1.1 General
In this calculation sheet, the following data are calculated and selected
calculation of ventilation system, smoke exhaust system and air-
conditioning system. Mechanical and Natural Ventilation system is
selected for main & auxiliary powerhouse. The control rooms are
equipped with VRF unit air conditioning.
S.No Standard
6
SMACNA.1998 HVAC Duct Construction Standards
and Ventilation design of switchyard.
Item Ventilation
Item Ventilation
Room Ventilation Flow Calculated by Design Minimum Room Air Change Rates
Room Volume
"V" (m3) Ventilation
Air Change DATA PROVIDED BY Flow
S No Area Altitude (m)
rate (h-1) POWER HOUSE CIVIL Qv=ACR∗V
DESIGN (Approximated (m3/h)
Volume)
Main
1
Powerhouse
Cone Ring
1.1 712 3 1800 5400
Floor
Turbine
1.2 728.5 3 8500 25500
Floor
Generator
1.3 739 2 45000 90000
Floor
Spiral Case
1.4 724.3 2 8000 16000
Floor
Machine
1.4 Repair 739 10 800 8000
Room
144900
3 Transformer
Main
3.1 Transformer 739 6 900 5400
Room
3.2 Pump Room 6 740 4440
3.3 GIS Room 0
9840
Auxiliary
4
Powerhouse
Dewatering
4.1 6 350 2100
Pump Room
Pressure Air
4.2 Equipment 8 650 5200
Room
Oil Tank
4.3 6 600 3600
Room
Distribution
4.5 Cabinet 10 850 8500
Room
4.6 Toilet 10 80 800
4.7 LCU Room 8 340 2720
Battery
4.8 8 420 3360
Room
24180
Total Ventilation Flow 181020
As per the Table 1.4 the Ventilation flow is calculated as 1,83,000 m^/hr Taking a design
margin of 15% we get the Air flow as 1,99,122 m^3/hr.
Hence 3 Cabinet fan of capacity 100000 m^3/hr is used for the Main and Auxiliary
Powerhouse, out of which 2 are working & 1 is standby.
3 Transformer
3.1 Main Transformer Room 5400 6500 1
3.2 Pump Room 4440 6000 1
3.3 GIS Room
4 Auxiliary Powerhouse
4.1 Dewatering Pump Room 2100 3000 1
4.2 Pressure Air Equipment Room 5200 6500 1
4.3 Oil Tank Room 3600 5000 1
4.5 Distribution Cabinet Room 8500 6000 2
4.6 Toilet 800 1200 1
4.7 LCU Room 2720 4300 1
4.8 Battery Room 3360 4500 1
200000
ii. Air conditioning design of auxiliary powerhouse
Fresh air unit shall be provided for Auxiliary powerhouse, where the
fresh air is heated in winter and cooled in summer through new fan and
then delivered to the rooms through air intake shaft.
Confere
Master Relay nce/ Total
Zone control Computer Document Resting protectio Meetin Cooling
Name rooms rooms Room Room n rooms Offices g room Load
Equipment
Heat
Emissi
on(K
W) 18 0.2 0.16 0.16 8 0.2 0.3 26.92
b. 1.4.2.1.b. Lighting Heat Emission
Total
Coolin
Master Relay Conference/
g Load
control Computer Document Resting protection Meeting
Zone Name rooms rooms Room Room rooms Offices room
Lighting Heat 1.6 0.3 0.18 0.18 1.2 0.25 0.4 4.31
Emission(KW)
Total
Coolin
Master Relay Conference/
g Load
control Computer Document Resting protection Meeting
Zone Name rooms rooms Room Room rooms Offices room
Lighting Heat 1.6 0.3 0.18 0.18 1.2 0.25 0.4 4.31
Emission(KW)
Latent
Sensible Heat/
Heat/ Person Person
Zone Name Number of people (W) (W) Total (KW)
Master control rooms 5 90 30 0.6
Computer rooms 5 90 30 0.6
Document Room 3 90 30 0.36
Resting Room 5 90 30 0.6
0
Relay protection rooms - - -
Offices 10 90 30 1.2
Conference/ Meeting
room 20 90 30 2.4
Total 5.76
B. 1.4.2.2 External loads
30.58485
Total
VRV system shall be applied or any other suitable system for the master
control room, computer room, document room, resting room, relay
protection room, offices, conference/meeting rooms.
Indoor Units
Calculation formulas
Qex = qexAd
Where
Selected
Smoke Exhaust Flow Area of single zone smoke
Altitude per unit area qex selected for smoke exhaust fan
No Area (m) (m^3/h*m^2) exhaust (m^3/hr)
Generator
1 Floor 739 120 350 42000
Where
Ps velocity pressure, Pa
P= Pt + Ps
Where
Pt total pressure, Pa
Ps static pressure, Pa
vii.
Design Basis and Standards
ANSI/ ASHRAE Standard 62-2004 Ventilation for Acceptable Indoor Air Quality.
ANSI/ ASHRAE Standard 22-2004 Methods of Testing For Rating Water-Cooled Refrigerant
Condensers.