INSTRUMENT PCS I/O LIST

Proger Proger Proger Proger


CD-FE 01 MAR. 2012 For Approval M. Di Russo
Bonincontro Bonincontro Puzone
Proger Proger Proger Proger
CD-FE 00 FEB. 2012 For Approval M. Di Russo
Bonincontro Bonincontro Puzone
Validity
Rev.
Status Date Description Prepared Checked Approved Contractor Company
by by by Approval Approval
Revision index
Company logo and business name Project name Company identification

NEW WATER
003028.00.BIEE.A0260
Eni CONGO TREATMENT AND
Job N.
INJECTION UNIT
Contractor logo and business name Contractor identification

Proger SpA Contract N. 50000314/205


Vendor logo and business name Vendor identification

Order N.
Facility Name Location Scale Sheet of Sheets

FOUKANDA WATER TREATMENT AND INJECTION CONGO-OFF SHORE N/A 1 / 27


Document Title Supersedes N.

Superseded by N.
INSTRUMENT PCS I/O LIST Plant Area Plant Unit

FOUKANDA PLATFORM

Software: Microsoft Excel File No.: 00302800BIEEA0260_CDFE01_27.xls


This document is property of ENI S.p.A. who will safeguard its rights according to the civil and penal provision of the law.
Company document identification Contractor document identification Validity Status Revision Sheet of Sheet

Eni CONGO 003028.00.BIEE.A0260 CD-FE 1 2 of 27

INDEX
Sh. Sh. Sh.

DENOMINATION REVISION N°
DENOMINATION REVISION N°
DENOMINATION REVISION

1 COVER 0 1 21 ALARM 0 41

2 INDEX 0 1 22 PMCC SIGNAL 0 42

3 INDEX 0 23 COMMAND 0 43

4 SPARE 0 24 PMCC SIGNAL 0 44

5 LEGEND 0 25 PMCC SIGNAL 0 45

6 NOTES - PHYSICAL I/O 0 26 DI 0 46


M
7 NOTES - SERIAL I/O 0 27 DI 47
O
D
8 LIMIT SW 0 28 48
.
S
9 INSTR 0 29 49
T
A
10 LIMIT SW 0 30 50
.
E
L
11 LIMIT SW 0 31 51
N
.
12 INSTR 0 32 52
1
0 13 LIMIT SW 0 33 53
1
/ 14 LIMIT SW 0 34 54
0
15 LIMIT SW 0 35 55
S
H 16 INSTR 0 36 56
.
0 17 INSTR 0 1 37 57
2
/ 18 INSTR 0 1 38 58
0
9 19 COMMAND 0 39 59

20 COMMAND 0 40 60

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.
Company document identification Contractor document identification Validity Status Revision Sheet of Sheet

Eni CONGO 003028.00.BIEE.A0260 CD-FE 0 3 of 27

INDEX
Sh. Sh. Sh.

DENOMINATION REVISION N°
DENOMINATION REVISION N°
DENOMINATION REVISION

58 77 96

59 78 97

60 79 98

61 80 99

62 81 100

63 82 101
M
64 83 102
O
D
65 84 103
.
S
T
66 85 104
A
.
67 86 105
E
L 68 87 106
N
. 69 88 107
1
0 70 89 108
1
/ 71 90 109
0
72 91 110
S
H 73 92 111
.
0 74 93 112
3
/ 75 94 113
0
9 76 95 114

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.
Company document identification Contractor document identification Validity Status Revision Sheet of Sheet

Eni CONGO 003028.00.BIEE.A0260 CD-FE 0 4 of 27

M
O
D
.
S
T
A
.
E
L
N
.
1
0
1
/
0

S
H
.
0
4
/
0
9

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.
Company document identification Contractor document identification Validity Status Revision Sheet of Sheet

Eni CONGO 003028.00.BIEE.A0260 CD-FE 0 5 of 27

LEGEND
INSTRUMENT LOCATION (LOCAT.) - Geographical Location of the Instrument LEGEND of INPUTS / OUTPUTS on SERIAL LINK

CR : Control Room TAG : Tag of the point (SLAVE Device)


IER : Instrument Equipment Room SERVICE : Description of the point (SLAVE Device)
TYPE : Digital or Analogue
L : Local DEVICE ADDRESS : MODBUS Address of the SLAVE Device
LCP : Local Control Panel MEMORY ADDRESS : Point's address in Memory (if present)
LP : Local Panel
MER : Main Electrical Room R/W : "R" for a point to be READ by the MASTER
"W" for a point to be WRITTEN by the MASTER
"RW" for a point to READ / WRITTEN by the MASTER
I/O TYPE - Input / Output Signal Connection Type
BIT : Bit position in a packed REGISTER, if present
AI : Analog Input FUN. CODE : MODBUS Function Code for the call of the relevant point
M
When the Redundancy is
AO : Analog Output
O required, the letter R has to be
DI : Digital Input INSTR. RANGE MIN : LOWER limit of the ENGINEERING VALUE (Analogue ONLY)
D
DO : Digital Output
added (i.e.: AIR) INSTR. RANGE MAX : HIGHER limit of the ENGINEERING VALUE (Analogue ONLY)
.
S
T HW : Hardware (electric) SW : Software LOW ALARM : THRESHOLD (in engineering units) of the LOW ALARM
A H: Hydraulic A: Analogue associated with the VARIABLE (Analogue ONLY)
. P: Pneumatic D: Digital HIGH ALARM : THRESHOLD (in engineering units) of the HIGH ALARM
E associated with the VARIABLE (Analogue ONLY)
L
N SYSTEM - Designation of System Involved ENG. UNIT : Engineering Unit of the VARIABLE (Analogue ONLY)
.
1
DCS : Distributed Control System CODING : Analogue value type of coding (i.e. : unsigned / signed 16 bits
0
1 ESD : Emergency Shut Down System register, unsigned / signed 32 bits register, IEEE754 floating
/ FG : Fire & Gas System point). If not specified, a 16 bits unsigned Most significant
0 HIPS : High Integrity Protection System Byte first will be assumed. In case of integer register, the
SCADA : Supervisory Control And data Acquisition maximum raw valid for all the analogue value shall be
S LCP : Local Control Panel (at Field) specified (default: 65535)
H ECS : Electrical Control System
.
PLC : Programmable Logic Controller (Package) STATE 0 : Logical State relevant to bit = 0 ("NORMAL", "STOP", etc.)
0
5 WCP : Wellhead Control Panel (Digital ONLY)
/ STATE 1 : Logical State relevant to bit = 1 ("ALARM", "RUNNING", etc.)
0 (Digital ONLY)
9

