NOTES:-

[GENERAL]
[1] ALL DIMENSIONS ARE IN M.M. UNLESS OTHERWISE MENTIONED.
[2] ONLY FIGURED DIMENSIONS ARE TO BE FOLLOWED NEITHER THE BARS SHALL
BRICK WALL / COLUMN SUPPORT. BE COUNTED NOR THE DIMENSIONS SCALED FROM THE DRG.
[3] ANY DISCREPANCY IN THE DRGS. SHALL BE BROUGHT TO THE NOTICE OF
t1+t2 THE ARCHITECT / CONSULTANT AND CLARIFICATION OBTAINED IN WRITING
t1 PRIOR TO EXECUTION OF WORK.
[4] HIGH YIELD STRENGTH DEFORMED BARS OF YIELD STRESS 500 N/MM2 (Fe-500)
t2
STPS WHICH SHALL CONFORM TO1786-1985 SHALL BE USED AS REINFORCEMENT
b2 [5] CLEAR COVER OF OUTER LAYER REINF. SHALL BE AS FOLLOWS.
(a) FOOTIG = 75 mm. (b) COLUMN = 40 mm. (c) BEAM = 35mm.(TOP & BOTTOM)
b1+b2 b1 OR DIA OF BAR ,WHICHEVER IS MORE (d) SLAB = 25 mm (c) WAIST SLAB = 25 mm.
[6] END/SIDE COVER OF ALL REINFORCEMENT IN BEAMS & SLAB = 25 mm. OR DIA
OF BAR WHICHEVER IS MORE
[7] THE COVER BLOCK OF CEMENT MORTAR SHALL BE USED TO ENSURE THE REQD.
COVER OF REINFORCEMENT
[8] DEVELOPMENT LENGTH ( Ld ) FOR DIFFERENT DIA METER OF BARS FOR
(E=D) CONC. MIX OF GRADE M - 20 SHALL BE = 49 X DIA OF BAR
(TO BE KEPT SUPPORTED TILL THE WALL ABOVE IS CAST) [9] CONC. MIX FOR R.C.C. WORK SHALL BE OF GRADE M - 25
CONFORMING TO I.S. 456 - 2000.
[10] NECESSARY FIXTURE FOR ELECTRICAL, PLUMBING, ETC. SHALL BE
SCHEDULE OF LINTELS PROVIDED IN SLAB, BEAMS BEFORE EXECUTION AS PER RELEVANT DRGS.
[11] THE STRUCTURE HAS BEEN DESIGNED AS SEISMIC ZONE - III
[12] THE STRUCTURE HAS BEEN DESIGNED FOR G.+1 =2 STOREY
[13] P.C.C.(1:4:8) SHALL BE PROVIDED.
REINFORCEMENT [14] ALL PLAIN CONCRETE & RCC SHALL BE STRICTLY IN ACCORDANCE WITH THE
L B D STIRRUPS REMARKS PROVISION OF IS - 456:2000
[15] CUTTING,BENDING,FIXING & PLACING OF BARS SHALL BE IN ACCORDANCE
b1 b2 t1 t2 WITH IS - 2502:1968, IS - 5525:1969 & IS - 456:2000
[FOUNDATION]
B C D [1] THE LAYOUT OF BUILDING SHALL BE GIVEN FROM THE ARCH. DRG.
A UP
TO 230 200 3010 - 2010 - 0 8@150 [2] SBC OF SOIL IS 15.0 T/M² AT DEPTH OF 1.5 M BELOW ORIGINAL N.G.L LEV.
1800 AS DIRECTED/ ASSURED BY CLIENT.

