559.0 mm
Shear Stress, νss = V × 1000 / (b × d) = 2.9 × 1000 / (225.0 × 559.0) = 0.02 N/mm²

Part 2 : Clause 2.4.6 and Table 2.3


Maximum Combined Stress Allowed, νtu = Min (0.8 × √fcu, 5) = 4.38 N/mm²
Total Stress, νTot = νss + νst = 0.02 + 0.00 = 0.02 N/mm² ≤ νtu (4.38 N/mm²)
Checking for Combined Stress Allowed Pass

Part 2: Clause 2.4.5


Additional Checking While Small Cross Section (y1 < 550 mm)
Larger Link Dimension, y1 = 540.0 mm < 550 mm
νtu × y1 / 550 = 4.38 × 540.0 / 550 = 4.30 N/mm²
νst = 0.00 N/mm² ≤ 4.30 N/mm²
Checking for Torsion Stress Allowed Pass
Part 2 : Clause 2.4.6 Table 2.3
Torsion Strength contributed by concrete, νt,min = Min (0.067 × √fcu, 0.4) = 0.37 N/mm²
Torsion Stress, νst = 0.00 N/mm² < νt,min = 0.37 N/mm² -> No Torsion Reinforcement is needed

Maximum Shear within Zone, V = 7.0 kN


Maximum Shear Stress Allowed, νMax = Min (0.8 × √30, 5) = 4.38 N/mm² - Clause 3.4.5.2
Shear Stress, νss = V × 1000 / (b × d) = 7.0 × 1000 / (225.0 × 559.0) = 0.06 N/mm² ≤ νMax (4.38 N/mm²)
Checking for Maximum Shear Stress Allowed Pass

Tension Steel Area Provided, Ast = 226 mm²


- Table 3.8: Values of νc, design concrete shear stress
Steel Percentage, 100 × As / (bv × d) = 0.18 % ≤ 3.0 %
Effective Depth Ratio, edr = 400 / d = 400 / 559.0 = 0.716
(400 / d)^ ¼ = 0.920 < 1, (400 / d)^ ¼ taken as 1
Minimum fcu, fcuMin = 25 N/mm², Concrete Grade Ratio, Min(fcu, 40) / fcuMin = 30 / 25 = 1.200
Concrete Shear Capacity, νc = 0.79 {100 As / (bv d)}⅓ (400 / d)¼ (fcu / 25)⅓ / γm
= 0.79 × {0.18}⅓ × 1.000 × (1.200)⅓ / 1.25 = 0.38 N/mm²
Minimum Design Shear Stress, νMin = 0.40 N/mm²
νss = 0.056 < νc + 0.4, Provides only minimum link
Design for minimum Shear Stress, νd = νmin = 0.40 N/mm²
Shear Link Area / Spacing Ratio, SAsv_Sv = (vd × b) / (fyy × fy) = (0.40 × 225) / (0.95 × 460) = 0.205 mm²/mm

Shear Reinforcement Provided : T10-250 (Link spacing is governed by user setting)


Shear Link Area / Spacing Ratio Provided = 0.628 mm²/mm > 0.205 mm²/mm

LOCATION : SECTION 1 RIGHT SUPPORT


(B:2625 mm E:3500 mm from left grid of span)

Maximum Torsion within Zone, T = 0.0 kNm


Shear at Location of Maximum Torsion, V = 11.0 kN
Link Horizontal Dimension, h1 = b - 2 × Side Cover - DiaLink = 225 - 2 × 25 - 10 = 165 mm
Link Vertical Dimension, v1 = h - 2 × Cover - DiaLink = 600 - 2 × 25 - 10 = 540 mm
Dimension x1 = Min (h1, v1) = 165 mm, y1 = Max (h1, v1) = 540 mm

Section Dimension: Dmin = 225.0 mm, Dmax = 600.0 mm


Torsion Stress, νst = 2 × T × 106 / (Dmin² × (Dmax - Dmin / 3)) = 0.00 N/mm²
Effective depth, d = 559.0 mm
Shear Stress, νss = V × 1000 / (b × d) = 11.0 × 1000 / (225.0 × 559.0) = 0.09 N/mm²

Part 2 : Clause 2.4.6 and Table 2.3


Maximum Combined Stress Allowed, νtu = Min (0.8 × √fcu, 5) = 4.38 N/mm²
Total Stress, νTot = νss + νst = 0.09 + 0.00 = 0.09 N/mm² ≤ νtu (4.38 N/mm²)
Checking for Combined Stress Allowed Pass

Part 2: Clause 2.4.5


Additional Checking While Small Cross Section (y1 < 550 mm)
Larger Link Dimension, y1 = 540.0 mm < 550 mm
νtu × y1 / 550 = 4.38 × 540.0 / 550 = 4.30 N/mm²
νst = 0.00 N/mm² ≤ 4.30 N/mm²
Checking for Torsion Stress Allowed Pass

Part 2 : Clause 2.4.6 Table 2.3


Torsion Strength contributed by concrete, νt,min = Min (0.067 × √fcu, 0.4) = 0.37 N/mm²
Torsion Stress, νst = 0.00 N/mm² < νt,min = 0.37 N/mm² -> No Torsion Reinforcement is needed

Maximum Shear within Zone, V = 10.5 kN


Maximum Shear Stress Allowed, νMax = Min (0.8 × √30, 5) = 4.38 N/mm² - Clause 3.4.5.2
Shear Stress, νss = V × 1000 / (b × d) = 10.5 × 1000 / (225.0 × 559.0) = 0.08 N/mm² ≤ νMax (4.38 N/mm²)
Checking for Maximum Shear Stress Allowed Pass

Tension Steel Area Provided, Ast = 226 mm²


- Table 3.8: Values of νc, design concrete shear stress
Steel Percentage, 100 × As / (bv × d) = 0.18 % ≤ 3.0 %
Effective Depth Ratio, edr = 400 / d = 400 / 559.0 = 0.716
(400 / d)^ ¼ = 0.920 < 1, (400 / d)^ ¼ taken as 1
Minimum fcu, fcuMin = 25 N/mm², Concrete Grade Ratio, Min(fcu, 40) / fcuMin = 30 / 25 = 1.200
Concrete Shear Capacity, νc = 0.79 {100 As / (bv d)}⅓ (400 / d)¼ (fcu / 25)⅓ / γm
= 0.79 × {0.18}⅓ × 1.000 × (1.200)⅓ / 1.25 = 0.38 N/mm²
Minimum Design Shear Stress, νMin = 0.40 N/mm²
νss = 0.084 < νc + 0.4, Provides only minimum link
Design for minimum Shear Stress, νd = νmin = 0.40 N/mm²
Shear Link Area / Spacing Ratio, SAsv_Sv = (vd × b) / (fyy × fy) = (0.40 × 225) / (0.95 × 460) = 0.205 mm²/mm

Shear Reinforcement Provided : T10-250 (Link spacing is governed by user setting)


Shear Link Area / Spacing Ratio Provided = 0.628 mm²/mm > 0.205 mm²/mm

DEFLECTION CHECKING FOR SPAN


Basic Span / Effective Depth Ratio, Br = 26.0
Span Length, l = 3500.0 mm, Effective Depth, d = 559.0 mm
Actual Span / Effective Depth Ratio, Ar = 6.3
Ultimate Design Moment, Mu = 2.4 kNm
Design Steel Strength, fy = 460.0 N/mm²
Tension Steel Area Required, AsReq = 176 mm²
Tension Steel Area Provided, AsProv = 226 mm²
Compression Steel Area Provided, AsProv (Comp.) = 226 mm²

- Checking for deflection is based on BS8110: 1997


- Table 3.9: Basic span / effective depth ratio for rectangular or flange beams
- Table 3.10: Modification factor for tension reinforcement
- Table 3.11: Modification factor for compression reinforcement

Design Service Stress in Tension Reinforcement, Equation 8


fs = {(2 × fy × AsReq) / (3 × AsProv)} × (1 / ßb)
= {(2 × 460.0 × 176) / (3 × 226)} × (1 / 1.00) = 237.9 N/mm²

Modification Factor for Tension Reinforcement, Equation 7


MFt = 0.55 + {(477 - fs) / (120 × (0.9 + (M/bd²)))}
= 0.55 + {(477 - 237.9) / (120 × (0.9 + (2.4 × 1000000 / (225 × 559.0²)))}
= 2.68 > 2.0
MFt taken as 2.0

