Professional Documents
Culture Documents
EE24564
Power Transmission and Distribution
EE24564 Power Transmission and Distribution 1
5.5 Voltage and Current Waves
➢ The rms phasor voltage:
𝑉 𝑥 = 𝐴1 𝑒 𝛼𝑥 𝑒 𝑗𝛽𝑥 + 𝐴2 𝑒 −𝛼𝑥 𝑒 −𝑗𝛽𝑥
𝑉𝑅 +𝐼𝑅 𝑍𝑐 𝛾𝑥 𝑉𝑅 −𝐼𝑅 𝑍𝑐 −𝛾𝑥
Recall 𝑉 𝑥 = 𝑒 + 𝑒 , from power system analysis
2 2
𝑣1 𝑡, 𝑥 = 2𝐴1 𝑒 𝛼𝑥 𝑒 𝑗(𝜔𝑡+𝛽𝑥)
To keep up with the wave and observe the peak, we must travel with a speed
𝑑𝑥 𝜔
=
𝑑𝑡 𝛽
𝜔 2𝜋𝑓
𝜐= =
𝛽 𝛽
➢ The wavelength 𝝀 or distance 𝒙 on the wave which results in a phase shift of 2𝜋 radian is:
2𝜋
𝛽𝜆 = 2𝜋 OR 𝜆= 𝛽
➢ When the line losses are neglected (𝒈 = 𝟎 and 𝒓 = 𝟎), the real part of propagation constant 𝛼 = 0, then:
𝛽 = 𝜔 𝐿𝐶
𝐿
𝑍𝐶 =
𝐶
➢ When the internal flux linkage of a conductor is neglected 𝐺𝑀𝑅𝐿 =𝐺𝑀𝑅𝐶 , 𝑡ℎ𝑒𝑛:
1 1
𝑣≅ and 𝜆≅𝑓
𝜇° 𝜀° 𝜇° 𝜀°
➢ Substituting for 𝜇° = 4𝜋 ∗ 10−7 and 𝜀° = 8.85 * 10−12 , the velocity of the wave is obtained to be
approximately 𝟑 ∗ 𝟏𝟎𝟖 𝑚/𝑠𝑒𝑐; i.e. the velocity of the light. At 60 Hz, the wavelength is 5000 km.
1 𝜇° 𝐺𝑀𝐷 𝐺𝑀𝐷
𝑍𝐶 ≅ 𝑙𝑛 ≅ 60𝑙𝑛
2𝜋 𝜀° 𝐺𝑀𝑅𝐶 𝐺𝑀𝑅𝐶
➢ For a lossless line 𝛾 = 𝑗𝛽 and cosh 𝛾𝑥 = cosh 𝑗𝛽𝑥 = cos 𝛽𝑥 and sinh 𝛾𝑥 = cosh 𝑗𝛽𝑥 = 𝑗 sin 𝛽𝑥 , the
equations for the rms voltage and current along the line become:
𝑉 𝑥 = cos 𝛽𝑥 𝑉𝑅 + 𝑗𝑍𝐶 sin 𝛽𝑥 𝐼𝑅
1
𝐼 𝑥 =𝑗 sin 𝛽𝑥 𝑉𝑅 + cos 𝛽𝑥 𝐼𝑅
𝑍𝐶
1
𝐼𝑆 = 𝑗 sin 𝛽𝑙 𝑉𝑅 + cos 𝛽𝑙 𝐼𝑅
𝑍𝐶
➢ For the example, for the open-circuited line 𝐼𝑅 = 0, and the No-load receiving end voltage is:
𝑉𝑆
𝑉𝑅(𝑛𝑙) =
cos 𝛽𝑙
➢ For a solid short circuit at the receiving end, 𝑉𝑅 = 0 and 𝑉𝑆 , 𝐼𝑆 become:
𝑉𝑆 = 𝑗𝑍𝐶 sin 𝛽𝑙 𝐼𝑅
𝐼𝑆 = cos 𝛽𝑙 𝐼𝑅
➢ When the line is loaded by being terminated with an impedance equal to its characteristic impedance, the
receiving end current is:
𝑉𝑅
𝐼𝑅 =
𝑍𝐶
➢ For a lossless line 𝑍𝐶 is a purely resistive. The load corresponding to the surge impedance at rated voltage is
known as the surge impedance loading (SIL), given by:
2
∗ 3 𝑉𝑅
𝑆𝐼𝐿 = 3𝑉𝑅 𝐼𝑅 =
𝑍𝐶
➢ Since 𝑉𝑅 = 𝑉𝐿𝑟𝑎𝑡𝑒𝑑 / 3 , SIL in MW becomes:
(𝑘𝑉𝐿𝑟𝑎𝑡𝑒𝑑 )2
𝑆𝐼𝐿 = 𝑀𝑊
𝑍𝐶
➢These two Equations show that in lossless line under surge impedance loading the
voltage and current at any point along the line are constant in magnitude and are
equal to their sending end values.
