Professional Documents
Culture Documents
7 Hydronic Systems March 2014 Slides
7 Hydronic Systems March 2014 Slides
1
System Components ‐ Heating
System Components
Expansion Tank
Air Separator Pump
Supply Pipe
Water Flow
Valve
Generate
Heat Source
Heat
Terminal Unit Space
Load
Water Flow
Return Pipe
2
System Components ‐ Cooling
System Components
Supply Pipe
Water Flow Valve
Reject Heat Sink
Heat (Chiller)
Terminal Unit
Expansion Tank Space
Load
Water Flow
Water Flow
Return Pipe
Air Separator
Pump
3
Heat Source or Sink
Heat Source or Sink
• Heating Hot Water (140˚F ‐
g ( 180˚F))
– Boiler
– Heat Exchanger
– Central Plant
C t l Pl t
• Chilled Water (37˚F ‐ 45˚F)
– Chiller
Chill
– Heat Exchanger
• Heat Pump Water (35˚F ‐
H tP W t (35˚F 90˚F)
– Ground Source: Ground / Pond
– Cooling Tower/Boiler
Cooling Tower/Boiler
4
Terminal Heat Transfer Units
Terminal Heat Transfer Units
• Distribute the heating/cooling to the space
Distribute the heating/cooling to the space
– Radiators
– Baseboard finned tube units
Baseboard finned tube units
– Coils within AHUs, fan coil units, variable air
volume terminals
volume terminals
– Heat pumps
5
Piping
• Configuration
• Sizing
6
Pipe Configuration
Pipe Configuration
• Direct Return
T‐1 T‐2 T‐3 T‐4
Balancing
Valve
• Reverse Return
T‐1 T‐2 T‐3 T‐4
7
Pipe Sizing
Pipe Sizing
• Related:
Related:
– Flow rate (GPM)
– Velocity (fpm)
Velocity (fpm)
– Pressure drop
– Pipe material
Pi t i l
8
Flow Rate
Flow Rate
GPM = Space Load/(500 x Δtwater)
GPM = Space Load/(500 x Δt
– Space Load in BTUh
– Δt in
Δt in ˚FF
9
Flow Rate
Flow Rate
Example:
GPM = 11,698 BTUh
GPM 11 698 BTUh /(500 x (180˚F‐160˚F))
/(500 (180˚F 160˚F))
GPM = 1.17
Pipe Space
Boiler Load
Pump
Increasing the Δt results in a lower GPM
Lower GPM results in smaller pump and smaller pipe
CAREFUL – Consider equipment capability
CAREFUL Consider equipment capability
10
Pipe Sizing
Pipe Sizing
• Related:
– Flow rate (GPM)
– Velocity (fpm)
– P
Pressure drop
d
– Pipe material
• Performance limitations:
P f li i i
– Velocity
• > 15 fps should be avoided
15 fps should be avoided
– Noise and erosion
– 6 ‐ 8 fps
– Pressure Drop (Head Loss)
p( )
• Range: 1ft/100ft ‐ 4ft/100ft
11
Pipe Sizing
Pipe Sizing
Influence on first‐costs and energy consumption
Pipe
Space
Boiler Load
Pump
Pipe size = Pipe $ Pipe size = Pipe $
PD
P.D. PD
P.D.
Energy Use Energy Use
Pump Size
p Pump Size
p
Lif C l C t C
Life Cycle Cost Comparison
i
12
Pipe Material
Pipe Material
• Related:
– Flow rate (GPM)
– Velocity (fpm)
– P
Pressure drop
d
– Pipe material
• Material
• Copper (Sch. L)
• Steel (Sch. 40)
• PVC (Sch. 80)
• Cross‐linked Polyethylene (PEX)
Cross‐linked Polyethylene (PEX)
13
Pipe Sizing Chart
Pipe Sizing Chart
14
Pipe Sizing
Pipe Sizing
• Certain
Certain pipe sizes are not standard:
pipe sizes are not standard:
5 in., 3‐½ in., 2‐½ in., 1‐¼ in.
