The pulse signal line's Check the pulse signal line's wiring Wire correctly.
connections are loose. at the controller and Servo Drive.
11
Check the controller's command Set the Servo Drive's pulse
pulse type and the Servo Drive's type to match the controller's
command pulse type. command pulse type.
Error and Maintenance
The gain is wrong. Perform manual tuning.
The CN1 input signal is Check the operation command (RUN), Wire correctly so that there is
chattering. error counter reset (ECRST), zero speed no chattering.
designation (VZERO), internally set
speed selection 1 (VSEL1) and internally
set speed selection 2 (VSEL2).
The motor is The ambient temperature is Check that the ambient temperature Lower the ambient temperature
overheating. too high. around the motor is 40C or less. around the motor to 40C or
less. (Use a fan or air
conditioner.)
Ventilation is obstructed. Check to see whether anything is Improve ventilation.
blocking ventilation.
The motor is overloaded. Try rotating the motor without a load. · Reduce the load.
(Disconnect it from the mechanical · Replace the Servomotor
The motor is vibrating.
system.) and Servo Drive with
higher capacity models.