10.SAMPLE DESCRIPTION
Laboratory General Terms and Conditions as mentioned in Annex A. This report shall not be reproduced, except in full, without the written approval of the laboratory
Sampling not done by the laboratory and result relates to sample tested only.
*Indicates information supplied by the customer for which the laboratory has no control.
Construction Services Laboratory, Bureau Veritas Lanka (Pvt) Ltd., No 34, Sanchi Arachchi Gardens, St. Sebastian Hill, Colombo12.
Tel : +94 11 244 0950, +94 11 473 4325 Fax : +94 11 462 8629 E-mail:cmtlab.colombo@lk.bureauveritas.com
Page 1 of 3
Lab Ref. No: 2022/294 Report No: CT/22/030_A
11.TESTS REQUESTED
1) Mechanical requirements
i. Compressive Strength: 2 days
ii. Compressive Strength: 28 days
2) Physical requirements
i. Initial Setting time
ii. Soundness (Expansion)
3) Chemical requirements
i. Alkali Limits
12.TEST SPECIFICATIONS*
≥ 42,5
2 28 days compressive strength EN 196-1
≤ 62,5 MPa
13.TEST METHODS
Code Title
Laboratory General Terms and Conditions as mentioned in Annex A. This report shall not be reproduced, except in full, without the written approval of the laboratory
Sampling not done by the laboratory and result relates to sample tested only.
*Indicates information supplied by the customer for which the laboratory has no control.
Construction Services Laboratory, Bureau Veritas Lanka (Pvt) Ltd., No 34, Sanchi Arachchi Gardens, St. Sebastian Hill, Colombo12.
Tel : +94 11 244 0950, +94 11 473 4325 Fax : +94 11 462 8629 E-mail:cmtlab.colombo@lk.bureauveritas.com
Page 2 of 3
Lab Ref. No: 2022/294 Report No: CT/22/030_A
Serial
Parameter Unit Results Specification* Compliance
No
Mechanical Requirement
Compressive Strength
19.4
19.6
21.3 Avg, Complies
i. Early Strength 2 Days N/mm2 ≥ 10.0
20.6 20.2
20.3
19.7
44.8
46.3
Avg,
2 45.8 ≥ 42.5
ii. Standard Strength: 28 days N/mm 46.4 Complies
45.9 ≤ 62.5
47.5
48.2
Physical Requirement
Setting time
i. Initial Setting time min 202 ≥ 60 Complies
Soundness mm 1.98 ≤ 10 Complies
Chemical requirements
Alkali Limit % 0.28 0.60% maximum Complies
Sign for,
Construction Materials Testing Laboratory, Bureau Veritas Lanka (Pvt) Ltd.
Laboratory General Terms and Conditions as mentioned in Annex A. This report shall not be reproduced, except in full, without the written approval of the laboratory
Sampling not done by the laboratory and result relates to sample tested only.
*Indicates information supplied by the customer for which the laboratory has no control.
Construction Services Laboratory, Bureau Veritas Lanka (Pvt) Ltd., No 34, Sanchi Arachchi Gardens, St. Sebastian Hill, Colombo12.
Tel : +94 11 244 0950, +94 11 473 4325 Fax : +94 11 462 8629 E-mail:cmtlab.colombo@lk.bureauveritas.com
Page 3 of 3
Lab Ref. No: 2022/291 Report No: CT/22/031_A
j. Quantity received
r��,.,,_-
�,r
.,rn;�Tini.
••v••-•·- •�• •
n'kiun•1�•
k ,uv,I ,·1�·'i•
� Construction Services Labon1tory
k. Sample drawn by Client No. 34, Sanchi Arachchi GardE1ns
ltll &
\'i�- �L �eoasuan n111 1 vv1v111uv 1.L, i>JI Lcul"".
Tel: +94112 440 948-50/+94114 734 325-6
#/#f. To be continued #/#f. �Fai_<: +94 114 628 629
�Email: cmllab.colombo@lk.bureauventas.com
REG. NO: PV 1550
Laboratory General Terms and Conditions as mentioned in Annex A This report shall not be reproduced , except in full, without the written approval of the laboratory
Sampling not done by the laboratory and result relates to sample tested only,
*Indicates info rmation supplied by the customer fo r which the laboratory has no control.
Construction Services Laboratory, Bureau Veritas Ll!-nka (Pvt) Ltd., No 34, Sanchi Arachchi Gardens, St. Sebastian Hill, Colombo 12.
Tel : +94 11 244 0950, +94 11 473 4325 Fax : +94 11 462 8629 E-mail:cmtlab.colombo@lk.bureauveritas.com
Page 1 of3
Lab Ref. No: 2022/291 Report No: CT/22/0 31_A
11.TESTS REQUESTED
1) Mechanical requirements
I. Compressive Strength: 2 days
II. Compressive Strength: 28 days
2) Physical requirements
I. Initial Setting time
II. Soundness (Expansion)
3) Chemical requirements
I. Alkali Limits
12.TEST SPECIFICATIONS*
:C: 42,5
2 28 days compressive strength EN 196-1
:S 62,5 MPa
13.TEST METHODS
Code Title
I
#:f:1:#. To be continued #:f:1:#. i O
BU!i!iiiivER iASLAllKA IPV f) LI:
Construction Services �aborntory,
No. 34, Sanchl Arachch1 Garde,,s,
SL Sebastian Hill, Colombo 12, Sri Lanka.
Tel: +94112 440 948·50 /+94114 734 325-6
WJJJtn
Fax: +94 114 628 629
[l!JJ Email: cmtlab.colombo@lk.bureauveritas.com
.
