This document provides design calculation for fire pump room.The structured is modelled and all applicable
forces are applied and checked.
AISC - LRFD
ASCE 07
Grade of steel used shall be S275, cold formed sections and complies to BS EN 10025
kN
Dead Load from Sheeting & services Wdl ≔ 0.15 ――
2
m
kN
UDL on the purlin due to roof sheeting WDL1 ≔ Wdl ⋅ sp WDL1 = 0.14 ――
m
kN
UDL on the girt due to roof sheeting WDL2 ≔ Wdl ⋅ sg WDL2 = 0.15 ――
m
Live Load
kN
Roof live load Wll ≔ 1 ――
2
m
kN
UDL on the purlin due to roof sheeting WLL ≔ Wll ⋅ sp WLL = 0.9 ――
m
Wind Load
m
Basic Wind speed - 3 sec gust speed Vb ≔ 45 ―
s
Factors KZ ≔ 0.85 KZt ≔ 1 Kd ≔ 0.9 k ≔ 0.613
kN
Wind load on the panels Wwl ≔ G ⋅ Cf ⋅ qh Wwl = 1.67 ――
2
m
kN
Wind load (UDL) on the module rail WWL ≔ Wwl ⋅ 0.1 m WWL = 0.17 ――
m
1.0 DL
0.6 DL + 1.0 WL
1.8 CONCLUSION
The structure is modelled in staad pro and above loads and combinations are applied.The structure is
found to be safe. The design reports and baseplate and anchor bolt designs are attached herewith.