HSQE PROCEDURE
CALIBRATION (CONTROL OF MEASURING EQUIPMENT)
PROCEDURE
Revisions History:
Rev. Issue Date Description Author Reviewer Approval
M. Ahmady M. Bassett M. Leone
D. Fatti
3rd Issue for
02 20/08/20
PMS Approval L. Paresy
B. Webster
TABLE OF FIGURES
To define the processes to ensure that all equipment used in monitoring and measuring Quality,
Safety and Environmental related activities is capable of demonstrating product/process conformity
to pre-determined requirements and or standards.
1.2 SCOPE
This procedure applies to all controlled measuring equipment used across FLOW Controlled
Infrastructure and Premises, whether supplied by FLOW or otherwise.
Infrastructure Director Responsible for implementation of this procedure within their area
of responsibility (Civils and Mechanical, Electrical & Plumbing
(MEP))
Deputy Project Director Responsible for implementation of this procedure within their area
for Transit Systems of responsibility (Signaling, Control & Communications, Track,
Maintenance Platform Screen Doors (PSD), Power Supply & Distribution, Rolling
Stock & Depot Engineering)
Users of Controlled All users of test equipment have a responsibility to follow this
Testing Equipment procedure
Abbreviations Definitions
3.2 TERMS
Terms Definitions
Measuring Equipment All devices used to gauge, measure, test, inspect, or otherwise
determine compliance with prescribed technical requirements.
All controlled measuring equipment will be uniquely numbered, and capable of indicating its
calibration status and re-calibration due date either on the equipment or the equipment case.
All personnel are responsible for ensuring that any controlled measuring equipment under their use
is in calibration before use.
Any new equipment must be accompanied by a calibration certificate either from the manufacturer
or from a third-party to prove the instrument is in calibration.
Reasonable steps shall be taken to preserve/protect measuring equipment from going out of
calibration, examples of ways in which equipment should be protected include:
Third-party calibration laboratories should be accredited to ISO 17025 whenever possible, as this
provides the best control of calibration activities and traceability to national standards.
In certain cases, non-accredited calibration laboratories must be utilised, where unique skill or
knowledge of a specialised calibration process is required, such as the original equipment
manufacturer (OEM) or a specific calibration lab having certain resources to perform the required
calibration.
Employees who perform in-house calibrations must have records of competence, education,
training, skills, etc. to demonstrate their calibration qualifications. They must have attended or
oriented regarding calibration awareness as the first part of the training or exposure to calibration
basics, and this is under quality surveillance. FLOW will determine all training required to be
delivered to the employees by third-parties or manufacturers to demonstrate their competences.
• Authorisations
• Training records
When employees perform in-house calibration, this shall be achieved following documented
procedures and must have all the calibration standards and reference materials available for each
type of calibration performed.
CMMS will be used as the Calibration Log and will be maintained by the CMMS Manager. This will
list for all Controlled Measuring Equipment:
For Controlled Measuring Equipment calibrated by third-party laboratories, these shall be returned
with a certificate of calibration showing the status of the calibration, as well as the condition the
equipment was found in (e.g., “defective,” “out of tolerance”, “in tolerance”, etc.). Such certificates
must have the identification of any standards used by the calibration house, and their serial
numbers, allowing for traceability.
For Controlled Measuring Equipment calibrated in-house by FLOW staff, the results and standards
used shall be recorded on the Calibration Record and shall include any standards and/or procedures
used.
Calibrated devices will be identified with a calibration sticker that includes the current calibration
status, calibration due date, and device identification number. Where the device cannot
accommodate a calibration sticker due to size or frequency of use, the device shall be numbered,
and the CMMS Manager shall keep a log of those devices and their status.
Employees shall submit expired Controlled Measuring Equipment to the Stores Manager for re-
calibration.
Any Controlled Measuring Equipment failing to meet calibration standards will immediately be
taken out of service, and the calibration log must be updated. The device may then be destroyed or
sent out for repair. Repaired devices must be calibrated before being returned to service. This will
be subject to sec. 4.6.
Controlled Measuring Equipment used by sub-contractors and suppliers must comply with this
procedure, with calibration records available upon request, as described in the FLOW Contractor
and Supplier Management Procedure.
Approved third-party calibration laboratories must maintain suitable environmental conditions for
calibration as per ISO 17025, and report temperature and relative humidity on any calibration test
certificates or other calibration documentation.
Controlled Measuring Equipment must be stored and handled in a manner that does not invalidate
their calibration or ability to function without error. When items need to be stored or conditioned
under specified environmental conditions, these conditions shall be maintained, monitored and
recorded.
The laboratory shall have a procedure for handling, transport, storage, use and planned
maintenance of equipment to ensure the proper functioning and to prevent contamination or
deterioration.
4.5 VERIFICATION
Where Controlled Measuring Equipment cannot be calibrated against traceable standards, it must
be verified against some known-good object or method. This may be done by comparing the part
against another part or tool which has been evaluated and validated and proven as acceptable (e.g.
tape rule, and feeler gauges etc.) or in accordance with the specific manufacturer’s instructions
(where available).
Known-good objects must be protected and have an identification sticker, so their status is not
altered, either by physical damage or deterioration.
Known-good methods must be documented in procedures, with a rationale for their acceptability
being documented.
Uncontrolled equipment shall be marked as such and labelled for indication only as (not calibrated)
and shall not be used to verify any product or processes.
Controlled Measuring Equipment which considered broken beyond repair, or life expired will be
disposed of in accordance with the FLOW Waste Management Procedure, HSE-PR-018 and the
CMMS Calibration Log should be updated/amended accordingly.
N/A
Procedural compliance monitoring will be undertaken as part of routine inspections and by the
Stores Manager.
Also, measurement results should be monitored and analysed if the below situations are
encountered:
6.2 AUDIT
Procedural compliance auditing will be undertaken in accordance with the FLOW HSQE Audit
Procedure, QUA-PR-010.
Ohmmeter