DWG Number 112T1200 Rev A Released 10/3/2014 Page 1 of 12

SIZE DWG NO SH REV

A 112T1200 1 A
DATE
REV SHEET DESCRIPTION APPROVED
(YYYY-MM-DD) Fecha de la firma: 2014/10/07 13:47:50 GMT +02:00

- Initial Release by ECO0142785 2014-04-04 See PLM


A 2, 3 Revise Electrical Design Data. ECO0163534 2014-09-29 See PLM

THIS DOCUMENT SHALL BE REVISED THIS DRAWING TO BE REVISED IN MICROSOFT


IN ITS ENTIRETY. ALL SHEETS OF WORD ONLY, THE SOURCE FILE IS STORED IN A
THIS DOCUMENT ARE THE SAME SECURE DATABASE.
REVISION LEVEL AS INDICATED.

REVISION DESCRIPTION IS FULLY


STATED ON THE FIRST SHEET OF
THIS DOCUMENT.

ITEM DESCRIPTION DWG. NO.


LIST OF COMPLEMENTARY DOCUMENTS

© COPYRIGHT 2014 General Electric Company (USA)


All rights reserved. The information herein is Proprietary and Technically Exclusive content that is solely owned by General Electric Company and/or its
affiliates. Thus, it is being provided with the explicit expectation of restricted and privileged use. All persons or legal entities receiving this information shall
be deemed by the act of its receipt have contractually agreed to make no duplications, reproductions of any nature by any means, modifications, disclosures,
or use any portion of this material; except as is expressly authorized in writing by the General Electric Company, and/or its legitimate affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


SIGNATURES & DATES
GE POWER & WATER
DRAWN Edith Jimenez Generator
DRAWN DATE (YYYY-MM-DD) 2014-04-04
CHECK See PLM
CHECK DATE (YYYY-MM-DD) 2014-04-04 GENERATOR REQUISITION SUMMARY
36 CC Baja California III
ENGRG See PLM
ENGRG DATE (YYYY-MM-DD) 2014-04-04
FIRST MADE FOR: GG10425 MLI/COST CODE: C907
ADDITIONAL APPROVALS
SIZE CAGE CODE DWG NO
APPLIED PRACTICES SEE PLM FOR APPROVAL INFORMATION
A 112T1200
SIM TO: NONE DOL CODE: US-NY, SCHENECTADY SHEET 1 of 12

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 112T1200 Rev A Released 10/3/2014 Page 2 of 12

SIZE DWG NO SH REV

A 112T1200 2 A

C907 – Requisition Summary Sheets

Customer Name: Iberdrola Energía Baja California S.A. de C.V.

Project Name: 36 CC Baja California III

Site Location: Baja California

Generator Serial Numbers: GG10425

Generator Model Type: 7FH2 Static Excitation

Generator Electrical Design Number: F317T185A

Gas Turbine DM No. 299391

Customer Drawing Appliqué

This is the only generator drawing that is requested by GE to be fully reviewed by the
customer and then returned to GE with inputted (or corrected) information.

© COPYRIGHT 2014 General Electric Company (USA)


All rights reserved. The information herein is Proprietary and Technically Exclusive content that is solely owned by General Electric Company and/or its
affiliates. Thus, it is being provided with the explicit expectation of restricted and privileged use. All persons or legal entities receiving this information shall
be deemed by the act of its receipt have contractually agreed to make no duplications, reproductions of any nature by any means, modifications, disclosures,
or use any portion of this material; except as is expressly authorized in writing by the General Electric Company, and/or its legitimate affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


SIZE CAGE CODE DWG NO

GE POWER & WATER


Generator
A 112T1200
DRAWN Edith Jimenez
DRAWN DATE (YYYY-MM-DD) 2014-04-04 DOL CODE: US-NY, SCHENECTADY SHEET 2 of 12

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 112T1200 Rev A Released 10/3/2014 Page 3 of 12

SIZE DWG NO SH REV

A 112T1200 3 A

Generator Performance

These design conditions are for Base Load:

Rating: 210000 kVA

Frequency: 60 Hz

Lagging Power Factor: 0.9

Leading Power Factor: Capability to 0.95

Armature Voltage: 18000 VAC Line to Line RMS

Active Power: 189000 kW

SCR: 0.5

Excitation: 495 kW 307 V 1609 D.C.Amps

Hydrogen Casing Pressure: 206.8 kPa (30 PSIG)

Maximum Cold Gas temperature at rating point: 40 deg C (104 deg F)

© COPYRIGHT 2014 General Electric Company (USA)


All rights reserved. The information herein is Proprietary and Technically Exclusive content that is solely owned by General Electric Company and/or its
affiliates. Thus, it is being provided with the explicit expectation of restricted and privileged use. All persons or legal entities receiving this information shall
be deemed by the act of its receipt have contractually agreed to make no duplications, reproductions of any nature by any means, modifications, disclosures,
or use any portion of this material; except as is expressly authorized in writing by the General Electric Company, and/or its legitimate affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


SIZE CAGE CODE DWG NO

GE POWER & WATER


Generator
A 112T1200
DRAWN Edith Jimenez
DRAWN DATE (YYYY-MM-DD) 2014-04-04 DOL CODE: US-NY, SCHENECTADY SHEET 3 of 12

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 112T1200 Rev A Released 10/3/2014 Page 4 of 12

SIZE DWG NO SH REV

A 112T1200 4 A

Line Terminal Configuration


Line Terminal Side
The Direction of the Leads Relative to Collector End is Right Side (Horizontal)

Line Terminal Phase Sequence


Definition of the Phase Sequence:
Voltage Reaches a Positive Maximum in the Order 1,2,3. Looking at the Leads from The
side that they exit the Generator. The Phase Sequence is:

1, 2, 3 is Right-Center-Left

© COPYRIGHT 2014 General Electric Company (USA)


All rights reserved. The information herein is Proprietary and Technically Exclusive content that is solely owned by General Electric Company and/or its
affiliates. Thus, it is being provided with the explicit expectation of restricted and privileged use. All persons or legal entities receiving this information shall
be deemed by the act of its receipt have contractually agreed to make no duplications, reproductions of any nature by any means, modifications, disclosures,
or use any portion of this material; except as is expressly authorized in writing by the General Electric Company, and/or its legitimate affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


SIZE CAGE CODE DWG NO

GE POWER & WATER


Generator
A 112T1200
DRAWN Edith Jimenez
DRAWN DATE (YYYY-MM-DD) 2014-04-04 DOL CODE: US-NY, SCHENECTADY SHEET 4 of 12

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 112T1200 Rev A Released 10/3/2014 Page 5 of 12

SIZE DWG NO SH REV

A 112T1200 5 A

Generator Bearing Lube Oil Piping Connection

Lube oil feed connection on the Right viewed from the collector end
Lube oil drain connection on the Right viewed from the collector end

Generator Rotation Direction

As viewed from the collector end, the generator rotates Counter-Clock-Wise

© COPYRIGHT 2014 General Electric Company (USA)


All rights reserved. The information herein is Proprietary and Technically Exclusive content that is solely owned by General Electric Company and/or its
affiliates. Thus, it is being provided with the explicit expectation of restricted and privileged use. All persons or legal entities receiving this information shall
be deemed by the act of its receipt have contractually agreed to make no duplications, reproductions of any nature by any means, modifications, disclosures,
or use any portion of this material; except as is expressly authorized in writing by the General Electric Company, and/or its legitimate affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


SIZE CAGE CODE DWG NO

GE POWER & WATER


Generator
A 112T1200
DRAWN Edith Jimenez
DRAWN DATE (YYYY-MM-DD) 2014-04-04 DOL CODE: US-NY, SCHENECTADY SHEET 5 of 12

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 112T1200 Rev A Released 10/3/2014 Page 6 of 12

SIZE DWG NO SH REV

A 112T1200 6 A

Site Conditions

Site Elevation: 15 m / 49 f
Installation: Outdoor
Outdoor ambient temp: Min 2.2 deg C (36 deg F)
Max 36.1 deg C (97 deg F)

