TESTING & COMMISSIONING

INSPECTION REQUEST (T&C)

Aconex Transmittal No: HBKC-TRANSMIT-01


T&C Reference No.: MMC-HBK-AP-TC-MD-00153 Rev. No.: 0 Date: 23-Oct-2023
Engineering, Procurement and Construction (EPC / Turnkey) for Military Medical City Hospital at Tarek Bin
Project Name:
Zeyad Camp in Sailiyah (South of Doha)
Project Number: AA-103-01
Mr. Alaaddin Aktan Brig. (Eng./Air) Abdulrahman Ali Al-Abdulmalik
From: To:
Project Director /Contractor's Representative MMC Project Director

QATAR ARMED FORCES


Contractor: HBK Contracting Company Employer: Military Medical City Hospital
Project Management Office

Discipline: Architectural Civil Structural Electrical / ICT Mechanical Medical General

Supporting
Proposed Inspection Date: 24-Oct-2023 Inspection time: 10am
Documents

Location: Building: Zone: Level: Approved Drawing


B01 Z01 L0
Material Approval
MST / ITP
Room No.: Z1-L0-IMD-002 Room Name: BONE DENSITY Others

MST Reference No.: Drawing Reference No.:


MMC-HBK-ABAM-AP-MST-MD-0009
MAT Reference No.:
MMC-ABAM-AP-MAT-MD-0045 0
IR Reference No.:
MMC-HBK-AP-IR-MD-00098

Inspection Detailed Description:

MEQ Inspection of Imaging & Dental Package

Material IR Reference (MIR) MEQ Delivery No. Supplier Country of Origin

MMC-HBK-AP-MIR-MD-00217 MO-32394104 Ali Bin Ali Medical USA

Cad ID Equipment Name Manufacturer Model Serial Number Quantity

Horizon W Bone
DST0051 Densitometer, Bone, Whole Body Hologic 307543M 1
Densitometer

SUB-CONTRACTOR CONTRACTOR
Engineer Engineer / CM QA/QC Representative Project Director
Requested by: Requested/Verified by: Verified by: Approved by:

Signature:
Company: Ali Bin Ali Medical Signature: Signature: Signature:
Name: Mr. Paulino Flores Name: Mr. Ibrahim Name: Mr. Rakesh NK Name: Mr. Alaaddin Aktan
Date: 23-Oct-2023 Date: 23-Oct-2023 Date: 23-Oct-2023 Date: 23-Oct-2023

EMPLOYER
Comments / Recommendation:

Employer Action Code: A (Approved) B (Approved with Comments) C (Revise & Resubmit) D (Rejected)

Note: To attach the Employer's comment response sheet after the inspection.
The approval and comments shall not in any ways relieve or absolve the Contractor from compliance of any obligations or liability under or in connection with the Contract, Project
Requirements and Specification.
MMC-HBK-QA-F024 Rev.0, Dated 12.09.2023 Page 1 of 1
MEDICAL EQUIPMENT
COMMISSIONING REPORT

Commissioning Report No.: MMC-HBK-AP-TC-MD-00152 Rev. No.: 0 Date: 23-Oct-23


Engineering, Procurement and Construction (EPC / Turnkey) for Military Medical City Hospital
Project Name:
at Tarek Bin Zeyad Camp in Sailiyah (South of Doha)
Project Number: AA-103-01
QATAR ARMED FORCES
Contractor: HBK Contracting Company Employer: Military Medical City Hospital
Project Management Office
MEQ Subcon: Ali Bin Ali Medical

Prot. n°: Real Property Tag No.:

Date: 23-Oct-23 Main Unit Tag No.: Real Property Tag


(in case of impossibility to attach on the item, it will be stick here)
Dept.: Radiology
Level: L0 Room No.: Attached List

Item Code: DST0051


Description: Densitometer, Bone, Whole Body
Quantity: 1 Brand: Hologic
Horizon W Bone
Serial No.: 307543M Model: Densitometer
Acc. Description:

MEQ INSTALLATION AND TEST REPORT DETAILS (to attached approval copy)

Installation and Test Report No. (ITR): MMC-HBK-AP-IR-MD-00098 Rev. No.: 0 Date: 23-Oct-23

COMMISSIONING

STATUS
SN ACTIVITIES
PASSED FAILED N/A

1 Software Integration

Consumables Check
2
(to be applied to the Consumables NOT inspected during the Testing phase)

3 Performance Assurance Testing (Quality Check)

Legend: Passed (Successfully Performed) Failed (Not Successfully Performed) N/A (Not Applicable)

DOCUMENTATION

SN DOCUMENT DOCUMENT REFERENCE ACONEX WF REFERENCE TO BE SUBMITTED N/A


1 As-built Drawings
2 Operator Manual Uploaded on Aconex under following path:
3 Service Manual Uploaded on Aconex under following path:
4 Medical Equipment commissioning manufacturer check List attached
Software Package
5
(CD or USB)
Calibration (or) Cleaning Kit,
6
where applicable

Remarks:

Enclosures

MEQ Subcontractor Contractor Employer


Signature: Signature: Signature:

Name: Paulino Flores Name: Name:

Designation: Project Engineer Designation: Designation:

