Assignment -1
TYPE OF QUESTION:MCQ
QUESTION 1:
A fault is detected in 2 cycles of a 50 Hz power system and the circuit breaker clears in 2.5 cycles. Calculate
the fault clearing time for the case.
Correct answer:(B) 90 ms
Detailed Solution:
Each cycle in 50 Hz system=1/50 s =20 ms.
Fault clearing time = detection time + breaker opening time
= 4.5 cycles= 4.5x20ms
= 90ms
NPTEL Online Certification Courses
QUESTION 2:
Detailed Solution:
For dependability improvement, lower level fault current should also be detected. Note in such case the
relay may compromise security, which is not to trip for fault in other elements or non-fault situations.
NPTEL Online Certification Courses
QUESTION 3:
Calculate the negative sequence component (with phase-a as reference) for the given voltage phasors for a
system with abc as phase sequence
QUESTION 4:
Calculate the phase-b current phasor for the given sequence data sets with abc as phase sequence
𝛼 = 1∠1200
NPTEL Online Certification Courses
QUESTION 5:
With abc as phase sequence, the positive sequence current calculated (with phase-a as reference) for the
phase-b-to-phase-c (bc) fault in a radial system, is 3∠440kA. The phase-B current is
Detailed Solution:For bc fault, Ia1 = -Ia2, Ia0 = 0 Ib1 = α2 Ia1 , Ia2 = αIa2 , Ib0 = Ia0 .
QUESTION 6:
For a 4 kHz sampling rate for 50 Hz power system, the sampling interval between two consecutive samples
is how much?
Detailed Solution:
∆t = 1/4000 s (Note For 50 Hz system, 1 cycle =20ms, 4000 kHzsampling rate implies 80 samples per
cycle.)
NPTEL Online Certification Courses
QUESTION 7:
The relay recorded data of a phase current is plotted below. What is the fault detection and decision time for
the relay?
(A) 984 ms and 1 s (B) 4 ms and 20 ms (C) 984 ms and 20 ms (D) 4 ms and 1 s
Detailed Solution:
Fault detection time for the relay = Fault detection instant – fault inception instant
= 0.984 s – 0.98 s = 4ms
Decision time for the relay = Decision instant – fault inception instant
= 1s – 0.98 s = 20 ms
NPTEL Online Certification Courses
QUESTION 8:
The relay recorded data of a phase current is plotted below, with a fault incepted at 0.98s. If the fault
detection algorithm uses sample to sample comparison, what is the maximum value of |in – i(n-1)|?
(n is the current measurement sample)
Detailed Solution:
Note: The required threshold can be set accordingly and the maximum value for fault detection must be
less than 3 kA.
NPTEL Online Certification Courses
QUESTION 9:
The relay recorded data of a phase current is plotted below, with a fault incepted at 0.98s. If the fault
detection algorithm uses cycle to cycle comparison, what is the maximum value of |in – i(n-N)|?
(n is the current measurement sample, N= number of samples per cycle)
Detailed Solution:
According to the figure, maximum value for fault detection must be less than 1.36 kA. Effect of noise
and measurement uncertainty, must be considered.
NPTEL Online Certification Courses
QUESTION 10:
For an 8 bit ADCwith largest possible input V, the quantization error will be