ABU DHABI CIVIL DEFENSE GENERAL NOTES FOR SHOP DRAWING

1. ALL THE SHOP/EXECUTIVE DRAWINGS ARCHITECTURAL LAYOUT


SHALL BE AS PER ADCD APPROVED FIRE LIFE SAFETY INITIAL
ARCHITECTURAL DRAWINGS.
2. ANY ARCHITECTURAL CHANGES LIKE ADDITION, DELETION,
MODIFICATION DURING CONSTRUCTION OR IN FUTURE SHALL BE
SUBMITTED TO ADCD FOR BOTH ARCHITECTURAL AND
SHOP APPROVALS.
3. FIRE ALARM, FIRE FIGHTING, EMERGENCY/EXIT LIGHT SYSTEM
AND VOICE EVACUATION SYSTEM SHALL BE INSTALLED AS PER
APPROVED SHOP DRAWING.
4. ALL THE MATERIALS, SYSTEMS, ASSEMBLIES, EQUIPMENT,
PRODUCTS AND ACCESSORIES, REFERRED TO IN THIS DRAWING
WITH RESPECT TO LIFE SAFETY, FIRE SAFETY AND EMERGENCY
SERVICES AND ALL OTHER SYSTEMS SHALL BE LISTED,

A B
APPROVED AND REGISTERED BY THE CIVIL DEFENCE MATERIAL
APPROVAL DEPARTMENT.
5. ALL PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED
AS PER (UAE FIRE AND LIFE SAFETY CODE AND NFPA 10)
6. EMERGENCY LIGHT AND EXIT SIGN SHALL BE PROVIDED
7600 ACCORDING TO (UAE FIRE AND LIFE SAFETY CODE AND NFPA 101)
7. ALL PORTIONS OF THESE BUILDINGS AND COMMON AND
SERVICES AREAS SHALL BE FULLY COVER BY SMOKE
DETECTIONS AND FULLY COVERED BY VOICE ANNOUNCEMENT
SYSTEM ACCORDING TO (NFPA 72).
8. ALL PORTIONS OF THESE BUILDING SHALL BE FULLY
SYMBOL DESCRIPTION
PROTECTED BY AUTOMATIC SPRINKLERS SYSTEM ACCORDING 6.5W LED SURFACE MOUNTED EMERGENCY LIGHT
TO (NFPA 13.) SELF-CONTAINED MONITORING WITH 3HRS BATTERY BACKUP.
NON-MAINTAINED TYPE (IP65); MAKE/ MODEL: EATON/ IP65+
9. ALL STANDPIPE SYSTEM SHALL BE PROVIDED IN THESE
3.8W LED ABOVE DOOR/ WALL MOUNTED EXIT LIGHT
BUILDING ACCORDING TO (NFPA 14). SELF-CONTAINED MONITORING WITH 3HRS BATTERY BACKUP.
10. ANY AREA PROVIDED WITH FALSE CEILING IF THE VOID MAINTAINED TYPE (IP65); MAKE/ MODEL: EATON/ SAFELITE
DEPTH MORE THAN 800MM SHALL BE PROTECTED WITH BOTH
CEILING VOID SMOKE DETECTORS AND CEILING VOID UPRIGHT EMERGENCY LIGHTING CONTROL PANEL

SPRINKLERS AS PER UAE FLS CODE


DATA: 2Cx1.5Sq.mm CABLE
11. ALL SPECIAL SYSTEM LIKE CLEAN AGENT, FOAM,
WATER SPRAY, WATER MIST, WET CHEMICAL KITCHEN HOOD POWER: 2x2.5Sq.mm CABLE
SYSTEMS SHALL BE INSTALLED IN THIS BUILDING IN ACCORDANCE
TO THE RELEVANT NFPA CODE.
FHC 12. ALL FIRE DOOR AND WINDOWS SHALL BE ACCORDING NOTE: UN SWITCHED REFERENCE SUPPLY FOR EML BATTERY
CHARGING & SENSING POWER FAILURE
TO (NFPA 80).
2x2.5sq.mm. PVC WIRES. SHALL BE FROM NEAREST
13. ALL TYPES OF SMOKE CONTROL SYSTEMS (INCLUDE PRESSURE
W.13 DIFFERENCE BETWEEN ADJACENT ZONES) SHALL BE INSTALLED IN
LIGHTING DB or NEAREST LIGHT