K‐P1‐QC‐F150 Rev.1,Dated 05.04.2023 Page 1 of 3


MEDICAL EQUIPMENT
COMMISSIONING REPORT

Date: 27-Aug-23 Date: Date:

K‐P1‐QC‐F150 Rev.1,Dated 05.04.2023 Page 2 of 3


MEDICAL EQUIPMENT
COMMISSIONING REPORT
MEDICAL EQUIPMENT COMMISSIONING CHECKLIST
STATUS
SN SECTION
PASSED FAILED N/A
1 IT Integration

1.a LIS
1.b RIS
1.c PIS
1.d PACS
1.e HIS / CIS
1.f Data Network connectivity
1.g Wireless Network connectivity
1.h Terminal Server integration
1.i Other #1:
1.j Other #2:
2 Software updated
3 Positioning
3.a Equipment positioned in the final location
3.b Equipment location is functional and operational
4 Accessories and consumables
4.a Expiry date of consumables subsequent commissioning date
4.b Accessories and consumables stored properly
5 Documents
5.a FDA/CE certification
5.b CoO (Country of origin) Certificate
5.c As-built Software configuration
5.d Operational and Service manuals uploaded on Aconex
6 Functional and Operational Verification
6.a Verification
6.b Image QA
6.c Functional and operational test as per the manufacture standards
6.d Test #1 not done in the RFIT:
6.e Test #2 not done in the RFIT:
Integration with other Medical equipment
7
Tag No. Item No. Item Description
7.a
7.b
7.c
7.d
7.e
8 Tags
8.a Electrical Safety Test Tag
8.b Inventory tag
8.c Battery check tag
9 ECRI/FDA recalls / clearance certificate to be attached
Legend: Passed (Successfully Performed) Failed (Not Successfully Performed) N/A (Not Applicable)

Notes

K‐P1‐QC‐F150 Rev.1,Dated 05.04.2023 Page 3 of 3


INSPECTION REQUEST (IR)

Aconex Transmittal No: HBKC-TRANSMIT-01


IR Reference No.: MMC-HBK-AP-IR-MD-00098 Rev. No.: 0 Date: 21-Oct-2023
Engineering, Procurement and Construction (EPC / Turnkey) for Military Medical City Hospital at Tarek
Project Name:
Bin Zeyad Camp in Sailiyah (South of Doha)
Project Number: AA-103-01
Mr. Alaaddin Aktan Brig. (Eng./Air) Abdulrahman Ali Al-Abdulmalik
From: To:
Project Director /Contractor's Representative MMC Project Director

QATAR ARMED FORCES


Contractor: HBK Contracting Company Employer: Military Medical City Hospital
Project Management Office

Discipline: Architectural Civil Structural Electrical / ICT Mechanical Medical General

Supporting
Proposed Inspection Date: 22-Oct-2023 Inspection time: 10:00am
Documents
Location: Building: Zone: Level: Approved Drawing
B01 Z01 L0
Material Approval
MST / ITP
Room No.: Z1-L0-IMD-002 Room Name: BONE DENSITY Others

MST Reference No.: MAT Reference No.: Type of Inspection:

MMC-HBK-ABAM-AP-MST-MD-0009 MMC-ABAM-AP-MAT-MD-0045 Hold

Inspection Detailed Description:

MEQ Inspection of Imaging & Dental Package

Material IR Reference (MIR) MEQ Delivery No. Supplier Country of Origin

MMC-HBK-AP-MIR-MD-00217 MO-32394104 Ali Bin Ali Medical USA

Cad ID Equipment Name Manufacturer Model Serial Number Quantity

Horizon W Bone
DST0051 Densitometer, Bone, Whole Body Hologic 307543M 1
Densitometer

SUB-CONTRACTOR CONTRACTOR
Engineer Engineer / CM QA/QC Representative Project Director
Requested by: Requested/Verified by: Verified by: Approved by:

Signature:
Company: Ali Bin Ali Medical Signature: Signature: Signature:
Name: Mr. Paulino Flores Name: Mr. Ibrahim Name: Mr. Rakesh NK Name: Mr. Alaaddin Aktan
Date: 21-Oct-2023 Date: 21-Oct-2023 Date: 21-Oct-2023 Date: 21-Oct-2023

EMPLOYER
Comments / Recommendation:

Employer Action Code: A (Approved) B (Approved with Comments) C (Revise & Resubmit) D (Rejected)

Note: To attach the Employer's comment response sheet after the inspection.
The approval and comments shall not in any ways relieve or absolve the Contractor from compliance of any obligations or liability under or in connection with the Contract, Project
Requirements and Specification.
MMC-HBK-QA-F007 Rev.7, Dated 08.10.2022 Page 1 of 1
MATERIAL INSPECTION REQUEST (MIR)

Aconex Transmittal No.: HBKC-TRANSMIT-01


MIR Reference No.: MMC-HBK-AP-MIR-MD-00217 Rev. No.: 0 Date: 2-Aug-2023
Engineering, Procurement and Construction (EPC / Turnkey) for Military Medical City Hospital at Tarek
Project Name :
Bin Zeyad Camp in Sailiyah (South of Doha)
Project Number: AA-103-01
Mr. Alaaddin Aktan Brig. (Eng./Air) Abdulrahman Ali Al-Abdulmalik
From: To:
Project Director /Contractor's Representative MMC Project Director

QATAR ARMED FORCES


Contractor: HBK Contracting Company Employer: Military Medical City Hospital
Project Management Office

Discipline: Architectural Civil Structural Electrical / ICT Mechanical Medical General

Proposed Inspection Date: 3-Aug-2023 Inspection Time: 10:00 AM Location: HBK Site Store (On-site)

Supporting Documents: Material Approval Delivery Note Country of Origin Test Reports Others

Supplier: Ali Bin Ali Medical

Material Inspection Detailed Description:

MEQ Material Inspection of Radiology Package

MAT Reference MEQ Delivery No.