New Modification Factor for Compression Reinforcement, Equation 9


MFc = 1 + {(100 × AsProv / (b × d)) / (3 + (100 × AsProv / (b × d)))}
= 1 + {(100 × 226 / (225.0 × 559.0)) / (3 + (100 × 226 / (225.0 × 559.0)))}
= 1.06 <= 1.5

New Deflection Ratio = (Br × MFt × MFc) / Ar = (26.0 × 2.00 × 1.06) / 6.3 = 8.77
Ratio >= 1.0 : Deflection Checked PASSED

BEAM GB9(225x450/600/450) SPAN NO. 5

FLEXURAL DESIGN CALCULATION


LOCATION : SPAN
Design Bending Moment = 12.1 kNm Width, b = 225.0 mm Effective Depth, d = 409.0 mm
Mu / bd² = 12.1 × 1000000 / (225.0 × 409.0²) = 0.321 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.321 <= 4.691

Design as Singly Reinforced Rectangular Beam


Concrete Neutral Axis, x = 10.982 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 10.982 / 1000 = 29.95 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 29.95 × 1000 / (460 / 1.05) = 69 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 29.95 × (409.0 - 0.4518 × 10.982) / 1000 = 12.1 kNm
Maximum Depth of Section = 450.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 450.0 = 132 mm²

Top Compression Steel Area Required = 132 mm²


Bottom Tension Steel Area Required = 132 mm²

Top Reinforcement Provided = 2T12 (226 mm²)


Bottom Reinforcement Provided = 2T12 (226 mm²)

LOCATION : LEFT SUPPORT


Design Bending Moment = 10.1 kNm Width, b = 225.0 mm Effective Depth, d = 409.0 mm
Mu / bd² = 10.1 × 1000000 / (225.0 × 409.0²) = 0.269 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.269 <= 4.691

Design as Singly Reinforced Rectangular Beam


Concrete Neutral Axis, x = 9.170 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 9.170 / 1000 = 25.01 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 25.01 × 1000 / (460 / 1.05) = 58 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 25.01 × (409.0 - 0.4518 × 9.170) / 1000 = 10.1 kNm
Maximum Depth of Section = 450.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 450.0 = 132 mm²

Top Tension Steel Area Required = 132 mm²


Bottom Compression Steel Area Required = 132 mm²

Top Reinforcement Provided = 2T12 (226 mm²)


Bottom Reinforcement Provided = 2T12 (226 mm²)

LOCATION : RIGHT SUPPORT


Design Bending Moment = 10.6 kNm Width, b = 225.0 mm Effective Depth, d = 409.0 mm
Mu / bd² = 10.6 × 1000000 / (225.0 × 409.0²) = 0.282 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.282 <= 4.691

Design as Singly Reinforced Rectangular Beam


Concrete Neutral Axis, x = 9.610 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 9.610 / 1000 = 26.21 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 26.21 × 1000 / (460 / 1.05) = 60 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 26.21 × (409.0 - 0.4518 × 9.610) / 1000 = 10.6 kNm
Maximum Depth of Section = 450.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 450.0 = 132 mm²

Top Tension Steel Area Required = 132 mm²


Bottom Compression Steel Area Required = 132 mm²

Top Reinforcement Provided = 2T12 (226 mm²)


Bottom Reinforcement Provided = 2T12 (226 mm²)

LOCATION : 1/4 SPAN


Design Bending Moment = 0.0 kNm Width, b = 225.0 mm Effective Depth, d = 409.0 mm
Mu / bd² = 0.0 × 1000000 / (225.0 × 409.0²) = 0.000 N/mm²
Design to minimum steel percentage specified by code,
Maximum Depth of Section = 450.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 450.0 = 132 mm²

Top Tension Steel Area Required = 132 mm²


Top Reinforcement Provided = 2T12 (226 mm²)
Bottom Reinforcement Provided = 2T12 (226 mm²)

SHEAR & TORSION DESIGN CALCULATION


LOCATION : SECTION 1 LEFT SUPPORT
(B:0 mm E:838 mm from left grid of span)

Maximum Torsion within Zone, T = 0.0 kNm


Shear at Location of Maximum Torsion, V = 26.7 kN
Link Horizontal Dimension, h1 = b - 2 × Side Cover - DiaLink = 225 - 2 × 25 - 10 = 165 mm
Link Vertical Dimension, v1 = h - 2 × Cover - DiaLink = 450 - 2 × 25 - 10 = 390 mm
Dimension x1 = Min (h1, v1) = 165 mm, y1 = Max (h1, v1) = 390 mm

Section Dimension: Dmin = 225.0 mm, Dmax = 450.0 mm


Torsion Stress, νst = 2 × T × 106 / (Dmin² × (Dmax - Dmin / 3)) = 0.00 N/mm²
Effective depth, d = 409.0 mm
Shear Stress, νss = V × 1000 / (b × d) = 26.7 × 1000 / (225.0 × 409.0) = 0.29 N/mm²

Part 2 : Clause 2.4.6 and Table 2.3


Maximum Combined Stress Allowed, νtu = Min (0.8 × √fcu, 5) = 4.38 N/mm²
Total Stress, νTot = νss + νst = 0.29 + 0.00 = 0.29 N/mm² ≤ νtu (4.38 N/mm²)
Checking for Combined Stress Allowed Pass

Part 2: Clause 2.4.5


Additional Checking While Small Cross Section (y1 < 550 mm)
Larger Link Dimension, y1 = 390.0 mm < 550 mm
νtu × y1 / 550 = 4.38 × 390.0 / 550 = 3.11 N/mm²
νst = 0.00 N/mm² ≤ 3.11 N/mm²
Checking for Torsion Stress Allowed Pass

Part 2 : Clause 2.4.6 Table 2.3


Torsion Strength contributed by concrete, νt,min = Min (0.067 × √fcu, 0.4) = 0.37 N/mm²
Torsion Stress, νst = 0.00 N/mm² < νt,min = 0.37 N/mm² -> No Torsion Reinforcement is needed

Maximum Shear within Zone, V = 25.3 kN


Maximum Shear Stress Allowed, νMax = Min (0.8 × √30, 5) = 4.38 N/mm² - Clause 3.4.5.2
Shear Stress, νss = V × 1000 / (b × d) = 25.3 × 1000 / (225.0 × 409.0) = 0.27 N/mm² ≤ νMax (4.38 N/mm²)
Checking for Maximum Shear Stress Allowed Pass

Tension Steel Area Provided, Ast = 226 mm²


- Table 3.8: Values of νc, design concrete shear stress
Steel Percentage, 100 × As / (bv × d) = 0.25 % ≤ 3.0 %
Effective Depth Ratio, edr = 400 / d = 400 / 409.0 = 0.978
(400 / d)^ ¼ = 0.994 < 1, (400 / d)^ ¼ taken as 1
Minimum fcu, fcuMin = 25 N/mm², Concrete Grade Ratio, Min(fcu, 40) / fcuMin = 30 / 25 = 1.200
Concrete Shear Capacity, νc = 0.79 {100 As / (bv d)}⅓ (400 / d)¼ (fcu / 25)⅓ / γm
= 0.79 × {0.25}⅓ × 1.000 × (1.200)⅓ / 1.25 = 0.42 N/mm²
Minimum Design Shear Stress, νMin = 0.40 N/mm²
νss = 0.275 < νc + 0.4, Provides only minimum link
Design for minimum Shear Stress, νd = νmin = 0.40 N/mm²
Shear Link Area / Spacing Ratio, SAsv_Sv = (vd × b) / (fyy × fy) = (0.40 × 225) / (0.95 × 460) = 0.205 mm²/mm

Shear Reinforcement Provided : T10-250 (Link spacing is governed by user setting)


Shear Link Area / Spacing Ratio Provided = 0.628 mm²/mm > 0.205 mm²/mm

LOCATION : SECTION 1 MIDDLE ZONE


(B:838 mm E:2513 mm from left grid of span)

Maximum Torsion within Zone, T = 0.0 kNm


Shear at Location of Maximum Torsion, V = 9.8 kN
Link Horizontal Dimension, h1 = b - 2 × Side Cover - DiaLink = 225 - 2 × 25 - 10 = 165 mm
Link Vertical Dimension, v1 = h - 2 × Cover - DiaLink = 450 - 2 × 25 - 10 = 390 mm
Dimension x1 = Min (h1, v1) = 165 mm, y1 = Max (h1, v1) = 390 mm

