SANS 10400 PART-XA

ENERGY EFFICIENCY CALCULATIONS


ERF/PORTION 30 OF LPT NO. 185
MEYERTON
• FENESTRATION

CONDUCTANCE = Total building area X Climatic zone (Table-5)


= 299msq X 1.2
= 358.80

SHGC = Total building X C.shgc (Table-5)


= 299msq X 0.15
= 44.85
• CONDUCTANCE

ELEVATIONS:
NORTH SOUTH EAST WEST
W1= 1.08 W1= 1.08 W1= 4.32 D1= 10.73
W1= 1.08 D1= 1.70 W2= 2.70 W1= 1.08
W3= 1.08 W2= 1.62 W3= 2.70 D2= 3.96
W4= 2.70 W3= 1.08 W2= 1.08
W5=1.08 W4=0.54 W3= 1.35
D4= 4.20 W5= 1.62 W4= 1.35
W6=1.08 W6= 1.08
W7=4.32 D2= 3.96
D2=8.57 W7= 1.08

SHGC (Solar heat gain connect)

Conductance = (A1xU1) + (A2xU2)


= (1.80x5.7) + (1.80x5.7)
= 20.52 (Single Low-E) Table-6
TABLE > (A1 x S1 x E1) + (A2 x S2 x E2) + (A3 x S3 x E3) + (A4 x S4 x E3) + (A5 x S5 x E5) etc.
NORTH ELEVATION = 0.15+0.15+0.15+0.39+0.15+0.60+0.15+0.62+01.24
= 3.60

SOUTH ELEVATION = 0.15+0.24+0.23+0.15+0.07+0.23+0.15+0.57+0.15


= 1.94

EAST ELEVATION = 0.62+0.39+0.39


=1.40

WEST ELEVATION = 1.55+0.15+0.57+0.15+0.19+0.19


=2.87
• SHADING

NB: TO ALL WINDOWS AND DOORS

PH = P/G
= 300/300
=0

• LIGHTING

Lighting hours per annum = 52- weeks x 7-days x 5-hours per day
1820 hours per annum

Demand of electricity for H3 building = Minimum watts x Building area


= 5-watts x 299msq
=1495 watts

Kilo-watts = Number of lamps x Watts of lamps


= 36 x 11
= 396-watts
Kilo-watts demand per annum = kilo watts x hours per annum
100
= 396 x 1820
100
= 7200 KW. H/A

• INSULATION

Climatic zone factor = 3.7msq K/W (Table 10)


ROOF = 0.38msq K/W (Concrete roof tile)
= 3.70msq – 0.38msq
= 3.32
26
= 0.127m x 1000
=127mm thickness