MMC-ABAM-AP-MAT-MD-0045_Rev.0 Code B MO-32394104

Country of
Cad ID MEQ Item Description Manufacturer Model Quantity
Origin

Horizon W Bone
DST0051 Densitometer, Bone, Whole Body Hologic USA 1
Densitometer

SUB-CONTRACTOR CONTRACTOR
Engineer Store QA/QC Representative Project Director
Requested by: Requested/Verified by: Verified by: Approved by:

Company: Ali Bin Ali MedicalSignature: Signature: Signature:


Name: Mr. Paulino Flores Name: Mr. Ghouse Name: Mr. Rakesh N.K. Name: Mr. Alaaddin Aktan
Date: 2-Aug-2023 Date: 2-Aug-2023 Date: 2-Aug-2023 Date: 2-Aug-2023

EMPLOYER
Comments / Recommendation:
1.) Refer attached HBK/SECO Comments
2.) Provide clarification regarding the COO.
3.) Packing list to be provided
4.) Final approval is subject to succesfull T&C and MOPH approval

Employer Action Code: A (Approved) B (Approved with Comments)  C (Revise & Resubmit) D (Rejected)

Note: To attach the Employer's comment response sheet after the inspection.
This document shall not relieve Contractor of his liabilities under the Contract or constitute authorization of any change to Contract documents.

MMC-HBK-QA-F004 Rev.6, Dated 08.10.2022 Page 1 of 1


SITE PLAN

E
N
B07 B08

S
N
LA
.63
W
QIB
252
B14

B09 B05

B02 B03
B01

B06
B12 B13
B11
B10
B04

3713
1715 1998
GENERAL NOTES
PROJECT REFERENCE ELEVATION ±0.00 IS AT +27.50 QATAR NATIONAL DATUM. ELEVATIONS SHOWN
ARE WITH RESPECT TO THE PROJECT REFERENCE ELEVATION OF ±0.00 AT GROUND FLOOR.
ALL DIMENSIONS ARE IN MM UNLESS NOTED OTHERWISE.
DO NOT OBTAIN DIMENSIONS BY SCALING FROM DRAWINGS.
REFER TO TOPOGRAPHICAL SURVEY MMC-HBK-AP-AD-GI-L0-AZ-1001_1015 BY GSL FOR ORIGIN OF
LEVELS.
THIS DRAWING SHALL BE READ IN CONJUNCTION WITH ALL DRAWINGS, ENGINEERING
1. SPECIFICATIONS, ALL OTHER CONSULTANT DOCUMENTATION, AND ALL OTHER WRITTEN
INSTRUCTIONS WHICH MAY BE ISSUED DURING THE COURSE OF THE CONTRACT.
2. CONTRACTOR TO COORDINATE AS PER SITE CONDITIONS.
3. IN THE EVENT OF CONFLICT BETWEEN DRAWINGS DATA & SPECIFICATION DATA. THE

DST0051b 4.

5.
SPECIFICATION SHALL GOVERN. DETAIL DRAWINGS TAKE PRECEDENCE OVER DRAWINGS OF
SMALLER SCALE. SHOULD THE CONTRACTOR AT ANYTIME DISCOVER AN ERROR IN A DRAWING OR
SPECIFICATIONS, OR A DISCREPANCY OR VARIATION BETWEEN DIMENSIONS ON DRAWINGS &
MEASUREMENT AT SITE, OR LACK OF DIMENSIONS OR OTHER INFORMATION CONTRACTOR SHALL

SCL0549 STL0112 6.
REPORT AT ONCE TO THE ARCHITECT FOR CLARIFICATION AND SHALL NOT PROCEED WITH THE
WORK AFFECTED UNTIL CLARIFICATION HAS BEEN MADE.

306

750
KEY PLAN 1
10 10.1 17 17.1
26

788
A
P01 P02 P03 P04 P05 A

P2.1 P3.1

1086 P2.A P15


F

P16
P06 P07 P08
P18
F

P19 P3.A

HAM0009 P2.F

P2.1
P17
P09 P10 P11
P20
P3.1
P3.F

P12 P13 P14


V V

1410 6 13 13.1 21

REFERENCE DOCUMENTS
2857

DOCUMENT NO TITLE REV


407
STL0170

2020
2404 DST0051 MILITARY MEDICAL CITY HOSPITAL - AL SAILIYAH

B 100 Approval Status

Approved as
Commented

C Re-Submit
A Approved

D Rejected
Revise &
3402 Authority Signature Date
5075

B
MMC-PMO

A The approval and comments shall not in any ways relieve or absolve the
Contractor from compliance of any obligations or liability under or in connection
with the contract, project requirements and specifications.