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.
Company document identification Contractor document identification Validity Status Revision Sheet of Sheet

Eni CONGO 003028.00.BIEE.A0260 CD-FE 0 6 of 27

NOTES - PHYSICAL INPUTS / OUTPUTS

INDICATION AND ALARM OF HIGH AND LOW ANALOGUE SIGNAL (HIGH AND LOW MUST
(1)
BE SET AT 80% AND 20% OF RANGE)

1 = NC = CONTACT NORMALLY CLOSED = NORMAL CONDITION


(2) ALARM STATUS
0 = NO = CONTACT NORMALLY OPENED = ABNORMAL CONDITION

0 = NO = CONTACT NORMALLY OPENED = NORMAL CONDITION


(3) SIGNAL STATUS
1 = NC = CONTACT NORMALLY CLOSED = ABNORMAL CONDITION

ZSH = 1 = NC = NORMALLY CLOSED = VALVE OPENED


VALVE SIGNAL ZSL = 1 = NC = NORMALLY CLOSED = VALVE CLOSED
(4)
STATUS ZSH = 0 = NO = NORMALLY OPENED = VALVE NOT OPENED
ZSL = 0 = NO = NORMALLY OPENED = VALVE NOT CLOSED
M
O UA = 1 = NC = CONTACT NORMALLY CLOSED = AVAILABLE OR NOT
D ALARM MOTOR BLOCK CONDITION
. (5)
STATUS UA = 0 = NO = CONTACT NORMALLY OPENED = NOT AVAILABLE
S
OR BLOCK CONDITION
T
A
. SIGNAL MOTOR UL = 1 = NC = CONTACT NORMALLY CLOSED = USER RUNNING
(6)
E STATUS UL = 0 = NO = CONTACT NORMALLY OPENED = USER NOT RUNNING
L
N TO COMMAND 1 = NC POWERED = START, NOT BLOCK AND LOCAL PERMISSION
. ELECTRICAL USERS ENABLED
1 (7)
(TO MCC FOR MOTOR, 0 = NO NOT POWERED = STOP, BLOCK AND LOCAL PERMISSION
0 PUMPS, ETC.) DISABLED
1
/
0 TO COMMAND
1 = NC = NORMALLY ENERGISED FOR FAIL SAFE CONDITION
(8) SOLENOID VALVES
S AND RELAYS 0 = NO = NOT POWERED FOR SHUT OFF CONDITION
H
. 0 = NO = NORMALLY DEENERGISED FOR NORMAL PROCESS
0 TO COMMAND CONDITION
6 (9)
SOLENOID VALVES 1 = NC = POWERED TO COMMAND NEW POSITION OF THE
/
0 RELATIVE DEVICE
9

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.
Company document identification Contractor document identification Validity Status Revision Sheet of Sheet

Eni CONGO 003028.00.BIEE.A0260 CD-FE 0 7 of 27

NOTES - SERIAL INPUTS / OUTPUTS

THE INPUTS / OUTPUTS SOFTWARE LIST FOR SERIAL LINK SHALL BE MAINLY
General
FILLED BY THE VENDOR SLAVE SYSTEM

M
O
D
.
S
T
A
.
E
L
N
.
1
0
1
/
0

S
H
.
0
7
/
0
9

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.
Notes
Contractor document Validity
company document identification Revision Sh of Sh
identification Status

Eni CONGO 003028.00.BIEE.A0260 CD-FE 0 8 / 27

PHYSICAL INPUTS / OUTPUTS LIST SYSTEM: PCS UNIT: 970 UNIT DESCRIPTION: SCADA SYSTEM

INSTRUMENT SIGNAL SOFTWARE ALARM SET


LOOP
NOTE
LOCA EXECU I/O ELECTRIC. RANGE ENG. REDUN MONI DIAGRAM
TAG SERVICE TYPE FED BY LL L H HH
TION TION TYPE SIGNAL MEASURE UNIT DANT TORING

200-ZSH-010 200SDV 010OPEN LIMIT SWITCH DI 24V

200-ZSL-010 200SDV 010CLOSE LIMIT SWITCH DI 24V

M
O
D
.
S
T
A
.
E
L
N
.
1
0
1
/
0

S
H
.
0
8 NOTES:
/
0
9

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.
Notes
Contractor document Validity
company document identification Revision Sh of Sh
identification Status

