You are on page 1of 2

INSPECTION REPORT

Report No. :- BD/QC/C-2101/Flex./01 Date of Inspection : 29/11/2016

Project : Meja Thermal Power Project (2x660 MW) Client / Supplier : M/s BHEL - Bangalore

Drg. No. : C-2101-1016-82023 Rev. 00 Product : 415V, 2500A NSPBD


Quantum Specified Value Observed Value
Sl. No. Description Result Code
of check in MM in MM
1 Cu. Flexibles at TRF. Side (Qty. 28 Nos.)
For MCC-1D Building

A Visual & Surface Finish 100% Found OK A

B Dimension

B.1 Develop Length 100% 405 404 - 406 A

B.2 Thickness 100% 12 12.12 - 12.42 A

B.3 Width 100% 48 48.12 - 48.24 A

B.4 Holes Pitch 100% 50 - 60 50 - 60 A

B.5 No. of Holes 100% 2 - 2 Nos. 2 - 2 Nos. A

B.6 Hole Diameter 100% Dia. 14 Dia. 14.12 - 14.46 A

B.7 Conductivity (In % IACS) Sample Min 99% 99.50 - 100.50% A

B.8 TIN Plating Finish 100% Found OK A

B.9 TIN Plating Thickness Sample Min 14 Micron 15.40 - 16.50 Micron A

Result Code :

A : Accepted ü
AD : Accepted with Deviation
RW : Rework QC Inspector
R : Reject Date :
INSPECTION REPORT

Report No. :- BD/QC/C-2101/Flex./02 Date of Inspection : 29/11/2016

Project : Meja Thermal Power Project (2x660 MW) Client / Supplier : M/s BHEL - Bangalore

Drg. No. : C-2101-1016-82023 Rev. 00 Product : 415V, 2500A NSPBD


Quantum Specified Value Observed Value
Sl. No. Description Result Code
of check in MM in MM
1 Cu. Flexibles at SWGR. Side (Qty. 28 Nos.)
For MCC-1D Building

A Visual & Surface Finish 100% Found OK A

B Dimension

B.1 Develop Length 100% 385 384 - 386 A

B.2 Thickness 100% 12 12.12 - 12.42 A

B.3 Width 100% 48 48.12 - 48.24 A

B.4 Holes Pitch 100% 50 - 50 50 - 50 A

B.5 No. of Holes 100% 2 - 2 Nos. 2 - 2 Nos. A

B.6 Hole Diameter 100% Dia. 14 Dia. 14.12 - 14.46 A

B.7 Conductivity (In % IACS) Sample Min 99% 99.50 - 100.50% A

B.8 TIN Plating Finish 100% Found OK A

B.9 TIN Plating Thickness Sample Min 14 Micron 14.50 - 15.40 Micron A

Result Code :

A : Accepted ü
AD : Accepted with Deviation
RW : Rework QC Inspector
R : Reject Date :