3402

2326 2 DEXA HOLOGIC SAMPLE IMAGE 1 ISSUED FOR CONSTRUCTION 03/05/2023 ABAM ABAM PR SG

MEQ-3401 SCALE: NTS 0 ISSUED FOR CONSTRUCTION 03/02/2023 ABAM ABAM PR SG


REV REVISION DETAILS DATE DWN DES CHD APD
EMPLOYER

QATAR ARMED FORCES


BONE DENSITY MILITARY MEDICAL CITY HOSPITAL PROJECT
MANAGEMENT OFFICE P.O. BOX 2075 DOHA,
QATAR

Z1-L0-IMD-002 EQUIPMENT LEGEND MAIN CONTRACTOR:

HBK CONTRACTING CO. WLL


2304
2218

P.O. BOX 1362 DOHA, QATAR


ITEM DESCRIPTION BTU/HR WT/LBS WIDTH DEPTH HEIGHT TEL: (974) 44451111 FAX: (974) 44451000

LEAD CONSULTANT:
HOLOGIC MEINHARDT
DST00521b 'HORIZON W' 34kg 610mm 670mm 1190mm 14TH FLOOR AMWAL TOWER WESTBAY
P.O. BOX 1362 DOHA, QATAR
OPERATOR CONSOLE TEL: (974) 44117840 FAX: (974) 4411 7845

3713 ARCHITECT & INTERIOR DESIGNER:

HOLOGIC
DST00521 'HORIZON W' 3400 311kg 2020mm 1287mm 1420mm
TABLE MEDICAL PLANNER: MEDICAL EQUIPMENT : SUBCONTRACTOR :

SITE CONDITIONS FOR 'HORIZON W SYSTEM PROJECT TITLE:

ENGINEERING, PROCUREMENT AND


CONSTRUCTION (EPC/TURNKEY) FOR
RECOMMENDED CEILING HEIGHT STANDARD HEIGHT MILITARY MEDICAL CITY HOSPITAL
(MMC) AT TAREK BIN ZEYAD CAMP
AMBIENT CONDITIONS: 15°C - 32°C IN SAILIYAH (SOUTH OF DOHA)
OPERATING TEMPERATURE
PROJECT NO. AA-103-01
RELATIVE HUMIDITY 20 - 80% , NON CONDENSING. DRAWING TITLE:

BUILDING 01 - ZONE 01 - PART 06- GROUND FLOOR - BONE


MAXIMUM ALLOWABLE CHANGE, 10% /HOUR DENSITOMETRY (Z1-L0-IMD-002) - DEXA (Hologic)

HALL 1 DEXA HOLOGIC PLACEMENT LAYOUT PLAN EQUIPMENT ENTRY REQUIREMENTS:


PRE-INSTALLATION - EQUIPMENT ARRANGEMENT PLAN
THIS DRAWING HAS BEEN CHECKED FOR COMPLETENESS, ACCURACY, COORDINATION, AND
COMPLIANCE WITH THE CONTRACT DOCUMENTS. ALL DIMENSIONS AND FIELD CONDITIONS

MEQ-3401 SCALE: 1:15 MINIMUM RECOMMENDED CORRIDOR WIDTH 1300mm HAVE BEEN VERIFIED.

MINIMUM DOOR WIDTH 1150mm x 2100mm


RECOMMENDED DOOR WIDTH 1200mm x 2100mm CONTRACTOR'S REPRESENTATIVE:
Mr. ALAADDIN AKTAN
DATE:
04 May 2023

STATUS:

ISSUED FOR CONSTRUCTION

SUBMISSION STAGE DATE

WORKING DRAWING 04/05/2023

DRAWN DESIGN CHECKED

ABAM PRABHU
ABAM

DESIGNED SCALE A1

ALI BIN ALI 1:50

DRAWING NO. REVISION NO.

MMC-HBK-P1-WD-B01-MEQ-L0-P06-3401 1

BIM MODEL REFERENCE :


SITE PLAN

E
N
B07 B08

S
N
3712

LA
.63
W
QIB
252
B14
3712 B05
2400 B09

2400 B02
B01
B03

1500 ELECTRICAL LEGEND


1500

B06
B12 B13
B11
B10
B04

ITEM DESCRIPTION

105
DEDICATED WALL SOCKET 230V, 13 AMP, 1PH H@500MM
150x100mm TRUNKING BY HBK
HOSPITAL GRADE 2X DUPLEX OUTLET FROM PDB
EMERGENCY 25mm GI CONDUIT FOR WITH ISOLATED GROUND.