Section Dimension: Dmin = 225.0 mm, Dmax = 450.0 mm


Torsion Stress, νst = 2 × T × 106 / (Dmin² × (Dmax - Dmin / 3)) = 0.00 N/mm²
Effective depth, d = 409.0 mm
Shear Stress, νss = V × 1000 / (b × d) = 9.8 × 1000 / (225.0 × 409.0) = 0.11 N/mm²

Part 2 : Clause 2.4.6 and Table 2.3


Maximum Combined Stress Allowed, νtu = Min (0.8 × √fcu, 5) = 4.38 N/mm²
Total Stress, νTot = νss + νst = 0.11 + 0.00 = 0.11 N/mm² ≤ νtu (4.38 N/mm²)
Checking for Combined Stress Allowed Pass

Part 2: Clause 2.4.5


Additional Checking While Small Cross Section (y1 < 550 mm)
Larger Link Dimension, y1 = 390.0 mm < 550 mm
νtu × y1 / 550 = 4.38 × 390.0 / 550 = 3.11 N/mm²
νst = 0.00 N/mm² ≤ 3.11 N/mm²
Checking for Torsion Stress Allowed Pass

Part 2 : Clause 2.4.6 Table 2.3


Torsion Strength contributed by concrete, νt,min = Min (0.067 × √fcu, 0.4) = 0.37 N/mm²
Torsion Stress, νst = 0.00 N/mm² < νt,min = 0.37 N/mm² -> No Torsion Reinforcement is needed

Maximum Shear within Zone, V = 9.8 kN


Maximum Shear Stress Allowed, νMax = Min (0.8 × √30, 5) = 4.38 N/mm² - Clause 3.4.5.2
Shear Stress, νss = V × 1000 / (b × d) = 9.8 × 1000 / (225.0 × 409.0) = 0.11 N/mm² ≤ νMax (4.38 N/mm²)
Checking for Maximum Shear Stress Allowed Pass

Tension Steel Area Provided, Ast = 226 mm²


- Table 3.8: Values of νc, design concrete shear stress
Steel Percentage, 100 × As / (bv × d) = 0.25 % ≤ 3.0 %
Effective Depth Ratio, edr = 400 / d = 400 / 409.0 = 0.978
(400 / d)^ ¼ = 0.994 < 1, (400 / d)^ ¼ taken as 1
Minimum fcu, fcuMin = 25 N/mm², Concrete Grade Ratio, Min(fcu, 40) / fcuMin = 30 / 25 = 1.200
Concrete Shear Capacity, νc = 0.79 {100 As / (bv d)}⅓ (400 / d)¼ (fcu / 25)⅓ / γm
= 0.79 × {0.25}⅓ × 1.000 × (1.200)⅓ / 1.25 = 0.42 N/mm²
Minimum Design Shear Stress, νMin = 0.40 N/mm²
νss = 0.107 < νc + 0.4, Provides only minimum link
Design for minimum Shear Stress, νd = νmin = 0.40 N/mm²
Shear Link Area / Spacing Ratio, SAsv_Sv = (vd × b) / (fyy × fy) = (0.40 × 225) / (0.95 × 460) = 0.205 mm²/mm

Shear Reinforcement Provided : T10-250 (Link spacing is governed by user setting)


Shear Link Area / Spacing Ratio Provided = 0.628 mm²/mm > 0.205 mm²/mm

LOCATION : SECTION 1 RIGHT SUPPORT


(B:2513 mm E:3350 mm from left grid of span)

Maximum Torsion within Zone, T = 0.0 kNm


Shear at Location of Maximum Torsion, V = 27.9 kN
Link Horizontal Dimension, h1 = b - 2 × Side Cover - DiaLink = 225 - 2 × 25 - 10 = 165 mm
Link Vertical Dimension, v1 = h - 2 × Cover - DiaLink = 450 - 2 × 25 - 10 = 390 mm
Dimension x1 = Min (h1, v1) = 165 mm, y1 = Max (h1, v1) = 390 mm

Section Dimension: Dmin = 225.0 mm, Dmax = 450.0 mm


Torsion Stress, νst = 2 × T × 106 / (Dmin² × (Dmax - Dmin / 3)) = 0.00 N/mm²
Effective depth, d = 409.0 mm
Shear Stress, νss = V × 1000 / (b × d) = 27.9 × 1000 / (225.0 × 409.0) = 0.30 N/mm²

Part 2 : Clause 2.4.6 and Table 2.3


Maximum Combined Stress Allowed, νtu = Min (0.8 × √fcu, 5) = 4.38 N/mm²
Total Stress, νTot = νss + νst = 0.30 + 0.00 = 0.30 N/mm² ≤ νtu (4.38 N/mm²)
Checking for Combined Stress Allowed Pass

Part 2: Clause 2.4.5


Additional Checking While Small Cross Section (y1 < 550 mm)
Larger Link Dimension, y1 = 390.0 mm < 550 mm
νtu × y1 / 550 = 4.38 × 390.0 / 550 = 3.11 N/mm²
νst = 0.00 N/mm² ≤ 3.11 N/mm²
Checking for Torsion Stress Allowed Pass

Part 2 : Clause 2.4.6 Table 2.3


Torsion Strength contributed by concrete, νt,min = Min (0.067 × √fcu, 0.4) = 0.37 N/mm²
Torsion Stress, νst = 0.00 N/mm² < νt,min = 0.37 N/mm² -> No Torsion Reinforcement is needed

Maximum Shear within Zone, V = 26.3 kN


Maximum Shear Stress Allowed, νMax = Min (0.8 × √30, 5) = 4.38 N/mm² - Clause 3.4.5.2
Shear Stress, νss = V × 1000 / (b × d) = 26.3 × 1000 / (225.0 × 409.0) = 0.29 N/mm² ≤ νMax (4.38 N/mm²)
Checking for Maximum Shear Stress Allowed Pass

Tension Steel Area Provided, Ast = 226 mm²


- Table 3.8: Values of νc, design concrete shear stress
Steel Percentage, 100 × As / (bv × d) = 0.25 % ≤ 3.0 %
Effective Depth Ratio, edr = 400 / d = 400 / 409.0 = 0.978
(400 / d)^ ¼ = 0.994 < 1, (400 / d)^ ¼ taken as 1
Minimum fcu, fcuMin = 25 N/mm², Concrete Grade Ratio, Min(fcu, 40) / fcuMin = 30 / 25 = 1.200
Concrete Shear Capacity, νc = 0.79 {100 As / (bv d)}⅓ (400 / d)¼ (fcu / 25)⅓ / γm
= 0.79 × {0.25}⅓ × 1.000 × (1.200)⅓ / 1.25 = 0.42 N/mm²
Minimum Design Shear Stress, νMin = 0.40 N/mm²
νss = 0.286 < νc + 0.4, Provides only minimum link
Design for minimum Shear Stress, νd = νmin = 0.40 N/mm²
Shear Link Area / Spacing Ratio, SAsv_Sv = (vd × b) / (fyy × fy) = (0.40 × 225) / (0.95 × 460) = 0.205 mm²/mm

Shear Reinforcement Provided : T10-250 (Link spacing is governed by user setting)


Shear Link Area / Spacing Ratio Provided = 0.628 mm²/mm > 0.205 mm²/mm

DEFLECTION CHECKING FOR SPAN


Basic Span / Effective Depth Ratio, Br = 26.0
Span Length, l = 3350.0 mm, Effective Depth, d = 409.0 mm
Actual Span / Effective Depth Ratio, Ar = 8.2
Ultimate Design Moment, Mu = 12.1 kNm
Design Steel Strength, fy = 460.0 N/mm²
Tension Steel Area Required, AsReq = 132 mm²
Tension Steel Area Provided, AsProv = 226 mm²
Compression Steel Area Provided, AsProv (Comp.) = 226 mm²

- Checking for deflection is based on BS8110: 1997


- Table 3.9: Basic span / effective depth ratio for rectangular or flange beams
- Table 3.10: Modification factor for tension reinforcement
- Table 3.11: Modification factor for compression reinforcement

