( Beam to Beam)
s2 Vertical leg
3 sides ( Site weld ) (Shop weld)
s1 s
Where
s1 :3 sides (site weld)
s2 :Vertical leg (field weld)
s :Vertical leg (shop weld)
524692456.xls
Page no. of
Beam size : ISMB200
Flange width of beam bb : 500 mm
Cleat Angle : ISA50506 Depth of beam h: 1200 mm
Web thickness of beam tw : 20 mm
Connection length h1 : 1120 mm
Cleat Angle Leg Size L1 : 100 mm
Leg Size L2 : 100 mm
Leg Thickness ta : 18 mm
Design forces
b
Properties of Weld x x
a = 100 -10
= 90 mm x2 x1
b = h1- 20 - 25 mm
= 105 mm ( Rounded down ) y
x1 = 2 x 90 x 90 /2
2 x 90 + 105
= 28.42 mm
x2 = a - x1
= 61.58 mm
Eccentricity e = 20 + x2
= 81.58 mm
M1 = Va x e
= 3.72 kN-m
qv = Va / (2xa + b ) + M1 x x2/ Ip
qh = M1 x ( b /2) / Ip
= 230.2 N/mm
qc = 366.5 N/mm
Since the actual shear stress is more than qc , increase weld size
b/18
b/6
Check of Weld for Shear and Bending
2 b/3
= 45.6 kN
5 b/6
b
b/6
M2 = Moment due to shear acting out of plane
= Va x e2 F
= 4.56 kN-m
5 b/18
Va Va
524692456.xls
Page no. of
qv = Va / b
F = 0.5 x qt x (5 b/6)
M2 = F x ( 2b/3)
= qt x (5/18) b2
qt = (18/5) x M2 / (b2)
= 1489 N/mm
= 1551 N/mm
qc = 366.5 N/mm
Since the actual shear stress is more than qc , increase weld size
qc = 458.1 N/mm
Since the actual shear stress is more than qc , increase weld size
Shear Stress
tv = Va / (b x ta)
524692456.xls
Page no. of
KORADI TPS EXPANSION PROJECT - 3 x 660 MW
LARSEN & TOUBRO LIMITED (UNIT #8,8 & 10), KORADI, MAHARASHTRA L&T - S&L LIMITED
MAIN PLANT PACKAGE SHEAR CONNECTION CALCULATIONS Rev. : P00
L&T Project No. : C10901 (FOR STEEL STANDARD DRAWINGS) Date : 12.01.2010
L&T - S&L Job No.: L555000 Document No. Page :
Angle Lenth Shear Capacity (kN) Actual Shear Capacity (kN) % shear capacity
Beam Section Cleat Angle
(mm) 6 mm 8 mm 10 mm 6 mm 8 mm 10 mm 6 mm 8 mm 10 mm
ISMB 200 ISA 50506 130 65 . . 65.28 . . 62 . .
ISMB 250 ISA 50506 170 108 . . 108.68 . . 63 . .
ISMB 300 ISA 75758 220 132 . . 132.75 . . 59 . .
ISMB 350 ISA 75758 265 175 . . 175.77 . . 62 . .
ISMB 400 ISA 909010 310 202 267 . 202.92 267 . 57 75 .
ISMB 450 ISA 909010 355 . 317 . . 317.25 . . 75 .
ISMB 500 ISA 909010 400 . 374 . . 374.85 . . 73.5 .
ISMB 600 ISA 10010012 475 . . 540 . . 540 . . 75
Note :
1. The weld considered is assumed to be site weld. `
KORADI TPS EXPANSION PROJECT - 3 x 660 MW
LARSEN & TOUBRO LIMITED (UNIT #8,8 & 10), KORADI, MAHARASHTRA L&T - S&L LIMITED
MAIN PLANT PACKAGE SHEAR CONNECTION CALCULATIONS Rev. : P00
L&T Project No. : C10901 (FOR STEEL STANDARD DRAWINGS) Date : 12.01.2010
L&T - S&L Job No.: L555000 Document No. Page :
KORADI TPS EXPANSION PROJECT - 3 x 660 MW
LARSEN & TOUBRO LIMITED (UNIT #8,8 & 10), KORADI, MAHARASHTRA L&T - S&L LIMITED
MAIN PLANT PACKAGE SHEAR CONNECTION CALCULATIONS Rev. : P00
L&T Project No. : C10901 (FOR STEEL STANDARD DRAWINGS) Date : 12.01.2010
L&T - S&L Job No.: L555000 Document No. Page :
Cleat Angle tw
`
Weld A
Weld A
s
Beam Section
Detail - I Angle
Check for Permissible stresses in web element : (for full capacity of the weld - Shop weld)
Stresses in weld A, fA = Capacity Factor x f x 0.707 x s N/mm
where,
f = Permissible stresses in Weld, MPa
s = Size of the weld, mm
Capacity factor = 1.0 (shop weld) ; 0.80 (site weld)
If fA < fW, the capacity of beam element (web) is greater than Stresses in weld, Hence O.K
If fA > fW, the capacity of beam element (web) is lesser than Stresses in weld, Hence needs revision.