1000
160 25mm GI CONDUIT FOR GENERAL NOTES
STOP SWITCH BY HBK PDB - Power Distribution WALL SOCKET FROM PDB PROJECT REFERENCE ELEVATION ±0.00 IS AT +27.50 QATAR NATIONAL DATUM. ELEVATIONS SHOWN

845
ARE WITH RESPECT TO THE PROJECT REFERENCE ELEVATION OF ±0.00 AT GROUND FLOOR.
+1500mm aFFL box by HBK EMERGENCY STOP FROM PDB DEDICATED FLOOR SOCKET 230V, 13 AMP, 1PH H@500MM ALL DIMENSIONS ARE IN MM UNLESS NOTED OTHERWISE.
DO NOT OBTAIN DIMENSIONS BY SCALING FROM DRAWINGS.
REFER TO TOPOGRAPHICAL SURVEY MMC-HBK-AP-AD-GI-L0-AZ-1001_1015 BY GSL FOR ORIGIN OF
1941 HOSPITAL GRADE 2X DUPLEX LEVELS.
THIS DRAWING SHALL BE READ IN CONJUNCTION WITH ALL DRAWINGS, ENGINEERING
1. SPECIFICATIONS, ALL OTHER CONSULTANT DOCUMENTATION, AND ALL OTHER WRITTEN
INSTRUCTIONS WHICH MAY BE ISSUED DURING THE COURSE OF THE CONTRACT.
2. CONTRACTOR TO COORDINATE AS PER SITE CONDITIONS.
3. IN THE EVENT OF CONFLICT BETWEEN DRAWINGS DATA & SPECIFICATION DATA. THE
FLOOR DATA POINT. 4. SPECIFICATION SHALL GOVERN. DETAIL DRAWINGS TAKE PRECEDENCE OVER DRAWINGS OF
SMALLER SCALE. SHOULD THE CONTRACTOR AT ANYTIME DISCOVER AN ERROR IN A DRAWING OR

150

150
5.

1715
2 SPECIFICATIONS, OR A DISCREPANCY OR VARIATION BETWEEN DIMENSIONS ON DRAWINGS &
MEASUREMENT AT SITE, OR LACK OF DIMENSIONS OR OTHER INFORMATION CONTRACTOR SHALL
REPORT AT ONCE TO THE ARCHITECT FOR CLARIFICATION AND SHALL NOT PROCEED WITH THE
POWER DISTRIBUTION BOARD 6. WORK AFFECTED UNTIL CLARIFICATION HAS BEEN MADE.

KEY PLAN 10 10.1 17 17.1

3262 490 APPROXIMATELY H@1200 cm FFL. 1 26

A
P01 P02 P03 P04 P05 A

WARNING LIGHTS- PROVIDE 25MM CONDUIT P2.1 P3.1

FROM WARNING LIGHTS to PDB. F


P06 P07 P08 F

P2.A P15 P16 P18 P19 P3.A

EMERGENCY STOP SWITCH H@1500 FROM FFL


P09 P10 P11
PROVIDE 25MM CONDUIT WITH WIRE TO PDB P2.F
P17 P20 P3.F

P2.1 P3.1

DST0051 DST0051 25MM GI CONDUIT


P12 P13 P14

B
V V

3402 6 13 13.1 21

150mm X 100mm Floor trUNKING REFERENCE DOCUMENTS


A DOCUMENT NO TITLE REV

3402 100mm X 40 mm wall tray

25mmØ GI CONDUIT FOR

3975
WARNING LIGHT CONNECT TO THE
MACHINE LEFT SIDE BOTTOM
CORNER OF MACHINE by HBK
ELECTRICAL USE REQUIREMENTS

BONE DENSITY BONE DENSITY REQUIREMENT TABLE

INPUT LINE VOLTAGE 230V

Z1-L0-IMD-002 Z1-L0-IMD-002 INPUT CURRENT


FREQUENCY
8.0
50, HZ
MILITARY MEDICAL CITY HOSPITAL - AL SAILIYAH
Approval Status
NUMBER OF PHASES SINGLE

Approved as
Commented

C Re-Submit
A Approved

D Rejected
Revise &
PHYSICAL AND ENVIRONMENTAL REQUIREMENTS Authority Signature Date

B
OPERATING TEMPERATURE RANGE 15° C TO 32° C (59° F to 90° F) MMC-PMO

OPERATING HUMIDITY RANGE 20% TO 80% NON-CONDENSING The approval and comments shall not in any ways relieve or absolve the
Contractor from compliance of any obligations or liability under or in connection
with the contract, project requirements and specifications.

HORIZON SYSTEM SPECIFICATIONS


SYSTEM
ABAM ABAM
INPUT LINE ........... 230 volts, 8 AMP, 50 HZ,
1 ISSUED FOR CONSTRUCTION 03/05/2023 PR SG

MAXIMUM APPARENT LINE RESISTANCE (OHMS) 1.28 0 ISSUED FOR CONSTRUCTION 03/02/2023 ABAM ABAM PR SG
REV REVISION DETAILS DATE DWN DES CHD APD
EMPLOYER
DESCRIPTION:
WARNING LIGHT = STANDARD BOX WITH "X-RAY ON" QATAR ARMED FORCES
MILITARY MEDICAL CITY HOSPITAL PROJECT
MANAGEMENT OFFICE P.O. BOX 2075 DOHA,
RADIATION WARNING (CONDUITS SUPPLIED & INSTALLED BY HOSPITAL'S ELECTRICAL CONTRACTOR.)
QATAR

LIGHT BY HBK
RADIATION WARNING MAIN CONTRACTOR:

LIGHT BY HBK HBK CONTRACTING CO. WLL


1 FLOOR AND WALL ELECTRICAL PLAN 2 CEILING AND WALL ELECTRICAL PLAN P.O. BOX 1362 DOHA, QATAR
TEL: (974) 44451111 FAX: (974) 44451000
MEQ-3402 SCALE: 1:15 MEQ-3402 SCALE: 1:15

