Owner

EPC CONTRACTOR EPC SUBCONTRACTOR

PROJECT

NE1 - 700MW CSP + 250MW PV Hybrid Project

04 2022.01.06 Update HeTao LuoWei Yun Feiran

03 2021.9.4 UPDATE HeTao LuoWei Yun Feiran

02 2020.11.17 UPDATE HeTao LuoWei Yun Feiran

01 2020.9.30 First issue HeTao LuoWei Yun Feiran

REV DATE DESCRIPTION DONE CHECKED APPROVED

DOCUMENT NAME
NE1-20-EM-JEP-LIS-BB_(R)-00003

Medium Voltage Protection


SUBCONTRACTOR DOCUMENT NUMBER

Setpoint List
CONTENT

1. 14BBA10 6.6kV MV switch-gear Protection Setting Table.........................................................1


1.1 14BBA10GS101 (UAT incoming) Protection Setting Table.....................................................1
1.2 14BBA10GS301 (Bus PT) Protection Setting Table...............................................................6
1.3 14BBA10GS401/402/403 (Condensate pump VSD 1/2/3) Protection Setting........................8
1.4 14BBA10GS404/405/406 (Feedwater pump VSD 1/2/3) Protection Setting........................12
1.5 14BBA10GS407/408 (BOP MV/LV transformer 1/2) Protection Setting...............................16
1.6 14BBA10GS409 (Emergency MV/LV transformer) Protection Setting Table........................20
1.7 14BBA10GS410/411/412/413 (ACC MV/LV transformer) Protection Setting Table..............24
1.8 14BBA10GS501/502 (Closed circuit cooling water pump VSD 1/2) Protection Setting.......28
2. 20BBA10 11kV MV switch-gear Protection Calculation............................................................33
2.1 20BBA10GS101 (UAT incoming) Protection Setting............................................................33
2.2 20BBA10GS102 (PAT incoming) Protection Setting.............................................................39
2.3 20BBA10GS103/104 (EDG incoming) Protection Setting....................................................44
2.4 20BBA10GS301 (Bus PT) Protection Setting Table.............................................................48
2.5 20BBA10GS401/402/414/415 (Electrical Control room Solar field) Protection Setting........50
2.6 20BBA10GS410/423 (HTF Electrical Building Transformer 1/2) Protection Setting Table...52
2.7 20BBA10GS403/416 (TES Electrical Building) Protection Setting Table..............................57
2.8 20BBA10GS404/405/406/407/417/418/419/420 (HTF Main Pumps-Far Group
19/18/17/16/23/22/21/20) Protection Setting Table.....................................................................60
2.9 20BBA10GS408/409/421/422 (HTF Main Pumps-Near Group 03/02/05/04) Protection
Setting.........................................................................................................................................64
2.10 20BBA10GS413 (Intermediate Substation Services) Protection Setting Table..................68
3. 13BBA10/13BBA20 11kV MV switch-gear Protection Setting..................................................71
3.1 13BBA10/20GS101 (incoming) Protection Setting...............................................................71
3.2 13BBA10/20 GS401/402 (TES MV/LV TRANSFORMER 1/2) Protection Setting................76
3.3 13BBA10/20 GS403/404/405/406/407/408 (COLD and HOT SALT PUMP VSD) Protection
Setting.........................................................................................................................................80
4. 11BBA10/20/30/40/50/60 11kV MV switch-gear Protection Calculation...................................84
4.1 11BBA10/40GS001、11BBA1030/60GS002 (Electrical Control room Solar field) Protection
Setting.........................................................................................................................................84
4.2 11BBA10/20/40 /50GS002、11BBA20/30/50/60GS001(Electrical Control room Solar field)
Protection Setting........................................................................................................................90
4.3 11BBA10/20/30/40/50/60GT003(11BFT10/20/30/40/50/60) (Electrical Control room
Solar field) Protection Setting......................................................................................................92
4.4 11BBA10/20/30/40/50/60GS000 (Electrical Control room Solar field) Protection Setting...99
5. 15BBT10 PAT protection setting table(7UT85).......................................................................101
6. 15BBT10 PAT protection setting table(RED670)...............................................................111
7. 15BBT10 PAT protection setting table(7SD82)..................................................................122
8. Beside15BBT10 PAT protection setting table(7SL82).......................................................127
9. 光伏出线保护整定 CT solar outgoing protection setting table(RED670)..........................132
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 1 of 103

1. 14BBA10 6.6kV MV switch-gear Protection Setting Table

1.1 14BBA10GS101 (UAT incoming) Protection Setting Table

1.1.1 设备参数 Equipment parameter

厂变压器及保护参数

Parameters of GT and protection

额定容量( ) 低压侧额定电压( )
70MVA 6.9kV

Rated capacity( ) LV rated voltage( )

H-L=9%
低压侧额定电流( ) 短路阻抗
1673A H-M=11.5%
Impedance
LV rated current( ) M-L=34.25%

低压侧 LV side:2000/1
CT
低压中性点 LV neutral line:600/1

PT
低压侧 LV side:

综保型号 protection device 7SJ-82

1.1.2 Overcurrent Protection, Phases(Definite-Time)(50)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

661:1 Definite-T 1:Mode Off/On/Test On

Definite-T 1:Operate &


661:2 No/yes No
flt.rec. blocked

Definite-T 1:1-pole
661:11 No/yes No
operate allowed

661:26 Definite-T
661:26 No/yes No
1:Dynamic settings

1
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 2 of 103

Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.

Definite-T 1:Method of Fundamental comp. Fundamental


661:8
measurement RMS value comp.

Definite-T 1:I0
661:120 No/yes No
elimination

661:3 Definite-T 1:Threshold 0.030 A to 35.000 A 9.77A

Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio

661:102 Definite-T 1:Pickup delay 0.00 s to 60.00 s 0.3s

Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay

Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0s
delay

1.1.3 Overcurrent Protection, Phases(Inverse-Time)(51)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

691:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


691:2 No/yes No
flt.rec. blocked

Inverse-T 1:1-pole
691:11 No/yes No
operate allowed

Inverse-T 1:Dynamic
691:26 No/yes No
settings

Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.

691:8 Inverse-T 1:Method of Fundamental comp. Fundamental

2
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 3 of 103

measurement RMS value comp.

Inverse-T 1:I0
691:120 No/yes No
elimination

691:3 Inverse-T 1:Threshold 0.030 A to 35.000 A 1.05A

691:108 Inverse-T 1:Pickup delay 0.00 s to 60.00 s 0.00s

Inverse-T 1:Type of
691:130 IEC V
character. curve

Inverse-T 1:Min. time of


691:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation

691:101 Inverse-T 1:Time dial 0.00 to 15.00 0.6

Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay

1.1.4 Undervoltage Protection(Definite-Time)(27)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

General:Current-flow
2311:104 Off/On Off
criterion

2311:101 General:Threshold I> 0.030 A to 10.000 A 0.050 A

2311:103 General:Stabilization 0 to 10 0
counter
Definite-T 1

421:1 Definite-T 1:Mode Off/On/Test On

421:2 Definite-T 1:Operate & No/yes No


flt.rec. blocked
Definite-T 1:Blk. by
421:10 No/Yes Yes
meas.-volt. failure

Phase-to-ground Phase-to
421:9 Definite-T 1:Measured
value Phase-to-phase -phase

3
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 4 of 103

Definite-T 1:Method of Fundamental comp. Fundamental


421:8
measurement RMS value comp.

Definite-T 1:Pickup 1 out of 3


421:101 1 out of 3
mode 3 out of 3

421:102 Definite-T 1:Pickup delay Off/On/Test On

421:3 Definite-T 1:Threshold 0.300V to 175.000V 45V

Definite-T 1:Dropout
421:4 1.01 to 1.20 1.05
ratio

421:6 Definite-T 1:Operate 0.00 s to 60.00 s 9s


delay
1.1.5 Overvoltage Protection with 3-Phase Voltage(59)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

Definite-T 1

• off
_:181:1 Definite-T 1:Mode • on Off
• test

_:181:2 Definite-T 1:Operate & • no


no
flt.rec. blocked • yes
• phase-to-ground
_:181:9 Definite-T1:Measured phase-to-phase
value • phase-to-phase

Definite-T 1:Method of •fundamentalcomp. fundamental


_:181:8
measurement • RMS value comp.

• 1 out of 3
_:181:101 Definite-T 1:Pickup 1 out of 3
mode • 3 out of 3

_:181:3 Definite-T1:Threshold 0.300 V to 340.000 V 130.000 V

_:181:4 Definite-T 1:Dropout 0.90 to 0.99 0.95


ratio

_:181:6 Definite-T 1:Operate 0.00 s to 300.00 s 2s


delay

1.1.6 Overcurrent Protection, Ground(Inverse-Time)(51N)

Stage with Inverse-Time Characteristic Curve

4
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 5 of 103

Addr. Parameter Setting Options Setting value Note

General

781:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


781:2 No/yes No
flt.rec. blocked

Inverse-T 1:Dynamic
781:26 No/yes No
settings

Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


781:8
measurement RMS value comp.

781:3 Inverse-T 1:Threshold 0.010 A to 35.000 A 0.09A 2000/1

Inverse-T 1:Type of IEC very


781:108
character. curve Inverse curve

Inverse-T 1:Min. time of


781:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation

781:101 Inverse-T 1:Time dial 0.00 to 15.00 0.08

Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.

5
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 6 of 103

1.2 14BBA10GS301 (Bus PT) Protection Setting Table

1.2.1 Power-System Data

PT 及保护参数 PT and protection

额定电压( )

6.6kV PT
Rated voltage (

保护装置
7SJ82
Protect device

1.2.2 Overvoltage Protection, Phases

Addr. Parameter Setting Options Setting value Note

Definite-T 1

181:1 Definite-T 1:Mode Off/On/Test On

Definite-T 1:Operate &


181:2 No/yes No
flt.rec. blocked

Definite-T 1: Measured Phase-to-phase/phase-


181:9 Phase-to-phase
value to-ground

Definite-T 1:Method of Fundamental Fundamental


181:8
measurement comp/RMS value comp

Definite-T 1:Pickup
181:101 1 out of 3/3 out of 3 1 out of 3
mode

181:3 Definite-T 1: Threshold 0.300V to 340.000V 130V

Definite-T 1: Dropout
181:4 0.90 to 0.99 0.95
ratio

Definite-T 1: Operate
181:6 0.00s to 300.00s 2s
delay

Note: Other functions of 7SJ82 setting Off and used default value.

1.2.3 Undervoltage Protection, Phases

Addr. Parameter Setting Options Setting value Note

Definite-T 1

6
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 7 of 103

421:1 Definite-T 1:Mode Off/On/Test On

Definite-T 1:
421:2 No/yes No
Operate&flt.rec.blocked

Definite-T 1:Blk.bu
421:10 No/yes No
mead.-volt.failure

Definite-T 1: Phase-to-phase/phase-
421:9 Phase-to-phase
Measured value to-ground

Definite-T 1:Method of Fundamental Fundamental


421:8
measurement comp/RMS value comp

Definite-T 1:Pickup
421:101 1 out of 3/3 out of 3 1 out of 3
mode

421:102 Definite-T 1:Pickup delay No/yes No

421:3 Definite-T 1: Threshold 0.300V to 175.000V 45V

Definite-T 1:
421:4 1.01 to 1.20 1.05
Dropout ratio

Definite-T 1:
421:6 0.00s to 60.00s 9s
Operate delay

Note: Other functions of 7SJ82 setting Off and used default value.

7
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 8 of 103

1.3 14BBA10GS401/402/403 (Condensate pump VSD 1/2/3) Protection Setting

1.3.1 Power-System Data

电机及保护参数 Motor and protection

额定功率( ) 额定电压( )
600kW 6.6kV
Rated power( ) Rated voltage( )

堵转电流( )
额定电流( )
61A 650%
Lock rotor current(
Rated current( )

启动时间
15s(hold) PT
Starting time

相间 Phase to phase: 200/1


CT
零序 CT Zero sequence CT: 100/1

KKS 14BBA10 GS401/GS402/GS403

保护装置
7SJ82
Protect device

1.3.2 Overcurrent Protection, Phases(Definite-Time)(50)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

661:1 Definite-T 1:Mode Off/On/Test On

Definite-T 1:Operate &


661:2 No/yes No
flt.rec. blocked

Definite-T 1:1-pole
661:11 No/yes No
operate allowed

661:26 Definite-T
661:26 No/yes No
1:Dynamic settings

8
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 9 of 103

Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.

Definite-T 1:Method of Fundamental comp. Fundamental


661:8
measurement RMS value comp.

661:3 Definite-T 1:Threshold 0.030 A to 35.000 A 3.27A

Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio

661:102 Definite-T 1:Pickup delay 0.00 s to 60.00 s 0s

Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay

Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay

Note: Other functions of 7SJ82 setting Off and used default value.

1.3.3 Overcurrent Protection, Phases(Inverse-Time)(51)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

691:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


691:2 No/yes No
flt.rec. blocked

Inverse-T 1:1-pole
691:11 No/yes No
operate allowed

Inverse-T 1:Dynamic
691:26 No/yes No
settings

Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


691:8
measurement RMS value comp.

691:3 Inverse-T 1:Threshold 0.030 A to 35.000 A 0.61A

9
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 10 of 103

691:108 Inverse-T 1:Pickup delay 0.00 s to 60.00 s 0.00s

Inverse-T 1:Type of IEC long time


691:130
character. curve Inverse curve

Inverse-T 1:Min. time of


691:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation

691:101 Inverse-T 1:Time dial 0.00 to 15.00 0.03

Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.

1.3.4 Overcurrent Protection, Ground(Inverse-Time)(50N)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

781:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


781:2 No/yes No
flt.rec. blocked

Inverse-T 1:Dynamic
781:26 No/yes No
settings

Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


781:8
measurement RMS value comp.

781:3 Inverse-T 1:Threshold 0.010 A to 35.000 A 1.2A 100/1CT

Inverse-T 1:Type of IEC very


781:108
character. curve Inverse curve

Inverse-T 1:Min. time of


781:113 0.00 s to 1.00 s 0.00s
the curve

10
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 11 of 103

Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation

781:101 Inverse-T 1:Time dial 0.00 to 15.00 0.05

Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.

11
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 12 of 103

1.4 14BBA10GS404/405/406 (Feedwater pump VSD 1/2/3) Protection Setting

1.4.1 Power-System Data

电机及保护参数 Motor and protection

额定功率( ) 额定电压( )
2600kW 6.6kV
Rated power( ) Rated voltage( )

堵转电流( )
额定电流( )
268A 650%
Lock rotor current (
Rated current( )

启动时间
30s(hold) PT
Starting time

相间 Phase to phase: 600/1


CT
零序 CT Zero sequence CT: 100/1

KKS 14BBA10 GS404/GS405/GS406

保护装置 Protect device 7SJ82

1.4.2 Overcurrent Protection, Phases(Definite-Time)(50)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

661:1 Definite-T 1:Mode Off/On/Test On

Definite-T 1:Operate &


661:2 No/yes No
flt.rec. blocked
Definite-T 1:1-pole
661:11 No/yes No
operate allowed
661:26 Definite-T
661:26 No/yes No
1:Dynamic settings
Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.

Definite-T 1:Method of Fundamental comp. Fundamental


661:8
measurement RMS value comp.

12
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 13 of 103

661:3 Definite-T 1:Threshold 0.030 A to 35.000 A 4.79A

Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio
661:102 Definite-T 1:Pickup delay 0.00 s to 60.00 s 0s

Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay
Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay
Note: Other functions of 7SJ82 setting Off and used default value.

1.4.3 Overcurrent Protection, Phases(Inverse-Time)(51)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

691:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


691:2 No/yes No
flt.rec. blocked

Inverse-T 1:1-pole
691:11 No/yes No
operate allowed

Inverse-T 1:Dynamic
691:26 No/yes No
settings

Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


691:8
measurement RMS value comp.

691:3 Inverse-T 1:Threshold 0.030 A to 35.000 A 0.89A

691:108 Inverse-T 1:Pickup delay 0.00 s to 60.00 s 0.00s

Inverse-T 1:Type of IEC long time


691:130
character. curve Inverse curve

Inverse-T 1:Min. time of


691:113 0.00 s to 1.00 s 0.00s
the curve

13
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 14 of 103

Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation

691:101 Inverse-T 1:Time dial 0.00 to 15.00 0.03

Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.