Eni CONGO 003028.00.BIEE.A0260 CD-FE 0 9 / 27

PHYSICAL INPUTS / OUTPUTS LIST SYSTEM: PCS UNIT: 970 UNIT DESCRIPTION: SCADA

INSTRUMENT SIGNAL SOFTWARE ALARM SET


LOOP
MONI NOTE
LOCA EXECU I/O ELECTRIC. RANGE ENG. FED REDUN DIAGRAM
TAG SERVICE TYPE TORIN LL L H HH
TION TION TYPE SIGNAL MEASURE UNIT BY DANT
G

M
O
F-200-0-LT-013 F-200-0-VS-001 SMART TX L AI 4-20mA 0-100 % LIC (1)
D
. WITH
S F-200-0-LY-013 LIQUID LEVEL REG. I/P COVERTER L AO 4-20mA 0-100 % OUT (1)
T SWITC
A F-560-0-LY-013 HYDROCICLON OUTLET I/P COVERTER L AO 4-20mA 0-100 % H
.
E
L
N
.
1
0
1
/
0

S
H
.
0
8
NOTES: (1) INSTRUMENTS CONNECTED TO F-970-0-JU-008
/
0
9

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.
Notes
Contractor document Validity
company document identification Revision Sh of Sh
identification Status

Eni CONGO 003028.00.BIEE.A0260 CD-FE 0 10 / 27

PHYSICAL INPUTS / OUTPUTS LIST SYSTEM: PCS UNIT: 970 UNIT DESCRIPTION: SCADA SYSTEM

INSTRUMENT SIGNAL SOFTWARE ALARM SET


LOOP
NOTE
LOCA EXECU I/O ELECTRIC. RANGE ENG. REDUN MONI DIAGRAM
TAG SERVICE TYPE FED BY LL L H HH
TION TION TYPE SIGNAL MEASURE UNIT DANT TORING

F-420-0-ZSH-005 420SDV 005 OPEN LIMIT SWITCH L DI 24V

F-420-0-ZSL-010 420SDV005 CLOSE LIMIT SWITCH L DI 24V

M
O
D
.
S
T
A
.
E
L
N
.
1
0
1
/
0

S
H
.
0
8 NOTES:
/
0
9

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.
Notes
Contractor document Validity
company document identification Revision Sh of Sh
identification Status

Eni CONGO 003028.00.BIEE.A0260 CD-FE 0 11 / 27

PHYSICAL INPUTS / OUTPUTS LIST SYSTEM: PCS UNIT: 970 UNIT DESCRIPTION: SCADA SYSTEM

INSTRUMENT SIGNAL SOFTWARE ALARM SET


LOOP
NOTE
LOCA EXECU I/O ELECTRIC. RANGE ENG. REDUN MONI DIAGRAM
TAG SERVICE TYPE FED BY LL L H HH
TION TION TYPE SIGNAL MEASURE UNIT DANT TORING

F-510-0-ZSH-001 510SDV001 OPEN LIMIT SWITCH L DI 24V

F-510-0-ZSL-001 510SDV001 CLOSE LIMIT SWITCH L DI 24V

F-510-0-ZSH-002 510SDV002 OPEN LIMIT SWITCH L DI 24V

F-510-0-ZSL-002 510SDV002 CLOSE LIMIT SWITCH L DI 24V


M
O
F-510-0-ZSH-003 510SDV003 OPEN LIMIT SWITCH L DI 24V
D
.
S F-510-0-ZSL-003 510SDV003 CLOSE LIMIT SWITCH L DI 24V
T
A F-510-0-ZSH-004 510SDV004 OPEN LIMIT SWITCH L DI 24V
.
E F-510-0-ZSL-004 510SDV004 CLOSE LIMIT SWITCH L DI 24V
L
N
F-510-0-ZSH-005 510SDV005 OPEN LIMIT SWITCH L DI 24V
.
1
0 F-510-0-ZSL-005 510SDV005 CLOSE LIMIT SWITCH L DI 24V
1
/ F-510-0-ZSH-006 510SDV006 OPEN LIMIT SWITCH L DI 24V
0
F-510-0-ZSL-006 510SDV006 CLOSE LIMIT SWITCH L DI 24V
S
H F-510-0-ZSH-007 510SDV007 OPEN LIMIT SWITCH L DI 24V
.
0
F-510-0-ZSL-007 510SDV007 CLOSE LIMIT SWITCH L DI 24V
8
/
0
NOTES:
9

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.
Notes
Contractor document Validity
company document identification Revision Sh of Sh
identification Status

Eni CONGO 003028.00.BIEE.A0260 CD-FE 0 12 / 27

PHYSICAL INPUTS / OUTPUTS LIST SYSTEM: PCS UNIT: 970 UNIT DESCRIPTION: SCADA

INSTRUMENT SIGNAL SOFTWARE ALARM SET


LOOP
NOTE
LOCA EXECU I/O ELECTRIC. RANGE ENG. REDUN MONI DIAGRAM
TAG SERVICE TYPE FED BY LL L H HH
TION TION TYPE SIGNAL MEASURE UNIT DANT TORING

F-510-0-PT-001 DISCHARGE PA 001A SMART TX L AI 4-20mA 0-100 BAR PI 001

DISCHARGE
F-510-0-PT-002 SMART TX L AI 4-20mA 0-100 BAR
COLLECTOR
PIC
F-510-0-PY-002 CONV / VALVE I/P CONVERTER L AO 4-20mA 0-100 %