LEAD CONSULTANT:
SHOP DRAWING NOTES
1
MEINHARDT
14TH FLOOR AMWAL TOWER WESTBAY
P.O. BOX 1362 DOHA, QATAR
· REVISION ON FLOOR TRUNKING AND POWER AND DATA SOCKET TEL: (974) 44117840 FAX: (974) 4411 7845

CONNECTION ARCHITECT & INTERIOR DESIGNER:

MEDICAL PLANNER: MEDICAL EQUIPMENT : SUBCONTRACTOR :

25mmØ CONDUIT
to PDB by HBK
CEILING LINE

PROJECT TITLE:

WIRE SIZES: TWO WIRE +


ENGINEERING, PROCUREMENT AND
2 GROUND TO WARNING LIGHT
CONCRETE SCREED CONSTRUCTION (EPC/TURNKEY) FOR
VINYL FLOOR FINISHED
MILITARY MEDICAL CITY HOSPITAL
CEILING LINE
(MMC) AT TAREK BIN ZEYAD CAMP
CEILING LINE
5mm THK MS STEEL
PLATE TRUNKING COVER IN SAILIYAH (SOUTH OF DOHA)
RECOMMENDED
ISOLATOR LOCATION
FLOOR CABLE
BY HBK
PROJECT NO. AA-103-01
25mmØ CONDUIT TRUNKING
by HBK DRAWING TITLE:
EMERGENCY
100x40mm wall STOP SWITCH 150 BUILDING 01 - ZONE 01 - PART 06- GROUND FLOOR - BONE
cable trunking by HBK BY HBK
DENSITOMETRY (Z1-L0-IMD-002) - DEXA (Hologic)
EMERGENCY
STOP SWITCH BY HBK PRE-INSTALLATION - ELECTRICAL LAYOUT PLAN
PDB - Power Distribution PDB - Power
box by HBK Distribution THIS DRAWING HAS BEEN CHECKED FOR COMPLETENESS, ACCURACY, COORDINATION, AND
box by HBK 25mm GI CONDUIT FOR COMPLIANCE WITH THE CONTRACT DOCUMENTS. ALL DIMENSIONS AND FIELD CONDITIONS

100
WALL SOCKET FROM PDB HAVE BEEN VERIFIED.

1300 915 1500 1025 CONTRACTOR'S REPRESENTATIVE:


Mr. ALAADDIN AKTAN
DATE:
04 May 2023
DEDICATED WALL SOCKET 230V, 13 AMP,
1500
1500

1PH H@500MM HOSPITAL GRADE 2X DUPLEX STATUS:


OUTLET FROM PDB WITH ISOLATED GROUND BY HBK
1230
1230

FFL: + +0.00 ISSUED FOR CONSTRUCTION

105 SUBMISSION STAGE DATE

2010 04/05/2023
500

150x100mm TRUNKING BY HBK


500

WORKING DRAWING

3 FLOOR TRUNKING DETAIL DRAWN DESIGN CHECKED

MEQ-3402 SCALE: 1:5 PRABHU


ABAM ABAM

TYPICAL WARNING LIGHT DETAIL


C ELEVATION -C DESIGNED SCALE A1

ALI BIN ALI 1:50


MEQ-3402 SCALE: 1:30
A ELEVATION - A B ELEVATION - B DRAWING NO. REVISION NO.
MEQ-3402 SCALE: 1:30 MEQ-3402 SCALE: 1:30 MMC-HBK-P1-WD-B01-MEQ-L0-P06-3402 1

BIM MODEL REFERENCE :


Date: 21 June 2023

TO WHOM IT MAY CONCERN

Relationship between Hologic BV and Flextronics Manufacturing

Through this letter, we confirm that Hologic BV, located at The Corporate Village, Building Caprese,
8th Floor, Da Vincilaan 5, 1930 Zaventem, Belgium, is the Authorized European Representative of
Hologic, Inc., located at 36 Apple Ridge Road, Danbury, Connecticut 06810, United States of
America.

Further, that Flextronics Manufacturing, located at Boulevard a Zacatecas Km. 9.5, Jesus Maria,
Aguascalientes 20900, Mexico, physically manufactures Horizon DXA devices on behalf of Hologic
Inc., Danbury, who is the legal manufacturer of these devices.

As such, we Hologic BV are authorized to register Horizon DXA in Hologic Inc., Danbury’s name
through all Europe, Middle East, and Africa.