Cooling Water System

Closed Loop Cooling Water System Supplied by Customer


Coolant is 100% Fresh Water
Fouling Factor is Less than or equal to 0.001 FF

Ambient Temperature Cooling Water Temperature


2.2 deg C 20.6 deg C
Minimum Day
36 deg F 69 deg F
36.1 deg C 33 deg C
Maximum Day
97 deg F 91 deg F

(Customer to Verify above)

Site Voltages

AC - Three phase 480 VAC


AC - Single phase 120 VAC
DC - 125 VDC
UPS - 120 VAC

© COPYRIGHT 2014 General Electric Company (USA)


All rights reserved. The information herein is Proprietary and Technically Exclusive content that is solely owned by General Electric Company and/or its
affiliates. Thus, it is being provided with the explicit expectation of restricted and privileged use. All persons or legal entities receiving this information shall
be deemed by the act of its receipt have contractually agreed to make no duplications, reproductions of any nature by any means, modifications, disclosures,
or use any portion of this material; except as is expressly authorized in writing by the General Electric Company, and/or its legitimate affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


SIZE CAGE CODE DWG NO

GE POWER & WATER


Generator
A 112T1200
DRAWN Edith Jimenez
DRAWN DATE (YYYY-MM-DD) 2014-04-04 DOL CODE: US-NY, SCHENECTADY SHEET 6 of 12

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 112T1200 Rev A Released 10/3/2014 Page 7 of 12

SIZE DWG NO SH REV

A 112T1200 7 A

Cooler Details

Generator Cooler Construction Materials


90-10 Copper Nickel Tubes
Carbon Steel Cooler Tube Sheet
Carbon w/Epoxy Waterbox & Coupling Flanges

5 Horizontally Mounted Cooler Connections


Cooler Ports on Left viewed from the collector end

Cooler Pressure Capability is 861.8 kPa (125 PSI)


Companion Flanges for Cooler Connection
ASME Stamp Required

Space Heaters

Three Phase Stator Heater


Single Phase Collector Heater

© COPYRIGHT 2014 General Electric Company (USA)


All rights reserved. The information herein is Proprietary and Technically Exclusive content that is solely owned by General Electric Company and/or its
affiliates. Thus, it is being provided with the explicit expectation of restricted and privileged use. All persons or legal entities receiving this information shall
be deemed by the act of its receipt have contractually agreed to make no duplications, reproductions of any nature by any means, modifications, disclosures,
or use any portion of this material; except as is expressly authorized in writing by the General Electric Company, and/or its legitimate affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


SIZE CAGE CODE DWG NO

GE POWER & WATER


Generator
A 112T1200
DRAWN Edith Jimenez
DRAWN DATE (YYYY-MM-DD) 2014-04-04 DOL CODE: US-NY, SCHENECTADY SHEET 7 of 12

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 112T1200 Rev A Released 10/3/2014 Page 8 of 12

SIZE DWG NO SH REV

A 112T1200 8 A

Instrumentation

Temperature Sensors
Bearing Thermocouples are Type K (Chromel Alumel - Dual Element), unless noted
otherwise
Lube Oil Thermocouples are Type K (Chromel Alumel) (Dual Element) unless noted
otherwise
RTDs are 100 Ohm @ 0 C Platinum, single element, 3-wire, unless noted otherwise. (GE
RTDs are DIN standard with K=0.00385 ohms/ohm/ deg C)

Stator Slots Temperature Instrumentation (Dual Element):


12 Stator Slot RTDs
3 Extra Stator Slot RTDs

Gas Temperature Instrumentation:


4 Cold Gas RTDs (cooler outlet gas) (Dual Element)
2 Hot Gas RTDs (cooler inlet gas) (Dual Element)
2 Common Cold Gas RTD (Dual Element)
1 Collector Inlet Air RTDs (Dual Element)
1 Collector Outlet Air RTDs (Dual Element)

Bearing and Lube Oil Instrumentation:


2 TCs for CE Bearing Metal, 2 TCs for TE Bearing Metal
1 TC in CE Drain Oil, 1 TC in TE Drain Oil

Vibration Instrumentation
2 Velocity (Seismic) Probes on TE
1 Velocity (Seismic) Probes on CE
2 Single Bently-Nevada 3300 Proximity Probes, 45/45 degree locations on TE
2 Single Bently-Nevada 3300 Proximity Probes, 45/45 degree locations on CE