M
O
F-510-0-PT-003 DISCHARGE PA 001B SMART TX L AI 4-20mA 0-100 BAR PI 003
D
.
S
T
A F-510-0-PT-004 FILTER OUTLET SMART TX L AI 4-20mA 0-100 BAR PI 001
.
E DISCHARGE
F-510-0-TT-001 SMART TX L AI 4-20mA 0-100 C° TI 001
L COLLECTOR
N FORM
F-510-0-FY-005 CONV / VALVE I/P CONVERTER L AO 4-20mA 0-100 %
. FIC-001/002/003
1
0
1
/
0
F-510-0-PDT-001 D.P. FILTER CL-010A SMART TX L AI 4-20mA 0-1 BAR PDI 001 X
S
H F-510-0-PDT-002 D.P. FILTER CL-010B SMART TX L AI 4-20mA 0-1 BAR PDI 001 X
.
0
8 NOTES:
/
0
9

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.
Notes
Contractor document Validity
company document identification Revision Sh of Sh
identification Status

Eni CONGO 003028.00.BIEE.A0260 CD-FE 0 13 / 27

PHYSICAL INPUTS / OUTPUTS LIST SYSTEM: PCS UNIT: 970 UNIT DESCRIPTION: SCADA SYSTEM

INSTRUMENT SIGNAL SOFTWARE ALARM SET


LOOP
NOTE
LOCA EXECU I/O ELECTRIC. RANGE ENG. REDUN MONI DIAGRAM
TAG SERVICE TYPE FED BY LL L H HH
TION TION TYPE SIGNAL MEASURE UNIT DANT TORING

F-560-0-ZSH-001 560SDV001 OPEN LIMIT SWITCH L DI 24V

F-560-0-ZSL-001 560SDV001 CLOSE LIMIT SWITCH L DI 24V

F-560-0-ZSH-002 560SDV002 OPEN LIMIT SWITCH L DI 24V


M
O
F-560-0-ZSL-002 560SDV002 CLOSE LIMIT SWITCH L DI 24V
D
.
S
T
A F-560-0-ZSH-003 560SDV003 OPEN LIMIT SWITCH L DI 24V
.
E F-560-0-ZSL-003 560SDV003 CLOSE LIMIT SWITCH L DI 24V
L
N
.
1
0 F-560-0-ZSH-004 560SDV004 OPEN LIMIT SWITCH L DI 24V
1
/ F-560-0-ZSL-004 560SDV004 CLOSE LIMIT SWITCH L DI 24V
0

S
H
.
0
8 NOTES:
/
0
9

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.
Notes
Contractor document Validity
company document identification Revision Sh of Sh
identification Status

Eni CONGO 003028.00.BIEE.A0260 CD-FE 0 14 / 27

PHYSICAL INPUTS / OUTPUTS LIST SYSTEM: PCS UNIT: 970 UNIT DESCRIPTION: SCADA SYSTEM

INSTRUMENT SIGNAL SOFTWARE ALARM SET


LOOP
NOTE
LOCA EXECU I/O ELECTRIC. RANGE ENG. REDUN MONI DIAGRAM
TAG SERVICE TYPE FED BY LL L H HH
TION TION TYPE SIGNAL MEASURE UNIT DANT TORING

F-560-0-ZSH-005 560SDV005 OPEN LIMIT SWITCH L DI 24V

F-560-0-ZSL-005 560SDV005 CLOSE LIMIT SWITCH L DI 24V

F-560-0-ZSH-006 560SDV006 OPEN LIMIT SWITCH L DI 24V


M
O
F-560-0-ZSL-006 560SDV006 CLOSE LIMIT SWITCH L DI 24V
D
.
S
T
A F-560-0-ZSH-007 560SDV007 OPEN LIMIT SWITCH L DI 24V
.
E F-560-0-ZSL-007 560SDV007 CLOSE LIMIT SWITCH L DI 24V
L
N
.
1
0 F-560-0-ZSH-008 560SDV008 OPEN LIMIT SWITCH L DI 24V
1
/ F-560-0-ZSL-008 560SDV008 CLOSE LIMIT SWITCH L DI 24V
0

S
H
.
0
8 NOTES:
/
0
9

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.
Notes
Contractor document Validity
company document identification Revision Sh of Sh
identification Status

Eni CONGO 003028.00.BIEE.A0260 CD-FE 0 15 / 27

PHYSICAL INPUTS / OUTPUTS LIST SYSTEM: PCS UNIT: 970 UNIT DESCRIPTION: SCADA SYSTEM

INSTRUMENT SIGNAL SOFTWARE ALARM SET


LOOP
NOTE
LOCA EXECU I/O ELECTRIC. RANGE ENG. REDUN MONI DIAGRAM
TAG SERVICE TYPE FED BY LL L H HH
TION TION TYPE SIGNAL MEASURE UNIT DANT TORING

F-560-0-ZSH-009 560SDV009 OPEN LIMIT SWITCH L DI 24V

F-560-0-ZSL-009 560SDV009 CLOSE LIMIT SWITCH L DI 24V

F-560-0-ZSH-010 560SDV010 OPEN LIMIT SWITCH L DI 24V


M
O
F-560-0-ZSL-010 560SDV010 CLOSE LIMIT SWITCH L DI 24V
D
.
S
T
A F-560-0-ZSH-011 560SDV011 OPEN LIMIT SWITCH L DI 24V
.
E F-560-0-ZSL-011 560SDV0011 CLOSE LIMIT SWITCH L DI 24V
L
N
.
1
0 F-560-0-ZSH-012 560SDV012 OPEN LIMIT SWITCH L DI 24V
1
/ F-560-0-ZSL-012 560SDV012 CLOSE LIMIT SWITCH L DI 24V
0

