Design Specifications
Anchor
Anchor system fischer Bolt anchor FAZ II
Anchor Bolt anchor FAZ II 16/25,
zinc plated steel
Calculated anchorage 85 mm
depth
Design Data Specification by manufacturer

Geometry / Loads / Scale units


mm, kN, kNm

Value of design actions (including

partial safety factor for the load) Static

Not drawn to scale

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 1
C-FIX 1.109.0.0
Database version
2022.6.9.13.4
Date
07/07/2022

Input data

Design method TR055/Design method ENSO Mechanical


Base material C25/30, EN 206
Concrete condition Non-cracked, dry hole
Reinforcement Normal or no reinforcement. No edge reinforcement
Drilling method Hammer drilling
Installation type Push-through installation
Annular gap Annular gap filled
Type of loading Permanent-Transient/Static
Base plate location Base plate flush installed on base material
Base plate geometry 300 mm x 250 mm x 12 mm
Profile type Customized profile

Design actions *⁾
# NSd VSd,x VSd,y MSd,x MSd,y MT,Sd Type of loading
kN kN kN kNm kNm kNm
1 -5.80 0.00 -20.50 1.55 0.00 0.00 Permanent-Transient/Static

*⁾ The required partial safety factors for actions are included

Resulting anchor forces


Tensile action Shear Action Shear Action x Shear Action y
Anchor no. kN kN kN kN
1 11.72 11.48 0.00 -11.48
2 11.92 9.02 0.00 -9.02

max. concrete compressive strain : 0.18 ‰


max. concrete compressive stress : 5.7 N/mm²
Resulting tensile actions : 23.64 kN , X/Y position ( 1 / 95 )
Resulting compression actions : 29.44 kN , X/Y position ( -2 / -1 )

Resistance to tension loads

Action Capacity Utilisation βN


Proof kN kN %
Steel failure * 11.92 44.67 26.7
Pullout failure * 11.92 28.31 42.1
Concrete cone failure 23.64 49.85 47.4
Splitting failure 23.64 51.28 46.1

* Most unfavourable anchor

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 2
C-FIX 1.109.0.0
Database version
2022.6.9.13.4
Date
07/07/2022

Steel failure

( NRd,s )

NRk,s γMs NRd,s NSd βN,s


kN kN kN %
67.00 1.50 44.67 11.92 26.7

βN,s
Anchor no. % Group N° Decisive Beta
1 26.2 1 βN,s;1
2 26.7 2 βN,s;2

Pullout failure

( NRd,p )

NRk,p Ψc γMp NRd,p NSd βN,p


kN kN kN %
42.46 1.100 1.50 28.31 11.92 42.1

The given Psi,c-factor may has been determined by interpolation.

βN,p
Anchor no. % Group N° Decisive Beta
1 41.4 1 βN,p;1
2 42.1 2 βN,p;2

Concrete cone failure

( NRd,c )

Eq. (5.2)

Eq. (5.2a)

Eq. (5.2c)

Eq. (5.2d)

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 3
C-FIX 1.109.0.0
Database version
2022.6.9.13.4
Date
07/07/2022

Eq. (5.2e)

NRk,c γMc NRd,c NSd βN,c


kN kN kN %
74.77 1.50 49.85 23.64 47.4

βN,c
Anchor no. % Group N° Decisive Beta
1, 2 47.4 1 βN,c;1

Splitting failure due to loading

( NRd,sp )

Eq. (5.3)

Eq. (5.2a)

Eq. (5.2c)

Eq. (5.2d)

Eq. (5.2e)

Eq. fib (10.1-5a)

NRk,sp γMsp NRd,sp NSd βN,sp


kN kN kN %
76.92 1.50 51.28 23.64 46.1

βN,sp
Anchor no. % Group N° Decisive Beta
1, 2 46.1 1 βN,sp;1

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 4
C-FIX 1.109.0.0
Database version
2022.6.9.13.4
Date
07/07/2022

Resistance to shear loads

Proof Action Capacity Utilisation βV


kN kN %
Steel failure without lever arm * 11.48 44.00 26.1
Concrete pry-out failure 20.50 134.92 15.2
Concrete edge failure 20.50 27.50 74.6

* Most unfavourable anchor

Steel failure without lever arm

( VRd,s )

VRk,s γMs VRd,s VSd βVs


kN kN kN %
55.00 1.25 44.00 11.48 26.1

βVs
Anchor no. % Group N° Decisive Beta
1 26.1 1 βVs;1
2 20.5 2 βVs;2

Concrete pry-out failure

( VRd,cp )