Design Service Stress in Tension Reinforcement, Equation 8


fs = {(2 × fy × AsReq) / (3 × AsProv)} × (1 / ßb)
= {(2 × 460.0 × 132) / (3 × 226)} × (1 / 1.00) = 178.5 N/mm²

Modification Factor for Tension Reinforcement, Equation 7


MFt = 0.55 + {(477 - fs) / (120 × (0.9 + (M/bd²)))}
= 0.55 + {(477 - 178.5) / (120 × (0.9 + (12.1 × 1000000 / (225 × 409.0²)))}
= 2.59 > 2.0
MFt taken as 2.0
New Modification Factor for Compression Reinforcement, Equation 9
MFc = 1 + {(100 × AsProv / (b × d)) / (3 + (100 × AsProv / (b × d)))}
= 1 + {(100 × 226 / (225.0 × 409.0)) / (3 + (100 × 226 / (225.0 × 409.0)))}
= 1.08 <= 1.5

New Deflection Ratio = (Br × MFt × MFc) / Ar = (26.0 × 2.00 × 1.08) / 8.2 = 6.83
Ratio >= 1.0 : Deflection Checked PASSED

BEAM GB9(225x450/600/450) SPAN NO. 6

FLEXURAL DESIGN CALCULATION

LOCATION : LEFT SUPPORT


Design Bending Moment = 11.5 kNm Width, b = 225.0 mm Effective Depth, d = 409.0 mm
Mu / bd² = 11.5 × 1000000 / (225.0 × 409.0²) = 0.306 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.306 <= 4.691

Design as Singly Reinforced Rectangular Beam


Concrete Neutral Axis, x = 10.437 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 10.437 / 1000 = 28.46 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 28.46 × 1000 / (460 / 1.05) = 65 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 28.46 × (409.0 - 0.4518 × 10.437) / 1000 = 11.5 kNm
Maximum Depth of Section = 450.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 450.0 = 132 mm²

Top Tension Steel Area Required = 132 mm²


Bottom Compression Steel Area Required = 132 mm²

Top Reinforcement Provided = 2T12 (226 mm²)


Bottom Reinforcement Provided = 2T12 (226 mm²)

LOCATION : RIGHT SUPPORT


Design Bending Moment = 22.6 kNm Width, b = 225.0 mm Effective Depth, d = 409.0 mm
Mu / bd² = 22.6 × 1000000 / (225.0 × 409.0²) = 0.602 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.602 <= 4.691

Design as Singly Reinforced Rectangular Beam


Concrete Neutral Axis, x = 20.782 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 20.782 / 1000 = 56.67 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 56.67 × 1000 / (460 / 1.05) = 130 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 56.67 × (409.0 - 0.4518 × 20.782) / 1000 = 22.6 kNm
Maximum Depth of Section = 450.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 450.0 = 132 mm²

Top Tension Steel Area Required = 132 mm²


Bottom Compression Steel Area Required = 132 mm²

Top Reinforcement Provided = 2T12 (226 mm²)


Bottom Reinforcement Provided = 2T12 (226 mm²)

LOCATION : 1/4 SPAN


Design Bending Moment = 14.2 kNm Width, b = 225.0 mm Effective Depth, d = 409.0 mm
Mu / bd² = 14.2 × 1000000 / (225.0 × 409.0²) = 0.379 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.379 <= 4.691

Design as Singly Reinforced Rectangular Beam


Concrete Neutral Axis, x = 12.958 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 12.958 / 1000 = 35.34 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 35.34 × 1000 / (460 / 1.05) = 81 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 35.34 × (409.0 - 0.4518 × 12.958) / 1000 = 14.2 kNm
Maximum Depth of Section = 450.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 450.0 = 132 mm²

Top Tension Steel Area Required = 132 mm²


Bottom Compression Steel Area Required = 132 mm²

Top Reinforcement Provided = 2T12 (226 mm²)


Bottom Reinforcement Provided = 2T12 (226 mm²)

SHEAR & TORSION DESIGN CALCULATION


LOCATION : SECTION 1 LEFT SUPPORT
(B:0 mm E:575 mm from left grid of span)

Maximum Torsion within Zone, T = 0.0 kNm


Shear at Location of Maximum Torsion, V = 17.0 kN
Link Horizontal Dimension, h1 = b - 2 × Side Cover - DiaLink = 225 - 2 × 25 - 10 = 165 mm
Link Vertical Dimension, v1 = h - 2 × Cover - DiaLink = 450 - 2 × 25 - 10 = 390 mm
Dimension x1 = Min (h1, v1) = 165 mm, y1 = Max (h1, v1) = 390 mm

Section Dimension: Dmin = 225.0 mm, Dmax = 450.0 mm


Torsion Stress, νst = 2 × T × 106 / (Dmin² × (Dmax - Dmin / 3)) = 0.00 N/mm²
Effective depth, d = 409.0 mm
Shear Stress, νss = V × 1000 / (b × d) = 17.0 × 1000 / (225.0 × 409.0) = 0.18 N/mm²

Part 2 : Clause 2.4.6 and Table 2.3


Maximum Combined Stress Allowed, νtu = Min (0.8 × √fcu, 5) = 4.38 N/mm²
Total Stress, νTot = νss + νst = 0.18 + 0.00 = 0.18 N/mm² ≤ νtu (4.38 N/mm²)
Checking for Combined Stress Allowed Pass

Part 2: Clause 2.4.5


Additional Checking While Small Cross Section (y1 < 550 mm)
Larger Link Dimension, y1 = 390.0 mm < 550 mm
νtu × y1 / 550 = 4.38 × 390.0 / 550 = 3.11 N/mm²
νst = 0.00 N/mm² ≤ 3.11 N/mm²
Checking for Torsion Stress Allowed Pass

Part 2 : Clause 2.4.6 Table 2.3


Torsion Strength contributed by concrete, νt,min = Min (0.067 × √fcu, 0.4) = 0.37 N/mm²
Torsion Stress, νst = 0.00 N/mm² < νt,min = 0.37 N/mm² -> No Torsion Reinforcement is needed

Maximum Shear within Zone, V = 15.4 kN


Maximum Shear Stress Allowed, νMax = Min (0.8 × √30, 5) = 4.38 N/mm² - Clause 3.4.5.2
Shear Stress, νss = V × 1000 / (b × d) = 15.4 × 1000 / (225.0 × 409.0) = 0.17 N/mm² ≤ νMax (4.38 N/mm²)
Checking for Maximum Shear Stress Allowed Pass

Tension Steel Area Provided, Ast = 226 mm²


- Table 3.8: Values of νc, design concrete shear stress
Steel Percentage, 100 × As / (bv × d) = 0.25 % ≤ 3.0 %
Effective Depth Ratio, edr = 400 / d = 400 / 409.0 = 0.978
(400 / d)^ ¼ = 0.994 < 1, (400 / d)^ ¼ taken as 1
Minimum fcu, fcuMin = 25 N/mm², Concrete Grade Ratio, Min(fcu, 40) / fcuMin = 30 / 25 = 1.200
Concrete Shear Capacity, νc = 0.79 {100 As / (bv d)}⅓ (400 / d)¼ (fcu / 25)⅓ / γm
= 0.79 × {0.25}⅓ × 1.000 × (1.200)⅓ / 1.25 = 0.42 N/mm²
Minimum Design Shear Stress, νMin = 0.40 N/mm²
νss = 0.167 < νc + 0.4, Provides only minimum link
Design for minimum Shear Stress, νd = νmin = 0.40 N/mm²
Shear Link Area / Spacing Ratio, SAsv_Sv = (vd × b) / (fyy × fy) = (0.40 × 225) / (0.95 × 460) = 0.205 mm²/mm

Shear Reinforcement Provided : T10-250 (Link spacing is governed by user setting)


Shear Link Area / Spacing Ratio Provided = 0.628 mm²/mm > 0.205 mm²/mm

LOCATION : SECTION 1 MIDDLE ZONE


(B:575 mm E:1725 mm from left grid of span)

Maximum Torsion within Zone, T = 0.0 kNm


Shear at Location of Maximum Torsion, V = 7.7 kN
Link Horizontal Dimension, h1 = b - 2 × Side Cover - DiaLink = 225 - 2 × 25 - 10 = 165 mm
Link Vertical Dimension, v1 = h - 2 × Cover - DiaLink = 450 - 2 × 25 - 10 = 390 mm
Dimension x1 = Min (h1, v1) = 165 mm, y1 = Max (h1, v1) = 390 mm