– The above specialty sizes are expensive
The above specialty sizes are expensive
• May not be available
• ½ in. minimum pipe size for commercial design
15
Pipe Sizing Example
Pipe Sizing Example
• ASHRAE
ASHRAE headquarter
headquarter’ss building ground source
building ground source
heat pump system
• 60 GPM with copper pipe
• What
What is the size of pipe if designed using 4 ft
is the size of pipe if designed using 4 ft
of head loss per 100 ft of length?
16
Example
17
Example
18
System Head Loss
System Head Loss
• Based on the run with the greatest losses
Based on the run with the greatest losses
– Longest length
– Most fittings / Valves
Most fittings / Valves
– Largest terminal unit loss
– Open vs. closed system
O l d t
• Vertical head
19
Equivalent Length
Equivalent Length
• Graphic of equivalent length chart
Graphic of equivalent length chart
ASHRAE Fund. 2005, Chpt. 36
Example:
(1) 2‐1/2 in. 45˚Elbow
6.7 ft X 0.7 = 4.7 ft
System Head Loss
System Head Loss
• Pipe Losses
Pipe Losses
– Exterior Bore:
– Internal Pipe Length:
21
22
System Head Loss
System Head Loss
• Pipe Losses
Pipe Losses
– Exterior Bore:
• 400 ft (2)bore depth =
400 ft (2)bore depth = 800 ft
800 ft
• 100 ft (2) horizontal = 200 ft
– Internal Pipe Length:
Internal Pipe Length:
23
GT07 Determine greatest PD:
Small furthest HP
Small furthest HP
80 ft x 2 (4 ft/100 ft) +1.5 ft = 7.9 ft
80’ vs.
Larger closer HP
Larger closer HP
GT38 15 ft
120’
Pump Location
System Head Loss
System Head Loss
• Pipe Losses
– Exterior Bore:
• 400 ft (2)bore depth = 800 ft
• 100 ft (2) horizontal = 200 ft
– Internal Pipe Length:
• 120 ft (2) horizontal = 240 ft
• 10 ft (2) vertical = 20 ft
1260 ft x 1.1 ft = 1386 ft
1386 ft length x 4 ft head loss/100 ft length = 55 ft head loss
• Heat Pump –
p highest PD unit
g
– 15 ft head loss
• Pump Fittings
– 5 ft head loss
ft head loss
Total Head: 55 +15 +5 = 75 ft
25
Pressuree Loss, Ft oof Head System Curve
System Curve
Q = Cs(Δh)1/2
Q = Flow Rate, GPM
Cs = System Constant
Δh = System Head Loss
Flow Rate, GPM
System head = friction pressure drop (piping, valves, terminal units, etc.) 26
System Curve Example
• Headquarters
Headquarters building ground source heat
building ground source heat
pump system
• 60 GPM with 75
60 GPM with 75 ft head
• What does the system curve look like?