Flux Probe Permanently Mounted Flux Probe

1 Permanent PDA (Partial Discharge Analyzer)

Liquid Detector
1 Liquid Level Detector Shipped Loose (Dual settings)
1 Liquid Level Detector in Generator Cab (Dual settings)
© COPYRIGHT 2014 General Electric Company (USA)
All rights reserved. The information herein is Proprietary and Technically Exclusive content that is solely owned by General Electric Company and/or its
affiliates. Thus, it is being provided with the explicit expectation of restricted and privileged use. All persons or legal entities receiving this information shall
be deemed by the act of its receipt have contractually agreed to make no duplications, reproductions of any nature by any means, modifications, disclosures,
or use any portion of this material; except as is expressly authorized in writing by the General Electric Company, and/or its legitimate affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


SIZE CAGE CODE DWG NO

GE POWER & WATER


Generator
A 112T1200
DRAWN Edith Jimenez
DRAWN DATE (YYYY-MM-DD) 2014-04-04 DOL CODE: US-NY, SCHENECTADY SHEET 8 of 12

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 112T1200 Rev A Released 10/3/2014 Page 9 of 12

SIZE DWG NO SH REV

A 112T1200 9 A

Excitation, Generator Protection, and CT Information


See One-Line diagram

Hydrogen System (For H2 Cooled Gen Only)


*Hydrogen Flow Totalizer
*Gas Purity Analyzer
*Gas Flow Meter
Two Gas Analyzers
Generator Core Monitor
Generator Humidity Sensor
Dual Tower Gas Dryer
Hydrogen Bottle Manifold
CO2 Bottle Manifold

*For more details on quantities, please verify G2FA drawing

Seal Oil Control (For H2 Cooled Gen Only)


Seal Oil Flow Meter
Pressure Differential Gauge

Generator Factory Test and Customer Witness

Notification for Customer Witness: 15 days for Official notification with 5 days confirmation

Customer Witness Point:


Generator Rotor Balance, Over Speed
Gen Rotor HI POT, Insulation Resistance Check
Gen Stator HI POT, Insulation Resistance Check
Gen Ready for Shipment
GPP Electrical test
GPP Visual Inspection
Exciter Electrical test
Exciter Visual Inspection
LCI Witness Inspection

Special Tests:
Field Thermal test at running speed

© COPYRIGHT 2014 General Electric Company (USA)


All rights reserved. The information herein is Proprietary and Technically Exclusive content that is solely owned by General Electric Company and/or its
affiliates. Thus, it is being provided with the explicit expectation of restricted and privileged use. All persons or legal entities receiving this information shall
be deemed by the act of its receipt have contractually agreed to make no duplications, reproductions of any nature by any means, modifications, disclosures,
or use any portion of this material; except as is expressly authorized in writing by the General Electric Company, and/or its legitimate affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


SIZE CAGE CODE DWG NO

GE POWER & WATER


Generator
A 112T1200
DRAWN Edith Jimenez
DRAWN DATE (YYYY-MM-DD) 2014-04-04 DOL CODE: US-NY, SCHENECTADY SHEET 9 of 12

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 112T1200 Rev A Released 10/3/2014 Page 10 of 12

SIZE DWG NO SH REV

A 112T1200 10 A

Other Information

Nameplate Information
GE standard nameplate information per IEC
GE English standard nameplate in Spanish per IEC
(Customer to advise if special info/language needed in Generator nameplate)

Paint
Epoxy Primer
Stator Tagging Paint
Rotor Tagging Paint

Maintenance Tools Provided (1 set per site)


Rotor Lifting Slings
Rotor Removal Equipment (Shoes, Pans, Pulling Devices)
Rotor Jacking Bolts
Tools and Wrenches (Special)

Transportation
Ship Coolers Installed
Ship with Rotor Assembled
Ship End Shields Assembled
Ship Collector Compartment/Enclosure Separate
Ship with High Voltage Bushings/Leads Installed
Ship with Generator Feet Installed (Integral)

