Professional Documents
Culture Documents
𝜑𝑝
𝜑𝐿 < 900
𝑰𝑳 𝑰𝑳
𝑰𝑳 𝜑𝐿 = 0 𝜑𝐿 < −90 0
Transformer on-Load
With Primary and Secondary Winding Reactance
𝑉𝑥1 = 𝐼1 𝑋1
𝑉1 𝐸1
𝐼1
⎖
𝑉1 = 𝐸1 + 𝐼1(𝑅1 + 𝑗𝑋1 ) 𝐼 2
𝐼0 𝛷
𝐸2 = 𝑉2 + 𝐼2(𝑅2 + 𝑗𝑋2) 𝜑1
𝑆𝑖𝑛𝑐𝑒 𝑅1 = 0
𝑉1 = 𝐸1 + 𝐼1 𝑗𝑋1 ) 𝐼2 𝜑2
𝐸2 = 𝑉2 + 𝐼2𝑗𝑋2) 𝑉2
𝐸2
𝑆𝑖𝑛𝑐𝑒 𝑅2 = 0 𝑉𝑥2 = 𝐼2 𝑋2
With Primary and Secondary Winding Impedance
Transformer on-Load
The load can be presented as:
𝑆2 , 𝑆𝐿 , 𝑃2 , 𝑃𝐿 𝑍2 𝑍𝐿 𝑤𝑖𝑡ℎ 𝑝. 𝑓.
𝑰𝟏 𝑿𝟏
𝑬𝟏 𝑰𝟏 𝒁𝟏
𝑰𝟎 𝑰𝟏 𝑹𝟏
𝑰𝒄 𝑰𝝁 𝑬𝟏
𝑹𝒄
𝑰𝟏
𝑰𝒐
𝐼2′
𝑰𝒄 𝛷0
𝐼0 = 𝐸1 𝑌0 𝑰𝝁
𝑰𝟐
𝜑2
𝑬𝟐
𝑉1 𝒁𝑳
𝑽𝟐
𝑰𝟐 𝑹𝟐
𝑰𝟐 𝒁𝟐
𝑰𝟐 𝑿𝟐
𝑍1 = 𝑅1 + 𝑗𝑋1 – primary winding impedance
𝑍2 = 𝑅2 + 𝑗𝑋2 – secondary winding impedance
𝑉1 = 𝐼1 𝑅1 + 𝑗𝑋1 + 𝐸1 𝐸2 = 𝐼2 𝑅2 + 𝑗𝑋2 + 𝑉2 𝑉𝐿 = 𝐼2 (𝑅2 ±𝑗𝑋2)
Example #: 5-1
A single phase transformer supplies a current of 80A at 80% power factor lagging. The
transformer has 1000 turns in the primary windings and 250 turns in the secondary
windings. Assuming that the transformer draws a primary current of 30A at 0.7 power
factor lagging, determine:
a. the hysteresis angle of displacement
b. The no-load current
c. Draw a phasor diagram
Solution
A single phase transformer supplies a load of 13,440W at 0.7 power factor leading, at 240V, 50Hz.
The transformer has 1000 turns in the primary windings and 200 turns in the secondary windings.
The respective primary and secondary windings resistances are 0.2Ω and 0.5Ω. Assuming that the
transformer draws a no-load current of 2A at a hysteresis angle of displacement of 80 degrees.
determine:
a. the current drawn from the primary 𝐼1
b. the voltage on the primary 𝑉1
c. Draw a phasor diagram
Solution
Example #: 5-3
A single phase transformer supplies a current of 80A at 70% power factor lagging, at 240V,
50Hz. The transformer has 800 turns in the primary windings and 200 turns in the
secondary windings. The respective primary and secondary windings inductances are
0.021H and 0.007H. Assuming that the transformer draws a no-load current of 1.4A at a
hysteresis angle of displacement of 85 degrees and the primary and secondary resistances
negligible, determine:
a. the current drawn from the primary 𝐼1
b. the voltage on the primary 𝑉1
c. Draw a phasor diagram
Example #: 5-3
A single phase transformer supplies a load of 1000KW at 80% power factor lagging, at 400V, 50Hz.
The transformer has 800 turns in the primary windings and 200 turns in the secondary windings. The
respective primary and secondary windings impedances are 8 < 600Ω and 4Ω . Assuming that the
transformer draws a no-load current of 3A at a hysteresis angle of displacement of 88 degrees.
determine:
a. the current drawn from the primary 𝐼1
b. the voltage on the primary 𝑉1
c. Draw a phasor diagram
Example #: 5-4
Group discussion – exercise 4 minutes
Group #: 1
Draw a phasor diagram for a leading power factor load
Group #: 2
Draw a phasor diagram for a unit power factor load
Group #: 3
Draw a phasor diagram for a pure capacitive load
Group #: 4
Draw a phasor diagram for a pure inductive load
Group #: 5
Draw a phasor diagram for an inductive load neglecting
the no-load current