S
H
.
0
8 NOTES:
/
0
9

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.
Notes
Contractor document Validity
company document identification Revision Sh of Sh
identification Status

Eni CONGO 003028.00.BIEE.A0260 CD-FE 0 16 / 27

PHYSICAL INPUTS / OUTPUTS LIST SYSTEM: PCS UNIT: 970 UNIT DESCRIPTION: SCADA SYSTEM

INSTRUMENT SIGNAL SOFTWARE ALARM SET


LOOP
NOTE
LOCA EXECU I/O ELECTRIC. RANGE ENG. REDUN MONI DIAGRAM
TAG SERVICE TYPE FED BY LL L H HH
TION TION TYPE SIGNAL MEASURE UNIT DANT TORING
DISCHARGE
F-560-0-FT-001 SMART /MAGNETIC L AI 4-20mA 0-75000 Kg/h FI-001
COLLECTOR

F-560-0-FT-002 SUCHTION COLLECTOR SMART TX L AI 4-20mA 3900-71400 Kg/h


FIC 002
F-510-0-FY-002 FLOW REGULATION I/P CONVERTE L AO 4-20mA 0-100 %
M
O
D
.
S F-560-0-PT-001 PRESS TX SMART TX L AI 4-20mA 0-15 BAR PI 001
T
A F-560-0-PT-002 DISCHARGE PA 001A SMART TX L AI 4-20mA 0-15 BAR PI 002
.
E F-560-0-PT-003 DISCHARGE PA 001B SMART TX L AI 4-20mA 0-15 BAR PI 003
L
N
F-560-0-PT-004 PRESS IGF SMART TX L AI 4-20mA 0-1 BAR PI 004
.
1 DISCHARGE
0 F-560-0-PT-005 SMART TX L AI 4-20mA 0-10 BAR PI 005
COLLECTOR
1
/
0
DISCHARGE
F-560-0-TT-001 SMART TX L AI 4-20mA 0-100 C° TI 001
COLLECTOR
S
H
.
0
8 NOTES:
/
0
9

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.
Notes
Contractor document Validity
company document identification Revision Sh of Sh
identification Status

Eni CONGO 003028.00.BIEE.A0260 CD-FE 1 17 / 27

PHYSICAL INPUTS / OUTPUTS LIST SYSTEM: PCS UNIT: 970 UNIT DESCRIPTION: SCADA SYSTEM

INSTRUMENT SIGNAL SOFTWARE ALARM SET


LOOP
NOTE
LOCA EXECU I/O ELECTRIC. RANGE ENG. REDUN MONI DIAGRAM
TAG SERVICE TYPE FED BY LL L H HH
TION TION TYPE SIGNAL MEASURE UNIT DANT TORING

F-560-0-PDT-001 DESANDER SMART TX L AI 4-20mA 0-1 (1) BAR PDI 001 X X

F-560-0-PDT-002 HYDROCYCLON SMART TX L AI 4-20mA 0-1 (1) BAR

F-560-0-PDT-003 HYDROCYCLON SMART TX L AI 4-20mA 0-1 (1) BAR PDIC


M
O
F-560-0-PDY-003 REG I/P COVERTER L AO 4-20mA 0-100 %
D
.
S
T
A F-560-0-LT-002 IGF SMART TX L AI 4-20mA 0-100 % X X
. LIC
E F-560-0-LY-002 REG I/P COVERTER L AI 4-20mA 0-100 %
L
N
.
1
0 F-560-0-FT-003 IGF RECYCLE SMART TX L AI 4-20mA 0-100 %
1 FIC
/ F-560-0-FY-003 REG I/P COVERTER L AI 4-20mA 0-100 %
0

S
H
.
0
8 NOTES: (1) CONFIRMED BY SKID MFR
/
0
9

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.
Notes
Contractor document Validity
company document identification Revision Sh of Sh
identification Status

Eni CONGO 003028.00.BIEE.A0260 CD-FE 1 18 / 27

PHYSICAL INPUTS / OUTPUTS LIST SYSTEM: PCS UNIT: 970 UNIT DESCRIPTION: SCADA SYSTEM

INSTRUMENT SIGNAL SOFTWARE ALARM SET


LOOP
NOTE
LOCA EXECU I/O ELECTRIC. ENG. REDUN MONI DIAGRAM
TAG SERVICE TYPE RANGE FED BY LL L H HH
TION TION TYPE SIGNAL UNIT DANT TORING

F-560-0-LT-003 IGF SMART TX L AI 4-20mA 0-100 %


LIC/FIC
F-510-0-FT-004 WATER INJECTION SMART TX L AI 4-20mA 0-100 % CASCAD
E MODE
F-510-0-FY-004 REG I/P COVERTER L AO 4-20mA 0-100 %

M
O
F-510-0-FT-005 WATER INJECTION SMART TX L AI 4-20mA 0-100 %
D
. FIC
S F-510-0-FY-005 REG I/P COVERTER L AO 4-20mA 0-100 % (1)
T
A (1)
.
E
L
N
.
1
0
1
/
0

