ILLUMINATION CALCULATION ACCORDING TO BZ- METHOD, IES
ITEM NO. DESCRIPTION SYMBOL FORMULA/UNIT VALUES FINAL 1 ROOM WIDTH W m 5.3 2 ROOM LENGTH L m 10.5 3 ROOM AREA Af L*W 55.65 4 TOTAL HEIGHT Ht m 4 5 SUSPENSION HEIGHT Hs m 1 6 MOUNTING HEIGHT Hm Ht-Hs-0.8 2.15 7 ROOM INDEX Kr L*W / Hm(L+W) 1.64 8 REFLECTANCE CEILING Rc 0.7 WALLS Rw 0.5 FLOOR Rf 0.3 9 NO. OF LIGHTING SOURCES n 1 PER LUMINAIRE 10 UTILIZATION FACTOR Uf 0.55 11 REDUCTION FACTOR k 2 12 DEPRECIATION FACTOR f SEE TABLE 1.37 13 TYPE OF LAMP SEE LAMP DATA 36W LED 14 LUMINOUS FLUX PER LAMP Lm SEE LAMP DATA 5200 15 WANTED ILLUMINANCE E LUX 300 16 NUMBER OF LUMINAIRES N E*Af*f / Lm*n*Uf*k 4.00 4 17 NUMBER OF LUMINAIRES SQR. ROOT OF 2.80 3 ALONG (L*N / W) 18 NUMBER OF LUMINAIRES SQR. ROOT OF 1.40 1 ACROSS (W*N / L) 19 CONTROL OF ILLUMINANCE E N*Lm*n*Uf*k /Af*f 300.10
TABLE FOR DEPRECIATION FACTORS ( f )
THE LABELLED VALUES ARE FOR Rw =0.3, CLEANING ONCE A YEAR. FOR Rw = 0.5 THE VALUES MUST BE INCREASED BY 0.04 LUMINAIRE TYPE SURROUNDINGS TUBES/INCANDESCENT OFFICES OTHERS Rw =0.5 OPEN LUMINAIRE CLEAN 1.27 1.33 (+0.04) SUBURBS 1.33 1.42 (+0.04) CENTER OF TOWN 1.42 1.48 (+0.04) DIRTY 1.48 1.54 (+0.04) VENTILATED THROUGH CLEAN 1.27 1.27 (+0.04) REFLECTOR SUBURBS 1.33 1.33 (+0.04) CENTER OF TOWN 1.42 1.42 (+0.04) DIRTY 1.48 1.48 (+0.04) DUSTIGHT LUMINAIRE CLEAN 1.27 1.27 (+0.04) SUBURBS 1.33 1.33 (+0.04) CENTER OF TOWN 1.42 1.42 (+0.04) DIRTY 4.48 1.18 (+0.04) NON- VENTILATED LUMINAIRE CLEAN 1.33 1.5 (+0.04) WITH PLASTIC DIFFUSER SUBURBS 1.39 1.61 (+0.04) CENTER OF TOWN 1.54 1.69 (+0.04) DIRTY 1.61 1.78 (+0.04) VENTILATED LUMINAIRE WITH CLEAN 1.33 1.45 (+0.04) LOUVER OR PLASTIC DIFFUSER SUBURBS 1.39 1.54 (+0.04) CENTER OF TOWN 1.48 1.61 (+0.04) DIRTY 1.54 1.69 (+0.04) RECESSED LUMINAIRE WITH CLEAN 1.27 1.39 (+0.04) LOUVER OR PLASTIC DIFFUSER SUBURBS 1.33 1.48 (+0.04) CENTER OF TOWN 1.42 1.54 (+0.04) DIRTY 1.48 1.61 (+0.04)