KORADI TPS EXPANSION PROJECT - 3 x 660 MW
LARSEN & TOUBRO LIMITED (UNIT #8,8 & 10), KORADI, MAHARASHTRA L&T - S&L LIMITED
MAIN PLANT PACKAGE SHEAR CONNECTION CALCULATIONS Rev. : P00
L&T Project No. : C10901 (FOR STEEL STANDARD DRAWINGS) Date : 12.01.2010
L&T - S&L Job No.: L555000 Document No. Page :
KORADI TPS EXPANSION PROJECT - 3 x 660 MW
LARSEN & TOUBRO LIMITED (UNIT #8,8 & 10), KORADI, MAHARASHTRA L&T - S&L LIMITED
MAIN PLANT PACKAGE SHEAR CONNECTION CALCULATIONS Rev. : P0
L&T Project No. : C10901 (FOR STEEL STANDARD DRAWINGS) Date : 05.01.2010
L&T - S&L Job No.: L555000 Document No. Page :
Vertical leg
(Site weld)
s2 Vertical leg
3 sides ( Shop weld )
(Site weld)
s1
s
Properties of Weld
b
x x
Allowing for erection gap and allowanace in slotted hole
in the beam,
a = 50 -10
= 40 mm
x2 x1
b = h1 - 10 -10 mm
= 130 mm ( Rounded down ) y
KORADI TPS EXPANSION PROJECT - 3 x 660 MW
LARSEN & TOUBRO LIMITED (UNIT #8,8 & 10), KORADI, MAHARASHTRA L&T - S&L LIMITED
MAIN PLANT PACKAGE SHEAR CONNECTION CALCULATIONS Rev. : P0
L&T Project No. : C10901 (FOR STEEL STANDARD DRAWINGS) Date : 05.01.2010
L&T - S&L Job No.: L555000 Document No. Page :
x1 = 2 x 40 x 40 /2
2 x 40 + 130
= 7.62 mm
x2 = a - x1
= 32.38 mm
Eccentricity e = 10 + x2
= 42 mm
M1 = Va x e
= 1.383 kN-m
qv = Va / (2xa + b ) + M1 x X2/ Ip
qh = M1 x ( b /2) / Ip
= 163 N/mm
= 287 N/mm
qc = 458 N/mm
Since the actual shear stress is less than qc , weld size is adequate.
= 32.64 kN
5 b/6
b
b/6
Va Va
KORADI TPS EXPANSION PROJECT - 3 x 660 MW
LARSEN & TOUBRO LIMITED (UNIT #8,8 & 10), KORADI, MAHARASHTRA L&T - S&L LIMITED
MAIN PLANT PACKAGE SHEAR CONNECTION CALCULATIONS Rev. : P0
L&T Project No. : C10901 (FOR STEEL STANDARD DRAWINGS) Date : 05.01.2010
L&T - S&L Job No.: L555000 Document No. Page :
qv = Va / b
F = 0.5 x qt x (5 b/6)
M2 = F x ( 2b/3)
= qt x (5/18) b2
qt = (18/5) x M2 / (b2)
= 348 N/mm
= 429 N/mm
qc = 367 N/mm
Since the actual stress is more than qc, weld size is inadequate
qc = 458 N/mm
Since the actual shear stress is less than qc , weld size is adequate.
Shear Stress
tv = Va / (b x ta)
say, S req = 8 mm .
1
1
1
SHEAR CONNECTION CALCULATIONS
(FOR STEEL STANDARD DRAWINGS)
Weld B
Fig : 1 (C)
Considering S1 = 6 mm size site fillet weld between cleat angle and beam.
y
a
Capcity factor of Shop weld : 1.00 (Ref. Cl.7.1, IS 816 - 1969) 10 max
Capcity factor of Site weld : 0.80 (Ref. Cl.7.2, IS 816 - 1969)
Properties of Weld A :
in the beam, x x
a = 50 -10
= 40 mm
b = h1 - 10 -10 mm
= 130 mm ( Rounded down )
x2 x1
x1 = 2 x 40 x 40 /2 = 7.62 mm
2 x 40 + 130 y
Fig : 2
x2 = a - x1
= 32.38 mm
Eccentricity e = 10 + x2
= 42.38 mm
SHEAR CONNECTION CALCULATIONS
(FOR STEEL STANDARD DRAWINGS)
SHEAR CONNECTION CALCULATIONS
(FOR STEEL STANDARD DRAWINGS)
M1 = Va x e
= 1.383 kN-m
qv = Va / (2.a + b ) + M1 x X2/ Ip
qh =M1 x ( b /2) / Ip
= 163 N/mm
Since the actual shear stress is less than qc , weld size is adequate.
b/18
(For one angle section)
b/6
F
b/2
e2 = leg2 - x1
e2 = 42.38 mm F
5 b/18
qv = Va / (2a + b) Fig : 3
F = 0.5 x qt x (5 b/6)
M2 = F x ( 2b/3)
= qt x (5/18) b2
qt = (18/5) x M2 / (b2)
= 295 N/mm
Since the actual shear stress is less than qc , weld size is adequate.
SHEAR CONNECTION CALCULATIONS
(FOR STEEL STANDARD DRAWINGS)
SHEAR CONNECTION CALCULATIONS
(FOR STEEL STANDARD DRAWINGS)
qc = 458 N/mm
Since the actual shear stress is less than qc , weld size is adequate.
Shear Stress
t v = Va / (b x ta)
= Ratio *0.75
No. TAG DEPTH FLANGE WEBTHK h1 Area s_1 s_2
1 ISMB200 200 100 5.7 152.7 3233 6 6
No
1
No Conn.Angle L1 L2 ta
1 ISA50506 50 50 6
2 ISA65656 65 65 6
3 ISA65658 65 65 8
4 ISA75758 75 75 8
5 ISA757510 75 75 10
6 ISA90908 90 90 8
7 ISA909010 90 90 10
8 ISA10010010 100 100 10
9 ISA10010012 100 100 12
10 ISA13013010 130 130 10 `
11 ISA15015012 150 150 12
Beamtype Pershear Peraxial k2
2 57.2625 0 25