Eq. (5.6)

Eq. (5.2)

Eq. (5.2a)

Eq. (5.2c)

Eq. (5.2d)

Eq. (5.2e)

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 5
C-FIX 1.109.0.0
Database version
2022.6.9.13.4
Date
07/07/2022

VRk,cp γMc VRd,cp VSd βV,cp


kN kN kN %
202.38 1.50 134.92 20.50 15.2

βV,cp
Anchor no. % Group N° Decisive Beta
1, 2 15.2 1 βV,cp;1

Concrete edge failure

( VRd,c )

Eq. (5.7)

Eq. (5.7a)

Eq. (5.7b/c)

Eq. (5.7e)

Eq. (5.7f)

Eq. (10.2-5f)

Eq. (5.7h)

VRk,c γMc VRd,c VSd βV,c


kN kN kN %
41.25 1.50 27.50 20.50 74.6

βV,c
Anchor no. % Group N° Decisive Beta
1, 2 74.6 1 βV,c;1

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 6
C-FIX 1.109.0.0
Database version
2022.6.9.13.4
Date
07/07/2022

Utilization of tension and shear loads

Tension loads Utilisation βN Shear Loads Utilisation βV


% %
Steel failure * 26.7 Steel failure without lever arm * 26.1
Pullout failure * 42.1 Concrete pry-out failure 15.2
Concrete cone failure 47.4 Concrete edge failure 74.6
Splitting failure 46.1
* Most unfavourable anchor

Resistance to combined tensile and shear loads


Utilisation steel
Eq. (5.8a)

Eq. (5.8b)

Eq. (5.9)

Utilisation concrete Proof successful


Eq. (5.8a)

Eq. (5.8b)

Eq. (5.9)

Information concerning the anchor plate


Base plate details
Plate thickness specified by user without proof t = 12 mm

Profile type Customized profile

Technical remarks
All data and information in the software is based on fischer products and common engineering knowledge. Please
check all the proof results against local valid standards and approvals.
As fischer is not the design office, the attached is no guarantee for incorrect input or assumptions. Any
recommendations have to be approved by the building-authority or project engineer. Results are valid only for
anchor system calculated in the attached. If any part of the system is changed, it will invalidate this report and new
calculations would be required.
The transmission of the anchor loads to the supports of the concrete member shall be shown for the ultimate limit state and
the serviceability limit state; for this purpose, the normal verifications shall be carried out under due consideration of the
actions introduced by the anchors. For these verifications the additional provisions given in the current design method shall
be taken into account.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate (if present) must
be sufficiently stiff. The C-Fix anchor plate design is based on a proof of stresses and does not allow a statement about the
stiffness of the plate. The proof of the necessary stiffness is not carried out by C-Fix.

During the design process, the following hints and warnings were issued:

• Filling Washer Required

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 7
C-FIX 1.109.0.0
Database version
2022.6.9.13.4
Date
07/07/2022

Installation data
Anchor
Anchor system fischer Bolt anchor FAZ II
Anchor Bolt anchor FAZ II 16/25, Art.-No. 95836
zinc plated steel

Accessories FFD 38x19x7 Art.-No. 538460


Blow-out pump ABG big Art.-No. 89300
SDS Plus-V II 16/160/210 Art.-No. 531827
or alternatively
FHD 16/250/380 Art.-No. 546599
Hammer drilling with or without
suction
The calculation consists a special
washer. With the filling washer it is
assured that the gap between plate
and anchor is eliminated and the
shear load is transfered to every
anchor in equal parts.

Installation details
Thread diameter M 16
Drill hole diameter d0 = 16 mm
Drill hole depth h2 = 133 mm
Calculated anchorage hef = 85 mm
depth
Installation depth hnom = 103 mm
Drilling method Hammer drilling
Drill hole cleaning Only blow out by hand
No borehole cleaning required in
case of using a hollow drill bit, e.g.
fischer FHD.
Installation type Push-through installation
Annular gap Annular gap filled
Installation torque Tinst = 110.0 Nm
Socket size 24 mm
Base plate thickness t = 12 mm
Total fixing thickness tfix = 19 mm
Tfix,max tfix, max = 25 mm

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 8
C-FIX 1.109.0.0
Database version
2022.6.9.13.4
Date
07/07/2022

Base plate details


Base plate material Not available
Base plate thickness t = 12 mm
Clearance hole in base df=18 mm
plate

Attachment
Profile type Customized profile

Profile dimensions mm
Height 3

Anchor coordinates

x y
Anchor no. mm mm
1 -125 95
2 125 95

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.