Section Dimension: Dmin = 225.0 mm, Dmax = 450.0 mm


Torsion Stress, νst = 2 × T × 106 / (Dmin² × (Dmax - Dmin / 3)) = 0.00 N/mm²
Effective depth, d = 409.0 mm
Shear Stress, νss = V × 1000 / (b × d) = 7.7 × 1000 / (225.0 × 409.0) = 0.08 N/mm²

Part 2 : Clause 2.4.6 and Table 2.3


Maximum Combined Stress Allowed, νtu = Min (0.8 × √fcu, 5) = 4.38 N/mm²
Total Stress, νTot = νss + νst = 0.08 + 0.00 = 0.08 N/mm² ≤ νtu (4.38 N/mm²)
Checking for Combined Stress Allowed Pass

Part 2: Clause 2.4.5


Additional Checking While Small Cross Section (y1 < 550 mm)
Larger Link Dimension, y1 = 390.0 mm < 550 mm
νtu × y1 / 550 = 4.38 × 390.0 / 550 = 3.11 N/mm²
νst = 0.00 N/mm² ≤ 3.11 N/mm²
Checking for Torsion Stress Allowed Pass

Part 2 : Clause 2.4.6 Table 2.3


Torsion Strength contributed by concrete, νt,min = Min (0.067 × √fcu, 0.4) = 0.37 N/mm²
Torsion Stress, νst = 0.00 N/mm² < νt,min = 0.37 N/mm² -> No Torsion Reinforcement is needed

Maximum Shear within Zone, V = 16.5 kN


Maximum Shear Stress Allowed, νMax = Min (0.8 × √30, 5) = 4.38 N/mm² - Clause 3.4.5.2
Shear Stress, νss = V × 1000 / (b × d) = 16.5 × 1000 / (225.0 × 409.0) = 0.18 N/mm² ≤ νMax (4.38 N/mm²)
Checking for Maximum Shear Stress Allowed Pass

Tension Steel Area Provided, Ast = 226 mm²


- Table 3.8: Values of νc, design concrete shear stress
Steel Percentage, 100 × As / (bv × d) = 0.25 % ≤ 3.0 %
Effective Depth Ratio, edr = 400 / d = 400 / 409.0 = 0.978
(400 / d)^ ¼ = 0.994 < 1, (400 / d)^ ¼ taken as 1
Minimum fcu, fcuMin = 25 N/mm², Concrete Grade Ratio, Min(fcu, 40) / fcuMin = 30 / 25 = 1.200
Concrete Shear Capacity, νc = 0.79 {100 As / (bv d)}⅓ (400 / d)¼ (fcu / 25)⅓ / γm
= 0.79 × {0.25}⅓ × 1.000 × (1.200)⅓ / 1.25 = 0.42 N/mm²
Minimum Design Shear Stress, νMin = 0.40 N/mm²
νss = 0.180 < νc + 0.4, Provides only minimum link
Design for minimum Shear Stress, νd = νmin = 0.40 N/mm²
Shear Link Area / Spacing Ratio, SAsv_Sv = (vd × b) / (fyy × fy) = (0.40 × 225) / (0.95 × 460) = 0.205 mm²/mm

Shear Reinforcement Provided : T10-250 (Link spacing is governed by user setting)


Shear Link Area / Spacing Ratio Provided = 0.628 mm²/mm > 0.205 mm²/mm

LOCATION : SECTION 1 RIGHT SUPPORT


(B:1725 mm E:2300 mm from left grid of span)

Maximum Torsion within Zone, T = 0.0 kNm


Shear at Location of Maximum Torsion, V = 25.9 kN
Link Horizontal Dimension, h1 = b - 2 × Side Cover - DiaLink = 225 - 2 × 25 - 10 = 165 mm
Link Vertical Dimension, v1 = h - 2 × Cover - DiaLink = 450 - 2 × 25 - 10 = 390 mm
Dimension x1 = Min (h1, v1) = 165 mm, y1 = Max (h1, v1) = 390 mm

Section Dimension: Dmin = 225.0 mm, Dmax = 450.0 mm


Torsion Stress, νst = 2 × T × 106 / (Dmin² × (Dmax - Dmin / 3)) = 0.00 N/mm²
Effective depth, d = 409.0 mm
Shear Stress, νss = V × 1000 / (b × d) = 25.9 × 1000 / (225.0 × 409.0) = 0.28 N/mm²

Part 2 : Clause 2.4.6 and Table 2.3


Maximum Combined Stress Allowed, νtu = Min (0.8 × √fcu, 5) = 4.38 N/mm²
Total Stress, νTot = νss + νst = 0.28 + 0.00 = 0.28 N/mm² ≤ νtu (4.38 N/mm²)
Checking for Combined Stress Allowed Pass

Part 2: Clause 2.4.5


Additional Checking While Small Cross Section (y1 < 550 mm)
Larger Link Dimension, y1 = 390.0 mm < 550 mm
νtu × y1 / 550 = 4.38 × 390.0 / 550 = 3.11 N/mm²
νst = 0.00 N/mm² ≤ 3.11 N/mm²
Checking for Torsion Stress Allowed Pass

Part 2 : Clause 2.4.6 Table 2.3


Torsion Strength contributed by concrete, νt,min = Min (0.067 × √fcu, 0.4) = 0.37 N/mm²
Torsion Stress, νst = 0.00 N/mm² < νt,min = 0.37 N/mm² -> No Torsion Reinforcement is needed

Maximum Shear within Zone, V = 24.2 kN


Maximum Shear Stress Allowed, νMax = Min (0.8 × √30, 5) = 4.38 N/mm² - Clause 3.4.5.2
Shear Stress, νss = V × 1000 / (b × d) = 24.2 × 1000 / (225.0 × 409.0) = 0.26 N/mm² ≤ νMax (4.38 N/mm²)
Checking for Maximum Shear Stress Allowed Pass

Tension Steel Area Provided, Ast = 226 mm²


- Table 3.8: Values of νc, design concrete shear stress
Steel Percentage, 100 × As / (bv × d) = 0.25 % ≤ 3.0 %
Effective Depth Ratio, edr = 400 / d = 400 / 409.0 = 0.978
(400 / d)^ ¼ = 0.994 < 1, (400 / d)^ ¼ taken as 1
Minimum fcu, fcuMin = 25 N/mm², Concrete Grade Ratio, Min(fcu, 40) / fcuMin = 30 / 25 = 1.200
Concrete Shear Capacity, νc = 0.79 {100 As / (bv d)}⅓ (400 / d)¼ (fcu / 25)⅓ / γm
= 0.79 × {0.25}⅓ × 1.000 × (1.200)⅓ / 1.25 = 0.42 N/mm²
Minimum Design Shear Stress, νMin = 0.40 N/mm²
νss = 0.263 < νc + 0.4, Provides only minimum link
Design for minimum Shear Stress, νd = νmin = 0.40 N/mm²
Shear Link Area / Spacing Ratio, SAsv_Sv = (vd × b) / (fyy × fy) = (0.40 × 225) / (0.95 × 460) = 0.205 mm²/mm

Shear Reinforcement Provided : T10-250 (Link spacing is governed by user setting)


Shear Link Area / Spacing Ratio Provided = 0.628 mm²/mm > 0.205 mm²/mm

DEFLECTION CHECKING FOR SPAN


No Sagging Moment on Span, No Deflection Check is Proceeded.
Deflection check is not required for this span due to reverse behaviour which may be caused by uplift effect or short span.