REG. NO: PV 1550
Laboratory General Terms and Conditions as mentioned in Annex A This report shall not be reproduced, except in full, without the written approval of the laboratory
Sampling not done by the laboratory and result relates to sample tested only.
*Indicates information supplied by the customer for which the laboratory has no control.
Construction Services Laboratory, Bureau Veritas Lanka (Pvt) Ltd., No 34, Sanchi Arachchi Gardens, St. Sebastian Hill, Colombo I 2.
Tel : +94 11 244 0950, +94 11 4 73 4325 Fax : +94 l l 462 8629 E-mail:cmtlab.colombo@lk.bureauveritas.com
Page 2 of3
Lab Ref. No: 2022/291 Report No: CT/22/031_A
Serial
Parameter Unit Results Specification* Compliance
No
Mechanical Requirement
• Compressive Strength
20.8
22.0
20.6 Avg, Complies
I. Early Strength 2 Days N/mm2 > 10.0
-
21.7 21.1
20.8
20.7
48.6
51.4
50.9 Avg, 2': 42.5
II. Standard Strength: 28 days N/mm2 Complies
49.7 50.4 :'.S 62.5
49.9
51.6
Physical Requirement
• Setting time
I. Initial Setting time min 202 :::: 60 Complies
• Soundness mm 1.7 :'.S 10 Complies
Chemical requirements
• Alkali Limit % 0.26 0.60% maximum Complies
Sign for,
Construction Materials Testing Laboratory, Bureau Veritas Lanka (Pvt) Ltd.
Checked by:
�
.
:
Authorized by: ......
;J¥.. . . . .
' >
Construction Services Laboratory, Bureau Yeritas Lanka (Pvt) Ltd., No 34, Sanchi Arachchi Gardens, St. Sebastian Hill, Colombo12.
Tel : +94 11 244 0950, +94 11 473 4325 Fax: +94 11 462 8629 E-mail:cmtlab.colombo@lk.bureauveritas.com
Page 3 of3
Lab Ref. No: 2022/292 Report No: CT/22/032_A
T
### To be continued### �::--BUREAi VER!i'As LANKA (r'Vf) l'rD.
Construction Services Laboratory,
No. 34, Sanchi Arachchi Gardens,
St Sebastian Hill, Colombo 12, Sri Lanka.
Labora tory General Terms and Condit ions as ment ioned in Annex A Th is report sh all not be reproduced, e c , Xf<illiVJ41Ji,u;iijll@.51111ll:)JjVjlj�ml! atory
Sampling not done by th e laboratory and result relates to sample tested only.
*Indicates informat ion supplied by th e customer for wh ich th e laboratory h as no control. mllll.ll
� Fax: +94114 628 629
Em�II: cmllab.colombo@lk.bureauveritas.com
REG. NO: PV 1550
Construction Services Laboratory, Bureau Veritas Lanka (Pvt) Ltd., No 34, Sanchi Arachchi Gardens, St. Sebastian Hill, Colombo 12.
Tel : +94 11 244 0950, +94 11 473 4325 Fax : +94 I I 462 8629 E-maiI :cmtl ab.colornbo@I k.bureau veritas.com
Page 1 of3
Lab Ref No: 2022/292 Report No: CT/22/032_A
11.TESTS REQU�STED
1) Mechanical requirements
1. Compressive Strength: 2 days
11. Compressive Strength: 28 days
2) Physical requirements
I. Initial Setting time
II. Soundness (Expansion)
3) Chymical requirements
I. Alkali Limits
12.TEST SPECIFICATIONS*
2': 42,5
2 28 days compressive strength EN 196-1
:S 62,5 MPa
13.TEST METHODS
Code Title
Construction Services Laboratory, Bureau Veritas. Lanka (Pvt) Ltd., No 34, Sanchi Arachchi Gardens, St. Sebastian Hill, Colombo 12.
Tel : +94 11 244 0950, +94 11 473 4325 Fax : +94 11 462 8629 E-mail:cmtlab.colombo@lk.bureauveritas.com
Page 2 of3
Lab Ref No: 2022/292 Report No: CT/22/032_A
Serial
Parameter Unit Results Specification* Compliance
No
Mechanical Requirement
• Compressive Strength
21.7
20.8 Avg,
I. Early St;ength 2 Days N/mm2 20.6 > 10.0 Complies
20.8 21.0
21.6
20.6
49.7
' 48.7 Avg, 2: 42.5
II. Standard Strength: 28 days N/mm 2 51.4
Complies
49.9 49.6 :S 62.5
47.9
49.8
Physical Requirement
• Setting time
I. Initial Setting time mm 209 2: 60 Complies
• Soundness mm 1.09 :s 10 Complies
Chemical requirements
• Alkali Limit % 0.23 0.60% maximum Complies
Sign for,
Construction Materials Testing Laboratory, Bureau Veritas Lanka (Pvt) Ltd.
Laboratory General Terms and Conditions as mentioned in Annex A This report shall not be reproduced, except in full, without the written approval of the laboratory
Sampling not done by the laboratory and result relates to sample tested only.
*Indicates information supplied by the customer for which the laboratory has no control.
Construction Services Laboratory, Bureau Veritas. Lanka (Pvt) Ltd., No 34, Sanchi Arachchi Gardens, St. Sebastian Hill, Colombo12.
Tel : +94 11 244 0950, +94 11 4 73 4325 Fax : +94 11 462 8629 E-mail:cmtlab.colombo@lk.bureauveritas.com
Page 3 of3