Professional Documents
Culture Documents
Prof. J. Meenakshi
• Three separate windings or coils with terminals a-a’, b-b’ and c-c’
are physically placed 120 degrees apart around the stator.
• As the rotor rotates, its magnetic field “cuts’ the flux from the three
coils and induces voltages in the coils. Because the coils are placed
120 degrees apart, the induced voltages in the coils are equal in
magnitude but out of phase by 120 degrees.
Three Phase Generator
Three-phase voltages with 120degrees
of phase shift
Three Phase Waveform (sample)
Three Phase Four Wire System
Star Connection
• Similar terminals (start or finish) of the 3
windings are joined together. The common
point is called “STAR” or “NEUTRAL” point.
Star Connected Source
a a
c
Star Connected Source
Delta or Mesh Connection
• Dissimilar terminals of the three windings are
joined together i.e. ‘finish’ terminal of one
winding is connected to the ‘start’ terminal of
other winding and so one.
a a
_ + Delta
Source
+ _
c b b
_ +
c
abc or Positive Sequence
abc sequence or Positive sequence
• Van leads Vbn, which in turn leads Vcn.
a A
Zl
ZL
n
N
ZL ZL
b
c B C
Zl
Zl
Delta – Delta System
a A
Zl
_ +
ZL
ZL
+ _
b
c _ + B C
Zl ZL
Zl
Delta – Wye System
a A
Zl
_ + ZL
+ _
ZL ZL
b
c _ + B C
Zl
Zl
Wye Delta System
a a
A
I aA I AB I CA
+
V0
_
Z Z
n
_ _
V-240 V-120 I BC
+ +
b b B C
c Z
c
Common Terminologies
• Phase Sequence – Sequence in which the voltages in the three phases reach
maximum positive value is called phase sequence or phase order. The phase
sequence is generally given as RYB.
• Balanced System – A three phase system is said to be balance if the voltages and
currents in the three phases are equal in magnitude and differ in phase from one
another by 120 degrees. Also the loads connected across the three phases are
identical.
Line and phase voltages in a Star
Connection
Line and phase currents in a Star
Connection.
Delta system voltage and current
relationships
Three Phase Systems
• All electric power is generated and distributed in three phase, at
the operating frequency of 60 Hz in the US or 50 Hz in India. When
one phase or two phase inputs are required, they are taken from
the three phase systems rather than generated independently.
• For the same amount of power, the three phase system is more
economical than single phase.
Advantages of 3 phase system
• Output is greater than that of a single phase system
• Three phase motors are self starting.
• Transmission and Distribution of a 3 phase system is cheaper
• The horsepower rating of three-phase motors and the kVA rating of
three-phase transformers are 150% greater than single-phase
motors or transformers of similar frame size.
• The power delivered by a single-phase system pulsates and falls to
zero. The three-phase power never falls to zero. The power
delivered to the load in a three-phase system is the same at any
instant. This produces superior operating characteristics for three-
phase motors.
• A three-phase system needs three conductors; however, each
conductor is only 75% the size of the equivalent kVA rated single-
phase conductors.
Balanced Star-Star Connection
• A balanced Y-Y system is a three-phase system
with a balanced Y-connected source and a
balanced Y-connected load.
Also the line voltages lead their corresponding phase voltages by 30◦.
that is, the voltage across the neutral wire is zero. The neutral line can
thus be removed without affecting the system. In fact, in long distance
power transmission, conductors in multiples of three are used with the
earth itself acting as the neutral conductor. Power systems designed in
this way are well grounded at all critical points to ensure safety.
Balanced Delta-Delta Connection
• A balanced Δ-Δ system is one in which both
the balanced source and balanced load are -
connected.
Three Phase Power
• Three-phase power can be computed in two ways,
using line values or phase values.