BEAM GB9(225x450/600/450) SPAN NO. 7

FLEXURAL DESIGN CALCULATION


LOCATION : SPAN
Design Bending Moment = 22.7 kNm Width, b = 225.0 mm Effective Depth, d = 409.0 mm
Mu / bd² = 22.7 × 1000000 / (225.0 × 409.0²) = 0.602 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.602 <= 4.691
Design as Singly Reinforced Rectangular Beam
Concrete Neutral Axis, x = 20.799 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 20.799 / 1000 = 56.72 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 56.72 × 1000 / (460 / 1.05) = 130 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 56.72 × (409.0 - 0.4518 × 20.799) / 1000 = 22.7 kNm
Maximum Depth of Section = 450.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 450.0 = 132 mm²

Top Compression Steel Area Required = 132 mm²


Bottom Tension Steel Area Required = 132 mm²

Top Reinforcement Provided = 2T12 (226 mm²)


Bottom Reinforcement Provided = 2T12 (226 mm²)

LOCATION : LEFT SUPPORT


Design Bending Moment = 21.7 kNm Width, b = 225.0 mm Effective Depth, d = 409.0 mm
Mu / bd² = 21.7 × 1000000 / (225.0 × 409.0²) = 0.576 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.576 <= 4.691

Design as Singly Reinforced Rectangular Beam


Concrete Neutral Axis, x = 19.883 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 19.883 / 1000 = 54.22 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 54.22 × 1000 / (460 / 1.05) = 124 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 54.22 × (409.0 - 0.4518 × 19.883) / 1000 = 21.7 kNm
Maximum Depth of Section = 450.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 450.0 = 132 mm²

Top Tension Steel Area Required = 132 mm²


Bottom Compression Steel Area Required = 132 mm²

Top Reinforcement Provided = 2T12 (226 mm²)


Bottom Reinforcement Provided = 2T12 (226 mm²)

LOCATION : RIGHT SUPPORT


Design Bending Moment = 16.3 kNm Width, b = 225.0 mm Effective Depth, d = 409.0 mm
Mu / bd² = 16.3 × 1000000 / (225.0 × 409.0²) = 0.433 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.433 <= 4.691

Design as Singly Reinforced Rectangular Beam


Concrete Neutral Axis, x = 14.843 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 14.843 / 1000 = 40.48 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 40.48 × 1000 / (460 / 1.05) = 93 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 40.48 × (409.0 - 0.4518 × 14.843) / 1000 = 16.3 kNm
Maximum Depth of Section = 450.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 450.0 = 132 mm²

Top Tension Steel Area Required = 132 mm²


Bottom Compression Steel Area Required = 132 mm²

Top Reinforcement Provided = 2T12 (226 mm²)


Bottom Reinforcement Provided = 2T12 (226 mm²)

LOCATION : 1/4 SPAN


Design Bending Moment = 0.0 kNm Width, b = 225.0 mm Effective Depth, d = 409.0 mm
Mu / bd² = 0.0 × 1000000 / (225.0 × 409.0²) = 0.000 N/mm²
Design to minimum steel percentage specified by code,
Maximum Depth of Section = 450.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 450.0 = 132 mm²
Top Tension Steel Area Required = 132 mm²

Top Reinforcement Provided = 2T12 (226 mm²)


Bottom Reinforcement Provided = 2T12 (226 mm²)

SHEAR & TORSION DESIGN CALCULATION


LOCATION : SECTION 1 LEFT SUPPORT
(B:0 mm E:1138 mm from left grid of span)

Maximum Torsion within Zone, T = 0.0 kNm


Shear at Location of Maximum Torsion, V = 39.2 kN
Link Horizontal Dimension, h1 = b - 2 × Side Cover - DiaLink = 225 - 2 × 25 - 10 = 165 mm
Link Vertical Dimension, v1 = h - 2 × Cover - DiaLink = 450 - 2 × 25 - 10 = 390 mm
Dimension x1 = Min (h1, v1) = 165 mm, y1 = Max (h1, v1) = 390 mm

Section Dimension: Dmin = 225.0 mm, Dmax = 450.0 mm


Torsion Stress, νst = 2 × T × 106 / (Dmin² × (Dmax - Dmin / 3)) = 0.00 N/mm²
Effective depth, d = 409.0 mm
Shear Stress, νss = V × 1000 / (b × d) = 39.2 × 1000 / (225.0 × 409.0) = 0.43 N/mm²

Part 2 : Clause 2.4.6 and Table 2.3


Maximum Combined Stress Allowed, νtu = Min (0.8 × √fcu, 5) = 4.38 N/mm²
Total Stress, νTot = νss + νst = 0.43 + 0.00 = 0.43 N/mm² ≤ νtu (4.38 N/mm²)
Checking for Combined Stress Allowed Pass

Part 2: Clause 2.4.5


Additional Checking While Small Cross Section (y1 < 550 mm)
Larger Link Dimension, y1 = 390.0 mm < 550 mm
νtu × y1 / 550 = 4.38 × 390.0 / 550 = 3.11 N/mm²
νst = 0.00 N/mm² ≤ 3.11 N/mm²
Checking for Torsion Stress Allowed Pass

Part 2 : Clause 2.4.6 Table 2.3


Torsion Strength contributed by concrete, νt,min = Min (0.067 × √fcu, 0.4) = 0.37 N/mm²
Torsion Stress, νst = 0.00 N/mm² < νt,min = 0.37 N/mm² -> No Torsion Reinforcement is needed

Maximum Shear within Zone, V = 37.6 kN


Maximum Shear Stress Allowed, νMax = Min (0.8 × √30, 5) = 4.38 N/mm² - Clause 3.4.5.2
Shear Stress, νss = V × 1000 / (b × d) = 37.6 × 1000 / (225.0 × 409.0) = 0.41 N/mm² ≤ νMax (4.38 N/mm²)
Checking for Maximum Shear Stress Allowed Pass

Tension Steel Area Provided, Ast = 226 mm²


- Table 3.8: Values of νc, design concrete shear stress
Steel Percentage, 100 × As / (bv × d) = 0.25 % ≤ 3.0 %
Effective Depth Ratio, edr = 400 / d = 400 / 409.0 = 0.978
(400 / d)^ ¼ = 0.994 < 1, (400 / d)^ ¼ taken as 1
Minimum fcu, fcuMin = 25 N/mm², Concrete Grade Ratio, Min(fcu, 40) / fcuMin = 30 / 25 = 1.200
Concrete Shear Capacity, νc = 0.79 {100 As / (bv d)}⅓ (400 / d)¼ (fcu / 25)⅓ / γm
= 0.79 × {0.25}⅓ × 1.000 × (1.200)⅓ / 1.25 = 0.42 N/mm²
Minimum Design Shear Stress, νMin = 0.40 N/mm²
νss = 0.409 < νc + 0.4, Provides only minimum link
Design for minimum Shear Stress, νd = νmin = 0.40 N/mm²
Shear Link Area / Spacing Ratio, SAsv_Sv = (vd × b) / (fyy × fy) = (0.40 × 225) / (0.95 × 460) = 0.205 mm²/mm

Shear Reinforcement Provided : T10-250 (Link spacing is governed by user setting)


Shear Link Area / Spacing Ratio Provided = 0.628 mm²/mm > 0.205 mm²/mm

LOCATION : SECTION 1 MIDDLE ZONE


(B:1138 mm E:3413 mm from left grid of span)
Maximum Torsion within Zone, T = 0.0 kNm
Shear at Location of Maximum Torsion, V = 17.1 kN
Link Horizontal Dimension, h1 = b - 2 × Side Cover - DiaLink = 225 - 2 × 25 - 10 = 165 mm
Link Vertical Dimension, v1 = h - 2 × Cover - DiaLink = 450 - 2 × 25 - 10 = 390 mm
Dimension x1 = Min (h1, v1) = 165 mm, y1 = Max (h1, v1) = 390 mm

Section Dimension: Dmin = 225.0 mm, Dmax = 450.0 mm


Torsion Stress, νst = 2 × T × 106 / (Dmin² × (Dmax - Dmin / 3)) = 0.00 N/mm²
Effective depth, d = 409.0 mm
Shear Stress, νss = V × 1000 / (b × d) = 17.1 × 1000 / (225.0 × 409.0) = 0.19 N/mm²

Part 2 : Clause 2.4.6 and Table 2.3


Maximum Combined Stress Allowed, νtu = Min (0.8 × √fcu, 5) = 4.38 N/mm²
Total Stress, νTot = νss + νst = 0.19 + 0.00 = 0.19 N/mm² ≤ νtu (4.38 N/mm²)
Checking for Combined Stress Allowed Pass

Part 2: Clause 2.4.5


Additional Checking While Small Cross Section (y1 < 550 mm)
Larger Link Dimension, y1 = 390.0 mm < 550 mm
νtu × y1 / 550 = 4.38 × 390.0 / 550 = 3.11 N/mm²
νst = 0.00 N/mm² ≤ 3.11 N/mm²
Checking for Torsion Stress Allowed Pass