S
H
.
0
8 NOTES:
/
0
9

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.
Notes
Contractor document Validity
company document identification Revision Sh of Sh
identification Status

Eni CONGO 003028.00.BIEE.A0260 CD-FE 0 19 / 27

MASTER SERIAL LINK


SERIAL INPUTS / OUTPUTS LIST SYSTEM:
PCS UNIT: 970 DESCRIPTION:
SCADA SYSTEM

INSTRUMENT RANGES & ALARMS


COMMENTS

FUN. CODE

HIGH ALARM
LOW ALARM

CODING
MAX RANGE
MIN RANGE

ENG. UNIT
TYPE MEMORY

R/W

BIT
TAG SERVICE DEVICE ADDRESS NOTE
ADDRESS
STATE 0 STATE 1

F-200-0-HS-100 O/C 200SDV 010 DO CLOSE OPEN

F-420-0-HS 200 O/C 420SDV005 DO CLOSE OPEN

F-560-0-HS-001 O/C 560SDV001 DO CLOSE OPEN

F-560-0-HS-002 O/C 560SDV002 DO CLOSE OPEN


M
O F-560-0-HS-003 O/C 560SDV003 DO CLOSE OPEN
D
. F-560-0-HS-004 O/C 560SDV004 DO CLOSE OPEN
S
T F-560-0-HS-005 O/C 560SDV005 DO CLOSE OPEN
A
. F-560-0-HS-006 O/C 560SDV006 DO CLOSE OPEN
E
L F-560-0-HS-007 O/C 560SDV007 DO CLOSE OPEN
N
. F-560-0-HS-008 O/C 560SDV008 DO CLOSE OPEN
1
F-560-0-HS-009 O/C 560SDV009 DO CLOSE OPEN
0
1 F-560-0-HS-010 O/C 560SDV010 DO CLOSE OPEN
/
0 F-560-0-HS-011 O/C 560SDV011 DO CLOSE OPEN

S F-560-0-HS-012 O/C 560SDV012 DO CLOSE OPEN


H
.
0
9 NOTES:
/
09

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.
Notes
Contractor document Validity
company document identification Revision Sh of Sh
identification Status

Eni CONGO 003028.00.BIEE.A0260 CD-FE 0 20 / 27

MASTER SERIAL LINK


SERIAL INPUTS / OUTPUTS LIST SYSTEM:
PCS UNIT: 970 DESCRIPTION:
SCADA SYSTEM

INSTRUMENT RANGES & ALARMS


COMMENTS

FUN. CODE

HIGH ALARM
LOW ALARM

CODING
MAX RANGE
MIN RANGE

ENG. UNIT
TYPE MEMORY

R/W

BIT
TAG SERVICE DEVICE ADDRESS NOTE
ADDRESS
STATE 0 STATE 1

F-510-0-HS-001 O/C 510SDV 001 DO CLOSE OPEN

F-510-0-HS-002 O/C 510SDV002 DO CLOSE OPEN

F-510-0-HS-003 O/C 510SDV003 DO CLOSE OPEN

F-510-0-HS-004 O/C 510SDV004 DO CLOSE OPEN


M
O F-510-0-HS-005 O/C 510SDV005 DO CLOSE OPEN
D
. F-510-0-HS-006 O/C 510SDV006 DO CLOSE OPEN
S
T F-510-0-HS-007 O/C 510SDV007 DO CLOSE OPEN
A
.
E
L
N
.
1
0
1
/
0

S
H
.
0
9 NOTES:
/
09

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.
Notes
Contractor document Validity
company document identification Revision Sh of Sh
identification Status

Eni CONGO 003028.00.BIEE.A0260 CD-FE 0 21 / 27

MASTER SERIAL LINK


SERIAL INPUTS / OUTPUTS LIST SYSTEM:
PCS UNIT: 970 DESCRIPTION:
SCADA SYSTEM

INSTRUMENT RANGES & ALARMS


COMMENTS

FUN. CODE

HIGH ALARM
LOW ALARM

CODING
MAX RANGE
MIN RANGE

ENG. UNIT
TYPE MEMORY

R/W

BIT
TAG SERVICE DEVICE ADDRESS NOTE
ADDRESS
STATE 0 STATE 1

F-560-0-LSXX-001 LSD ALARM S ALARM (1)

F-560-0-LSAX-002 LSD ALARM S ALARM (1)

F-560-0-LSXX-003 LSD ALARM S ALARM (1)

F-560-0-PSAX-001 LSD ALARM S ALARM (1)


M
O F-560-0-PSAX-002 LSD ALARM S ALARM (1)
D
. F-560-0-PSAX-004 LSD ALARM S ALARM (1)
S
T F-560-0-PSAX-005 LSD ALARM S ALARM (1)
A
. F-560-0-PDXX-001 LSD ALARM S ALARM (1)
E
L
N
.
1
0
1 F-510-0-DPSAXX-001 LSD ALARM S ALARM
/
0 F-510-0-PSAHH-001A ALARM S ALARM (1)

S F-510-0-PSAHH-001B ALARM S ALARM (1)


H
. F-510-0-PSAXX-001B LSD ALARM S Logic 2°°2 PSHH001+002 (1)
0
9 NOTES:
/
09 (1)This signal are transmissed by serial link controlnet from new cabinet F-980-0-JE-103

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.
Notes
Contractor document Validity
company document identification Revision Sh of Sh
identification Status