1800 [COLUMNS]
TO 230 300 3012 - 2010 - 0 8@125 [1] TIES IN PORTION OF COL. & BEAM JUNCTION SHALL BE SAME AS END ZONE.
3000 [2] OVER LAPS ARE ALLOWED ONLY AT MIDDLE ZONE OF THE COLUMNS.
3000 [3] NOT MORE THAN 50 % OF BARS SHALL BE LAPPED AT A SECTION AND
TO 3012 - 2012 - LAPS SHALL BE STAGGERED.
230 350 0 8@125 [4] TIES IN PORTION OF COL. BELOW PLINTH BEAM SHALL BE SAME AS END ZONE .
4000
[5] VERTICAL BARS OF RCC COLUMN AT TOP SLAB SHALL BE EXTENDED UPTO TOP
4000 OF BEAM & BENT INTO BEAM BY DEVELOPMENT LENGTH.
TO 230 400 3016 - 2012 - 0 8@100
4800
[BEAMS]
[1] FOR LOCATION OF BEAMS REFER SLAB PLAN.
[2] THE SPACING OF STIRRUPS AT OVERLAPS SHOULD NOT EXCEED 150 MM. C/C
[3] WHERE TWO LAYERS OF REINF. BARS ARE TO BE PROVIDED, SPACER BAR
ARE TO BE PROVIDED AT SPACING OF 1000 MM. MAX. AND THE DIA OF THE
SPACER BAR SHALL BE HIGHER OF DIA OF LONGITUDINAL BARS OR 25 MM.
[4] MAX. 3 NOS. OF BARS SHALL BE PROVIDED IN A LAYER OF 230 MM WIDE BEAM.
[5] AT THE JUNCTION OF TWO DIFF. NUMBER OF BEAMS THE HIGHER REINF.
AT THE SUPPORT SHALL BE ADOPTED.
[6] OVER LAP IN TOP BARS SHALL BE NEAR MID SPAN & IN BOTTOM BARS
SHALL BE NEAR SUPPORT OR AT COLUMN SUPPORT
[7] THE DEPTH OF BEAM/LINTEL M0N0LITHIC WITH SLAB AS SPECIFIED IN SCHEDULE
SHALL BE INCLUSIVE OF SLAB THICKNESS UNLESS OTHERWISE SPECIFIED
DEVELOPMENT LENGTH FOR DEFORMED BARS [8] HOOKS IN STIRRUPS OF BEAMS SHALL BE BENT INSIDE AT 135° & LENGTH OF
FY=500 N/ SQ.MM HOOKS SHALL BE 10 X DIA OF BAR OF STIRRUPS
[SLABS]
[1] DOTTED LINES ARE SHOWN AS TOP FACE REINFORCEMENT AND FIRM LINES AS
BAR TENSION BARS COMPRESSION BARS BOTTOM FACE REINFORCEMENT.
~ DIAMETER GRADE OF CONCRETE GRADE OF CONCRETE [2] ALL TOP FACE REINF.AT C0NTINU0US EDGE OF SLAB SHALL BE CONTINUED UP TO
L/3 OF SPAN & AT DISCONTINUOUS EDGE SHALL BE CRANKED FROM L/7 OF SPAN
(mm) M20 M25 M30 M35 M40 M20 M25 M30 M35 M40 [3] THE CROSS REINF. / TEMP. REINF. BELOW TOP REINF OF SLAB .i.e. #8@300 c/c IS TO
BE PROVIDED JUST BELOW THE MAIN TOP STEEL WHICH HAS NOT BEEN SHOWN
8 453 390 363 321 287 363 311 290 256 229 IN THE DRG.
[4] THE FIRST MAIN BAR OF SLAB SHALL BE PLACED AT 80 mm. OR HALF THE
10 570 485 453 400 358 453 389 363 321 287 SPACING SPECIFIED WHICHEVER IS LESS FROM THE FACE OF SUPPORT
12 680 583 544 480 430 544 470 435 384 344
[MASONRY WORK]
16 910 780 730 645 577 730 621 580 512 458 [1] 115 TH.(1/2 BRICK) WALL -1:4 CEMENT: SAND MORTAR SHALL BE USED & #8,1 NOS.
18 1020 880 820 724 648 820 700 653 577 516 BARS AT EVERY 4th COURSE SHALL BE PROVIDED
[2] 230 TH.(1 BRICK) WALL - 1:6 CEMENT: SAND MORTAR SHALL BE USED.
20 1135 971 910 803 719 910 780 730 645 577 [3] THE VERTICAL FACE OF CONCRETE AT JUNCTION OF WALL & RCC MEMBER
~ SHALL BE RAKED TO GIVE A ROUGH SURFACE & 1:4 CEMENT:SAND MORTAR
22 1250 1070 1000 883 790 1000 854 780 689 616
SHOULD BE APPLIED TO DEVELOPED BOND BETWEEN BRICK & RCC MEMBER.
25 1420 1214 1130 997 893 1133 971 910 803 719
28 1590 1360 1270 1121 1003 1270 1090 1020 900 806
32 1820 1555 1450 1280 1145 1450 1243 1210 1068 956
36 2040 1750 1630 1439 1287 1631 1400 1310 1156 1035

SECONDARY BEAM

1012 T&B (TYP)

DEVELOPMENT LENGTH FOR DEFORMED BARS


FY=415 N/ SQ.MM
>

1012 T&B (TYP)


80

1012 T&B (TYP)


MSC CELL , BHUBANESWAR.
M

Ø
M

BAR TENSION BARS COMPRESSION BARS


MAIN BEAM
2012(TYP.)
ADD.REINFORCING BARS DIAMETER GRADE OF CONCRETE GRADE OF CONCRETE E mail-marutistructural2014@gmail.com
ADD.REINFORCING BARS
2012 UPTO 700 mm. DIA.
2012 UPTO 700x700 (mm) M20 M25 M30 M35 M40 M20 M25 M30 M35 M40 Mobile-8895014557
2016 UPTO 900 mm.DIA.
2016 UPTO 900x900
8 380 325 305 270 241 305 260 205 181 162
10 470 405 380 336 300 380 325 305 270 241
(FOR CIRCULAR OPENING IN A SLAB) INDIAN OIL CORPORATION LIMITED
(FOR RECTANGULAR OPENING IN A SLAB) 12 565 485 455 402 360 455 390 365 322 289
16 755 645 605 534 478 605 520 485 428 383
18 850 725 680 600 537 680 580 545 481 431
MARINE CENTER OF EXCELLENCE BUILDING.
20 940 810 755 667 596 755 645 605 534 478
BEAM COL. BEAM 22 1040 890 830 733 656 830 710 665 587 525
REINF. REINF. 25 1175 1010 940 830 743 940 810 755 667 596 DETAILING OF REINFORCEMENT
Ø
28 1320 1130 1055 931 833 1055 905 845 746 668
32 1510 1290 1205 1064 952 1205 1035 965 852 762
36 1700 1450 1355 1196 1070 1355 1165 1085 958 857

COL.TIES COL.REINF. BEAM STIRUPS.