Part 2 : Clause 2.4.6 Table 2.3


Torsion Strength contributed by concrete, νt,min = Min (0.067 × √fcu, 0.4) = 0.37 N/mm²
Torsion Stress, νst = 0.00 N/mm² < νt,min = 0.37 N/mm² -> No Torsion Reinforcement is needed

Maximum Shear within Zone, V = 17.1 kN


Maximum Shear Stress Allowed, νMax = Min (0.8 × √30, 5) = 4.38 N/mm² - Clause 3.4.5.2
Shear Stress, νss = V × 1000 / (b × d) = 17.1 × 1000 / (225.0 × 409.0) = 0.19 N/mm² ≤ νMax (4.38 N/mm²)
Checking for Maximum Shear Stress Allowed Pass

Tension Steel Area Provided, Ast = 226 mm²


- Table 3.8: Values of νc, design concrete shear stress
Steel Percentage, 100 × As / (bv × d) = 0.25 % ≤ 3.0 %
Effective Depth Ratio, edr = 400 / d = 400 / 409.0 = 0.978
(400 / d)^ ¼ = 0.994 < 1, (400 / d)^ ¼ taken as 1
Minimum fcu, fcuMin = 25 N/mm², Concrete Grade Ratio, Min(fcu, 40) / fcuMin = 30 / 25 = 1.200
Concrete Shear Capacity, νc = 0.79 {100 As / (bv d)}⅓ (400 / d)¼ (fcu / 25)⅓ / γm
= 0.79 × {0.25}⅓ × 1.000 × (1.200)⅓ / 1.25 = 0.42 N/mm²
Minimum Design Shear Stress, νMin = 0.40 N/mm²
νss = 0.186 < νc + 0.4, Provides only minimum link
Design for minimum Shear Stress, νd = νmin = 0.40 N/mm²
Shear Link Area / Spacing Ratio, SAsv_Sv = (vd × b) / (fyy × fy) = (0.40 × 225) / (0.95 × 460) = 0.205 mm²/mm

Shear Reinforcement Provided : T10-250 (Link spacing is governed by user setting)


Shear Link Area / Spacing Ratio Provided = 0.628 mm²/mm > 0.205 mm²/mm

LOCATION : SECTION 1 RIGHT SUPPORT


(B:3413 mm E:4550 mm from left grid of span)

Maximum Torsion within Zone, T = 0.0 kNm


Shear at Location of Maximum Torsion, V = 36.2 kN
Link Horizontal Dimension, h1 = b - 2 × Side Cover - DiaLink = 225 - 2 × 25 - 10 = 165 mm
Link Vertical Dimension, v1 = h - 2 × Cover - DiaLink = 450 - 2 × 25 - 10 = 390 mm
Dimension x1 = Min (h1, v1) = 165 mm, y1 = Max (h1, v1) = 390 mm

Section Dimension: Dmin = 225.0 mm, Dmax = 450.0 mm


Torsion Stress, νst = 2 × T × 106 / (Dmin² × (Dmax - Dmin / 3)) = 0.00 N/mm²
Effective depth, d = 409.0 mm
Shear Stress, νss = V × 1000 / (b × d) = 36.2 × 1000 / (225.0 × 409.0) = 0.39 N/mm²
Part 2 : Clause 2.4.6 and Table 2.3
Maximum Combined Stress Allowed, νtu = Min (0.8 × √fcu, 5) = 4.38 N/mm²
Total Stress, νTot = νss + νst = 0.39 + 0.00 = 0.39 N/mm² ≤ νtu (4.38 N/mm²)
Checking for Combined Stress Allowed Pass

Part 2: Clause 2.4.5


Additional Checking While Small Cross Section (y1 < 550 mm)
Larger Link Dimension, y1 = 390.0 mm < 550 mm
νtu × y1 / 550 = 4.38 × 390.0 / 550 = 3.11 N/mm²
νst = 0.00 N/mm² ≤ 3.11 N/mm²
Checking for Torsion Stress Allowed Pass

Part 2 : Clause 2.4.6 Table 2.3


Torsion Strength contributed by concrete, νt,min = Min (0.067 × √fcu, 0.4) = 0.37 N/mm²
Torsion Stress, νst = 0.00 N/mm² < νt,min = 0.37 N/mm² -> No Torsion Reinforcement is needed

Maximum Shear within Zone, V = 34.6 kN


Maximum Shear Stress Allowed, νMax = Min (0.8 × √30, 5) = 4.38 N/mm² - Clause 3.4.5.2
Shear Stress, νss = V × 1000 / (b × d) = 34.6 × 1000 / (225.0 × 409.0) = 0.38 N/mm² ≤ νMax (4.38 N/mm²)
Checking for Maximum Shear Stress Allowed Pass

Tension Steel Area Provided, Ast = 226 mm²


- Table 3.8: Values of νc, design concrete shear stress
Steel Percentage, 100 × As / (bv × d) = 0.25 % ≤ 3.0 %
Effective Depth Ratio, edr = 400 / d = 400 / 409.0 = 0.978
(400 / d)^ ¼ = 0.994 < 1, (400 / d)^ ¼ taken as 1
Minimum fcu, fcuMin = 25 N/mm², Concrete Grade Ratio, Min(fcu, 40) / fcuMin = 30 / 25 = 1.200
Concrete Shear Capacity, νc = 0.79 {100 As / (bv d)}⅓ (400 / d)¼ (fcu / 25)⅓ / γm
= 0.79 × {0.25}⅓ × 1.000 × (1.200)⅓ / 1.25 = 0.42 N/mm²
Minimum Design Shear Stress, νMin = 0.40 N/mm²
νss = 0.376 < νc + 0.4, Provides only minimum link
Design for minimum Shear Stress, νd = νmin = 0.40 N/mm²
Shear Link Area / Spacing Ratio, SAsv_Sv = (vd × b) / (fyy × fy) = (0.40 × 225) / (0.95 × 460) = 0.205 mm²/mm

Shear Reinforcement Provided : T10-250 (Link spacing is governed by user setting)


Shear Link Area / Spacing Ratio Provided = 0.628 mm²/mm > 0.205 mm²/mm

DEFLECTION CHECKING FOR SPAN


Basic Span / Effective Depth Ratio, Br = 26.0
Span Length, l = 4550.0 mm, Effective Depth, d = 409.0 mm
Actual Span / Effective Depth Ratio, Ar = 11.1
Ultimate Design Moment, Mu = 22.7 kNm
Design Steel Strength, fy = 460.0 N/mm²
Tension Steel Area Required, AsReq = 132 mm²
Tension Steel Area Provided, AsProv = 226 mm²
Compression Steel Area Provided, AsProv (Comp.) = 226 mm²

- Checking for deflection is based on BS8110: 1997


- Table 3.9: Basic span / effective depth ratio for rectangular or flange beams
- Table 3.10: Modification factor for tension reinforcement
- Table 3.11: Modification factor for compression reinforcement

Design Service Stress in Tension Reinforcement, Equation 8


fs = {(2 × fy × AsReq) / (3 × AsProv)} × (1 / ßb)
= {(2 × 460.0 × 132) / (3 × 226)} × (1 / 1.00) = 178.5 N/mm²

Modification Factor for Tension Reinforcement, Equation 7


MFt = 0.55 + {(477 - fs) / (120 × (0.9 + (M/bd²)))}
= 0.55 + {(477 - 178.5) / (120 × (0.9 + (22.7 × 1000000 / (225 × 409.0²)))}
= 2.21 > 2.0
MFt taken as 2.0

New Modification Factor for Compression Reinforcement, Equation 9


MFc = 1 + {(100 × AsProv / (b × d)) / (3 + (100 × AsProv / (b × d)))}
= 1 + {(100 × 226 / (225.0 × 409.0)) / (3 + (100 × 226 / (225.0 × 409.0)))}
= 1.08 <= 1.5

New Deflection Ratio = (Br × MFt × MFc) / Ar = (26.0 × 2.00 × 1.08) / 11.1 = 5.03
Ratio >= 1.0 : Deflection Checked PASSED

BEAM GB9(225x450/600/450) SPAN NO. 8

FLEXURAL DESIGN CALCULATION

LOCATION : LEFT SUPPORT


Design Bending Moment = 16.9 kNm Width, b = 225.0 mm Effective Depth, d = 409.0 mm
Mu / bd² = 16.9 × 1000000 / (225.0 × 409.0²) = 0.448 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.448 <= 4.691

