AUTOMATIC AND MANUAL SEQUENCE OPERATION OF

MONTRELEC SM708 ATS CONTROLLER

FOR AUTOMATIC OPERATION:


• PRESS AUTO
- Make sure that the Source 1 or Source 2 is available.
- For Source 1, make sure that the Source 1 indicator light is “on”.
If it is not connected to the load, it will automatically transfer the
Source 1 Breaker to the common load.
- When there’s a power interruption, or some abnormalities in the
Source 1 like over voltage or under voltage, the ATS Controller
will automatically trigger the Genset Load and then transfer the
load to Source 2 (Genset).
- When the Source 1 goes normal, the Source 1 indicator light will
stop blinking, it will be permanently “on” when there is no
interruption or abnormalities in the power source and it will
automatically transfer the load from Emergency (Genset) to
Source 1 (Normal).
- When the power source is successfully transferred from Source 2
(Emergency) to Source 1 (Normal) the cool down of the genset
goes next.

Reminders:
- When there are some power interruptions from the Source 1
(Normal), it will always indicate on the ATS Controller.
- In Auto Operation, always turn on the miniature circuit breaker
of the ATS Controller.
FOR MANUAL OPERATION:
• PRESS MANUAL

Reminders:
- There are two options when the ATS Controller is in Manual
Mode/Operation
#1 – Manual Operation from ATS Controller
#2 – Manual Operation of the Source 1 and Source 2 Circuit
Breakers.
#1: Manual Operation from ATS Controller
- Press Manual Button (with Hand Sign) on the ATS Controller
- When transferring to Source 1 manually, make sure that the
Source 1 is available, just press the “C/O” (Close/Open) button to
close and to open the breaker.

Reminders:
▪ If the Source 1 does not close, check the breaker of
the Source 2. If it is closed, the operator can press the
“C/O” (Close/Open) button of the Source 2 to open the
breaker of Source 2. And then try again to press the
“C/O” (Close/Open) button of the Source 1 Circuit
Breaker.

- When transferring to Source 2 manually, make sure that the


Source 2 (Genset) is available, just press the “C/O” (Close/Open)
button to close and to open the breaker.
-
Reminders:
▪ If the Source 2 does not close, check the breaker of
the Source 1. If it is closed, the operator can press the
“C/O” (Close/Open) button of the Source 2 to open the
breaker of Source 1. And then try again to press the
“C/O” (Close/Open) button of the Source 2 Circuit
Breaker.

#2: Manual Operation of the Source 1 and Source 2 Circuit Breakers


- Press manual button (with hand sign) on the ATS Controller
- The operation will be the same with #1 Manual Operation but it
is direct on the circuit breakers, just follow the steps in #1
manual operation.
MANUAL OPERATIONS OF THE FOLLOWING CIRCUIT BREAKERS:
▪ LVSG-1
▪ LVSG-2
▪ LANDCO 1
▪ LANDCO 2

SOURCE 1 AVAILABLE
- Turn off LVSG-1, LANDCO 1 and LANDCO 2
- Then Turn on LVSG-2
Reminders:
In Source 1, the only circuit breaker that needs to be turned on is
the LVSG-2.

SOURCE 2 AVAILABLE
- Turn off LVSG-2
- Then first turn on the LVSG-1, second the LANDCO 1 and
LANDCO 2

Note:
➢ “Safety is Everyone’s Responsibility”
➢ Follow the safety operation Procedure
➢ Learn to work safely & take all rules seriously

Prepared by:

Mr. Reynante Dante


General Manager