1
THIS BUILDING IN ACCORDANCE WITH UAE FLS CODE AND OTHER
INTERNATIONAL CODES AND STANDARDS.
REFERENCE NO:

344
14. ALL INTERIORS FINISHING MATERIAL SHALL BE PROVIDED AS IFC 256282-BLD7A-DRG-ELE-0101-2
(UAE FIRE AND LIFE SAFETY CODE AND NFPA 101). AE 1156-4TCD-PROSW-ELE-SPE-0001
1 SPECIFICATION
15. FIRE PUMP AND FIRE WATER TANK SHALL BE LISTED AND 31.SECTION 26 52 00
TESTED AND INSTALLED ACCORDING TO CIVIL DEFENSE
REQUIREMENT AND INTERNATIONAL STANDARDS. AND ALL PUMP

L-08
CAPACITY THAT LESS THAN 350 GPM SHALL BE ONLY REGISTER
WITH ABUDHABI QUALITY AND CONFORMITY COUNCIL WITHOUT
ANY REGISTRATION AND APPROVAL FROM ANY REGISTER

1200
1 LABORATORY.
P6A 16. EMERGENCY POWER SYSTEM SHALL BE INSTALLED IN THIS
P6A BUILDING IN ACCORDANCE TO THE RELEVANT NFPA CODE.

W.20
17. ALL PENETRATIONS THROUGH FIRE RESISTANCE RATED
WALLS SHALL BE PROTECTED BY APPROVED FIRE STOP SYSTEM
AND MATERIALS, INSTALLED AND TESTED IN ACCORDANCE WITH
3100

ASTM E 814 OR UL 1479.


18. ALL MEANS OF AGGRESS COMPONENTS DETAILS AND
DIMENSIONS SHALL BE PROVIDED AND CONSTRUCTED ACCORDING
P6B TO (UAE FIRE AND LIFE SAFETY CODE AND NFPA 101 AND 5000).
19.CONSULTANT AND CONTRACTOR SHALL COMPLY WITH
UAE FIRE AND LIFE SAFETY CODE CHAPTER 12 IN TERMS OF
REQUIREMENTS OF BUILDING UNDER CONSTRUCTION.
TOILET 20. EMERGENCY ACTION PLAN SHALL BE IMPLEMENTING IN

1556
7A.GF.03 PANTRY +4.750 FFL THESE BUILDINGS ACCORDING TO UAE FIRE AND LIFE SAFETY CODE.

W.19
21.ALL DECORATION DESIGN AND MATERIALS AND ALL SERVICE

D17A 7A.GF.02 SYSTEMS IN THIS BUILDING SHALL NOT OBSTRUCT ALL


FIRE SAFETY SYSTEM ESPECIALLY SPRINKLER SYSTEM
GUARD ROOM 22.AIR CONDITION EQUIPMENT'S IS NOT ALLOWED INSIDE
A PROTECTED STAIRCASE. REVISION
D47 07.GF.01 23.CONSULTANT AND CONTRACTORS MUST COMPLY WITH THE
GENERAL NOTES AND APPLICABLE CODES AND STANDARDS

2 EVEN IF THE CODE REQUIREMENT WAS MISSED DURING


PLAN REVIEW.

L-08 W.10 W.13

1 GROUND FLOOR PLAN


SCALE 1 : 30

1
FZ - LLC
1

STEEL BUILDING CONTRACTING Co. L.L.C. P.O.BOX: 27444, DUBAI, UAE.

2 SCHEMATIC DIAGRAM P.O.Box: 46625


Tel: 02-4067888, Fax: 02-5512955
SCALE Abu Dhabi, U.A.E
NTS E-mail : gisco@giscoauh.ae,

SCHLUMBERGER ACE BASE EXPANSION


ABU DHABI

BUILDING 7A
CENTRAL BATTERY MONITORING
SYSTEM LAYOUT

AJ-420-0-EN-SEE-07A-GIS-0100