Design as Singly Reinforced Rectangular Beam


Concrete Neutral Axis, x = 15.389 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 15.389 / 1000 = 41.97 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 41.97 × 1000 / (460 / 1.05) = 96 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 41.97 × (409.0 - 0.4518 × 15.389) / 1000 = 16.9 kNm
Maximum Depth of Section = 450.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 450.0 = 132 mm²

Top Tension Steel Area Required = 132 mm²


Bottom Compression Steel Area Required = 132 mm²

Top Reinforcement Provided = 2T12 (226 mm²)


Bottom Reinforcement Provided = 2T12 (226 mm²)

LOCATION : 1/4 SPAN


Design Bending Moment = 8.2 kNm Width, b = 225.0 mm Effective Depth, d = 409.0 mm
Mu / bd² = 8.2 × 1000000 / (225.0 × 409.0²) = 0.217 N/mm²
Singly Reinforced Design, limit Mu / bd² < kk1
Mu / bd² = 0.217 <= 4.691

Design as Singly Reinforced Rectangular Beam


Concrete Neutral Axis, x = 7.399 mm
Concrete Compression Force, Fc = k1 × b × x / 1000 = 12.12 × 225 × 7.399 / 1000 = 20.18 kN
Steel Area Required, AsReq = Fc × 1000 / (fy / γs) = 20.18 × 1000 / (460 / 1.05) = 47 mm²
Moment Capacity = Fc × (d - k2 × x) / 1000 = 20.18 × (409.0 - 0.4518 × 7.399) / 1000 = 8.2 kNm
Maximum Depth of Section = 450.0 mm
Minimum Tension Steel Area Required = 0.13% × 225.0 × 450.0 = 132 mm²

Top Tension Steel Area Required = 132 mm²


Bottom Compression Steel Area Required = 132 mm²

Top Reinforcement Provided = 2T12 (226 mm²)


Bottom Reinforcement Provided = 2T12 (226 mm²)

SHEAR & TORSION DESIGN CALCULATION


LOCATION : SECTION 1 (B:0 mm E:1563 mm from left grid of span)

Maximum Torsion within Zone, T = 0.0 kNm


Shear at Location of Maximum Torsion, V = 14.7 kN
Link Horizontal Dimension, h1 = b - 2 × Side Cover - DiaLink = 225 - 2 × 25 - 10 = 165 mm
Link Vertical Dimension, v1 = h - 2 × Cover - DiaLink = 450 - 2 × 25 - 10 = 390 mm
Dimension x1 = Min (h1, v1) = 165 mm, y1 = Max (h1, v1) = 390 mm

Section Dimension: Dmin = 225.0 mm, Dmax = 450.0 mm


Torsion Stress, νst = 2 × T × 106 / (Dmin² × (Dmax - Dmin / 3)) = 0.00 N/mm²
Effective depth, d = 409.0 mm
Shear Stress, νss = V × 1000 / (b × d) = 14.7 × 1000 / (225.0 × 409.0) = 0.16 N/mm²

Part 2 : Clause 2.4.6 and Table 2.3


Maximum Combined Stress Allowed, νtu = Min (0.8 × √fcu, 5) = 4.38 N/mm²
Total Stress, νTot = νss + νst = 0.16 + 0.00 = 0.16 N/mm² ≤ νtu (4.38 N/mm²)
Checking for Combined Stress Allowed Pass

Part 2: Clause 2.4.5


Additional Checking While Small Cross Section (y1 < 550 mm)
Larger Link Dimension, y1 = 390.0 mm < 550 mm
νtu × y1 / 550 = 4.38 × 390.0 / 550 = 3.11 N/mm²
νst = 0.00 N/mm² ≤ 3.11 N/mm²
Checking for Torsion Stress Allowed Pass

Part 2 : Clause 2.4.6 Table 2.3


Torsion Strength contributed by concrete, νt,min = Min (0.067 × √fcu, 0.4) = 0.37 N/mm²
Torsion Stress, νst = 0.00 N/mm² < νt,min = 0.37 N/mm² -> No Torsion Reinforcement is needed

Maximum Shear within Zone, V = 14.4 kN


Maximum Shear Stress Allowed, νMax = Min (0.8 × √30, 5) = 4.38 N/mm² - Clause 3.4.5.2
Shear Stress, νss = V × 1000 / (b × d) = 14.4 × 1000 / (225.0 × 409.0) = 0.16 N/mm² ≤ νMax (4.38 N/mm²)
Checking for Maximum Shear Stress Allowed Pass

Tension Steel Area Provided, Ast = 226 mm²


- Table 3.8: Values of νc, design concrete shear stress
Steel Percentage, 100 × As / (bv × d) = 0.25 % ≤ 3.0 %
Effective Depth Ratio, edr = 400 / d = 400 / 409.0 = 0.978
(400 / d)^ ¼ = 0.994 < 1, (400 / d)^ ¼ taken as 1
Minimum fcu, fcuMin = 25 N/mm², Concrete Grade Ratio, Min(fcu, 40) / fcuMin = 30 / 25 = 1.200
Concrete Shear Capacity, νc = 0.79 {100 As / (bv d)}⅓ (400 / d)¼ (fcu / 25)⅓ / γm
= 0.79 × {0.25}⅓ × 1.000 × (1.200)⅓ / 1.25 = 0.42 N/mm²
Minimum Design Shear Stress, νMin = 0.40 N/mm²
νss = 0.156 < νc + 0.4, Provides only minimum link
Design for minimum Shear Stress, νd = νmin = 0.40 N/mm²
Shear Link Area / Spacing Ratio, SAsv_Sv = (vd × b) / (fyy × fy) = (0.40 × 225) / (0.95 × 460) = 0.205 mm²/mm

Shear Reinforcement Provided : T10-250 (Link spacing is governed by user setting)


Shear Link Area / Spacing Ratio Provided = 0.628 mm²/mm > 0.205 mm²/mm

DEFLECTION CHECKING FOR SPAN


Basic Span / Effective Depth Ratio, Br = 7.0
Span Length, l = 1562.5 mm, Effective Depth, d = 409.0 mm
Actual Span / Effective Depth Ratio, Ar = 3.8
Ultimate Design Moment, Mu = 16.9 kNm
Design Steel Strength, fy = 460.0 N/mm²
Tension Steel Area Required, AsReq = 132 mm²
Tension Steel Area Provided, AsProv = 226 mm²
Compression Steel Area Provided, AsProv (Comp.) = 226 mm²

- Checking for deflection is based on BS8110: 1997


- Table 3.9: Basic span / effective depth ratio for rectangular or flange beams
- Table 3.10: Modification factor for tension reinforcement
- Table 3.11: Modification factor for compression reinforcement
Design Service Stress in Tension Reinforcement, Equation 8
fs = {(2 × fy × AsReq) / (3 × AsProv)} × (1 / ßb)
= {(2 × 460.0 × 132) / (3 × 226)} × (1 / 1.00) = 178.5 N/mm²

Modification Factor for Tension Reinforcement, Equation 7


MFt = 0.55 + {(477 - fs) / (120 × (0.9 + (M/bd²)))}
= 0.55 + {(477 - 178.5) / (120 × (0.9 + (16.9 × 1000000 / (225 × 409.0²)))}
= 2.40 > 2.0
MFt taken as 2.0

New Modification Factor for Compression Reinforcement, Equation 9


MFc = 1 + {(100 × AsProv / (b × d)) / (3 + (100 × AsProv / (b × d)))}
= 1 + {(100 × 226 / (225.0 × 409.0)) / (3 + (100 × 226 / (225.0 × 409.0)))}
= 1.08 <= 1.5

New Deflection Ratio = (Br × MFt × MFc) / Ar = (7.0 × 2.00 × 1.08) / 3.8 = 3.94
Ratio >= 1.0 : Deflection Checked PASSED

BEAM SUPPORT REACTION TABLE


Current Beam Grid Mark: 1/D1-A2

Beam Support Reactions


Support Reaction, kN
Support No. Grid Mark Support Type
Dead Load Live Load
1 C1B Column 18.2 0.0
2 C1A Column 2.0 0.0
3 C1 Column 7.4 0.0
4 B1B Column 25.8 0.0
5 B1 Column 29.1 0.0
6 A1C Column 44.3 0.0
7 A1 Column 35.3 0.0

You might also like