Eni CONGO 003028.00.BIEE.A0260 CD-FE 0 22 / 27

MASTER SERIAL LINK


SERIAL INPUTS / OUTPUTS LIST SYSTEM:
PCS UNIT: 970 DESCRIPTION:
SCADA SYSTEM

INSTRUMENT RANGES & ALARMS


COMMENTS

FUN. CODE

HIGH ALARM
LOW ALARM

CODING
MAX RANGE
MIN RANGE

ENG. UNIT
TYPE MEMORY

R/W

BIT
TAG SERVICE DEVICE ADDRESS NOTE
ADDRESS
STATE 0 STATE 1

F-970-0-HS-400 START / STOP DO STOP 510 PA-001A START (1)

F-970-0-HS-401 PERMISSIVE LOC START DO LOC START 510PA001A (1)


M
O F-970-0-HS-402 START / STOP DO STOP 510 PA-001B START (1)
D
. F-970-0-HS-403 PERMISSIVE LOC START DO LOC START 510PA001B (1)
S
T
A
. F-970-0-HS-404 START / STOP DO STOP 560 PA-001A START (1)
E
L F-970-0-HS-405 PERMISSIVE LOC START DO LOC START 560PA001A (1)
N
F-970-0-HS-406 START / STOP DO STOP 560 PA-001B START (1)
.
1
F-970-0-HS-407 PERMISSIVE LOC START DO LOC START 560PA001B (1)
0
1 F-970-0-HS-408 START / STOP DO STOP 560 PA-002A START (1)
/
0 F-970-0-HS-409 PERMISSIVE LOC START DO LOC START 560PA002A (1)

S F-970-0-HS-410 START / STOP DO STOP 560 PA-002B START (1)


H
. F-970-0-HS-411 PERMISSIVE LOC START DO LOC START 560PA002B (1)
0
9 NOTES:
/ NOTES: (1) CABLE FROM/TO 970-JD-101 TO/FROM INTERFACE PANEL. I/P
09

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.
Notes
Contractor document Validity
company document identification Revision Sh of Sh
identification Status

Eni CONGO 003028.00.BIEE.A0260 CD-FE 0 23 / 27

MASTER SERIAL LINK


SERIAL INPUTS / OUTPUTS LIST SYSTEM:
PCS UNIT: 970 DESCRIPTION:
SCADA SYSTEM

INSTRUMENT RANGES & ALARMS


COMMENTS

FUN. CODE

HIGH ALARM

CODING
LOW ALARM
MAX RANGE
MIN RANGE

ENG. UNIT
TYPE
MEMORY

R/W

BIT
TAG SERVICE DEVICE ADDRESS NOTE
ADDRESS
STATE 0 STATE 1

F-970-0-HS-420 START / STOP DO STOP 120PD-011A START (1)

F-970-0-HS-421 PERMISSIVE LOC PANEL DO PERMISSIVE LOC PANEL (1)

F-970-0-HS-422 START / STOP DO STOP120PD 011B START (1)

(1)
M
O F-970-0-HS-423 START / STOP DO STOP120PD012A START (1)
D
. F-970-0-HS-424 PERMISSIVE LOC PANEL DO PERMISSIVE LOC PANEL (1)
S
T F-970-0-HS-425 START / STOP DO STOP120PD 012B START (1)
A
.
E
L F-970-0-HS-426 START / STOP DO STOP 120PD013A START (1)
N
F-970-0-HS-427 PERMISSIVE LOC PANEL DO PERMISSIVE LOC PANEL (1)
.
1
F-970-0-HS-428 START / STOP DO STOP 120PD013B START (1)
0
1
/
0

S
H
.
0
9
/
09 NOTES:
(1)THIS SIGNALS ARE FROM FLEX I/O F-970-0-JU-013

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.
Notes
Contractor document Validity
company document identification Revision Sh of Sh
identification Status

Eni CONGO 003028.00.BIEE.A0260 CD-FE 0 24 / 27

MASTER SERIAL LINK


SERIAL INPUTS / OUTPUTS LIST SYSTEM:
PCS UNIT: 970 DESCRIPTION:
SCADA SYSTEM

INSTRUMENT RANGES & ALARMS


COMMENTS

FUN. CODE

HIGH ALARM
LOW ALARM

CODING
MAX RANGE
MIN RANGE

ENG. UNIT
TYPE MEMORY

R/W

BIT
TAG SERVICE DEVICE ADDRESS NOTE
ADDRESS
STATE 0 STATE 1

F-920-0-UL-400 RUNNING DI 510PA001A RUNNING (1)

F-920-0-UL-401 UNAVAILABLE DI 510PA001A UNAVAILABLE (1)

F-920-0-IAX-500 CURRENT MEASURE AI IAX MOTOR CURRENT 4-20mA / 0-500A (1)

(1)
M
O F-920-0-UL-402 RUNNING DI 510PA001B RUNNING (1)
D
. F-920-0-UL-403 UNAVAILABLE DI 510PA001B UNAVAILABLE (1)
S
T F-920-0-IAX-501 CURRENT MEASURE AI IAX MOTOR CURRENT 4-20mA / 0-500A (1)
A
. (1)
E
L F-920-0-UL-404 RUNNING DI 560PA001A RUNNING (1)
N
F-920-0-UL-405 UNAVAILABLE DI 560PA001A UNAVAILABLE (1)
.
1
F-920-0-IAX-502 CURRENT MEASURE AI IAX MOTOR CURRENT 4-20mA / 0-100A (1)
0
1 (1)
/
0 F-920-0-UL-406 RUNNING DI 560PA001B RUNNING (1)