➢Since 𝑍𝐶 has NO reactive component, there is NO reactive power in the line, 𝑄𝑆 =
𝑄𝑅 = 0.
2 𝑉𝑅 𝐿
supplied by the shunt capacitance or 𝜔𝐿 𝐼𝑅 = 𝜔𝐶 𝑉𝑅 2 . From this relation, we find that 𝑍𝐶 = = .
𝐼𝑅 𝐶
➢ SIL for typical transmission lines varies from approximately 150 MW for 230-kV lines to about 2000 MW for
765-kV lines.
➢ SIL is useful measure of transmission line capacity as it indicates a loading where the line’s reactive
requirements are small.
➢ For loads significantly above SIL, shunt capacitors may be needed to minimize voltage drop along the line,
while for light loads significantly below SIL, shunt inductors may be needed.
➢ Generally, the transmission line full-load is much higher than SIL.
𝐿 0.97 ∗ 10−3
𝑍𝐶 = = = 290.43 Ω
𝐶 0.0115 ∗ 10−9
1 1
𝑣= =𝑣= = 2.994 ∗ 105 𝐾𝑚/𝑠
𝐿𝐶 0.97 ∗ 0.0115 ∗ 10−9
𝑣 1
𝜆= = 2.994 ∗ 105 = 4990 𝐾𝑚
𝑓 60
500∠0°
𝑉𝑅 = = 288.675∠0° 𝐾𝑉
3
▪ The receiving end apparent power is:
800
𝑆𝑅(3−𝑝ℎ) = ∠𝑐𝑜𝑠 −1 0.8 = 1000∠36.87° = 800 + 𝑗600 𝑀𝑉𝐴
0.8
▪ The receiving end current per phase is given by:
𝑆𝑅(3−𝑝ℎ) ∗ 1000∠−36.87° ∗103
𝐼𝑅 = = = 1154.7∠ −36.87° A
3𝑉𝑅 ∗ 3∗288.675∠0°
𝑉𝑆 = cos 𝛽𝑙 𝑉𝑅 + 𝑗𝑍𝐶 sin 𝛽𝑙 𝐼𝑅 = 0.9295 288.675∠0° + 𝑗 290.43 0.3688 1154.7∠ −36.87° 10−3 = 356.53∠16.1° 𝐾𝑉
𝑉𝑆(𝐿−𝐿) = 3 𝑉𝑆 = 617.53 𝐾𝑉
1 1
𝐼𝑆 = 𝑗 sin 𝛽𝑙 𝑉𝑅 + cos 𝛽𝑙 𝐼𝑅 = 𝑗 0.6388 288.675∠0° 103 + 0.9295 1154.7∠ −36.87° = 902.3∠ −17.9° 𝐴
𝑍𝐶 290.43
▪ The sending end power is:
𝑆𝑆(3−𝑝ℎ) = 3𝑉𝑆 𝐼𝑆 ∗ = 3 ∗ 356.53∠16.1° ∗ 902.3∠ −17.9° ∗ 10−3 = 800 𝑀𝑊 + 𝑗539.672 𝑀𝑉𝐴𝑟 = 965.1∠34° 𝑀𝑉𝐴
356.53
− 288.675
Percent VR = 0.9295 ∗ 100% = 32.87%
288.675
