Professional Documents
Culture Documents
BDBS 1st Review BLDC2022-0143 533 E 3rd ST Redlined Plans......
BDBS 1st Review BLDC2022-0143 533 E 3rd ST Redlined Plans......
Digitally signed by
Carl Carl Anderson
Date: 2022.08.15
Anderson 12:53:59 -04'00' 6/30/2024
6 Provide door
schedule, framing
details and structural
calculations
ktillema
09/19/2022 11:36:04 AM
The approval of plans and specifications does not
permit the violation, deletion, omission or faulty
installation of any requirements of Title 24 or any
Local Codes or Ordinances. Construction shall
remain accessible and exposed for inspection
purposes until approved by the Fire Department.
FP2022-0060
PRIOR TO APPROVAL THE ADDED SMOKE
AND HEAT VENTS AND ADDED FIRE
DEPARTMENT ACCESS DOOR SHALL BE
REQUIRED.
8 16.2.1.4.1.4 In-rack sprinklers at one level only for storage
up to and including 25 ft (7.6 m) high shall be located at the
first tier level at or above one-half of the storage height.
Digitally signed
Carl by Carl Anderson
6/30/2024