- When there are some power interruptions from the Source 1
(Normal), it will always indicate on the ATS Controller.
- In Auto Operation, always turn on the miniature circuit breaker
of the ATS Controller.
FOR MANUAL OPERATION:
• PRESS MANUAL
Reminders:
- There are two options when the ATS Controller is in Manual
Mode/Operation
#1 – Manual Operation from ATS Controller
#2 – Manual Operation of the Source 1 and Source 2 Circuit
Breakers.
#1: Manual Operation from ATS Controller
- Press Manual Button (with Hand Sign) on the ATS Controller
- When transferring to Source 1 manually, make sure that the
Source 1 is available, just press the “C/O” (Close/Open) button to
close and to open the breaker.
Reminders:
▪ If the Source 1 does not close, check the breaker of
the Source 2. If it is closed, the operator can press the
“C/O” (Close/Open) button of the Source 2 to open the
breaker of Source 2. And then try again to press the
“C/O” (Close/Open) button of the Source 1 Circuit
Breaker.
SOURCE 1 AVAILABLE
- Turn off LVSG-1, LANDCO 1 and LANDCO 2
- Then Turn on LVSG-2
Reminders:
In Source 1, the only circuit breaker that needs to be turned on is
the LVSG-2.
SOURCE 2 AVAILABLE
- Turn off LVSG-2
- Then first turn on the LVSG-1, second the LANDCO 1 and
LANDCO 2
Note:
➢ “Safety is Everyone’s Responsibility”
➢ Follow the safety operation Procedure
➢ Learn to work safely & take all rules seriously