Sincerely,

Hologic BV, The Corporate Village, Building Caprese, 8th floor, Da Vincilaan 5, 1930 Zaventem, Belgium
T: +32 2 711 46 80 | F: +32 2 725 20 87 | Hologic.com
BNP PARIBAS FORTIS, IBAN BE75 2100 8769 7651, BIC BEBABEBB, BTW: BE 0445 434 787, RPR Brussel: 0445 434 787
1 Consignor - Expéditeur - Afzender - Absender
ORIGINAL
DSV Solutions, Eddastraat 21, 9042 St-Kruis-Winkel, België ORIGINEEL
= = = = = = = = = = = = On behalf of: = = = = = = = = = = = = 93 2023 016556
Hologic BV, Building Caprese, 3rd Floor Da Vincilaan 5, 1930
Zaventem, Belgium EUROPEAN UNION
UNION EUROPEENNE
2 Consignee - Destinataire - Geadresseerde - Empfänger EUROPESE UNIE
EUROPÄISCHE UNION

KHALID SCIENTIFIC CO CERTIFICATE OF ORIGIN


CERTIFICAT D'ORIGINE
SHEIKH KHALID BLDG GULF STREET PO BOX 4349 CERTIFICAAT VAN OORSPRONG
DOHA URSPRUNGSZEUGNIS
QATAR
3 Country of Origin - Pays d'origine - Land van oorsprong -
Ursprungsland
Mexico(MX)

4 Transport details (optional) 5 Remarks - Remarques - Opmerkingen - Bemerkungen


Informations relatives au transport (mention facultative)
Gegevens in verband met het vervoer (facultatief)
Angaben über die Beförderung (Ausfüllung freigestellt) Order: 678602
Invoice: 139168549
xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx

6 Item number; marks, numbers, number and kind of packages; description of goods 7 Quantity
No d'ordre; marques, numéros, nombre et nature des colis; désignation des marchandises Quantité
Volgnummer, merken, nummers, aantal en aard van colli; omschrijving van de goederen Hoeveelheid
Laufende Nummer; Zeichen, Nummern, Anzahl und Art der Packstücke; Warenbezeichnung Menge

medical goods 546.14 (kg)


2 PL xxxxxxxxxxxxxxxxxxxxx
xxxxxxxxxxxxxxxxxxxxx
MX xxxxxxxxxxxxxxxxxxxxx
xxxxxxxxxxxxxxxxxxxxx
CMP-01793HORIZON FLAT PANEL MONITOR - (UG) xxxxxxxxxxxxxxxxxxxxx
INNERCORE-APEXAPEX VISCERAL FAT OPTION - (UG) xxxxxxxxxxxxxxxxxxxxx
HP 7000EUR DISCOVERY PRINTER HP 7000 xxxxxxxxxxxxxxxxxxxxx
RESEARCH-APEXRESEARCH OPTION KIT APEX - xxxxxxxxxxxxxxxxxxxxx
(UG) xxxxxxxxxxxxxxxxxxxxx
HORIZON-WHORIZON-W xxxxxxxxxxxxxxxxxxxxx
ASY-07185ASSY, P4 COMPUTER, PCIE, W7 - (UG) xxxxxxxxxxxxxxxxxxxxx
APEX-LANGUAGEAPEX LANGUAGE OPTION - (UG) xxxxxxxxxxxxxxxxxxxxx
AFF-APEXATYPICAL FEMUR FRACTURE OPTION xxxxxxxxxxxxxxxxxxxxx
FRAX-APEXFRAX OPTION FOR APEX - (UG) xxxxxxxxxxxxxxxxxxxxx
ASY-07152POWER KIT FOR 200-240VAC - (UG) xxxxxxxxxxxxxxxxxxxxx
ASY-07542KIT, PCIE CABLE, INTERFACE 45' xxxxxxxxxxxxxxxxxxxxx
IRIS-ENT-APEXAPEX IRIS CONNECTIVITY SUITE W/ENTE

8 THE UNDERSIGNED AUTHORITY CERTIFIES THAT THE GOODS DESCRIBED ABOVE ORIGINATE IN THE COUNTRY SHOWN IN BOX 3.
L'AUTORITE SOUSSIGNEE CERTIFIE QUE LES MARCHANDISES DESIGNEES CI-DESSUS SONT ORIGINAIRES DU PAYS FIGURANT DANS LA CASE NO 3.
ONDERGETEKENDE AUTORITEIT VERKLAART DAT DE HIERBOVEN VERMELDE GOEDEREN VAN OORSPRONG ZIJN UIT HET IN VAK 3 GENOEMDE LAND.
DIE UNTERZEICHNENDE STELLE BESCHEINIGT, DASS DIE OBEN BEZEICHNETEN WAREN IHREN URSPRUNG IN DEM IN FELD 3 GENANNTEN LAND HABEN.

Oost-Vlaanderen
8/08/2023

93 2023 016556
Pascal Buysse
09B3-C6AE-593A

Place and date of issue; name; signature and stamp of competent authority.
Lieu et date de délivrance; désignation, signature et cachet de l'autorité compétente.
Plaats en datum van afgifte; aanduiding, handtekening en stempel van de bevoegde autoriteit.
Ort und Datum der Ausstellung; Bezeichnung, Unterschrift und Stempel der zuständigen Stelle.