• Q = Cs(Δh)1/2 60 = Cs(75)1/2 Cs=6.92
27
Headquarter’s System Curve
80
70
60
Pressurre Loss (Ft of Head)
50
40
30
20
10
0
0 1 10 20 30 40 50 60
Flow Rate (GPM)
28
System Operating Point
System Operating Point
System Curve
Pressuree Loss, Ft oof Head
Pump Curve
Operating Point
Flow Rate, GPM
29
30
Actual System Operating Point
Actual System Operating Point
Pump Curve System Curve
Pressuree Loss, Ft oof Head
Actual
Actual
Operating
Design Operating Point
Point
Flow Rate, GPM
31
Primary‐Secondary
Primary Secondary Pumping
Pumping
• ‘Compound pumping’
o pou d pu p g
• Used in larger systems ‐ simplifies the system control
• Attain different water temps in different loops of system
p p y
Primary Secondary
Pump Pump
32
Primary‐Secondary
Primary Secondary Pumping
Pumping
Primary Secondary
Pump Pump
160˚F 160˚F
33
Primary‐Secondary
Primary Secondary Pumping
Pumping
Primary Secondary
Pump Pump
170˚F 160˚F
34
System Components
System Components
Expansion Tank
p
Ai S
Air Separator Pump
Supply Pipe
Valve
Heat Source Load
Return Pipe
35
System Components
System Components
Expansion Tank
p
Ai S
Air Separator Pump
Supply Pipe
Valve
Heat Source Load
Return Pipe
36
Expansion Tank
Expansion Tank
• Reference
Reference pressure point in system
pressure point in system
• Compensates for water expansion and
contraction
– Sized based on quantity of water, pressure of
system and change in water temperature
system, and change in water temperature
• Located on return side of pump
37
System Components
System Components
Expansion Tank
p
Ai S
Air Separator Pump
Supply Pipe
Valve
Heat Source Load
Return Pipe
38
Air Separator
Air Separator
• Air eliminator
e ato
– Velocity
• Reduces velocity < 0.5 fps
– Centrifugal
– Coalescence
• Air in hydronic
Ai i h d i system can cause problems
t bl
– Binding in the terminal units
– Corrosion
– Noise
– Cavitation
39
System Components
System Components
Expansion Tank
p
Ai S
Air Separator Pump
Supply Pipe
Valve
Heat Source
Load
Return Pipe
40
Valves
• Purpose: control, isolation, safety relief
Purpose: control isolation safety relief
– Control – open and close water path in response
to thermostatic setpoints
to thermostatic setpoints
– Isolation – enable the maintenance and removal
of components without draining system
of components without draining system
– Safety Relief – prevent over‐pressurization of the
system (required on all boilers)
system (required on all boilers)
41
Unit Control
Unit Control
T T T
T‐1 T‐2 T‐3 T‐4
Three‐Way
Modulating
Control
Control
Valve
(Mixing Valve)
Office 1 Office 2 Office 3
Bypass
42
Unit Control
Unit Control
T T T
Bypass T‐1 T‐2 T‐3 T‐4
P
Two‐Way
Modulating
Control
Valve
Office 1 Office 2 Office 3
43
Unit Control
Unit Control
T T T
T‐1 T‐2 T‐3 T‐4
P
Two‐Way
VFD Modulating
Control
Valve
Office 1 Office 2 Office 3
44
Other Components
Other Components
• Makeup water
Makeup water
• Drains
• Strainers
• Thermometers
• Fl ibl
Flexible connectors
t
• Pressure sensors
• Filters
• Etc.
45
Steam
• Distributed from a central plant for:
– Distant transportation
– Process
• Sterilization
• Manufacturing
• Laundry
• No supply pump
pp y p p
• Condensate return – gravity or pump
• Heat exchanger: hot water
h h
46
Steam
• Not typically used in occupied spaces
Not typically used in occupied spaces
– Expensive to install
– Difficult to control
Difficult to control
– Noise issues
– Safety
S f t
47
Steam Design
Steam Design
• Classifications:
– Low‐Pressure System, < 15psig
– High‐Pressure System, > 15psig
High Pressure System > 15psig
• Pressure to be kept to minimum
– Low pressure for most HVAC applications
• ASME Boiler and Pressure Vessel Code
– Annual testing required
48
Steam Design
Steam Design
• Slope piping down in direction of flow
Slope piping down in direction of flow
– Supply: 0.25 in./10 ft
– Return: 0.5 in./10 ft
Return: 0 5 in /10 ft
• Drip Leg ‐ separate & collect condensate
• Trap ‐ control release of condensate to return
piping while preventing the escape of steam
Steam Main
Drip Leg Trap
Condensate Return
Condensate Return
Dirt Pocket
Isolation Valves
49
Questions?
50