1.4.4 Overcurrent Protection, Ground(Inverse-Time)(50N)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

781:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


781:2 No/yes No
flt.rec. blocked

Inverse-T 1:Dynamic
781:26 No/yes No
settings

Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


781:8
measurement RMS value comp.

781:3 Inverse-T 1:Threshold 0.010 A to 35.000 A 1.2A 100/1CT

Inverse-T 1:Type of IEC very


781:108
character. curve Inverse curve

Inverse-T 1:Min. time of


781:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous Disk
781:109 Inverse-T 1:Reset
Disk emulation emulation

781:101 Inverse-T 1:Time dial 0.00 to 15.00 0.05

Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay

14
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 15 of 103

Note: Other functions of 7SJ82 setting Off and used default value.

15
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 16 of 103

1.5 14BBA10GS407/408 (BOP MV/LV transformer 1/2) Protection Setting

1.5.1 Power-System Data

设备和保护参数 Parameter of equipment and protection

额定容量 额定电压
2800kVA 6.6kV
Rated capacity Rated voltage of HV

额定电压 高压侧额定电流
0.42kV 244.9A
Rated voltage of LV Rated current of HV

低压侧额定电流 短路阻抗
3849A 8%
Rated current of LV Impedance

CT 400/1 零序 CT Zero CT 100/1

PT

KKS 14BBA10GS407/GS408

综保 Protect device 7SJ82

1.5.2 Overcurrent Protection, Phases(Definite-Time)(50)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

661:1 Definite-T 1:Mode Off/On/Test On

Definite-T 1:Operate &


661:2 No/yes No
flt.rec. blocked

Definite-T 1:1-pole
661:11 No/yes No
operate allowed

661:26 Definite-T
661:26 No/yes No
1:Dynamic settings

Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.

16
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 17 of 103

Definite-T 1:Method of Fundamental comp. Fundamental


661:8
measurement RMS value comp.

Definite-T 1:
661:3 0.030 A to 35.000 A 11.89A
Threshold

Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio

661:102 Definite-T 1:Pickup delay 0.00 s to 60.00 s 0s

Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay

Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay

Note: Other functions of 7SJ82 setting Off and used default value.

1.5.3 Overcurrent Protection, Phases(Inverse-Time)(51)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

691:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


691:2 No/yes No
flt.rec. blocked

Inverse-T 1:1-pole
691:11 No/yes No
operate allowed

Inverse-T 1:Dynamic
691:26 No/yes No
settings

Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


691:8
measurement RMS value comp.

691:3 Inverse-T 1:Threshold 0.030 A to 35.000 A 0.77A

691:108 Inverse-T 1:Pickup delay 0.00 s to 60.00 s 0.00s

17
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 18 of 103

Inverse-T 1:Type of IEC very


691:130
character. curve Inverse curve

Inverse-T 1:Min. time of


691:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation

691:101 Inverse-T 1:Time dial 0.00 to 15.00 0.3

Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.

1.5.4 Overcurrent Protection, Ground(Inverse-Time)(50N)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

781:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


781:2 No/yes No
flt.rec. blocked

Inverse-T 1:Dynamic
781:26 No/yes No
settings

Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


781:8
measurement RMS value comp.

781:3 Inverse-T 1:Threshold 0.010 A to 35.000 A 1.2A 100/1CT

Inverse-T 1:Type of IEC very


781:108
character. curve Inverse curve

Inverse-T 1:Min. time of


781:113 0.00 s to 1.00 s 0.00s
the curve

781:109 Inverse-T 1:Reset Instantaneous Disk emulation

18
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 19 of 103

Disk emulation

781:101 Inverse-T 1:Time dial 0.00 to 15.00 0.05

Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.

19
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 20 of 103

1.6 14BBA10GS409 (Emergency MV/LV transformer) Protection Setting Table

1.6.1 Power-System Data

设备和保护参数 Parameter of equipment and protection

额定容量 额定电压
2800kVA 6.6kV
Rated capacity Rated voltage of HV

额定电压 高压侧额定电流
0.42kV 244.9A
Rated voltage of LV Rated current of HV

低压侧额定电流 短路阻抗
3849A 8%
Rated current of LV Impedance

CT 400/1 零序 CT Zero CT 100/1

PT

KKS 14BBA10GS409

综保 Protect device 7SJ82

1.6.2 Overcurrent Protection, Phases(Definite-Time)(50)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

661:1 Definite-T 1:Mode Off/On/Test On

Definite-T 1:Operate &


661:2 No/yes No
flt.rec. blocked

Definite-T 1:1-pole
661:11 No/yes No
operate allowed

661:26 Definite-T
661:26 No/yes No
1:Dynamic settings

Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.

20
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 21 of 103

Definite-T 1:Method of Fundamental comp. Fundamental


661:8
measurement RMS value comp.

Definite-T 1:
661:3 0.030 A to 35.000 A 11.89A
Threshold

Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio

661:102 Definite-T 1:Pickup delay 0.00 s to 60.00 s 0s

Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay

Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay

Note: Other functions of 7SJ82 setting Off and used default value.

1.6.3 Overcurrent Protection, Phases(Inverse-Time)(51)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

691:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


691:2 No/yes No
flt.rec. blocked

Inverse-T 1:1-pole
691:11 No/yes No
operate allowed

Inverse-T 1:Dynamic
691:26 No/yes No
settings

Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


691:8
measurement RMS value comp.

691:3 Inverse-T 1:Threshold 0.030 A to 35.000 A 0.77A

691:108 Inverse-T 1:Pickup delay 0.00 s to 60.00 s 0.00s

21
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 22 of 103

Inverse-T 1:Type of IEC very


691:130
character. curve Inverse curve

Inverse-T 1:Min. time of


691:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation

691:101 Inverse-T 1:Time dial 0.00 to 15.00 0.3

Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.

1.6.4 Overcurrent Protection, Ground(Inverse-Time)(50N)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

781:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


781:2 No/yes No
flt.rec. blocked

Inverse-T 1:Dynamic
781:26 No/yes No
settings

Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


781:8
measurement RMS value comp.

781:3 Inverse-T 1:Threshold 0.010 A to 35.000 A 1.2A 100/1CT

Inverse-T 1:Type of IEC very


781:108
character. curve Inverse curve

Inverse-T 1:Min. time of


781:113 0.00 s to 1.00 s 0.00s
the curve

781:109 Inverse-T 1:Reset Instantaneous Disk

22
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 23 of 103

Disk emulation emulation

781:101 Inverse-T 1:Time dial 0.00 to 15.00 0.05

Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.

23
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 24 of 103

1.7 14BBA10GS410/411/412/413 (ACC MV/LV transformer) Protection Setting Table

1.7.1 Power-System Data

设备和保护参数 Parameter of equipment and protection

额定容量 额定电压
2800kVA 6.6kV
Rated capacity Rated voltage of HV

额定电压 高压侧额定电流
0.42kV 244.9A
Rated voltage of LV Rated current of HV

低压侧额定电流 短路阻抗
3849A 10%
Rated current of LV Impedance

CT 400/1 零序 CT Zero CT 100/1

PT

KKS 14BBA10GS410/GS411/GS412/GS413

综保 Protect device 7SJ82

1.7.2 Overcurrent Protection, Phases(Definite-Time)(50)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

661:1 Definite-T 1:Mode Off/On/Test On

Definite-T 1:Operate &


661:2 No/yes No
flt.rec. blocked

Definite-T 1:1-pole
661:11 No/yes No
operate allowed

661:26 Definite-T
661:26 No/yes No
1:Dynamic settings

Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.

24
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 25 of 103

Definite-T 1:Method of Fundamental comp. Fundamental


661:8
measurement RMS value comp.

661:3 Definite-T 1:Threshold 0.030 A to 35.000 A 9.75A

Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio

661:102 Definite-T 1:Pickup delay 0.00 s to 60.00 s 0s

Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay

Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay

Note: Other functions of 7SJ82 setting Off and used default value.

1.7.3 Overcurrent Protection, Phases(Inverse-Time)(51)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

691:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


691:2 No/yes No
flt.rec. blocked

Inverse-T 1:1-pole
691:11 No/yes No
operate allowed

Inverse-T 1:Dynamic
691:26 No/yes No
settings

Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


691:8
measurement RMS value comp.

691:3 Inverse-T 1:Threshold 0.030 A to 35.000 A 0.77A

691:108 Inverse-T 1:Pickup delay 0.00 s to 60.00 s 0.00s

691:130 Inverse-T 1:Type of IEC very

25
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 26 of 103

character. curve Inverse curve

Inverse-T 1:Min. time of


691:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation

691:101 Inverse-T 1:Time dial 0.00 to 15.00 0.23

Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.

1.7.4 Overcurrent Protection, Ground(Inverse-Time)(50N)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

781:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


781:2 No/yes No
flt.rec. blocked

Inverse-T 1:Dynamic
781:26 No/yes No
settings

Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


781:8
measurement RMS value comp.

781:3 Inverse-T 1:Threshold 0.010 A to 35.000 A 1.2A 100/1CT

Inverse-T 1:Type of IEC very


781:108
character. curve Inverse curve

Inverse-T 1:Min. time of


781:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous Disk
781:109 Inverse-T 1:Reset
Disk emulation emulation

26
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 27 of 103

781:101 Inverse-T 1:Time dial 0.00 to 15.00 0.05

Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.

27
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 28 of 103

1.8 14BBA10GS501/502 (Closed circuit cooling water pump VSD 1/2) Protection Setting

1.8.1 Power-System Data

电机及保护参数 Motor and protection

额定功率( ) 额定电压( )
475kW 6.6kV
Rated power( ) Rated voltage( )

额定电流( ) 堵转电流( )
49A 650%
Rated current( ) Lock rotor current( )

启动时间
15s(hold) PT
Starting time

相间 Phase to phase: 200/1


CT
零序 CT Zero sequence CT:100/1

KKS 14BBA10 GS501/GS502

保护装置
7SK82
Protect device

1.8.2 Overcurrent Protection, Phases(Definite-Time)(50)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

661:1 Definite-T 1:Mode Off/On/Test On

Definite-T 1:Operate &


661:2 No/yes No
flt.rec. blocked

Definite-T 1:1-pole
661:11 No/yes No
operate allowed

661:26 Definite-T
661:26 No/yes No
1:Dynamic settings

661:27 Definite-T 1:Blk. w. No/yes No

28
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 29 of 103

inrush curr. detect.

Definite-T 1:Method of Fundamental comp. Fundamental


661:8
measurement RMS value comp.

661:3 Definite-T 1:Threshold 0.030 A to 35.000 A 2.63A

Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio

661:102 Definite-T 1:Pickup delay 0.00 s to 60.00 s 0s

Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay

Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay

Note: Other functions of 7SK82 setting Off and used default value.

1.8.3 Overcurrent Protection, Phases(Inverse-Time)(51)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

691:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


691:2 No/yes No
flt.rec. blocked

Inverse-T 1:1-pole
691:11 No/yes No
operate allowed

Inverse-T 1:Dynamic
691:26 No/yes No
settings

Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


691:8
measurement RMS value comp.

691:3 Inverse-T 1:Threshold 0.030 A to 35.000 A 0.37A

691:108 Inverse-T 1:Pickup delay 0.00 s to 60.00 s 0.00s

29
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 30 of 103

Inverse-T 1:Type of IEC long time


691:130
character. curve Inverse curve

Inverse-T 1:Min. time of


691:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation

691:101 Inverse-T 1:Time dial 0.00 to 15.00 0.5

Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SK2 setting Off and used default value.

1.8.4 Negative-Sequence Protection (Definite-Time)(46)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

Pos. seq. current


2311:106 General:Reference value Rated current
Rated current

2311:107 General:Current No/yes No


limitation Imax
2311:104 General:Release current 0.030 A to 10.000 A 0.050 A
Definite-T 1

1981:1 Definite-T 1:Mode Off/On/Test On

1981:2 Definite-T 1:Operate & No/yes No


flt.rec. blocked
1981:3 Definite-T1:Threshold 5.0 % to 999.9 % 40 %

Definite-T 1:Dropout
1981:4 0.40 to 0.99 0.95
ratio

Definite-T 1:Blk. w.
1981:104 No/yes No
inrush curr. detect.

Definite-T 1:Dropout
1981:101 0.00 s to 60.00 s 0.00 s
delay

Definite-T 1:Operate
1981:6 0.00 s to 60.00 s 2.5s
delay

30
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 31 of 103

Note: Other functions of 7SK82 setting Off and used default value.

1.8.5 Overcurrent Protection, Ground(Inverse-Time)(50N)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

781:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


781:2 No/yes No
flt.rec. blocked

Inverse-T 1:Dynamic
781:26 No/yes No
settings

Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


781:8
measurement RMS value comp.

781:3 Inverse-T 1:Threshold 0.010 A to 35.000 A 1.2A 100/1CT

Inverse-T 1:Type of IEC very


781:108
character. curve Inverse curve

Inverse-T 1:Min. time of


781:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous Disk
781:109 Inverse-T 1:Reset
Disk emulation emulation

781:101 Inverse-T 1:Time dial 0.00 to 15.00 0.05

Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SK82 setting Off and used default value.

1.8.6 Overcurrent Protection, Phases(Definite-Time)(49)

Setting
Addr. Parameter Setting Options Note
value

31
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 32 of 103

49 Th.overl. #

1 49 Th.overl. #:Mode Off/On/Test On

2 49 Th.overl. #:Operate & No/yes No


flt.rec. blocked
101 49 Th.overl. #:Threshold 0.030 A to 35.000 A 0.27A
current warning
104 49 Th.overl. #:Threshold 50 % to 100 % 83 %
thermal warn.
105 49 Th.overl. #:Dropout 50 % to 99 % 50 %
threshold operate
49 Th.overl. #:Emerg.
112 0 s to 15000 s 300 s
start T overtravel

106 49 Th.overl. #:K-factor 0.10 to 4.00 1.10 Parameter is

110 49 Th.overl. #:Thermal 10 s to 60000 s 900 s specified by the


time constant
49 Th.overl. #:Cooling machine
111 10 s to 60000 s 3600 s
time constant manufacturer
49 Th.overl.
109 #:Temperature rise at 40 K to 200 K 70 K
Irated
49 Th.overl. #:Imax
107 0.030 A to 10.000 A 2.500 A
thermal

49 Th.overl. #:Imin
108 0.000 A to 10.000 A 0.250 A
cooling

113 49 Th.overl. #:Storage of No/yes No


thermal replica
Current limiting current
114 49 Th.overl. #:Behav. at
I> Imax therm. Freeze therm. rep. limiting

Note: Other functions of 7SK82 setting Off and used default value.

1.8.7 Motor-starting time supervision, Phases(Definite-Time)(48)

Setting
Addr. Parameter Setting Options Note
value

Inverse-T 1

_:11551:1 Inverse-T 1:Mode Off/On/Test On

_:11551:2 Inverse-T No/yes No


1:Operate&flt.rec.blocke
32
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 33 of 103

d
_:11551:10
Inverse-T 1:Max.locked 0.5s to 180.0s 2s
1 rotor time

_:11551:10 Inverse-T 1.00 I/IrObj to 20.00


1:Start.cur./mot.rated 6.5
4 I/IrObj
cur.
_:11551:10 Inverse-T
1:Max.start.time,cold 1.0s to 180.0s 15s
2
motor
Inverse-T
_:11551:10
1:Max.str.time,warmmot 0.5s to 180.0s 15s
3
or

Note: Other functions of 7SK82 setting Off and used default value.

2. 20BBA10 11kV MV switch-gear Protection Calculation

2.1 20BBA10GS101 (UAT incoming) Protection Setting

2.1.1 设备参数 Equipment parameter

厂变压器及保护参数
Parameters of GT and protection

额定容量( )
70MVA 中压侧额定电压( ) 11.3kV

Rated capacity( )

H-L=9%
中压侧额定电流( ) 短路阻抗
2555A H-M=11.5%
Impedance
MV rated current( ) M-L=34.25%

中压侧 MV side:4000/1
CT
中压中性点 MV neutral line:600/1

PT
中压侧 MV side:

保护装置
7SJ-82
Protect device

33
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 34 of 103

2.1.2 Overcurrent Protection, Phases(Definite-Time)(50)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

661:1 Definite-T 1:Mode Off/On/Test On

Definite-T 1:Operate &


661:2 No/yes No
flt.rec. blocked

Definite-T 1:1-pole
661:11 No/yes No
operate allowed

661:26 Definite-T
661:26 No/yes No
1:Dynamic settings

Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.