S F-920-0-UL-407 UNAVAILABLE DI 560PA001B UNAVAILABLE (1)


H
. F-920-0-IAX-503 CURRENT MEASURE AI IAX MOTOR CURRENT 4-20mA / 0-100A (1)
0
9 NOTES:
/ NOTES: (1) CABLE FROM/TO 970-JD-101 TO/FROM INTERFACE PANEL. I/P,SPARE CARD.DETAIL WIRING WILL BE DURING DETAIL ENGINEERING.
09

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.
Notes
Contractor document Validity
company document identification Revision Sh of Sh
identification Status

Eni CONGO 003028.00.BIEE.A0260 CD-FE 0 25 / 27

MASTER SERIAL LINK


SERIAL INPUTS / OUTPUTS LIST SYSTEM:
PCS UNIT: 970 DESCRIPTION:
SCADA SYSTEM

INSTRUMENT RANGES & ALARMS


COMMENTS

FUN. CODE

HIGH ALARM
LOW ALARM

CODING
MAX RANGE
MIN RANGE

ENG. UNIT
TYPE MEMORY

R/W

BIT
TAG SERVICE DEVICE ADDRESS NOTE
ADDRESS
STATE 0 STATE 1

F-920-0-UL-408 RUNNING DI 560PA002A RUNNING (1)

F-920-0-UL-409 UNAVAILABLE DI 560PA002A UNAVAILABLE (1)

F-920-0-IAX-504 CURRENT MEASURE AI IAX MOTOR CURRENT 4-20mA / 0-50A (1)

(1)
M
O F-920-0-UL-410 RUNNING DI 560PA002B RUNNING (1)
D
. F-920-0-UL-411 UNAVAILABLE DI 560PA002B UNAVAILABLE (1)
S
T F-920-0-IAX-505 CURRENT MEASURE AI IAX MOTOR CURRENT 4-20mA / 0-50A (1)
A
.
E
L
N
.
1
0
1
/
0

S
H
.
0
9 NOTES:
/ NOTES: (1) CABLE FROM/TO 970-JD-101 TO/FROM INTERFACE PANEL. I/P
09

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.
Notes
Contractor document Validity
company document identification Revision Sh of Sh
identification Status

Eni CONGO 003028.00.BIEE.A0260 CD-FE 0 26 / 27

MASTER SERIAL LINK


SERIAL INPUTS / OUTPUTS LIST SYSTEM:
PCS UNIT: 970 DESCRIPTION:
SCADA SYSTEM

INSTRUMENT RANGES & ALARMS


COMMENTS

FUN. CODE

HIGH ALARM

CODING
LOW ALARM
MAX RANGE
MIN RANGE

ENG. UNIT
TYPE
MEMORY

R/W

BIT
TAG SERVICE DEVICE ADDRESS NOTE
ADDRESS
STATE 0 STATE 1

F-120-0-UL-450 RUNNING DI 120PD011A RUNNING (1)

F-120-0-UL-451 UNAVAILABLE DI 120PA001A UNAVAILABLE (1)

F-120-0-UL-452 RUNNING DI 120PD011B RUNNING (1)

F-120-0-UL-453 UNAVAILABLE DI 120PA001B UNAVAILABLE (1)


M
O (1)
D
. F-120-0-UL-454 RUNNING DI 120PD012A RUNNING (1)
S
T F-120-0-UL-455 UNAVAILABLE DI 120PA002A UNAVAILABLE (1)
A
. F-120-0-UL-456 RUNNING DI 120PD012B RUNNING (1)
E
L F-120-0-UL-458 UNAVAILABLE DI 120PA002B UNAVAILABLE (1)
N
. (1)
1
F-120-0-UL-459 RUNNING DI 120PD013A RUNNING (1)
0
1
F-120-0-UL-460 UNAVAILABLE DI 120PA003A UNAVAILABLE (1)
/
0 F-120-0-UL-461 RUNNING DI 120PD013B RUNNING (1)

S F-120-0-UL-462 UNAVAILABLE DI 120PA003B UNAVAILABLE (1)


H
.
0
9
/
NOTES: (1) THIS SIGNALS ARE FROM FLEX I/O F-970-0-JU-013
09

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.
Notes
Contractor document Validity
company document identification Revision Sh of Sh
identification Status

Eni CONGO 003028.00.BIEE.A0260 CD-FE 0 27 / 27

PHYSICAL INPUTS / OUTPUTS LIST SYSTEM: PCS UNIT: 970 UNIT DESCRIPTION: SCADA SYSTEM

INSTRUMENT SIGNAL SOFTWARE ALARM SET


LOOP
NOTE
LOCA EXECU I/O ELECTRIC. RANGE ENG. REDUN MONI DIAGRAM
TAG SERVICE TYPE FED BY LL L H HH
TION TION TYPE SIGNAL MEASURE UNIT DANT TORING

F-120-0--FSL-001 CHEMICALS FLOW SWITCH DI 24V

F-120-0-FSL-002 CHEMICALS FLOW SWITCH DI 24V

F-120-0-FSL-003 CHEMICALS FLOW SWITCH DI 24V

F-120-0-FSL-004 CHEMICALS FLOW SWITCH DI 24V


M
O
D
.
S
T
A
.
E
L
N
.
1
0
1
/
0

S
H
.
0
8 NOTES:
/
0
9

INTERNAL NORMALIZATION This document is Company property. The Company lawfully reserves all rights.