Special Requirements
Acoustic guarantee (Near Field Avg) w/o barrier wall: 85 dBA
Will there be static start (LCI) applied to this generator? Yes
Are there any special requirements on generator cooler material? No
Is GE required to provide the ASME code stamp certificate? Yes
Are there Lift Oil Provisions for the Generator Bearings? Yes

© COPYRIGHT 2014 General Electric Company (USA)


All rights reserved. The information herein is Proprietary and Technically Exclusive content that is solely owned by General Electric Company and/or its
affiliates. Thus, it is being provided with the explicit expectation of restricted and privileged use. All persons or legal entities receiving this information shall
be deemed by the act of its receipt have contractually agreed to make no duplications, reproductions of any nature by any means, modifications, disclosures,
or use any portion of this material; except as is expressly authorized in writing by the General Electric Company, and/or its legitimate affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


SIZE CAGE CODE DWG NO

GE POWER & WATER


Generator
A 112T1200
DRAWN Edith Jimenez
DRAWN DATE (YYYY-MM-DD) 2014-04-04 DOL CODE: US-NY, SCHENECTADY SHEET 10 of 12

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 112T1200 Rev A Released 10/3/2014 Page 11 of 12

SIZE DWG NO SH REV

A 112T1200 11 A

Customer Drawings
The cycle for customer drawings begin after the information for the C907 (Req Summary Sheets) is made
available to GE (i.e., phase sequence is usually the last information available).

GE Item Description Commitment Cycle


0070 Elementary Diagram 11
0444 One-Line Diagram 17
0445 Interconnection Diagram 48
0463 Cable Summary 16
A1D0 Outline Electrical 10
C900 Exciter Model 10
C902 Generator Data and Curves 6
C907 Generator Requisition Summary Sheets 5
F015 Outline Foundation Interface, Off-Base Electrical Equipment 20
G1DO Outline Liquid Level Detector Assembly 14
G1EO Outline H2 Bottle Manifold 14
G1FO Outline CO2 Bottle Manifold 14
G2FA P&ID Generator Auxiliary Systems 14
G2MA Outline H2 Gas Dryer 14
G3EA Outline H2 Flow Totalizer 14
4023 Diagram, schematic LCI 17
40SS Static Start Duty Cycle 16
A1CJ Stator Handling Drawing 8
C184 Protection study 40

© COPYRIGHT 2014 General Electric Company (USA)


All rights reserved. The information herein is Proprietary and Technically Exclusive content that is solely owned by General Electric Company and/or its
affiliates. Thus, it is being provided with the explicit expectation of restricted and privileged use. All persons or legal entities receiving this information shall
be deemed by the act of its receipt have contractually agreed to make no duplications, reproductions of any nature by any means, modifications, disclosures,
or use any portion of this material; except as is expressly authorized in writing by the General Electric Company, and/or its legitimate affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


SIZE CAGE CODE DWG NO

GE POWER & WATER


Generator
A 112T1200
DRAWN Edith Jimenez
DRAWN DATE (YYYY-MM-DD) 2014-04-04 DOL CODE: US-NY, SCHENECTADY SHEET 11 of 12

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 112T1200 Rev A Released 10/3/2014 Page 12 of 12

SIZE DWG NO SH REV

A 112T1200 12 A

STATION DESIGNERS HANDBOOK

This is a compilation of “typical” data, drawings, and instructions that allow the plant
designers to understand the generator configuration and design. It also includes standard
design functional specification recommendations for piping up or applying the GE scope
equipment.

Three CD copies are normally provided at the Customer Kick-Off meeting.

SDH provided for this project: 7FH2 Leads Up Rev L

© COPYRIGHT 2014 General Electric Company (USA)


All rights reserved. The information herein is Proprietary and Technically Exclusive content that is solely owned by General Electric Company and/or its
affiliates. Thus, it is being provided with the explicit expectation of restricted and privileged use. All persons or legal entities receiving this information shall
be deemed by the act of its receipt have contractually agreed to make no duplications, reproductions of any nature by any means, modifications, disclosures,
or use any portion of this material; except as is expressly authorized in writing by the General Electric Company, and/or its legitimate affiliates.