Visual Inspection Report: V6-0714 Butane Day Tank (Sphere) PMT 108045 VEX/GPP-6/TA/14/174
Visual Inspection Report: V6-0714 Butane Day Tank (Sphere) PMT 108045 VEX/GPP-6/TA/14/174
DEFECT TEAM
Name plate:V6-0714 Correct PMT No.: (Received by)
S/N: - PMT 108045
Name: ______________________
Notification by NDT ‐ refer attached NDT/DT reports (Fill‐up by Doc. Controller) Date : ______________________
Activities Performed (Fill‐up by Doc. Controller)
All Repairs are
NDT Done : MPI / DPI / UTFlaw / UTTG / RT / ECT / RFET / MFL / IRIS / CUI / Videoscope completed
(By Defect Mgr)
Others : Ext Paint / Int Paint / HT / Pneumatic / AE / PR
DOSH INSPECTION (Fill‐up by DOSH Escorter) Name: ______________________
FINDINGS / RECOMMENDATIONS / REMARKS by DOSH OFFICER: Date : ______________________
Equipment Ready
for BOX‐UP
(By Doc. Controller)
__________________________ Name: ______________________
EQUIPMENT ORIENTATION: Vertical
(Escorter Initial & Date) Date : ______________________
A. The equipment were found fully paint. Painting was noted still intact and in
satisfactory condition.
A B. Mostly of the foundation and fire proofing concrete was found with hair line
crack as per previous report.
C. The earthing lugs were found still intact and in satisfactory condition.
For Repair
RECOMMENDATION: defect Completed
Repair (Put date)
A. Nil. -
B C B. To be monitored. -
C. Nil. -
A & B. The serial number was noted not been punch on the name plate.
A
For Repair
RECOMMENDATION: defect Completed
Repair (Put date)
B Y
A & B. To punch the serial No.
For Repair
C RECOMMENDATION: defect
Repair
Completed
(Put date)
B -
A . Nil.
D
Inspected By: Amri b. Muhammad Inspection Date: 09 Feb 2014
Inspection Agency: Testex (M) Sdn. Bhd. Reviewed By: Ir. M. Zubir b. Mat Dahan
VISUAL INSPECTION REPORT PAGE: 5
INSPECTION COMMENTS
ID & DESCRIPTION CONDITION LOCATION NCR COMMENTS
V14 ‐ Shell Good All sections No No abnormality
V33 ‐ Nozzles Good Nozzles No No abnormality
V37 ‐ Bolting Poor Manhole & all Nozzle No Paint deteriorated
V38 ‐ Flanges Poor All sections No Crevice corrosion
V7 ‐ Platform Good All sections No No abnormality
V22 ‐ Foundation Fair All sections No Hair line crack
V26 ‐ Fireproofing Fair All sections No Hair line crack
V11 ‐ Coating/Painting Good Shell body No No abnormality
INSPECTION SUMMARY
Generally the external equipment were found in satisfactory condition. Except mostly of foundation and fire proofing concrete was found with hair line crack as per previous
report. serial number was noted not been punch on the name plate. Paintwork deteriorated (peel-off) with presence surface corrosion were found at entire of fasteners(M1,
M2, N1, N2, N3, N4, CN1,CN2, CN3, CN4, CN6, CN7 & CN8) and crevice corrosion in between the contact point of flanges nozzle.
INSPECTION COMMENTS
ID & DESCRIPTION CONDITION LOCATION NCR COMMENTS
V21 ‐ Internals Other (Please explain) No
V1 ‐ General Other (Please Explain) No
INSPECTION SUMMARY