Definite-T 1:Method of Fundamental comp. Fundamental


661:8
measurement RMS value comp.

Definite-T 1:I0
661:120 No/yes No
elimination

661:3 Definite-T 1:Threshold 0.030 A to 35.000 A 2.58A

Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio

661:102 Definite-T 1:Pickup delay 0.00 s to 60.00 s 0.5s

Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay

Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0s
delay

2.1.3 Overcurrent Protection, Phases(Inverse-Time)(51)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

34
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 35 of 103

691:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


691:2 No/yes No
flt.rec. blocked

Inverse-T 1:1-pole
691:11 No/yes No
operate allowed

Inverse-T 1:Dynamic
691:26 No/yes No
settings

Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


691:8
measurement RMS value comp.

Inverse-T 1:I0
691:120 No/yes No
elimination

691:3 Inverse-T 1:Threshold 0.030 A to 35.000 A 0.8A

691:108 Inverse-T 1:Pickup delay 0.00 s to 60.00 s 0.00s

Inverse-T 1:Type of
691:130 IEC V
character. curve

Inverse-T 1:Min. time of


691:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation

691:101 Inverse-T 1:Time dial 0.00 to 15.00 0.3

Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay

2.1.4 Undervoltage Protection(Definite-Time)(27)(11.3kV)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

General:Current-flow
2311:104 Off/On Off
criterion

35
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 36 of 103

2311:101 General:Threshold I> 0.030 A to 10.000 A 0.050 A

2311:103 General:Stabilization 0 to 10 0
counter
Definite-T 1

421:1 Definite-T 1:Mode Off/On/Test On

421:2 Definite-T 1:Operate & No/yes No


flt.rec. blocked
Definite-T 1:Blk. by
421:10 No/Yes Yes
meas.-volt. failure

Phase-to-ground Phase-to
421:9 Definite-T 1:Measured
value Phase-to-phase -phase

Definite-T 1:Method of Fundamental comp. Fundamental


421:8
measurement RMS value comp.

Definite-T 1:Pickup 1 out of 3


421:101 1 out of 3
mode 3 out of 3

421:102 Definite-T 1:Pickup delay Off/On/Test On

421:3 Definite-T 1:Threshold 0.300V to 175.000V 45V

Definite-T 1:Dropout
421:4 1.01 to 1.20 1.05
ratio

421:6 Definite-T 1:Operate 0.00 s to 60.00 s 9s


delay
2.1.5 Overvoltage Protection with 3-Phase Voltage(59)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

Definite-T 1

• off
_:181:1 Definite-T 1:Mode • on Off
• test
_:181:2 Definite-T 1:Operate & • no
no
flt.rec. blocked • yes
• phase-to-ground
_:181:9 Definite-T1:Measured phase-to-phase
value • phase-to-phase

Definite-T 1:Method of •fundamentalcomp. fundamental


_:181:8
measurement • RMS value comp.

36
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 37 of 103

• 1 out of 3
_:181:101 Definite-T 1:Pickup 1 out of 3
mode • 3 out of 3

_:181:3 Definite-T1:Threshold 0.300 V to 340.000 V 130.000 V

_:181:4 Definite-T 1:Dropout 0.90 to 0.99 0.95


ratio
_:181:6 Definite-T 1:Operate 0.00 s to 300.00 s 2s
delay

2.1.6 Overcurrent Protection, Ground(Inverse-Time)(51N)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

781:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


781:2 No/yes No
flt.rec. blocked

Inverse-T 1:Dynamic
781:26 No/yes No
settings

Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


781:8
measurement RMS value comp.

781:3 Inverse-T 1:Threshold 0.010 A to 35.000 A 0.02A 4000/1

Inverse-T 1:Type of IEC very


781:108
character. curve Inverse curve

Inverse-T 1:Min. time of


781:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation

781:101 Inverse-T 1:Time dial 0.00 to 15.00 0.3

Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.
37
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 38 of 103

38
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 39 of 103

2.2 20BBA10GS102 (PAT incoming) Protection Setting

2.2.1 设备参数 Equipment parameter

设备和保护参数 Parameter of equipment and protection

额定电压 额定电流
11kV 2044A
Rated voltage Rated current

CT 4000/1 零序 CT Zero CT /

综保
7SJ82 PT
Protect device

2.2.2 Overcurrent Protection, Phases(Definite-Time)(50)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

661:1 Definite-T 1:Mode Off/On/Test On

Definite-T 1:Operate &


661:2 No/yes No
flt.rec. blocked

Definite-T 1:1-pole
661:11 No/yes No
operate allowed

661:26 Definite-T
661:26 No/yes No
1:Dynamic settings

Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.

Definite-T 1:Method of Fundamental comp. Fundamental


661:8
measurement RMS value comp.

Definite-T 1:I0
661:120 No/yes No
elimination

661:3 Definite-T 1:Threshold 0.030 A to 35.000 A 1.65A

Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio

39
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 40 of 103

661:102 Definite-T 1:Pickup delay 0.00 s to 60.00 s 0.5s

Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay

Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0s
delay

2.2.3 Overcurrent Protection, Phases(Inverse-Time)(51)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

691:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


691:2 No/yes No
flt.rec. blocked

Inverse-T 1:1-pole
691:11 No/yes No
operate allowed

Inverse-T 1:Dynamic
691:26 No/yes No
settings

Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


691:8
measurement RMS value comp.

Inverse-T 1:I0
691:120 No/yes No
elimination

691:3 Inverse-T 1:Threshold 0.030 A to 35.000 A 0.64A

691:108 Inverse-T 1:Pickup delay 0.00 s to 60.00 s 0.00s

Inverse-T 1:Type of
691:130 IEC V
character. curve

Inverse-T 1:Min. time of


691:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation

40
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 41 of 103

691:101 Inverse-T 1:Time dial 0.00 to 15.00 0.3

Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay

2.2.4 Undervoltage Protection(Definite-Time)(27)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

General:Current-flow
2311:104 Off/On Off
criterion

2311:101 General:Threshold I> 0.030 A to 10.000 A 0.050 A

2311:103 General:Stabilization 0 to 10 0
counter
Definite-T 1

421:1 Definite-T 1:Mode Off/On/Test On

421:2 Definite-T 1:Operate & No/yes No


flt.rec. blocked
Definite-T 1:Blk. by
421:10 No/Yes Yes
meas.-volt. failure

Phase-to-ground Phase-to
421:9 Definite-T 1:Measured
value Phase-to-phase -phase

Definite-T 1:Method of Fundamental comp. Fundamental


421:8
measurement RMS value comp.

Definite-T 1:Pickup 1 out of 3


421:101 1 out of 3
mode 3 out of 3

421:102 Definite-T 1:Pickup delay Off/On/Test On

421:3 Definite-T 1:Threshold 0.300V to 175.000V 45V

Definite-T 1:Dropout
421:4 1.01 to 1.20 1.05
ratio

421:6 Definite-T 1:Operate 0.00 s to 60.00 s 9s


delay
2.2.5 Overvoltage Protection with 3-Phase Voltage(59)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

Definite-T 1
41
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 42 of 103

• off
_:181:1 Definite-T 1:Mode • on Off
• test
_:181:2 Definite-T 1:Operate & • no
no
flt.rec. blocked • yes
• phase-to-ground
_:181:9 Definite-T1:Measured phase-to-phase
value • phase-to-phase

Definite-T 1:Method of •fundamentalcomp. fundamental


_:181:8
measurement • RMS value comp.

• 1 out of 3
_:181:101 Definite-T 1:Pickup 1 out of 3
mode • 3 out of 3

_:181:3 Definite-T1:Threshold 0.300 V to 340.000 V 130.000 V

_:181:4 Definite-T 1:Dropout 0.90 to 0.99 0.95


ratio
_:181:6 Definite-T 1:Operate 0.00 s to 300.00 s 2s
delay

2.2.6 Overcurrent Protection, Ground(Inverse-Time)(51N)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

781:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


781:2 No/yes No
flt.rec. blocked

Inverse-T 1:Dynamic
781:26 No/yes No
settings

Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


781:8
measurement RMS value comp.

781:3 Inverse-T 1:Threshold 0.010 A to 35.000 A 0.02A 4000/1

781:108 Inverse-T 1:Type of IEC very

42
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 43 of 103

character. curve Inverse curve

Inverse-T 1:Min. time of


781:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation

781:101 Inverse-T 1:Time dial 0.00 to 15.00 0.1

Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.

43
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 44 of 103

2.3 20BBA10GS103/104 (EDG incoming) Protection Setting

2.3.1 设备参数 Equipment parameter

设备和保护参数 Parameter of equipment and protection

额定电压 额定功率
11kV 2112kW
Rated voltage Rated Power

额定电流 额定容量
138.6A 2640kVA
Rated current Rated Capacity

CT 200/1 零序 CT Zero CT -

综保
7SJ82 PT
Protect device

发电机两相短路时流过保护的最小短路电流
Short circuit current through protect device when 11kV EDG phase-
732A

phase fault

2.3.2 Overcurrent Protection, Phases(Definite-Time)(50)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

661:1 Definite-T 1:Mode Off/On/Test On

Definite-T 1:Operate &


661:2 No/yes No
flt.rec. blocked

Definite-T 1:1-pole
661:11 No/yes No
operate allowed

661:26 Definite-T
661:26 No/yes No
1:Dynamic settings

Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.

661:8 Definite-T 1:Method of Fundamental comp. Fundamental

44
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 45 of 103

measurement RMS value comp.

661:3 Definite-T 1:Threshold 0.030 A to 35.000 A 1.83A

Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio

661:102 Definite-T 1:Pickup delay 0.00 s to 60.00 s 0.25s

Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay

Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay

Note: Other functions of 7SJ82 setting Off and used default value.

2.3.3 Overcurrent Protection, Phases(Inverse-Time)(51)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

691:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


691:2 No/yes No
flt.rec. blocked

Inverse-T 1:1-pole
691:11 No/yes No
operate allowed

Inverse-T 1:Dynamic
691:26 No/yes No
settings

Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


691:8
measurement RMS value comp.

691:3 Inverse-T 1:Threshold 0.030 A to 35.000 A 1.04A

691:108 Inverse-T 1:Pickup delay 0.00 s to 60.00 s 0.00s

Inverse-T 1:Type of IEC very


691:130
character. curve Inverse curve

45
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 46 of 103

Inverse-T 1:Min. time of


691:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation

691:101 Inverse-T 1:Time dial 0.00 to 15.00 0.6

Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.

2.3.4 Overcurrent Protection, Ground(Inverse-Time)(50N)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

781:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


781:2 No/yes No
flt.rec. blocked

Inverse-T 1:Dynamic
781:26 No/yes No
settings

Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


781:8
measurement RMS value comp.

200/1C
781:3 Inverse-T 1:Threshold 0.010 A to 35.000 A 0.38A
T

Inverse-T 1:Type of IEC very


781:108
character. curve Inverse curve

Inverse-T 1:Min. time of


781:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation

46
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 47 of 103

781:101 Inverse-T 1:Time dial 0.00 to 15.00 0.1

Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.

47
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 48 of 103

2.4 20BBA10GS301 (Bus PT) Protection Setting Table

2.4.1 Power-System Data

PT 及保护参数 PT and protection

额定电压( )

11kV PT
Rated voltage (

保护装置
7SJ82
Protect device

2.4.2 Overvoltage Protection, Phases

Addr. Parameter Setting Options Setting value Note

Definite-T 1

181:1 Definite-T 1:Mode Off/On/Test On

Definite-T 1:Operate &


181:2 No/yes No
flt.rec. blocked

Definite-T 1: Measured Phase-to-phase/phase-


181:9 Phase-to-phase
value to-ground

Definite-T 1:Method of Fundamental Fundamental


181:8
measurement comp/RMS value comp

Definite-T 1:Pickup
181:101 1 out of 3/3 out of 3 1 out of 3
mode

181:3 Definite-T 1: Threshold 0.300V to 340.000V 130V

Definite-T 1: Dropout
181:4 0.90 to 0.99 0.95
ratio

Definite-T 1: Operate
181:6 0.00s to 300.00s 2s
delay

Note: Other functions of 7SJ82 setting Off and used default value.

2.4.3 Undervoltage Protection, Phases

Addr. Parameter Setting Options Setting value Note

Definite-T 1

48
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 49 of 103

421:1 Definite-T 1:Mode Off/On/Test On

Definite-T 1:
421:2 No/yes No
Operate&flt.rec.blocked

Definite-T 1:Blk.bu
421:10 No/yes No
mead.-volt.failure

Definite-T 1: Phase-to-phase/phase-
421:9 Phase-to-phase
Measured value to-ground

Definite-T 1:Method of Fundamental Fundamental


421:8
measurement comp/RMS value comp

Definite-T 1:Pickup
421:101 1 out of 3/3 out of 3 1 out of 3
mode

421:102 Definite-T 1:Pickup delay No/yes No

421:3 Definite-T 1: Threshold 0.300V to 175.000V 45V

Definite-T 1:
421:4 1.01 to 1.20 1.05
Dropout ratio

Definite-T 1:
421:6 0.00s to 60.00s 9s
Operate delay

Note: Other functions of 7SJ82 setting Off and used default value.

49
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 50 of 103

2.5 20BBA10GS401/402/414/415 (Electrical Control room Solar field) Protection Setting

2.5.1 Power-System Data

设备和保护参数 Parameter of equipment and protection

额定电压 额定电流 196.83A


11kV
按三台变压器考虑
Rated voltage Rated current

CT 250/1 零序 CT Zero CT 50/1

综保
7SJ82 PT
Protect device

KKS 10BBA10GS401/GS402/GS414/GS415

2.5.2 Overcurrent Protection, Phases(Definite-Time)(50S)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

661:1 Definite-T 1:Mode Off/On/Test On

Definite-T 1:Operate &


661:2 No/yes No
flt.rec. blocked

Definite-T 1:1-pole
661:11 No/yes No
operate allowed

661:26 Definite-T
661:26 No/yes No
1:Dynamic settings

Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.

Definite-T 1:Method of Fundamental comp. Fundamental


661:8
measurement RMS value comp.

661:3 Definite-T 1:Threshold 0.030 A to 35.000 A 10.8A

Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio

661:102 Definite-T 1:Pickup delay 0.00 s to 60.00 s 0.25s

661:101 Definite-T 1:Dropout 0.00 s to 60.00 s 0.00s


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 51 of 103

delay

Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay

Note: Other functions of 7SJ82 setting Off and used default value.

2.5.3 Overcurrent Protection, Phases(Inverse-Time)(51)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

691:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


691:2 No/yes No
flt.rec. blocked

Inverse-T 1:1-pole
691:11 No/yes No
operate allowed

Inverse-T 1:Dynamic
691:26 No/yes No
settings

Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


691:8
measurement RMS value comp.

691:3 Inverse-T 1:Threshold 0.030 A to 35.000 A 0.98A

691:108 Inverse-T 1:Pickup delay 0.00 s to 60.00 s 0.00s

Inverse-T 1:Type of IEC very


691:130
character. curve Inverse curve

Inverse-T 1:Min. time of


691:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation

691:101 Inverse-T 1:Time dial 0.00 to 15.00 0.9

Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 52 of 103

Note: Other functions of 7SJ82 setting Off and used default value.

2.5.4 Overcurrent Protection, Ground(Inverse-Time)(51N)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

781:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


781:2 No/yes No
flt.rec. blocked

Inverse-T 1:Dynamic
781:26 No/yes No
settings

Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


781:8
measurement RMS value comp.

781:3 Inverse-T 1:Threshold 0.010 A to 35.000 A 1.5A 50/1CT

Inverse-T 1:Type of IEC very


781:108
character. curve Inverse curve

Inverse-T 1:Min. time of


781:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation

781:101 Inverse-T 1:Time dial 0.00 to 15.00 0.16

Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.

2.6 20BBA10GS410/423 (HTF Electrical Building Transformer 1/2) Protection Setting Table

2.6.1 Power-System Data

设备和保护参数 Parameter of equipment and protection

额定容量 额定电压
2500kVA 11kV
Rated capacity Rated voltage of HV
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 53 of 103

额定电压 高压侧额定电流
0.42kV 131.2A
Rated voltage of LV Rated current of HV

低压侧额定电流 短路阻抗
3437A 7.5%
Rated current of LV Impedance

CT 200/1 零序 CT Zero CT 50/1

PT

KKS 10BBA10 GS410/423

综保 Protect device 7SJ82

2.6.2 Overcurrent Protection, Phases(Definite-Time)(50)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

661:1 Definite-T 1:Mode Off/On/Test On

Definite-T 1:Operate &


661:2 No/yes No
flt.rec. blocked

Definite-T 1:1-pole
661:11 No/yes No
operate allowed

661:26 Definite-T
661:26 No/yes No
1:Dynamic settings

Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.

Definite-T 1:Method of Fundamental comp. Fundamental


661:8
measurement RMS value comp.

661:3 Definite-T 1:Threshold 0.030 A to 35.000 A 13.5A

Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio

661:102 Definite-T 1:Pickup delay 0.00 s to 60.00 s 0s


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 54 of 103

Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay

Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay

Note: Other functions of 7SJ82 setting Off and used default value.

2.6.3 Overcurrent Protection, Phases(Inverse-Time)(51)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

691:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


691:2 No/yes No
flt.rec. blocked

Inverse-T 1:1-pole
691:11 No/yes No
operate allowed

Inverse-T 1:Dynamic
691:26 No/yes No
settings

Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


691:8
measurement RMS value comp.

691:3 Inverse-T 1:Threshold 0.030 A to 35.000 A 0.82A

691:108 Inverse-T 1:Pickup delay 0.00 s to 60.00 s 0.00s

Inverse-T 1:Type of IEC very


691:130
character. curve Inverse curve

Inverse-T 1:Min. time of


691:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation

691:101 Inverse-T 1:Time dial 0.00 to 15.00 0.49

691:115 Inverse-T 1:Additional 0.00 s to 60.00 s 0.00s


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 55 of 103

time delay

Note: Other functions of 7SJ82 setting Off and used default value.

2.6.4 Overcurrent Protection, Ground(Inverse-Time)(50N)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

781:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


781:2 No/yes No
flt.rec. blocked

Inverse-T 1:Dynamic
781:26 No/yes No
settings

Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


781:8
measurement RMS value comp.

781:3 Inverse-T 1:Threshold 0.010 A to 35.000 A 1.2A 50/1CT

Inverse-T 1:Type of IEC very


781:108
character. curve Inverse curve

Inverse-T 1:Min. time of


781:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation

781:101 Inverse-T 1:Time dial 0.00 to 15.00 0.05

Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 56 of 103

2.7 20BBA10GS403/416 (TES Electrical Building) Protection Setting Table

2.7.1 Power-System Data

设备和保护参数 Parameter of equipment and protection

额定电压 额定电流 630A


11kV
按开关最大额定电流
Rated voltage Rated current

CT 750/1 零序 CT Zero CT 50/1

综保
7SJ82 PT
Protect device

KKS 10BBA10 GS403/GS416

2.7.2 Overcurrent Protection, Phases(Definite-Time)(50S)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

661:1 Definite-T 1:Mode Off/On/Test On

Definite-T 1:Operate &


661:2 No/yes No
flt.rec. blocked

Definite-T 1:1-pole
661:11 No/yes No
operate allowed

661:26 Definite-T
661:26 No/yes No
1:Dynamic settings

Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.

Definite-T 1:Method of Fundamental comp. Fundamental


661:8
measurement RMS value comp.

661:3 Definite-T 1:Threshold 0.030 A to 35.000 A 8.8A

Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio

661:102 Definite-T 1:Pickup delay 0.00 s to 60.00 s 0.25s

661:101 Definite-T 1:Dropout 0.00 s to 60.00 s 0.00s


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 57 of 103

delay

Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay

Note: Other functions of 7SJ82 setting Off and used default value.

2.7.3 Overcurrent Protection, Phases(Inverse-Time)(51)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

691:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


691:2 No/yes No
flt.rec. blocked

Inverse-T 1:1-pole
691:11 No/yes No
operate allowed

Inverse-T 1:Dynamic
691:26 No/yes No
settings

Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


691:8
measurement RMS value comp.

691:3 Inverse-T 1:Threshold 0.030 A to 35.000 A 1.05A

691:108 Inverse-T 1:Pickup delay 0.00 s to 60.00 s 0.00s

Inverse-T 1:Type of IEC very


691:130
character. curve Inverse curve

Inverse-T 1:Min. time of


691:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation

691:101 Inverse-T 1:Time dial 0.00 to 15.00 0.4

Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 58 of 103

Note: Other functions of 7SJ82 setting Off and used default value.

2.7.4 Overcurrent Protection, Ground(Inverse-Time)(51N)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

781:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


781:2 No/yes No
flt.rec. blocked

Inverse-T 1:Dynamic
781:26 No/yes No
settings

Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


781:8
measurement RMS value comp.

781:3 Inverse-T 1:Threshold 0.010 A to 35.000 A 1.5A 50/1CT

Inverse-T 1:Type of IEC very


781:108
character. curve Inverse curve

Inverse-T 1:Min. time of


781:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation

781:101 Inverse-T 1:Time dial 0.00 to 15.00 0.16

Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 59 of 103

2.8 20BBA10GS404/405/406/407/417/418/419/420 (HTF Main Pumps-Far Group

19/18/17/16/23/22/21/20) Protection Setting Table

2.8.1 Power-System Data

电机及保护参数 Motor and protection

额定功率( ) 额定电压( )
2900kW 11kV
Rated power( ) Rated voltage( )

额定电流( ) 堵转电流( )
180A 650%
Rated current( ) Lock rotor current( )

启动时间
30s(hold) PT
Starting time

相间 Phase to phase: 250/1


CT
零序 CT Zero sequence CT: 50/1

KKS 10BBA10GS404/405/406/407/417/418/419/420

保护装置
7SJ82
Protect device

2.8.2 Overcurrent Protection, Phases(Definite-Time)(50)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

661:1 Definite-T 1:Mode Off/On/Test On

Definite-T 1:Operate &


661:2 No/yes No
flt.rec. blocked

Definite-T 1:1-pole
661:11 No/yes No
operate allowed

661:26 Definite-T
661:26 No/yes No
1:Dynamic settings

661:27 Definite-T 1:Blk. w. No/yes No


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 60 of 103

inrush curr. detect.

Definite-T 1:Method of Fundamental comp. Fundamental


661:8
measurement RMS value comp.

661:3 Definite-T 1:Threshold 0.030 A to 35.000 A 7.72A

Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio

661:102 Definite-T 1:Pickup delay 0.00 s to 60.00 s 0s

Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay

Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay

Note: Other functions of 7SJ82 setting Off and used default value.

2.8.3 Overcurrent Protection, Phases(Inverse-Time)(51)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

691:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


691:2 No/yes No
flt.rec. blocked

Inverse-T 1:1-pole
691:11 No/yes No
operate allowed

Inverse-T 1:Dynamic
691:26 No/yes No
settings

Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


691:8
measurement RMS value comp.

691:3 Inverse-T 1:Threshold 0.030 A to 35.000 A 0.9A

691:108 Inverse-T 1:Pickup delay 0.00 s to 60.00 s 0.00s

691:130 Inverse-T 1:Type of IEC long time


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 61 of 103

character. curve Inverse curve

Inverse-T 1:Min. time of


691:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation

691:101 Inverse-T 1:Time dial 0.00 to 15.00 0.8

Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.

2.8.4 Overcurrent Protection, Ground(Inverse-Time)(50N)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

781:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


781:2 No/yes No
flt.rec. blocked

Inverse-T 1:Dynamic
781:26 No/yes No
settings

Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


781:8
measurement RMS value comp.

781:3 Inverse-T 1:Threshold 0.010 A to 35.000 A 1.2A 50/1CT

Inverse-T 1:Type of IEC very


781:108
character. curve Inverse curve

Inverse-T 1:Min. time of


781:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation

781:101 Inverse-T 1:Time dial 0.00 to 15.00 0.05


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 62 of 103

Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 63 of 103

2.9 20BBA10GS408/409/421/422 (HTF Main Pumps-Near Group 03/02/05/04) Protection

Setting

2.9.1 Power-System Data

电机及保护参数 Motor and protection

额定功率( ) 额定电压( )
2700kW 11kV
Rated power( ) Rated voltage( )

额定电流( ) 堵转电流( )
167A 650%
Rated current( ) Lock rotor current( )

启动时间
30s(hold) PT
Starting time

相间 Phase to phase: 250/1


CT
零序 CT Zero sequence CT: 50/1

KKS 10BBA10 GS408/GS409/GS421/GS422

保护装置
7SJ82
Protect device

2.9.2 Overcurrent Protection, Phases(Definite-Time)(50)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

661:1 Definite-T 1:Mode Off/On/Test On

Definite-T 1:Operate &


661:2 No/yes No
flt.rec. blocked

Definite-T 1:1-pole
661:11 No/yes No
operate allowed

661:26 Definite-T
661:26 No/yes No
1:Dynamic settings

661:27 Definite-T 1:Blk. w. No/yes No


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 64 of 103

inrush curr. detect.

Definite-T 1:Method of Fundamental comp. Fundamental


661:8
measurement RMS value comp.

661:3 Definite-T 1:Threshold 0.030 A to 35.000 A 7.16A

Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio

661:102 Definite-T 1:Pickup delay 0.00 s to 60.00 s 0s

Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay

Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay

Note: Other functions of 7SJ82 setting Off and used default value.

2.9.3 Overcurrent Protection, Phases(Inverse-Time)(51)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

691:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


691:2 No/yes No
flt.rec. blocked

Inverse-T 1:1-pole
691:11 No/yes No
operate allowed

Inverse-T 1:Dynamic
691:26 No/yes No
settings

Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


691:8
measurement RMS value comp.

691:3 Inverse-T 1:Threshold 0.030 A to 35.000 A 0.84A

691:108 Inverse-T 1:Pickup delay 0.00 s to 60.00 s 0.00s

691:130 Inverse-T 1:Type of IEC long time


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 65 of 103

character. curve Inverse curve

Inverse-T 1:Min. time of


691:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation

691:101 Inverse-T 1:Time dial 0.00 to 15.00 0.8

Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.

2.9.4 Overcurrent Protection, Ground(Inverse-Time)(50N)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

781:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


781:2 No/yes No
flt.rec. blocked

Inverse-T 1:Dynamic
781:26 No/yes No
settings

Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


781:8
measurement RMS value comp.

781:3 Inverse-T 1:Threshold 0.010 A to 35.000 A 1.2A 50/1CT

Inverse-T 1:Type of IEC very


781:108
character. curve Inverse curve

Inverse-T 1:Min. time of


781:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation

781:101 Inverse-T 1:Time dial 0.00 to 15.00 0.05


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 66 of 103

Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 67 of 103

2.10 20BBA10GS413 (Intermediate Substation Services) Protection Setting Table

2.11.1 Power-System Data

设备和保护参数 Parameter of equipment and protection

额定电压 额定电流
11kV 33.1A
Rated voltage Rated current

CT 100/1 零序 CT Zero CT 50/1

综保
7SJ82 PT
Protect device

KKS 05BBA10GS101

2.11.2 Overcurrent Protection, Phases(Definite-Time)(50S)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

661:1 Definite-T 1:Mode Off/On/Test On

Definite-T 1:Operate &


661:2 No/yes No
flt.rec. blocked

Definite-T 1:1-pole
661:11 No/yes No
operate allowed

661:26 Definite-T
661:26 No/yes No
1:Dynamic settings

Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.

Definite-T 1:Method of Fundamental comp. Fundamental


661:8
measurement RMS value comp.

661:3 Definite-T 1:Threshold 0.030 A to 35.000 A 14.3A

Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio

661:102 Definite-T 1:Pickup delay 0.00 s to 60.00 s 0.25s

661:101 Definite-T 1:Dropout 0.00 s to 60.00 s 0.00s


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 68 of 103

delay

Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay

Note: Other functions of 7SJ82 setting Off and used default value.

2.11.3 Overcurrent Protection, Phases(Inverse-Time)(51)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

691:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


691:2 No/yes No
flt.rec. blocked

Inverse-T 1:1-pole
691:11 No/yes No
operate allowed

Inverse-T 1:Dynamic
691:26 No/yes No
settings

Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


691:8
measurement RMS value comp.

691:3 Inverse-T 1:Threshold 0.030 A to 35.000 A 4.9A

691:108 Inverse-T 1:Pickup delay 0.00 s to 60.00 s 0.00s

Inverse-T 1:Type of IEC very


691:130
character. curve Inverse curve

Inverse-T 1:Min. time of


691:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation

691:101 Inverse-T 1:Time dial 0.00 to 15.00 0.43

Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 69 of 103

Note: Other functions of 7SJ82 setting Off and used default value.

2.11.4 Overcurrent Protection, Ground(Inverse-Time)(51N)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

781:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


781:2 No/yes No
flt.rec. blocked

Inverse-T 1:Dynamic
781:26 No/yes No
settings

Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


781:8
measurement RMS value comp.

781:3 Inverse-T 1:Threshold 0.010 A to 35.000 A 1.8A 50/1CT

Inverse-T 1:Type of IEC very


781:108
character. curve Inverse curve

Inverse-T 1:Min. time of


781:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation

781:101 Inverse-T 1:Time dial 0.00 to 15.00 0.1

Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 70 of 103

3. 13BBA10/13BBA20 11kV MV switch-gear Protection Setting

3.1 13BBA10/20GS101 (incoming) Protection Setting

3.1.1 Power-System Data

设备和保护参数 Parameter of equipment and protection

额定电压 额定电流 630A


11kV
按开关最大额定电流
Rated voltage Rated current

CT 750/1 零序 CT Zero CT -

综保
7SJ82 PT
Protect device

KKS 13BBA10 GS101/13BBA20 GS101

3.1.2 Overcurrent Protection, Phases(Definite-Time)(50S)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

661:1 Definite-T 1:Mode Off/On/Test On

Definite-T 1:Operate &


661:2 No/yes No
flt.rec. blocked

Definite-T 1:1-pole
661:11 No/yes No
operate allowed

661:26 Definite-T
661:26 No/yes No
1:Dynamic settings

Definite-T 1:Blk. w.
661:27 No/yes No
inrush curr. detect.

Definite-T 1:Method of Fundamental comp. Fundamental


661:8
measurement RMS value comp.

661:3 Definite-T 1:Threshold 0.030 A to 35.000 A 4.4A

Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 71 of 103

661:102 Definite-T 1:Pickup delay 0.00 s to 60.00 s 0.25s

Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay

Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay

Note: Other functions of 7SJ82 setting Off and used default value.

3.1.3 Overcurrent Protection, Phases(Inverse-Time)(51)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

691:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


691:2 No/yes No
flt.rec. blocked

Inverse-T 1:1-pole
691:11 No/yes No
operate allowed

Inverse-T 1:Dynamic
691:26 No/yes No
settings

Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


691:8
measurement RMS value comp.

691:3 Inverse-T 1:Threshold 0.030 A to 35.000 A 1.05A

691:108 Inverse-T 1:Pickup delay 0.00 s to 60.00 s 0.00s

Inverse-T 1:Type of IEC very


691:130
character. curve Inverse curve

Inverse-T 1:Min. time of


691:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation

691:101 Inverse-T 1:Time dial 0.00 to 15.00 0.3


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 72 of 103

Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.

3.1.4 Overcurrent Protection, Ground(Inverse-Time)(51N)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

781:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


781:2 No/yes No
flt.rec. blocked

Inverse-T 1:Dynamic
781:26 No/yes No
settings

Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


781:8
measurement RMS value comp.

750/1
781:3 Inverse-T 1:Threshold 0.010 A to 35.000 A 0.1A
CT

Inverse-T 1:Type of IEC very


781:108
character. curve Inverse curve

Inverse-T 1:Min. time of


781:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation

781:101 Inverse-T 1:Time dial 0.00 to 15.00 0.1

Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.

3.1.5 Overvoltage Protection (Definite-Time)(59)


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 73 of 103

Addr. Parameter Setting Options Setting value Note

Definite-T 1

181:1 Definite-T 1:Mode Off/On/Test On

Definite-T 1:Operate &


181:2 No/yes No
flt.rec. blocked

Definite-T 1: Measured Phase-to-phase/phase-


181:9 Phase-to-phase
value to-ground

Definite-T 1:Method of Fundamental Fundamental


181:8
measurement comp/RMS value comp

Definite-T 1:Pickup
181:101 1 out of 3/3 out of 3 1 out of 3
mode

181:3 Definite-T 1: Threshold 0.300V to 340.000V 130V

Definite-T 1: Dropout
181:4 0.90 to 0.99 0.95
ratio

Definite-T 1: Operate
181:6 0.00s to 300.00s 2s
delay

Note: Other functions of 7SJ82 setting Off and used default value.

3.1.6 Undervoltage Protection (Definite-Time)(27)

Addr. Parameter Setting Options Setting value Note

Definite-T 1

421:1 Definite-T 1:Mode Off/On/Test On

Definite-T 1:Operate &


421:2 No/yes No
flt.rec. blocked

Definite-T 1:Blk.by
421:10 No/yes yes
meas. -volt. failure

Definite-T 1: Measured Phase-to-phase/phase-


421:9 Phase-to-phase
value to-ground

Definite-T 1:Method of Fundamental Fundamental


421:8
measurement comp/RMS value comp

Definite-T 1:Pickup
421:101 1 out of 3/3 out of 3 1 out of 3
mode
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 74 of 103

421:102 Definite-T 1:Pickup delay No/yes No

421:3 Definite-T 1: Threshold 0.300V to 175.000V 45V

Definite-T 1: Dropout
421:4 1.01 to 1.20 1.05
ratio

Definite-T 1:Operate
421:6 0.00s to 60.00s 9s
delay

Note: Other functions of 7SJ82 setting Off and used default value.
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 75 of 103

3.2 13BBA10/20 GS401/402 (TES MV/LV TRANSFORMER 1/2) Protection Setting

3.2.1 Power-System Data

设备和保护参数 Parameter of equipment and protection

额定容量 额定电压
2500kVA 11kV
Rated capacity Rated voltage of HV

额定电压 高压侧额定电流
0.42kV 131.2A
Rated voltage of LV Rated current of HV

低压侧额定电流 短路阻抗
3437A 13%
Rated current of LV Impedance

CT 200/1 零序 CT Zero CT 50/1

PT

13BBA10GS401/GS402
KKS
13BBA20GS401/GS402

综保 Protect device 7SJ82

注:请现场核实 CT 是否为 300/1

3.2.2 Overcurrent Protection, Phases(Definite-Time)(50)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

661:1 Definite-T 1:Mode Off/On/Test On

Definite-T 1:Operate &


661:2 No/yes No
flt.rec. blocked

Definite-T 1:1-pole
661:11 No/yes No
operate allowed

661:26 Definite-T
661:26 No/yes No
1:Dynamic settings

661:27 Definite-T 1:Blk. w. No/yes No


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 76 of 103

inrush curr. detect.

Definite-T 1:Method of Fundamental comp. Fundamental


661:8
measurement RMS value comp.

661:3 Definite-T 1:Threshold 0.030 A to 35.000 A 8.25A

Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio

661:102 Definite-T 1:Pickup delay 0.00 s to 60.00 s 0s

Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay

Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay

Note: Other functions of 7SJ82 setting Off and used default value.

3.2.3 Overcurrent Protection, Phases(Inverse-Time)(51)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

691:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


691:2 No/yes No
flt.rec. blocked

Inverse-T 1:1-pole
691:11 No/yes No
operate allowed

Inverse-T 1:Dynamic
691:26 No/yes No
settings

Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


691:8
measurement RMS value comp.

691:3 Inverse-T 1:Threshold 0.030 A to 35.000 A 0.82A

691:108 Inverse-T 1:Pickup delay 0.00 s to 60.00 s 0.00s

691:130 Inverse-T 1:Type of IEC very


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 77 of 103

character. curve Inverse curve

Inverse-T 1:Min. time of


691:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation

691:101 Inverse-T 1:Time dial 0.00 to 15.00 0.3

Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.

3.2.4 Overcurrent Protection, Ground(Inverse-Time)(50N)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

781:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


781:2 No/yes No
flt.rec. blocked

Inverse-T 1:Dynamic
781:26 No/yes No
settings

Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


781:8
measurement RMS value comp.

781:3 Inverse-T 1:Threshold 0.010 A to 35.000 A 1.2A 50/1CT

Inverse-T 1:Type of IEC very


781:108
character. curve Inverse curve

Inverse-T 1:Min. time of


781:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
781:109 Inverse-T 1:Reset Disk emulation
Disk emulation

781:101 Inverse-T 1:Time dial 0.00 to 15.00 0.05


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 78 of 103

Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 79 of 103

3.3 13BBA10/20 GS403/404/405/406/407/408 (COLD and HOT SALT PUMP VSD) Protection

Setting

3.3.1 电机及保护参数 Motor and protection

电机及保护参数 Motor and protection

额定功率( ) 额定电压( )
1400kW 11kV
Rated power( ) Rated voltage( )

额定电流( ) 堵转电流( )
85A 650%
Rated current( ) Lock rotor current( )

启动时间
30s(hold) PT
Starting time

相间 Phase to phase: 100/1


CT
零序 CT Zero sequence CT: 50/1

保护装置
7SJ82
Protect device

3.3.2 Overcurrent Protection, Phases(Definite-Time)(50)

Stage with Definite-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

661:1 Definite-T 1:Mode Off/On/Test On

Definite-T 1:Operate &


661:2 No/yes No
flt.rec. blocked

Definite-T 1:1-pole
661:11 No/yes No
operate allowed

661:26 Definite-T
661:26 No/yes No
1:Dynamic settings

661:27 Definite-T 1:Blk. w. No/yes No


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 80 of 103

inrush curr. detect.

Definite-T 1:Method of Fundamental comp. Fundamental


661:8
measurement RMS value comp.

661:3 Definite-T 1:Threshold 0.030 A to 35.000 A 9.12A

Definite-T 1:Dropout
661:4 0.90 to 0.99 0.95
ratio

661:102 Definite-T 1:Pickup delay 0.00 s to 60.00 s 0s

Definite-T 1:Dropout
661:101 0.00 s to 60.00 s 0.00s
delay

Definite-T 1:Operate
661:6 0.00 s to 100.00 s 0.00s
delay

Note: Other functions of 7SJ82 setting Off and used default value.

3.3.3 Overcurrent Protection, Phases(Inverse-Time)(51)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

691:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


691:2 No/yes No
flt.rec. blocked

Inverse-T 1:1-pole
691:11 No/yes No
operate allowed

Inverse-T 1:Dynamic
691:26 No/yes No
settings

Inverse-T 1:Blk. w.
691:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


691:8
measurement RMS value comp.

691:3 Inverse-T 1:Threshold 0.030 A to 35.000 A 1.06A

691:108 Inverse-T 1:Pickup delay 0.00 s to 60.00 s 0.00s


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 81 of 103

Inverse-T 1:Type of IEC long time


691:130
character. curve Inverse curve

Inverse-T 1:Min. time of


691:113 0.00 s to 1.00 s 0.00s
the curve

Instantaneous
691:131 Inverse-T 1:Reset Disk emulation
Disk emulation

691:101 Inverse-T 1:Time dial 0.00 to 15.00 0.8

Inverse-T 1:Additional
691:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.

3.3.4 Overcurrent Protection, Ground(Inverse-Time)(50N)

Stage with Inverse-Time Characteristic Curve

Addr. Parameter Setting Options Setting value Note

General

781:1 Inverse-T 1:Mode Off/On/Test On

Inverse-T 1:Operate &


781:2 No/yes No
flt.rec. blocked

Inverse-T 1:Dynamic
781:26 No/yes No
settings

Inverse-T 1:Blk. w.
781:27 No/yes No
inrush curr. detect.

Inverse-T 1:Method of Fundamental comp. Fundamental


781:8
measurement RMS value comp.

781:3 Inverse-T 1:Threshold 0.010 A to 35.000 A 1.2A 50/1CT

Inverse-T 1:Type of IEC very


781:108
character. curve Inverse curve

Inverse-T 1:Min. time of


781:113 0.00 s to 1.00 s 0.00s
the curve

781:109 Inverse-T 1:Reset Instantaneous Disk emulation


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 82 of 103

Disk emulation

781:101 Inverse-T 1:Time dial 0.00 to 15.00 0.05

Inverse-T 1:Additional
781:115 0.00 s to 60.00 s 0.00s
time delay

Note: Other functions of 7SJ82 setting Off and used default value.
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 83 of 103

4. 11BBA10/20/30/40/50/60 11kV MV switch-gear Protection Calculation

4.1 11BBA10/40GS001 、 11BBA1030/60GS002 (Electrical Control room Solar field)

Protection Setting

4.4.1 Power-System Data

设备和保护参数 Parameter of equipment and protection

额定电压 额定电流 196.83A


11kV
按三台变压器考虑
Rated voltage Rated current

CT 200/1 零序 CT Zero CT -/1

综保
P143 PT
Protect device

KKS 11BBA10/40GS001、11BBA1030/60GS002

4.4.2 Overcurrent Protection, Phases(Definite-Time)(50S)

DESCR
MENU TEXT COL ROW SETTING AVAILABLE OPTIONS
IPTION

0 = Disabled, 1 =
I>3 Status
35 40 Enabled Enabled

0 = Non-Directional, 1

Non- = Directional Fwd, 2 =


I﹥3 Direction 35 41
Directional Directional Rev

From 0.08*In to 32.0*In


I﹥3 Current Set 35 44 13.5
step 0.01In

From 0s to 100s step

I﹥3 Time Delay 35 45 0.25 0.01s

4.4.3 Overcurrent Protection, Phases(Inverse-Time)(51)


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 84 of 103

DESCR
MENU TEXT COL ROW SETTING AVAILABLE OPTIONS
IPTION

Disabled

DT

IEC S Inverse

IEC V Inverse

IEC E Inverse

UK LT Inverse

UK Rectifier

RI
IEC V
IEEE M Inverse
I﹥2 Function 35 32 Inverse
IEEE V Inverse

IEEE E Inverse

US Inverse

US ST Inverse

Def User Curve1

Def User Curve2

Def User Curve3

Def User Curve4

[Indexed String]

Non- Non-Directional

I﹥2 Direction 35 33 Directiona [Indexed String]

From 0.05** Expression is faulty

**I1 to 4.0** Expression is faulty

I﹥2 Current Set 35 36 1.23 **I1 in steps of 0.01** Expression

is faulty **I1

[CourierNumber(current)]

From 0 to 100 in steps of 0.01


I﹥2 Time Delay 35 38 0
[Courier Number(time-seconds)]
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 85 of 103

From 0.025 to 1.2 in steps of

I﹥2 TMS 35 39 0.9 0.005

[Courier Number(decimal)]

From 0.01 to 100 in steps of

I﹥2 Time Dial 35 3A 0.9 0.01

[Courier Number(decimal)]

From 0.1 to 10 in steps of 0.05


I﹥2 k(RI) 35 3B 1
[Courier Number(decimal)]

From 0 to 100 in steps of 0.01


I﹥2 DT Adder 35 3C 0
[Courier Number(time-seconds)]

DT

I﹥2 Reset Char 35 3D DT Inverse

[Indexed String]

From 0 to 100 in steps of 0.01


I﹥2 tRESET 35 3E 0
[Courier Number(time-seconds)]

DT

Def User Curve 1

Def User Curve 2


I﹥2 Usr Rst Char 35 3F DT
Def User Curve 3

Def User Curve 4

[Indexed String]

4.4.4 Overcurrent Protection, Ground(Inverse-Time)(51N)

DESCR
MENU TEXT COL ROW SETTING AVAILABLE OPTIONS
IPTION

Derived
GROUP1:EARTH
39 00 Earth
FAULT2
Fault

IN2﹥Input 39 01 Derived Measured

Derived
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 86 of 103

[Indexed String]

Disabled

DT

IEC S Inverse

IEC V Inverse

IEC E Inverse

UK LT Inverse

RI

IEC M Inverse

IEC V Inverse
IN2﹥1 Function 39 25 IEC V Inverse
IEC E Inverse

US Inverse

US ST Inverse

IDG

Def User Curve 1

Def User Curve 2

Def User Curve 3

Def User Curve 4

[Indexed String]

Non- Non-Directional
IN2﹥1 Direction 39 26
Directional [Indexed String]

From 0.05 to 4 in steps

of 0.01
IN2﹥1 Current 39 29 0.38
[Courier

Number(current)]

From 1 to 4 in steps of

0.1
IN2﹥1 IDG Is 39 2A 1
[Courier

Number(decimal)]

IN2﹥1 Time Delay 39 2C 0 From 0 to 200 in steps


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 87 of 103

of 0.01

[Courier Number(time-

seconds)]

From 0.025 to 1.2 in

steps of 0.005
IN2﹥1 TMS 39 2D 0.16
[Courier

Number(decimal)]

From 0.01 to 100 in

steps of 0.01
IN2﹥1 Time Dial 39 2E 0.16
[Courier

Number(decimal)]

From 0.1 to 10 in steps

of 0.05
IN2﹥1 k(RI) 39 2F 1
[Courier

Number(decimal)]

From 1 to 2 in steps of

0.01
IN2﹥1 IDG Time 39 30 1
[Courier Number(time-

seconds)]

From 0 to100 in steps

of 0.01
IN2﹥1 DT Adder 39 31 0
[Courier Number(time-

seconds)]

DT

IN2﹥1 Reset Char 39 32 DT Inverse

[Indexed String]

IN2﹥1 tRESET 39 33 0 From 0 to100 in steps

of 0.01

[Courier Number(time-
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 88 of 103

seconds)]

DT

Def User Curve 1

Def User Curve 2


IN2﹥1 Usr RstChr 39 34 DT
Def User Curve 3

Def User Curve 4

[Indexed String]
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 89 of 103

4.2 11BBA10/20/40 /50GS002 、 11BBA20/30/50/60GS001(Electrical Control room Solar

field) Protection Setting

4.2.1 Power-System Data

Parameter of equipment and protection

11kV 131.22A
Rated voltage Rated current

CT 200/1 CT Zero CT 50/1

Protect device P143 PT

KKS 11BBA10/20/40 /50GS002、11BBA20/30/50/60GS001

4.2.2 Overcurrent Protection, Phases(Definite-Time)(50S)

DESCR
MENU TEXT COL ROW SETTING AVAILABLE OPTIONS
IPTION

0 = Disabled, 1 =
I>3 Status
35 40 Enabled Enabled

0 = Non-Directional, 1

Non- = Directional Fwd, 2 =


I﹥3 Direction 35 41
Directional Directional Rev

From 0.08*In to 32.0*In


I﹥3 Current Set 35 44 13.5
step 0.01In

From 0s to 100s step

I﹥3 Time Delay 35 45 0.25 0.01s

4.2.3 Overcurrent Protection, Phases(Inverse-Time)(51)

DESCR
MENU TEXT COL ROW SETTING AVAILABLE OPTIONS
IPTION
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 90 of 103

Disabled

DT

IEC S Inverse

IEC V Inverse

IEC E Inverse

UK LT Inverse

UK Rectifier

RI
IEC V
IEEE M Inverse
I﹥2 Function 35 32 Inverse
IEEE V Inverse

IEEE E Inverse

US Inverse

US ST Inverse

Def User Curve1

Def User Curve2

Def User Curve3

Def User Curve4

[Indexed String]

Non- Non-Directional

I﹥2 Direction 35 33 Directiona [Indexed String]

From 0.05** Expression is faulty

**I1 to 4.0** Expression is faulty

I﹥2 Current Set 35 36 0.82 **I1 in steps of 0.01** Expression

is faulty **I1

[CourierNumber(current)]

From 0 to 100 in steps of 0.01


I﹥2 Time Delay 35 38 0
[Courier Number(time-seconds)]

I﹥2 TMS 35 39 0.31 From 0.025 to 1.2 in steps of

0.005
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 91 of 103

[Courier Number(decimal)]

From 0.01 to 100 in steps of

I﹥2 Time Dial 35 3A 0.31 0.01

[Courier Number(decimal)]

From 0.1 to 10 in steps of 0.05


I﹥2 k(RI) 35 3B 1
[Courier Number(decimal)]

From 0 to 100 in steps of 0.01


I﹥2 DT Adder 35 3C 0
[Courier Number(time-seconds)]

DT

I﹥2 Reset Char 35 3D DT Inverse

[Indexed String]

From 0 to 100 in steps of 0.01


I﹥2 tRESET 35 3E 0
[Courier Number(time-seconds)]

DT

Def User Curve 1

Def User Curve 2


I﹥2 Usr Rst Char 35 3F DT
Def User Curve 3

Def User Curve 4

[Indexed String]

4.3 11BBA10/20/30/40/50/60GT003 ( 11BFT10/20/30/40/50/60 ) (Electrical Control room

Solar field) Protection Setting

4.3.1 Power-System Data

Parameter of equipment and protection

Rated capacity 1250kVA Rated voltage of HV 11kV

Rated voltage of LV 0.42kV Rated current of HV 65.61A

Rated current of LV 1718A Impedance 6%

CT 200/1 Zero CT 50/1

PT
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 92 of 103

KKS 11BBA10/20/30/40/50/60GT003

Protect device P143

4.3.2 Overcurrent Protection, Phases(Definite-Time)(50S)

DESCR
MENU TEXT COL ROW SETTING AVAILABLE OPTIONS
IPTION

0 = Disabled, 1 =
I>3 Status
35 40 Enabled Enabled

0 = Non-Directional, 1

Non- = Directional Fwd, 2 =


I﹥3 Direction 35 41
Directional Directional Rev

From 0.08*In to 32.0*In


I﹥3 Current Set 35 44 9
step 0.01In

From 0s to 100s step

I﹥3 Time Delay 35 45 0 0.01s

4.3.3 Overcurrent Protection, Phases(Inverse-Time)(51)

DESCR
MENU TEXT COL ROW SETTING AVAILABLE OPTIONS
IPTION

I﹥2 Function 35 32 IEC V Disabled

Inverse DT

IEC S Inverse

IEC V Inverse

IEC E Inverse

UK LT Inverse

UK Rectifier

RI
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 93 of 103

IEEE M Inverse

IEEE V Inverse

IEEE E Inverse

US Inverse

US ST Inverse

Def User Curve1

Def User Curve2

Def User Curve3

Def User Curve4

[Indexed String]

Non- Non-Directional

I﹥2 Direction 35 33 Directiona [Indexed String]

From 0.05** Expression is faulty

**I1 to 4.0** Expression is faulty

I﹥2 Current Set 35 36 0.41 **I1 in steps of 0.01** Expression

is faulty **I1

[CourierNumber(current)]

From 0 to 100 in steps of 0.01


I﹥2 Time Delay 35 38 0
[Courier Number(time-seconds)]

From 0.025 to 1.2 in steps of

I﹥2 TMS 35 39 0.4 0.005

[Courier Number(decimal)]

From 0.01 to 100 in steps of

I﹥2 Time Dial 35 3A 0.4 0.01

[Courier Number(decimal)]

From 0.1 to 10 in steps of 0.05


I﹥2 k(RI) 35 3B 1
[Courier Number(decimal)]

From 0 to 100 in steps of 0.01


I﹥2 DT Adder 35 3C 0
[Courier Number(time-seconds)]
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 94 of 103

DT

I﹥2 Reset Char 35 3D DT Inverse

[Indexed String]

From 0 to 100 in steps of 0.01


I﹥2 tRESET 35 3E 0
[Courier Number(time-seconds)]

DT

Def User Curve 1

Def User Curve 2


I﹥2 Usr Rst Char 35 3F DT
Def User Curve 3

Def User Curve 4

[Indexed String]

4.3.4 Overcurrent Protection, Ground(Inverse-Time)(51N)

DESCR
MENU TEXT COL ROW SETTING AVAILABLE OPTIONS
IPTION

GROUP 1
38 00
EARTH FAULT 1

IN1> Input 38 01 Measured Not Settable

IN1﹥1 Function 38 25 IEC V Inverse Disabled

DT

IEC S Inverse

IEC V Inverse

IEC E Inverse

UK LT Inverse

RI

IEC M Inverse

IEC V Inverse

IEC E Inverse

US Inverse

US ST Inverse

IDG
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 95 of 103

Def User Curve 1

Def User Curve 2

Def User Curve 3

Def User Curve 4

[Indexed String]

Non- Non-Directional
IN1﹥1 Direction 38 26
Directional [Indexed String]

From 0.05 to 4 in steps

of 0.01
IN1﹥1 Current 38 29 0.38
[Courier

Number(current)]

From 1 to 4 in steps of

0.1
IN1﹥1 IDG Is 38 2A 1
[Courier

Number(decimal)]

From 0 to 200 in steps

of 0.01
IN1﹥1 Time Delay 38 2C 0
[Courier Number(time-

seconds)]

From 0.025 to 1.2 in

steps of 0.005
IN1﹥1 TMS 38 2D 0.16
[Courier

Number(decimal)]

From 0.01 to 100 in

steps of 0.01
IN1﹥1 Time Dial 38 2E 0.16
[Courier

Number(decimal)]

IN1﹥1 k(RI) 38 2F 1 From 0.1 to 10 in steps

of 0.05

[Courier
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 96 of 103

Number(decimal)]

From 1 to 2 in steps of

0.01
IN1﹥1 IDG Time 38 30 1
[Courier Number(time-

seconds)]

From 0 to100 in steps

of 0.01
IN1﹥1 DT Adder 38 31 0
[Courier Number(time-

seconds)]

DT

IN1﹥1 Reset Char 38 32 DT Inverse

[Indexed String]

From 0 to100 in steps

of 0.01
IN1﹥1 tRESET 38 33 0
[Courier Number(time-

seconds)]

DT

Def User Curve 1

Def User Curve 2


IN1﹥1 Usr RstChr 38 34 DT
Def User Curve 3

Def User Curve 4

[Indexed String]
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 97 of 103

4.4 11BBA10/20/30/40/50/60GS000 (Electrical Control room Solar field) Protection Setting

4.4.1 Power-System Data

Parameter of equipment and protection

Rated voltage 11kV PT

Protect device P141 KKS 11BBA10/20/30/40/50/60 GS000

4.4.2 Voltage Protection

DESCR
MENU TEXT COL ROW SETTING AVAILABLE OPTIONS
IPTION

GROUP 1
42 00
VOLT PROTECTION

0=Phase-Phase
V< Measur't Mode 42 02 Phase-Phase
1=Phase-Neutral

0=Any Phase
V< Operate Mode 42 03 Any Phase
1=Three Phase

0=Disabled

V<1 Function 42 04 DT 1=DT

2=IDMT

From 10*V1 to 120*V1


V<1 Voltage Set 42 05 45V
step 1*V1

From 0s to 100s step


V<1 Time Delay 42 06 10s Alarm
0.01s

0 = Disabled or 1 =
V<1 Poledead Inh 42 08 Enabled
Enabled

0 = Disabled or 1 =
V<2 Status 42 09 Disabled
Enabled

OVERVOLTAGE

0=Phase-Phase
V> Measur't Mode 42 0E Phase-Phase
1=Phase-Neutral

V> Operate Mode 42 0F Any Phase 0=Any Phase


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 98 of 103

1=Three Phase

0=Disabled
V>1 Function 42 10 DT
1=DT 2=IDMT

From 40*V1 to 185*V1


V>1 Voltage Set 42 11 130V
step 1*V1

From 0s to 100s step


V>1 Time Delay 42 12 2s Alarm
0.01s

0 = Disabled or 1 =
V>2 Status 42 14 Disabled
Enabled

4.4.3 Residual Overvoltage

DESCR
MENU TEXT COL ROW SETTING AVAILABLE OPTIONS
IPTION

GROUP 1
3B 00
RESIDUAL O/V NVD

Derived Not Settable


VN Input 3B 01
Measured

0 = Disabled, 1 = DT or
VN>1 Function 3B 02 DT
2 = IDMT

1V to 80V step 1V
VN>1 Voltage Set 3B 03 15V Alarm
4V to 320V step 4V

From 0s to 100s step


VN>1 Time Delay 3B 04 5s Alarm
0.01s

From 0s to 100s step


VN>1 tReset 3B 05 0
0.01s

0 = Disabled or 1 =
VN>2 Status 3B 06 Disabled
Enabled
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 99 of 103

5. 15BBT10 PAT protection setting table(7UT85)

厂光伏变压器及保护参数
Parameters of PAT and protection

额定容量( ) 高压侧额定电压( )
40MVA 33kV

Rated capacity( ) HV rated voltage( )

低压侧额定电压( ) 高压侧额定电流( )
11.3kV 699.8A

LV rated voltage( ) HV rated current( )

低压侧额定电流( ) 短路阻抗
2044A 10%
Impedance
LV rated current( )

高压侧 HV side:1500/1
CT 低压侧 LV side:4000/1

低压中性点 LV neutral line:300/1

高压侧 HV side:
PT

低压侧 LV side:

87LT/50/51
RED-670
保护装置 87TN /51N/24/50BF

Protect device 87T/50(W1)/51(W1)


7UT-85
87TN /51N/24/50BF

6.1.1. PROTECTION SETTING


1.1.1. Transformer differential protection(87T)(HV)
Addr. Parameter C Setting Options Setting

General
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 100 of 103

General:MU-ID Side
_:2311:151 0 to 100 1
1Mp3ph 1

General:MU-ID Side
_:2311:156 0 to 100 2
2Mp3ph 1

General:MU-ID Side
_:2311:160 0 to 100 3
2Mp1ph 1

General:MU-ID Side
_:2311:158 0 to 100 6
2Mp3ph 3

General

off

_:11041:1 I-DIFF:Mode on on

test

I-
no
_:11041:2 DIFF:Operate&flt.rec.block no
yes
ed

_:11041:6 I-DIFF:Operate delay 0.00 s to 60.00 s 0.00 s

Operate curve

_:11041:3 I-DIFF:Threshold 0.05 I/IrObj to 2.00 I/IrObj 0.40 I/IrObj

_:11041:100 I-DIFF:Slope 1 0.00 to 0.80 0.40

_:11041:101 I-DIFF:Intersection 1 Irest 0.00 I/IrObj to 5.00 I/IrObj 1.0 I/IrObj

_:11041:102 I-DIFF:Slope 2 0.25 to 0.95 0.60

_:11041:103 I-DIFF:Intersection 2 Irest 1.00 I/IrObj to 20.00 I/IrObj 3.0 I/IrObj

Starting detection

•no
_:11041:106 I-DIFF:Starting detection yes
•yes

I-DIFF:Thresh. startup
_:11041:107 0.1 I/IrObj to 2.0 I/IrObj 0.2 I/IrObj
detection

I-DIFF:Factor
_:11041:108 1.0 to 5.0 1.0
increasingchar.

_:11041:109 I-DIFF:Max. perm. 0.1 s to 180.0 s 5.0 s


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 101 of 103

Start.time

DC offset detection

I-DIFF:Factor
_:11041:110 1.0 to 5.0 2.3
increasingchar. DC

Inrush blocking

I-DIFF:Blocking with •no


_:11041:115 yes
2.harmonic •yes

I-DIFF:2nd harmonic
_:11041:116 10 % to 45 % 15 %
content

I-DIFF:Crossblock. time
_:11041:117 0.00 s to 200.00 s;∞ 0.11 s
2ndhar.

•no
_:11041:118 I-DIFF:Blocking with CWA no
•yes

Overexcit.blocking

I-DIFF:Blocking with •no


_:11041:121 no
3rdharm. •yes

I-DIFF:3rd
_:11041:122 10 % to 80 % 30 %
harmonicscontent

I-DIFF:Crossblock. time
_:11041:123 0.00 s to 200.00 s;∞ 0.00 s
3rdhar.

I-DIFF:Blocking with •no


_:11041:124 yes
5thharm. •yes

I-DIFF:5th
_:11041:125 10 % to 80 % 25 %
harmonicscontent

I-DIFF:Crossblock. time
_:11041:126 0.00 s to 200.00 s;∞ 0.11 s
5thhar.

I-DIFF:LimitIdiff 3.,
_:11041:127 0.5 I/IrObj to 20.0 I/IrObj 1.5 I/IrObj
5.harmonics

Ext. faultdetection

_:11041:128 I-DIFF:Threshold add- 1.00 I/IrObj to 20.00 I/IrObj 2.00 I/IrObj


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 102 of 103

onstabiliz.

I-DIFF:Time of add-
_:11041:129 0.00 s to 5.00 s;∞ 0.30 s
onstabiliz.

I-DIFF:Cross-blk. time
_:11041:130 0.00 s to 2.00 s;∞ 0.30 s
add-on st.

I-DIFF fast

•off

_:11071:1 I-DIFF fast:Mode •on on

•test

_:11071:3 I-DIFF fast:Threshold 0.5 I/IrObj to 35.0 I/IrObj 10 I/IrObj

_:11071:6 I-DIFF fast:Operate delay 0.00 s to 60.00 s 0.00 s

I-DIFF
•no
_:11071:100 fast:Operate&flt.rec.blocke no
•yes
d

1.1.2. Definite Time Overcurrent Protection(50/51)(HV)

Addr. Parameter C Setting Options Setting

Definite Time Instantaneous Protection

•off

•on

_:661:1 Definite-T 1:Mode •test off

Definite-T •no

_:661:2 1:Operate&flt.rec. blocked •yes no

Definite-T 1:1-pole •no

_:661:11 operate allowed •yes no

Definite- •no

_:661:26 T1:Dynamicsettings •yes no

Definite-T 1:Method •fundamental comp. fundamental

_:661:8 ofmeasurement •RMS value comp.


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 103 of 103

_:661:3 Definite-T 1:Threshold 0.030 A to 35.000 A 35A

_:661:4 Definite-T 1:Dropoutratio 0.90 to 0.99 0.95

_:661:102 Definite-T 1:Pickup delay 0.00 s to 60.00 s 0.00s

_:661:101 Definite-T 1:Dropoutdelay 0.00 s to 60.00 s 0.00 s

_:661:6 Definite-T 1:Operatedelay 0.00 s to 60.00 s 0.00 s

•off

•on

_:662:1 Definite-T 2:Mode •test off

Inverse-T 1

• off

• on

_:691:1 Inverse-T 1:Mode • test on

Inverse-T 1:Operate & • no

_:691:2 flt.rec. blocked • yes no

Inverse-T 1:1-pole • no

_:691:11 operate allowed • yes no

Inverse-T 1:Dynamic • no

_:691:26 settings • yes no

Inverse-T 1:Blk. w. inrush • no

_:691:27 curr. detect. • yes no

Inverse-T 1:Method of • fundamental comp. fundamental

_:691:8 measurement • RMS value comp.

• no

_:691:120 Inverse-T 1:I0 elimination • yes no

_:691:3 Inverse-T 1:Threshold 0.030 A to 35.000 A 0.22A

_:691:108 Inverse-T 1:Pickup delay 0.00 s to 60.00 s 0.00 s

_:691:130 IEV Very


Inverse-T 1:Type of
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 104 of 103

character.curve

Inverse-T 1:Min. time of

_:691:113 the curve 0.00 s to 1.00 s 0.00 s

• instantaneous

_:691:131 Inverse-T 1:Reset • disk emulation disk emulation

_:691:101 Inverse-T 1:Time dial 0.00 to 15.00 0.3

Inverse-T 1:Additional

_:691:115 time delay 0.00 s to 60.00 s 0.00 s

1.1.3. Overexcitation Protection(24T)(HV)


Addr. Parameter C Setting Options Setting

Definite-T 1

off

on

_:13621:1 Definite-T 1:Mode test on

Definite-T 1:Operate&flt.rec. no

_:13621:2 blocked yes no

_:13621:3 Definite-T 1:Threshold 1.00 to 1.40 1.20

_:13621:6 Definite-T 1:Operatedelay 0.00 s to 60.00 s 1.0s

off

on

_:13591:1 Therm.charact.:Mode test ON

Therm.charact.:Operate&flt.re no

_:13591:2 c. blocked yes no

_:13591:3 Therm.charact.:Threshold 1.00 to 1.20 1.05

_:13591:101 Therm.charact.:Warningdelay 0.00 s to 60.00 s 5s

Therm.charact.:Coolingtime

_:13591:102 therm.replica 0 s to 100 000 s 3600 s


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 105 of 103

1.1.4. Restricted Ground-Fault Protection(87N)(LV)


Addr. Parameter C Setting Options Setting

87N REF #

off

_:1 87N REF #:Mode on on

test

87N REF #:Operate no


_:2 no
&flt.rec.blocked yes

_:103 87N REF #:Threshold 0.05 I/IrObjto 2.00 I/IrObj 0.30 I/IrObj

_:105 87N REF #:Slope 0.00 to 0.95 0.5

_:109 87N REF #:Operate delay 0.00 s to 60.00 s; ∞ 0.00 s

1.1.5. Overcurrent Protection, Ground(51N)(LV)


Addr. Parameter C Setting Options Setting

General

•off

•on

_:12691:1 Inverse-T 1:Mode •test on

Inverse-T 1:Operate & • no

_:12691:2 flt.rec. blocked • yes no

Inverse-T 1:Blk. w. inrush • no

_:12691:27 curr. detect. • yes no

Inverse-T 1:Method of • fundamental comp. fundamental

_:12691:8 measurement • RMS value comp.

_:12691:3 Inverse-T 1:Threshold 0.010 A to 35.000 A 0.3

Inverse-T 1:Type of

_:12691:108 character.curve IEC Very

_:12691:109 Inverse-T 1:Reset • instantaneous disk emulation


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 106 of 103

• disk emulation

_:12691:101 Inverse-T 1:Time dial 0.05 to 15.00 0.1

1.1.6. Circuit-Breaker Failure Protection


Addr. Parameter C Setting Options Setting

General

•off

•on

_:1 50BF Ad.CBF #:Mode •test on

50BF Ad.CBF #:Holding • no

_:105 int. start signal • yes yes

• no

50BF Ad.CBF #:Start via • 2 channel

_:107 binary input. • 1 channel no

50BF Ad.CBF #:CB • no

_:103 aux.cont. crit. allowed • w. 'CB pos. closed 3p.' no

• with effective criterion with effective

_:104 50BF Ad.CBF #:Dropout • w. aux.c. and curr.crit. criterion

• no

50BF Ad.CBF #:Retrip • start T2 after T1

_:108 after T1 • parallel start T2, T1 no

50BF Ad.CBF #:Threshold

_:102 phase current 0.030 A to 35.000 A 0.060 A

50BF Ad.CBF #:Threshold

_:101 sensitive 0.030 A to 35.000 A 0.060 A

50BF Ad.CBF #:Delay T1 for

_:109 3-pole retrip 0.000 s to 60.000 s 0.150 s

50BF Ad.CBF #:Delay T2 for

_:110 3-pole trip 0.050 s to 60.000 s 0.250 s

_:112 0.00 s to 60.00 s 0.10 s


50BF Ad.CBF
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 107 of 103

#:Minimum operate time

• Direct release Plausibility

_:120 50BF Ad.CBF #:3I0 criterion • Plausibility check check

• Direct release Plausibility

_:121 50BF Ad.CBF #:I2 criterion • Plausibility check check

50BF Ad.CBF #:Threshold

_:122 3I0 dir. release 0.030 A to 35.000 A 0.100 A

50BF Ad.CBF #:Threshold

_:123 I2 dir. release 0.030 A to 35.000 A 0.100 A


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 108 of 103

6. 15BBT10 PAT protection setting table(RED670)

厂光伏变压器及保护参数
Parameters of PAT and protection

高压侧额定电压(
额定容量( )
40MVA ) 33kV

Rated capacity( )
HV rated voltage( )

低压侧额定电压(
高压侧额定电流( )
) 11.3kV 699.8A

HV rated current( )
LV rated voltage( )

低压侧额定电流( ) 短路阻抗
2044A 10%
Impedance
LV rated current( )

高压侧 HV side:1500/1
CT 低压侧 LV side:4000/1

低压中性点 LV neutral line:300/1

高压侧 HV side:
PT

低压侧 LV side:

87LT/50/51
RED-670
保护装置 87TN /51N/24/50BF

Protect device 87T/50(W1)/51(W1)


7UT-85
87TN /51N/24/50BF

6.1.1. Line differential protection


Name Range Unit Step Setting Note
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 109 of 103

Off
Operation - - On
On

IdMin 0.20 - 2.00 IB 0.01 0.4 IB=2044A

IdMinHigh 0.20 - 10.00 IB 0.01 1.2

tIdMinHigh 0.000 - 60.0 s 0.001 0.1

IdUnre 1.00 - 50.00 IB 0.01 10

Off
NegSeqDiffEn - - Off
On

No
CrossBlockEn - - No
Yes

Off
ChargCurEnable - - Off
On

Off
AddDelay - - Off
On

IMaxAddDelay 0.20 - 5.00 IB 0.01 1.00

tDefTime 0.000 - 6.000 s 0.001 0.000

tMinInv 0.001 - 6.000 s 0.001 0.010

CurveType ANSI Ext. inv. IEC Def.

ANSI Very inv. Time


ANSI Norm. inv.

ANSI Mod. inv.

ANSI Def. Time

L.T.E. inv.

L.T.V. inv.

L.T. inv.

IEC Norm. inv.

IEC Very inv.

IEC inv.

IEC Ext. inv.

IEC S.T. inv.

IEC L.T. inv.


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 110 of 103

IEC Def. Time

Programmable

RI type

RD type

k 0.05 - 1.10 0.01 1.00

IdiffAlarm 0.05 - 1.00 IB 0.01 0.15

tAlarmdelay 0.000 - 60.0 s 0.001 10

EndSection1 0.20 - 1.50 IB 0.01 1

EndSection2 1.00 - 10.00 IB 0.01 3

SlopeSection2 10.0 - 50.0 % 0.1 40.0

SlopeSection3 30.0 - 100.0 % 0.1 60.0

I2/I1Ratio 5.0 - 100.0 % 1.0 15.0

I5/I1Ratio 5.0 - 100.0 % 1.0 25.0

p 0.01 - 1000.00 0.01 0.02

a 0.01 - 1000.00 0.01 0.14

b 0.01 - 1000.00 0.01 1.00

c 0.01 - 1000.00 0.01 1.00

Off
OpenCTEnable On
On

tOCTAlarmDelay 0.100 - 10.000 s 0.001 1.000

tOCTResetDelay 0.100 - 10.000 s 0.001 0.250

Off
OCTBlockEn On
On

LT3CPDIF Non group settings (basic)

Selection of one

of the
GlobalBaseSel 1 - 12 1 1
GlobalBase

Valuegroups

NoOfUsedCTs 2 2 Total number of

3 3-Ph CT sets

connected
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 111 of 103

to diff protection

Off/On for

elimination of
Off
ZerSeqCurSubtr Off zero seq. from
On
diff. and bias

curr

No Transf A Power

1 transformer A
TraAOnInpCh 1
2 applied on input
3 channel X

Transformer A

rated voltage

RatVoltW1TraA 1.0 - 9999.9 kV 0.1 33 (kV) on

winding 1 (HV

winding)

Transformer A

rated voltage
RatVoltW2TraA 1.0 - 9999.9 kV 0.1 11
(kV) on winding

2 (LV winding)

ClockNumTransA 0 [0 deg] 1 [30 deg Transf. A phase

1 [30 deg lag] lag] shift in multiples


2 [60 deg lag] of 30
3 [90 deg lag] deg, 5 for 150
4 [120 deg lag]
deg
5 [150 deg lag]

6 [180 deg lag]

7 [210 deg lag]

8 [240 deg lag]

9 [270 deg lag]

10 [300 deg lag]


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 112 of 103

11 [330 deg lag]

No Transf B Power

1 No Transf transformer B
TraBOnInpCh
2 B applied on input
3 channel X

6.1.1. Instantaneous phase overcurrent protection PHPIOC


Name Range Unit Step Setting Note

Off
Operation - - On IB=4000
On

2 out of 3
OpMode 1 out of 3
1 out of 3

IP>> 5 - 2500 %IB 1 494

6.1.1. Directional phase overcurrent protection, four steps


OC4PTOC
OC4PTOCGroup settings (basic)
Name Values(Range) Unit Step Setting Note

Operation Off/On - - On

AngleRCA 40 - 65 Deg 1 55

AngleROA 40 - 89 Deg 1 80

StartPhSel 1 out of 3 - - 1 out of 3

2 out of 3

3 out of 3

DirMode1 Off - - Non-directional

Non-directional

Forward

Reverse

Characterist1 ANSI Ext. - - IEC Norm

inv./ANSI Very

inv./ANSI Norm.

inv./ANSI Mod.
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 113 of 103

inv./ANSI Def.

Time/L.T.E.

inv./L.T.V. inv./L.T.

inv./IEC Norm.

inv./IEC Very

inv./IEC inv./IEC

Ext. inv./IEC S.T.

inv./IEC L.T.

inv./IEC Def.

Time/Reserved/Pr

ogrammable/RI

type/RD type

I1> 5 - 2500 %IB 1 64 IB=4000A

k1 0.05 - 999.00 - 0.01 0.3

t1 0.000 - 60.000 s 0.001 0.000

IMin1 1 - 10000 %IB 1 10

t1Min 0.000 - 60.000 s 0.001 0.000

I1Mult 1.0 - 10.0 - 0.1 1.0

DirMode2 Off/Non- - - Off

directional/

Forward/Reverse

6.1.1. Directional residual overcurrent protection, four steps


EF4PTOC
OC4PTOCGroup settings (basic)
Name Values(Range) Unit Step Setting Note

DirMode1 Off - - Non-directional

Non-directional

Forward

Reverse
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 114 of 103

Characterist1 ANSI Ext. - - IEC Norm

inv./ANSI Very

inv./ANSI Norm.

inv./ANSI Mod.

inv./ANSI Def.

Time/L.T.E.

inv./L.T.V. inv./L.T.

inv./IEC Norm.

inv./IEC Very

inv./IEC inv./IEC

Ext. inv./IEC S.T.

inv./IEC L.T.

inv./IEC Def.

Time/Reserved/Pr

ogrammable/RI

type/RD type

IN1> 5 - 2500 %IB 1 30 IB=300A

k1 0.05 - 999.00 - 0.01 0.1

t1 0.000 - 60.000 s 0.001 0.000

IMin1 1 - 10000 %IB 1 10

t1Min 0.000 - 60.000 s 0.001 0.000

IN1Mult 1.0 - 10.0 - 0.1 1.0

DirMode2 Off/Non- - - Off

directional/

Forward/Reverse

6.1.1. Breaker failure protection CCRBRF


Name Range Unit Step Setting Note

Operation Off - - On
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 115 of 103

On

Current

FunctionMode Contact - - Current

Current/Contact

LatchedStart

FollowStart
StartMode LatchedStart
FollowStart&Mod

2 out of 4

BuTripMode 1 out of 3 - - 1 out of 3

1 out of 4

Off

RetripMode UseFunctionMode - - UseFunctionM

Always

IP> 5 - 200 %IB 1 10 IB=4000A

IN> 2 - 200 %IB 1 10

t1 0.000 - 60.000 s 0.001 0.15

t2MPh 0.000 - 60.000 s 0.001 0.25

tPulse 0.000 - 60.000 s 0.001 0.25

I>BlkCont 2 - 200 %IB 1 20

t3 0.000 - 60.000 s 0.001 0.030

tCBAlarm 0.000 - 60.000 s 0.001 5.000

6.1.1. Low impedance restricted earth fault protection REFPDIF

Name Range Unit Step Setting Note

Off
Operation - - On
On

IdMin 4.0 - 100.0 %IB 0.1 30.0 IB=300A

CTFactorPri1 1.0 - 10.0 0.1 1.0


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 116 of 103

CTFactorPri2 1.0 - 10.0 0.1 1.0

CTFactorSec1 1.0 - 10.0 0.1 1.0

CTFactorSec2 1.0 - 10.0 0.1 1.0

6.1.1. Overexcitation protection Setting parameters

Overexcitation protection Setting parameters

OEXPVPH Group settings (basic)


Name Values (Range) Unit Step Setting Description

Off
Operation - - On Operation Off / On
On

Operate level of V/Hz at no

V/Hz> 100.0 - 180.0 %UB/f 0.1 110.0 load and rated freq in % of

(Ubase/frated)

High level of V/Hz above

V/Hz>> 100.0- 200.0 %UB/f 0.1 120.0 which tMin is used, in % of

(Ubase/frated)

Winding leakage reactance in


XLeak 0.000- 200.000 ohm 0.001 0.000
primary ohms

Length of the pulse for trip


TrPulse 0.000- 60.000 s 0.001 0.100
signal (in sec)

Minimum trip delay for V/Hz


tMin 0.000- 60.000 s 0.001 1.000
inverse curve, in sec

Maximum trip delay for V/Hz


tMax 0.00- 9000.00 s 0.01 35
inverse curve, in sec

Transformer magnetic core


tCooling 0.10- 9000.00 s 0.01 3600.00
cooling time constant, in sec

Inverse time curve selection,


CurveType IEEE Tailor made - - IEEE
IEEE/Tailor made

kForIEEE 1 - 60 - 1 2 Time multiplier for IEEE


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 117 of 103

inverse type curve

Alarm operate level as % of


AlarmLevel 50.0- 120.0 % 0.1 105.0
operate level

tAlarm 0.00- 9000.00 s 0.01 5.00 Alarm time delay, in sec

OEXPVPH Non group settings (basic)

Uni
Name Values (Range) Step Setting Description
t

PosSeq

L1L2
MeasuredU - - L1L2 Selection of measured voltage
L2L3

L3L1

L1L2

L2L3
MeasuredI - - L1L2 Selection of measured current
L3L1

PosSeq
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 118 of 103

7. 15BBT10 PAT protection setting table(7SD82)

线路及保护参数 line and protection

额定电压( )
33kV PT
Rated voltage( )

保护装置
7SD82 CT 1500/1
Protect device

6.1.1. Line differential protection


(1)IDiff Stage
Addr. Parameter Setting Options Setting value Note

I-DIFF

Off
3451:1 I-DIFF: Mode On
On

I-DIFF: Operate & No


3451:2 No
flt. rec. blocked Yes

3451:3 I-DIFF: Threshold 0.100A to 20.000A 0.19A

I-DIFF: Thresh.
3451:101 0.100A to 20.000A 1.7A
Switch onto fault

I-DIFF: Operate
3451:6 0.00s to 60.00s 0.00s
delay

(2)IDiff Fast Stage


Addr. Parameter Setting Options Setting value Note

I-DIFF fast

Off
3481:1 I-DIFF fast: Mode On
On

I-DIFF fast: Operate No


3481:2 No
& flt. rec. blocked Yes

I-DIFF fast:
3481:3 0.100A to 20.000A 3.5A
Threshold
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 119 of 103

I-DIFF fast: Thresh.