➢ Expressing the ABCD constants in polar form as 𝑨 = 𝐴 ∠𝜃𝐴 , 𝑩 = 𝐵 ∠𝜃𝐵 , the sending end voltage as 𝑽𝑺 =
𝑉𝑆 ∠𝛿, the receiving end voltage as reference 𝑽𝑹 = 𝑉𝑅 ∠0, 𝑰𝑹 can be written as:
𝑉𝑆 ∠𝛿 − 𝐴 ∠𝜃𝐴 𝑉𝑅 ∠0 𝑉𝑆 𝐴 𝑉𝑅
𝐼𝑅 = = ∠ 𝛿 − 𝜃𝐵 − ∠ 𝜃𝐴 − 𝜃𝐵
𝐵 ∠𝜃𝐵 𝐵 𝐵
➢ The receiving end complex power is:
➢ Substituting for 𝐼𝑅 :
2
𝑉𝑆 𝑉𝑅 𝐴 𝑉𝑅
𝑆𝑅(3−𝑝ℎ) =3 ∠ 𝜃𝐵 − 𝛿 − 3 ∠ 𝜃𝐵 − 𝜃𝐴
𝐵 𝐵
𝐴 ∠𝜃𝐴 𝑉𝑆 ∠𝛿 − 𝑉𝑅 ∠0
𝐼𝑆 =
𝐵 ∠𝜃𝐵
➢ Substituting for 𝐼𝑠 :
2
𝐴 𝑉𝑆 𝐿−𝐿 𝑉𝑆(𝐿−𝐿) 𝑉𝑅(𝐿−𝐿)
𝑃𝑆(3−𝑝ℎ) = 𝑐𝑜𝑠 𝜃𝐵 − 𝜃𝐴 − 𝑐𝑜𝑠 𝜃𝐵 + 𝛿
𝐵 𝐵
2
𝐴 𝑉𝑆 𝐿−𝐿 𝑉𝑆(𝐿−𝐿) 𝑉𝑅(𝐿−𝐿)
𝑄𝑆(3−𝑝ℎ) = 𝑠𝑖𝑛 𝜃𝐵 − 𝜃𝐴 − 𝑠𝑖𝑛 𝜃𝐵 + 𝛿
𝐵 𝐵
➢ The real and reactive transmission line losses are:
ሖ 𝜃𝐴 = 0, 𝜃𝐵 = 90° , and 𝐴 = cos 𝛽𝑙, and the real power transferred over the line is
➢ For a lossless line 𝐵 = 𝑗𝑋,
given by:
𝑉𝑆(𝐿−𝐿) 𝑉𝑅(𝐿−𝐿)
𝑃(3−𝑝ℎ) = sin 𝛿
𝑋ሖ
➢ And the receiving end reactive power is:
2
𝑉𝑆(𝐿−𝐿) 𝑉𝑅(𝐿−𝐿) 𝑉𝑅 𝐿−𝐿
𝑄(3−𝑝ℎ) = cos 𝛿 − cos 𝛽𝑙
𝑋ሖ 𝑋ሖ
➢The expression for real power transfer over the line for a lossless line is given by:
𝑉𝑆(𝐿−𝐿) 𝑉𝑅(𝐿−𝐿)
𝑃(3−𝑝ℎ) = sin 𝛿
𝑋ሖ
➢The theoretical maximum power transfer is when 𝛿 = 90°
➢The practical operating load angle for the line alone is limited to NO more than
30° 𝑡𝑜 45° . This because of the generator and transformer reactances which, when
added to the line, will result in a larger 𝛿 for a given load.
➢ For a lossless line 𝑋ሖ = 𝑍𝐶 sin 𝛽𝑙, and 𝑃(3−𝑝ℎ) may be written as:
➢ The first two terms are the p.u. voltages denoted by 𝑉𝑆𝑝𝑢 and 𝑉𝑅𝑝𝑢 and the third term is recognized as SIL.
Then 𝑃(3−𝑝ℎ) may written as:
(1.0)(0.9)(𝑆𝐼𝐿)
700 = °
sin 36.87°
sin 22.68
▪ Thus:
𝑆𝐼𝐿 = 499.83 𝑀𝑊
▪ From: