Comment Review Sheet

Document Number 2018SNE2714601137 Revision 00

Document Title LOCAL PANEL WIRING

Status
Sr. CLIENT Comment FLOWSERVE Response

LCP Layout for Lube oil system is missing No response on


1 comment
This document in SA std. dwg already commented before. Closed
2 Re-submit this along with P&ID, instrument list I/O list, panel Done
GA and control narrative.
Agreed
3 See comments of panel GA dwg. AD-2714601 Done
Tag numbering to be updated as commented on GA dwg of Closed
pannel
4 Done

Keep separate terminal strips w.r.t ESD, DCS and MCC Disagree
5 interface Done
SLFEL Noted. But not marked on the drawing
Agreed
6 Keep voltage sepregation for termianl strips Done

Agreed
7 Be consistent either AWG or min perferable is AWG Done

Mention req of screen: Disagree


8 I.A screen O.A screen Done
SLFE: Interconnection diagram not provided
Typical give here system type DCS/ESD/MCC - Disagree
9 - Done
SLFE: Interconnection diagram not provided
Use aramco approved cable tag Nos. as commented Disagree
erlies.
10 Done
Make scope limits for client and flowserve.
SLFE: Interconnection diagram not provided
Lamptest is panel internal checking of bubls /LED no response on re-
comment by
11 status. Does it required to be taken to DCS/ESD please Done Vendor
check and clarify.
SLFE: not done
Is this ESD logic reset. Disagree
12 Done
SLFE: Answer not relevant

1/5
Status
Sr. CLIENT Comment FLOWSERVE Response
Disagree

Panel is made to resist max


55°C
13 Please see sheet 2

“SERVICE TEMPERATURE”

closed

Done
14
See attached Wiring diagram

closed

Done
See attached Wiring diagram

2/5
Status
Sr. CLIENT Comment FLOWSERVE Response
Disagree

ESD

Disagree

The lamp test must be done


from external system (DCS)

Disagree

Done
See attached Wiring diagram

Agreed

Done
See attached Wiring diagram

3/5
Status
Sr. CLIENT Comment FLOWSERVE Response
Disagree

Done
See attached Wiring diagram

Disagree

Done
See attached Wiring diagram

Disagree

It must be done from DCS

4/5
Status
Sr. CLIENT Comment FLOWSERVE Response
Disagree

Done
See attached Wiring diagram

If additional information or clarification is needed, please drop an email to DColapietro@flowserve.com