Site Test Report

Contract No. – N-6166.1 CONSORTIIUM


New 132/11KV Substations at E12,Zayed Sports
City, ADNEC Capital Centre, 132/22kv SIEMENS-
Substations at New Airport and Capital District ELECTROMECHANICAL
and All Related 132kv Cable works

Date:10.06.2012 Bay/Feeder : =E02-132/11 KV TRANSFORMER FEEDER (-T201) Page 1 of 3

High Voltage Switchgear Type 8DN8 72,5 kV and above


Current Transformers
Hochspannungsschaltanlagen 8D . . ab 72,5 kV
Stromwandler
Customer: Contract No.:
Kunde: TRANSCO Vertragsnr.: N-6166.1
Consultant: Bay/Feeder:
Berater: ENERGO CONSULT Abzweig: =E02
Substation: Serial No.:
Anlage: ADNEC Fabrik-Nr.: 31259836
Switchgear type: Rated voltage:
Schaltanlagentyp: 8DN8 Bemessungsspannung: 145 kV

Current transformer: item designation: Type: P1 in direction busbar-2


Stromwandler: Betriebsmittelkennz.: T1.2 Typ: AMT145/3 in Richtung SaS*/Feld*

Serial-No.:
Fabrik-Nr.: L1: 11/101 208 L2: 11/101 208 L3: 11/101 208

Core-No.
Kern-Nr. Core 1 Core 2 Core 3 Core 4
Core data Kern 1 Kern 2 Kern 3 Kern 4
Kerndaten
Nominal power VA VA
Nennleistung
Nominal Ratio 600-400/1A 600-400/1A
Nennübersetzung
Class PX PX
Klasse
Magnetizing – U0 ≥400-300 V ≥400-300 V
Magnetizing – I0 ≤50-80 mA ≤30-50 mA
Resistance Rct ≤2.8-2.1 Ω ≤2.8-2.1 Ω
Earthed at 1S3 2S3
Geerdet an
Used for DIFFERENTIAL HV REF
Verwendet für
Polarity check Error: Error: Error: Error: Error: Error: Error: Error: Error: Error: Error: Error:
Polaritätsprüfung Refer Refer Refer Refer Refer Refer Refer Refer Refer Refer Refer Refer
Secondary circuits
checked up to: +S3 +S3
Sekundärverdrahtung
geprüft bis:

TESTED BY WITNESSED BY WITNESSED / APPROVED BY

Signature: Signature: Signature:

Name: TIMM Name: SENTHILKUMAR Name:

Date Date Date


CSE ENERGO CONSULT L.L.C TRANSCO
Site Test Report
Contract No. – N-6166.1 CONSORTIIUM
New 132/11KV Substations at E12,Zayed Sports
City, ADNEC Capital Centre, 132/22kv SIEMENS-
Substations at New Airport and Capital District ELECTROMECHANICAL
and All Related 132kv Cable works

Date:10.06.2012 Bay/Feeder : =E02-132/11 KV TRANSFORMER FEEDER (-T201) Page 2 of 3

INSULATION TEST (with 1000V insulation tester) Amb Temp:32 °C

TERMINAL WINDINGS R Y B
MARKING C.T + LEAD WIRE C.T + LEAD WIRE C.T + LEAD WIRE
UPTO TB UPTO TB UPTO TB

Core1-Earth 9.34 G Ω 7.68 G Ω 9.24 G Ω


T1.2 Core2-Earth 9.6 G Ω 8.19 G Ω 10.8 G Ω

Core 1-Core2 15.9 G Ω 12.9 G Ω 15.5 G Ω

RESISTANCE MEASUREMENT OF SECONDARY WINDINGS


Amb Temp:28.4 °C

CORE Resistance at Amb Temp in Ohms Resistance at 75˚C in Ohms


PHASE 1S1-1S2 1S1-1S3 2S1-2S2 2S1-2S3 1S1-1S2 1S1-1S3 2S1-2S2 2S1-2S3
R 1.182 1.785 1.231 1.853 1.391 2.101 1.499 2.181
Y 1.195 1.791 1.251 1.879 1.406 2.108 1.472 2.212
B 1.195 1.794 1.267 1.911 1.407 2.112 1.492 2.249

CT RATIO TEST

CURRENT CURRENT MEASURED ACROSS


% ERROR
INJECTED SECONDARY TERMINALS (A)
CT RATIO
TERMINALS ACROSS
(A)
PRIMARY R-Phase Y-Phase B-Phase R-Phase Y-Phase B-Phase
(A)
1S1-1S2 400/1A 400 0.999 0.999 0.998 -0.12 -0.12 -0.14
1S1-1S3 600/1A 600 0.999 0.999 0.999 -0.09 -0.09 -0.10
2S1-2S2 400/1A 400 0.998 0.999 0.998 -0.14 -0.12 -0.13
2S1-2S3 600/1A 600 0.999 0.999 0.999 -0.10 -0.08 -0.09

TESTED BY WITNESSED BY WITNESSED / APPROVED BY

Signature: Signature: Signature:

Name: TIMM Name: SENTHILKUMAR Name:

Date Date Date


CSE ENERGO CONSULT L.L.C TRANSCO
Site Test Report
Contract No. – N-6166.1 CONSORTIIUM
New 132/11KV Substations at E12,Zayed Sports
City, ADNEC Capital Centre, 132/22kv SIEMENS-
Substations at New Airport and Capital District ELECTROMECHANICAL
and All Related 132kv Cable works

Date:10.06.2012 Bay/Feeder : =E02-132/11 KV TRANSFORMER FEEDER (-T201) Page 3 of 3

Used Instruments Stock no Calibration Certificate Certificate valid until


available
OMICRON CPC-100 JH808Q(VI) YES 09.05.2013
MEGGER MIT 510 3381 YES 08.05.2013

Remarks:
Bemerkungen: For Magnetizing Curve -See attached Printouts of CPC 100
For C.T Secondary Winding Resistance- See attached Printouts of CPC 100

For Polarity test done as per approved drawing - See attached Printouts of CPC 100

For Ratio Test- See attached Printouts of CPC 100

TESTED BY WITNESSED BY WITNESSED / APPROVED BY

Signature: Signature: Signature:

Name: TIMM Name: SENTHILKUMAR Name:

Date Date Date


CSE ENERGO CONSULT L.L.C TRANSCO