Site Test Report

Contract No. – N-6166.1 CONSORTIIUM


New 132/11KV Substations at E12,Zayed Sports
City, ADNEC Capital Centre, 132/22kv SIEMENS-
Substations at New Airport and Capital District ELECTROMECHANICAL
and All Related 132kv Cable works

Date:10.06.2012 Bay/Feeder : =E02-132/11 KV TRANSFORMER FEEDER (-T201) Page 1 of 3

High Voltage Switchgear Type 8DN8 72,5 kV and above


Current Transformers
Hochspannungsschaltanlagen 8D . . ab 72,5 kV
Stromwandler
Customer: Contract No.:
Kunde: TRANSCO Vertragsnr.: N-6166.1
Consultant: Bay/Feeder:
Berater: ENERGO CONSULT Abzweig: =E02
Substation: Serial No.:
Anlage: ADNEC Fabrik-Nr.: 31259836
Switchgear type: Rated voltage:
Schaltanlagentyp: 8DN8 Bemessungsspannung: 145 kV

Current transformer: item designation: Type: P2 in direction busbar


Stromwandler: Betriebsmittelkennz.: T2 Typ: AMT145/3 in Richtung SaS*/Feld*

Serial-No.:
Fabrik-Nr.: L1: 11/101 215 L2: 11/101 215 L3: 11/101 215

Core-No.
Kern-Nr. Core 1 Core 2 Core 3 Core 4
Core data Kern 1 Kern 2 Kern 3 Kern 4
Kerndaten
Nominal power VA VA 30-20 VA
Nennleistung
Nominal Ratio 600-400/1A 600-400/1A 600-400/1A
Nennübersetzung
Class PX PX 0.5 FS5
Klasse
Magnetizing – U0 ≥400-300 V ≥400-300 V V
Magnetizing – I0 ≤50-80 mA ≤50-80 mA mA
Resistance Rct ≤2.8-2.1 Ω ≤2.8-2.1 Ω ≤1.3-0.8 Ω
Earthed at 1S3 2S3 3S3
Geerdet an
Used for BUSBAR PRTN OC+EF BCU
Verwendet für
Polarity check Error: Error: Error: Error: Error: Error: Error: Error: Error: Error: Error: Error:
Polaritätsprüfung Refer Refer Refer Refer Refer Refer Refer Refer Refer Refer Refer Refer
Secondary circuits
checked up to: +S3 +S3 +S3
Sekundärverdrahtung
geprüft bis:

TESTED BY WITNESSED BY WITNESSED / APPROVED BY

Signature: Signature: Signature:

Name: TIMM Name: SENTHIL KUMAR Name:

Date Date Date


CSE ENERGO CONSULT L.L.C TRANSCO
Site Test Report
Contract No. – N-6166.1 CONSORTIIUM
New 132/11KV Substations at E12,Zayed Sports
City, ADNEC Capital Centre, 132/22kv SIEMENS-
Substations at New Airport and Capital District ELECTROMECHANICAL
and All Related 132kv Cable works

Date:10.06.2012 Bay/Feeder : =E02-132/11 KV TRANSFORMER FEEDER (-T201) Page 2 of 3

INSULATION TEST (with 1000V insulation tester) Amb Temp:31.7 °C

TERMINAL WINDINGS R Y B
MARKING C.T + LEAD WIRE C.T + LEAD WIRE C.T + LEAD WIRE
UPTO TB UPTO TB UPTO TB

Core1-Earth 6.49 G Ω 5.42 G Ω 6.80 G Ω

Core2-Earth 6.48 G Ω 5.39 G Ω 6.48 G Ω

Core3-Earth 7.32 G Ω 6.02 G Ω 5.53 G Ω


T2
Core 1-Core2 9.95 G Ω 8.49 G Ω 10.40 G Ω

Core 1-Core3 11.6 G Ω 10.2 G Ω 12.3 G Ω

Core 2-Core3 11.0 G Ω 9.48 G Ω 10.9 G Ω

RESISTANCE MEASUREMENT OF SECONDARY WINDINGS


Amb Temp:28.4 °C

CORE Resistance at Amb Temp in Ohms Resistance at 75˚C in Ohms


PHASE 1S1-1S2 1S1-1S3 2S1-2S2 2S1-2S3 1S1-1S2 1S1-1S3 2S1-2S2 2S1-2S3
R 1.254 1.867 1.214 1.818 1.476 2.197 1.429 2.140
Y 1.259 1.877 1.206 1.806 1.482 2.209 1.4196 2.126
B 1.273 1.891 1.212 1.814 1.518 2.226 1.426 2.135

CORE Resistance at Amb Temp in Ohms Resistance at 75˚C in Ohms


PHASE 3S1-3S2 3S1-3S3 3S1-3S2 3S1-3S3
R 0.577 0.859 0.680 1.011
Y 0.578 0.858 0.680 1.009
B 0.577 0.858 0.688 1.010

TESTED BY WITNESSED BY WITNESSED / APPROVED BY

Signature: Signature: Signature:

Name: TIMM Name: SENTHIL KUMAR Name:

Date Date Date


CSE ENERGO CONSULT L.L.C TRANSCO
Site Test Report
Contract No. – N-6166.1 CONSORTIIUM
New 132/11KV Substations at E12,Zayed Sports
City, ADNEC Capital Centre, 132/22kv SIEMENS-
Substations at New Airport and Capital District ELECTROMECHANICAL
and All Related 132kv Cable works

Date:10.06.2012 Bay/Feeder : =E02-132/11 KV TRANSFORMER FEEDER (-T201) Page 3 of 3

CT RATIO TEST

CURRENT CURRENT MEASURED ACROSS


% ERROR
INJECTED SECONDARY TERMINALS (A)
CT RATIO
TERMINALS ACROSS
(A)
PRIMARY R-Phase Y-Phase B-Phase R-Phase Y-Phase B-Phase
(A)
1S1-1S2 400/1A 400 0.999 0.999 0.999 -0.07 -0.11 -0.12
1S1-1S3 600/1A 600 0.999 0.999 0.999 -0.08 -0.08 -0.09
2S1-2S2 400/1A 400 0.999 0.998 0.999 -0.12 -0.12 -0.12
2S1-2S3 600/1A 600 0.999 0.999 0.999 -0.08 -0.05 -0.09
3S1-3S2 400/1A 400 1.0016 1.0015 1.0015 0.20 0.18 0.17
3S1-3S3 600/1A 600 1.0009 1.0008 1.0009 0.11 0.10 0.11

Used Instruments Stock no Calibration Certificate Certificate valid until


available
OMICRON CPC-100 JH808Q(VI) YES 09.05.2013
MEGGER MIT 510 3381 YES 08.05.2013

Remarks:
Bemerkungen: For Magnetizing Curve -See attached Printouts of CPC 100
For C.T Secondary Winding Resistance- See attached Printouts of CPC 100

For Polarity test done as per approved drawing - See attached Printouts of CPC 100

For Ratio Test- See attached Printouts of CPC 100

TESTED BY WITNESSED BY WITNESSED / APPROVED BY

Signature: Signature: Signature:

Name: TIMM Name: SENTHIL KUMAR Name:

Date Date Date


CSE ENERGO CONSULT L.L.C TRANSCO