H21 MCB
H21 MCB
1- GENERAL DATA
PANEL : H09
RATED VOLTAGE DC &AC : iC60N - 415V AC
MAKE : SCHNEIDER
2- MECHANICAL CHECK AND VISUAL INSPECTION :
ITEM DESCRIPTION CHECKED
1 INSPECT FOR PHYSICAL DAMAGE / DEFECTS. YES N/A
2 VERIFY CONNECTIONS AS PER APPROVED DRW. YES N/A
3 CHECK TIGHTNESS OF ALL CONNECTIONS. YES N/A
4 CHECK FERRULES YES N/A
1 Q1 iC60N C 2 6 12 16 1NO+1NC OK
2 Q1.1 iC60N C 2 6 12 18 1NO+1NC OK
LIMIT: FOR MCB TYPE CURVE C THE OPERATING TIME RANGE IS (7-120 SEC) @ 2IN
1- GENERAL DATA
Tested By: ENG IBRAHIM SAAD - BAB092 Witnessed By: ENG SULTAN AL AJMI
PRECHECK
Date & Signature:15/08/2022 Date & Signature:15/08/2022
PANEL : H09
RATED VOLTAGE DC &AC : C60H-DC - 500V DC
MAKE : SCHNEIDER
2- MECHANICAL CHECK AND VISUAL INSPECTION :
ITEM DESCRIPTION CHECKED
1 INSPECT FOR PHYSICAL DAMAGE / DEFECTS. YES N/A
2 VERIFY CONNECTIONS AS PER APPROVED DRW. YES N/A
3 CHECK TIGHTNESS OF ALL CONNECTIONS. YES N/A
4 CHECK FERRULES YES N/A
LIMIT: FOR MCB TYPE CURVE C THE OPERATING TIME RANGE IS (7-150 SEC) @ 2IN
1- GENERAL DATA
PANEL : H09
Tested By: ENG IBRAHIM SAAD - BAB092 Witnessed By: ENG SULTAN AL AJMI
PRECHECK
Date & Signature:15/08/2022 Date & Signature:15/08/2022
1 Q7 iC60N C 4 3 6 27 1NO+1NC OK
2 Q8 iC60N C 4 3 6 28 1NO+1NC OK
LIMIT: FOR MCB TYPE CURVE C THE OPERATING TIME RANGE IS (7-120 SEC) @ 2IN
Tested By: ENG IBRAHIM SAAD - BAB092 Witnessed By: ENG SULTAN AL AJMI
PRECHECK
Date & Signature:15/08/2022 Date & Signature:15/08/2022