3481:101 0.100A to 20.000A 4.2A
Switch onto fault

6.1.1. Overcurrent Protection, Phases


Addr. Parameter Setting Options Setting value Note

General 1

Off

_:691:1 Inverse-T 1: Mode On On

Test

Inverse-T 1:
No
_:691:2 Operate & flt. Rec. No
Yes
blocked

Inverse-T 1:1-pole
No
_:691:11 operate allowed No
Yes

Inverse-T 1: No
_:691:26 No
Dynamic settings Yes

Inverse-T 1:
Fundamental comp.
_:691:8 Method of Fundamental
RMS value
measurement

Inverse-T 1:
_:691:3 0.030A to 35.000A 0.58A
Threshold

Inverse-T 1:Type of

_:691:130 character. IEC V

curve

Inverse-T 1:Min.
_:691:113 0.00 s to 1.00 s 0.0s
time of the curve

instantaneous
_:691:131 Inverse-T 1:Reset disk emulation
disk emulation

Inverse-T 1:Time
_:691:101 0.00 to 15.00 0.3
dial
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 120 of 103

Inverse-T

_:691:115 1:Additional 0.00 s to 60.00 s 0.00 s

time delay

6.1.1. Circuit-Breaker Failure Protection


Addr. Parameter Setting Options Setting value Note

50BF Ad.CBF #

50BF Ad.CBF Off

1 #:Holding On On

int. start signal Test

50BF Ad.CBF
No
105 #:Holding No
Yes
int. start signal

50BF Ad.CBF #:Start no

107 via • 2 channel no

binary input • 1 channel

50BF Ad.CBF
no
106 #:Holding no.
yes
ext. start signal

50BF Ad.CBF #:CB


no
103 aux.cont. crit. no
w. 'CB pos. closed 3p.'
allowed

50BF Ad.CBF with effective criterion with effective


104
#:Dropout w. aux.c. and curr.crit. criterion

50BF Ad.CBF no
parallel start
108 #:Retrip start T2 after T1
T2, T1
after T1 parallel start T2, T1

50BF Ad.CBF

102 #:Threshold 0.030 A to 35.000 A 0.58

phase current

101 50BF Ad.CBF 0.030 A to 35.000 A 0.03


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 121 of 103

#:Threshold

sensitive

50BF Ad.CBF

109 #:Delay T1 0.050 s to 60.000 s 0.15

for 3-pole retrip

50BF Ad.CBF

110 #:Delay T2 0.050 s to 60.000 s 0.25

for 3-pole trip

50BF Ad.CBF

112 #:Minimum 0.00 s to 60.00 s 0.10 s

operate time

50BF Ad.CBF #:3I0 Direct release Plausibility


120
criterion Plausibility check check

50BF Ad.CBF #:I2 Direct release Plausibility


121
criterion Plausibility check check

50BF Ad.CBF

122 #:Threshold 0.030 A to 35.000 A 0.03

3I0 dir. release

50BF Ad.CBF

123 #:Threshold 0.030 A to 35.000 A 1.03

I2 dir. release
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 122 of 103

8. Beside15BBT10 PAT protection setting table(7SL82)

线路及保护参数 line and protection

额定电压( )
33kV PT
Rated voltage( )

保护装置
7SL82 CT 1000/1
Protect device

6.1.1. Line differential protection

(1)IDiff Stage
Addr. Parameter Setting Options Setting value Note

I-DIFF

Off
3451:1 I-DIFF: Mode On
On

I-DIFF: Operate & No


3451:2 No
flt. rec. blocked Yes

3451:3 I-DIFF: Threshold 0.100A to 20.000A 0.28A

I-DIFF: Thresh.
3451:101 0.100A to 20.000A 2.55A
Switch onto fault

I-DIFF: Operate
3451:6 0.00s to 60.00s 0.00s
delay

(2)IDiff Fast Stage


Addr. Parameter Setting Options Setting value Note

I-DIFF fast

Off
3481:1 I-DIFF fast: Mode On
On

I-DIFF fast: Operate No


3481:2 No
& flt. rec. blocked Yes

3481:3 I-DIFF fast: 0.100A to 20.000A 5.25A


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 123 of 103

Threshold

I-DIFF fast: Thresh.


3481:101 0.100A to 20.000A 6.3A
Switch onto fault

6.1.1. Overcurrent Protection, Phases


Addr. Parameter Setting Options Setting value Note

General 1

Off

_:691:1 Inverse-T 1: Mode On On

Test

Inverse-T 1:
No
_:691:2 Operate & flt. Rec. No
Yes
blocked

Inverse-T 1:1-pole
No
_:691:11 operate allowed No
Yes

Inverse-T 1: No
_:691:26 No
Dynamic settings Yes

Inverse-T 1:
Fundamental comp.
_:691:8 Method of Fundamental
RMS value
measurement

Inverse-T 1:
_:691:3 0.030A to 35.000A 0.87A
Threshold

Inverse-T 1:Type of

_:691:130 character. IEC V

curve

Inverse-T 1:Min.
_:691:113 0.00 s to 1.00 s 0.0s
time of the curve

instantaneous
_:691:131 Inverse-T 1:Reset disk emulation
disk emulation

_:691:101 Inverse-T 1:Time 0.00 to 15.00 0.3


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 124 of 103

dial

Inverse-T

_:691:115 1:Additional 0.00 s to 60.00 s 0.00 s

time delay

6.1.1. Circuit-Breaker Failure Protection


Addr. Parameter Setting Options Setting value Note

50BF Ad.CBF #

50BF Ad.CBF Off

1 #:Holding On On

int. start signal Test

50BF Ad.CBF
No
105 #:Holding No
Yes
int. start signal

50BF Ad.CBF #:Start no

107 via • 2 channel no

binary input • 1 channel

50BF Ad.CBF
no
106 #:Holding no.
yes
ext. start signal

50BF Ad.CBF #:CB


no
103 aux.cont. crit. no
w. 'CB pos. closed 3p.'
allowed

50BF Ad.CBF with effective criterion with effective


104
#:Dropout w. aux.c. and curr.crit. criterion

50BF Ad.CBF no
parallel start
108 #:Retrip start T2 after T1
T2, T1
after T1 parallel start T2, T1

50BF Ad.CBF

102 #:Threshold 0.030 A to 35.000 A 0.58

phase current
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 125 of 103

50BF Ad.CBF

101 #:Threshold 0.030 A to 35.000 A 0.05

sensitive

50BF Ad.CBF

109 #:Delay T1 0.050 s to 60.000 s 0.15

for 3-pole retrip

50BF Ad.CBF

110 #:Delay T2 0.050 s to 60.000 s 0.25

for 3-pole trip

50BF Ad.CBF

112 #:Minimum 0.00 s to 60.00 s 0.10 s

operate time

50BF Ad.CBF #:3I0 Direct release Plausibility


120
criterion Plausibility check check

50BF Ad.CBF #:I2 Direct release Plausibility


121
criterion Plausibility check check

50BF Ad.CBF

122 #:Threshold 0.030 A to 35.000 A 0.05

3I0 dir. release

50BF Ad.CBF

123 #:Threshold 0.030 A to 35.000 A 1.71

I2 dir. release
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 126 of 103

9. 光伏出线保护整定 CT solar outgoing protection setting table(RED670)

线路及保护参数
Parameters of line and protection

额定电压( ) 额定电流( )
33kV 699.8A

Rated voltage( ) Rated current( )

1000/1(Phase)
CT
50/1(Zero)

PT

保护装置 87LT/50/51/21/21N/67/67N
RED-670
Protect device 59N/51N/50BF

1.5.1 Line differential protection


Name Range Unit Step Setting Note

Off
Operation - - On
On

IdMin 0.20 - 2.00 IB 0.01 0.4 IB=699.8A

IdMinHigh 0.20 - 10.00 IB 0.01 1.2

tIdMinHigh 0.000 - 60.0 s 0.001 0.1

IdUnre 1.00 - 50.00 IB 0.01 10

Off
NegSeqDiffEn - - Off
On

No
CrossBlockEn - - No
Yes

Off
ChargCurEnable - - Off
On

Off
AddDelay - - Off
On
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 127 of 103

IMaxAddDelay 0.20 - 5.00 IB 0.01 1.00

tDefTime 0.000 - 6.000 s 0.001 0.000

tMinInv 0.001 - 6.000 s 0.001 0.010

ANSI Ext. inv.

ANSI Very inv.

ANSI Norm. inv.

ANSI Mod. inv.

ANSI Def. Time

L.T.E. inv.

L.T.V. inv.

L.T. inv.
IEC Def.
CurveType IEC Norm. inv.
Time
IEC Very inv.

IEC inv.

IEC Ext. inv.

IEC S.T. inv.

IEC L.T. inv.

IEC Def. Time

Programmable

RI type

RD type

k 0.05 - 1.10 0.01 1.00

IdiffAlarm 0.05 - 1.00 IB 0.01 0.15

tAlarmdelay 0.000 - 60.0 s 0.001 10

EndSection1 0.20 - 1.50 IB 0.01 1

EndSection2 1.00 - 10.00 IB 0.01 3

SlopeSection2 10.0 - 50.0 % 0.1 40.0

SlopeSection3 30.0 - 100.0 % 0.1 60.0

I2/I1Ratio 5.0 - 100.0 % 1.0 15.0

I5/I1Ratio 5.0 - 100.0 % 1.0 25.0

p 0.01 - 1000.00 0.01 0.02


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 128 of 103

a 0.01 - 1000.00 0.01 0.14

b 0.01 - 1000.00 0.01 1.00

c 0.01 - 1000.00 0.01 1.00

Off
OpenCTEnable On
On

tOCTAlarmDelay 0.100 - 10.000 s 0.001 1.000

tOCTResetDelay 0.100 - 10.000 s 0.001 0.250

Off
OCTBlockEn On
On

LT3CPDIF Non group settings (basic)

Selection of one

of the
GlobalBaseSel 1 - 12 1 1
GlobalBase

Valuegroups

Total number of

2 3-Ph CT sets
NoOfUsedCTs 2
3 connected

to diff protection

Off/On for

elimination of
Off
ZerSeqCurSubtr Off zero seq. from
On
diff. and bias

curr

No Transf A Power

1 transformer A
TraAOnInpCh 1
2 applied on input
3 channel X

RatVoltW1TraA 1.0 - 9999.9 kV 0.1 33 Transformer A

rated voltage

(kV) on
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 129 of 103

winding 1 (HV

winding)

Transformer A

rated voltage
RatVoltW2TraA 1.0 - 9999.9 kV 0.1 11
(kV) on winding

2 (LV winding)

0 [0 deg]

1 [30 deg lag]

2 [60 deg lag]

3 [90 deg lag] Transf. A phase

4 [120 deg lag] shift in multiples

5 [150 deg lag] 1 [30 deg of 30


ClockNumTransA
6 [180 deg lag] lag] deg, 5 for 150

7 [210 deg lag] deg


8 [240 deg lag]

9 [270 deg lag]

10 [300 deg lag]

11 [330 deg lag]

No Transf B Power

1 No Transf transformer B
TraBOnInpCh
2 B applied on input
3 channel X

1.5.2 Directional phase overcurrent protection, four steps OC4PTOC


OC4PTOCGroup settings (basic)
Name Values(Range) Unit Step Setting Note

Operation Off/On - - On

AngleRCA 40 - 65 Deg 1 55

AngleROA 40 - 89 Deg 1 80

StartPhSel 1 out of 3 - - 1 out of 3


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 130 of 103

2 out of 3

3 out of 3

DirMode1 Off - - Non-directional

Non-directional

Forward

Reverse

Characterist1 ANSI Ext. - - IEC Def.

inv./ANSI Very

inv./ANSI Norm.

inv./ANSI Mod.

inv./ANSI Def.

Time/L.T.E.

inv./L.T.V. inv./L.T.

inv./IEC Norm.

inv./IEC Very

inv./IEC inv./IEC

Ext. inv./IEC S.T.

inv./IEC L.T.

inv./IEC Def.

Time/Reserved/Pr

ogrammable/RI

type/RD type

I1> 5 - 2500 %IB 1 245 IB=1000A

k1 0.05 - 999.00 - 0.01 0.05

t1 0.000 - 60.000 s 0.001 0.5

IMin1 1 - 10000 %IB 1 10

t1Min 0.000 - 60.000 s 0.001 0.000

I1Mult 1.0 - 10.0 - 0.1 1.0

DirMode2 Off/Non- - - Non-directional

directional/
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 131 of 103

Forward/Reverse

Characterist2 ANSI Ext. - - IEC Norm

inv./ANSI Very

inv./ANSI Norm.

inv./ANSI Mod.

inv./ANSI Def.

Time/L.T.E.

inv./L.T.V. inv./L.T.

inv./IEC Norm.

inv./IEC Very

inv./IEC inv./IEC

Ext. inv./IEC S.T.

inv./IEC L.T.

inv./IEC Def.

Time/Reserved/Pr

ogrammable/RI

type/RD type

I2> 5 - 2500 %IB 1 87 IB=1000A

K2 0.05 - 999.00 - 0.01 0.3

T2 0.000 - 60.000 s 0.001 0.000

IMin2 1 - 10000 %IB 1 10

t2Min 0.000 - 60.000 s 0.001 0.000

I2Mult 1.0 - 10.0 - 0.1 1.0

DirMode3 Off/Non- - - Off

directional/

Forward/Reverse

Characterist3 ANSI Ext. - - IEC Norm

inv./ANSI Very

inv./ANSI Norm.
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 132 of 103

inv./ANSI Mod.

inv./ANSI Def.

Time/L.T.E.

inv./L.T.V. inv./L.T.

inv./IEC Norm.

inv./IEC Very

inv./IEC inv./IEC

Ext. inv./IEC S.T.

inv./IEC L.T.

inv./IEC Def.

Time/Reserved/Pr

ogrammable/RI

type/RD type

I3> 5 - 2500 %IB 1 110

K3 0.05 - 999.00 - 0.01 0.3

t3 0.000 - 60.000 s 0.001 0.000

IMin3 1 - 10000 %IB 1 10

t3Min 0.000 - 60.000 s 0.001 0.000

I3Mult 1.0 - 10.0 - 0.1 1.0

DirMode4 Off/Non- - - Off

directional/

Forward/Reverse

Characterist4 ANSI Ext. - - IEC Norm

inv./ANSI Very

inv./ANSI Norm.

inv./ANSI Mod.

inv./ANSI Def.

Time/L.T.E.

inv./L.T.V. inv./L.T.
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 133 of 103

inv./IEC Norm.

inv./IEC Very

inv./IEC inv./IEC

Ext. inv./IEC S.T.

inv./IEC L.T.

inv./IEC Def.

Time/Reserved/Pr

ogrammable/RI

type/RD type

I4> 5 - 2500 %IB 1 110

K4 0.05 - 999.00 - 0.01 0.3

t4 0.000 - 60.000 s 0.001 0.000

IMin4 1 - 10000 %IB 1 10

t4Min 0.000 - 60.000 s 0.001 0.000

I4Mult 1.0 - 10.0 - 0.1 1.0

1.5.3 Directional residual overcurrent protection, four steps EF4PTOC


OC4PTOCGroup settings (basic)
Name Values(Range) Unit Step Setting Note

DirMode1 Off - - Non-directional

Non-directional

Forward

Reverse

Characterist1 ANSI Ext. - - IEC Def.

inv./ANSI Very

inv./ANSI Norm.

inv./ANSI Mod.

inv./ANSI Def.

Time/L.T.E.

inv./L.T.V. inv./L.T.
Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 134 of 103

inv./IEC Norm.

inv./IEC Very

inv./IEC inv./IEC

Ext. inv./IEC S.T.

inv./IEC L.T.

inv./IEC Def.

Time/Reserved/Pr

ogrammable/RI

type/RD type

IN1> 5 - 2500 %IB 1 7 IB=50A

k1 0.05 - 999.00 - 0.01 0.1

t1 0.000 - 60.000 s 0.001 0.5 Alarm

IMin1 1 - 10000 %IB 1 10

t1Min 0.000 - 60.000 s 0.001 0.000

IN1Mult 1.0 - 10.0 - 0.1 1.0

DirMode2 Off/Non- - - Off

directional/

Forward/Reverse

1.5.4 Two step residual overvoltage protection ROV2PTOVC


Name Range Unit Step Setting Note

Off
Operation - - On
On

OperationStep1 Off
- - On
On

Definite time

Inverse curve A
Characterist1
Inverse curve B Definite time

Inverse curve C

Prog. inv. curve


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 135 of 103

U1> 1.0 - 200.0 %UB 0.1 10.0 UB=33kV

t1 0.00 - 6000.00 s 0.01 0.5 Alarm

t1Min 0.000 - 60.000 s 0.01 5.00

k1 0.05 - 1.10 - 0.01 0.05

1.5.5 Breaker failure protection CCRBRF


Name Range Unit Step Setting Note

Off
Operation - - On
On

Current

FunctionMode Contact - - Current

Current/Contact

LatchedStart

FollowStart
StartMode LatchedStart
FollowStart&Mod

2 out of 4

BuTripMode 1 out of 3 - - 1 out of 3

1 out of 4

Off

RetripMode UseFunctionMode - - UseFunctionM

Always

IP> 5 - 200 %IB 1 87 IB=1000A

IN> 2 - 200 %IB 1 3

t1 0.000 - 60.000 s 0.001 0.15

t2MPh 0.000 - 60.000 s 0.001 0.25

tPulse 0.000 - 60.000 s 0.001 0.25

I>BlkCont 2 - 200 %IB 1 20

t3 0.000 - 60.000 s 0.001 0.030

tCBAlarm 0.000 - 60.000 s 0.001 5.000


Document Name NE1-20-EM-JEP-LIS-BB_(R)-00003

Rev No. 03
Medium Voltage Protection Setpoint List
Page 136 of 103