E4-0061
Packages as Per MOD Packages as Per Packages as Per
Department Dept Ref ID Room Name Room # CAD ID Description ItemQty Arch Code Supplier Manufacturer Model Serial No.
Contract MAT RBR

Imaging & Dental Radiology Imaging Diagnostic Ground Densitometer, Bone, HORIZON W BONE
BONE DENSITY Z1-L0-IMD-002 DST0051 1 1-Fixed ABAM Hologic 307543M
Package Package Packages Imaging Floor Whole Body DENSITOMETER
Powerful images.
Clear answers.
Horizon® DXA System: An Innovative Solution
for Accurate Diagnosis
Hologic, the pioneer in X-ray based bone densitometry, takes advanced health
assessment to a new level with the Horizon DXA system. This multi-faceted system
can help clinicians assess bone health, body composition and cardiovascular risk —
critical elements that will help patients keep life in motion.1

The Horizon DXA system features the latest innovations in bone densitometry
technology; including a new digital high resolution ceramic detector array, as well as a
new high frequency X-ray Generator.2 When paired with our exclusive OnePass™ true
fan-beam acquisition geometry, Horizon DXA system delivers rapid, dual-energy bone
density measurements in a single-sweep, eliminating beam overlap errors and image
distortion found in rectilinear acquisition techniques. We’ve also improved our Dynamic
Calibration™ System, which delivers pixel-by-pixel calibration2 through bone and tissue
equivalents — for greater long-term precision.3

Model shown: Horizon A


Horizon DXA system product specifications
Patient Weight Limit Horizon Advance Reporting Solutions
500 lbs (227 kg) QDR OnePage™ Report with Rate of Change Assessment
Typical Exposure Time and Entrance Dose* FRAX® 10 Year Fracture Assessment
Lumbar spine..........................10 sec / 0.04 mGy (C, W, A models) New Dual Hip™ Report
Proximal Femur .....................10 sec / 0.04 mGy (C, W, A models) New integrated Physicians Report Writer™ DX Feature
SE femur ..................................15 sec / 0.025mGy (C, W, A models)
Horizon Scan and Analysis Protocols
IVA™ option in HD...................15 sec / 0.025 mGy (C, W, A models)
AP Lumbar Spine with Automatic Low Density Analysis
Whole body.............................113 sec / 0.007 mGy (A models) and Scoliosis Analysis
290 sec / 0.015 mGy (Wi, W models)
Supine Lateral Spine with Baseline Compensation (A models)
Advanced Fan-Beam DXA Technology Proximal Femur, Automatic Low Density Analysis and Hip
OnePass™ Acquisition Technique; Multi-Detector Array Structure Analysis™ (HSA) Feature
Scanning Method Dual Hip™ Feature
New High-resolution multi-element detector array with gadolinium Forearm
sulfoxylate GADOX scintillator technology used in modern CT
Whole Body BMD (Wi, W, A models)
devices (64 to 216 detectors, model dependent)
A
 dvanced Body Composition™ Analysis with InnerCore™
New High Frequency X-ray Generator Visceral Fat Assessment
X-ray System Switched-pulse dual-energy (100 kVp/140 kVp) IVA HD with Image Pro High Resolution Imaging Capability
Superior Precision and Accuracy 3 (C, W, A models)
Quantitative Morphometry
Dynamic Calibration™ System for Continuous Calibration
Integrated Physicians Viewer™ with MXApro™ Feature
QDR™ Anthropomorphic Spine Phantom
New Atypical Femur Fracture Assessment (AFF) High Resolution
Mechanical and Positioning System Features Imaging Capability (C, W, A models)
Pediatric Analysis for Spine, Femur and Forearm
Indexing Scan Table with Positioning Accessories
Pediatric Whole Body with Body Composition Assessment
Motorized Table with Rotating C-arm (A model)
(Wi, W, A models)
Motorized Table with C-arm (Ci, Wi, C, W models)
External Shielding
Standard Computer Hardware (Minimum Configuration)
None required‡
Computer Workstation with Dual Core 3 GHz
BMD Precision
Windows® 10 LTSB 2016
<1.0%
250 GB hard drive
4 GB RAM Scan Region
18.5" Widescreen LCD Monitor 38" x 20” (77" x 26" on whole body models)
HP Professional Series Color DeskJet printer ®
Table Height
DVD RAM drive 28"
Standard Configuration: C-arm Clearance
Horizon APEX™ Operating System 24”
Automatic PASS/FAIL Quality Control Calibration
Express BMD 10 Second Acquisition (C, W, A models) Automatic, continuous calibration using Hologic’s automatic
Single Energy Scan Display Capability internal reference system
Window/Level Control for Image Optimization Operator calibration not required
NAPEX Productivity Tools Automatic quality control program with multiple system checks
Express Exam Workflow Management

Operating Requirements
OneTime™ Auto Analysis with Histogram Temperature: 60° - 90°F (15°-32°C)
ProTech with DXApro Power:100 VAC (16 A); 120 VAC (14 A); 230 VAC (8 A)
Auto Hip Positioning Humidity: 20% - 80% relative humidity, noncondensing
Reposition/Rescan Feature Average heat load: 3,400 BTU/hr.
Automatic Scan Comparison for Serial Exams
Least Significant Change Configuration

NOTE: Features and specifications subject to change without notice.



Some components of the IRIS™ package can be purchased separately.

Installation requirements for X-ray equipment vary. Check with local regulatory authorities.
* Times are dependent on area scanned and represent total irradiation time at 60Hz.
Scan site specifications according to model

Horizon A Horizon W Horizon C Horizon Wi Horizon Ci

216 Detectors 128 Detectors 128 Detectors 64 Detectors 64 Detectors

Regional Scans 10 s Regional Scans 10 s Regional Scans 30 s


Regional Scans 10 s Regional Scans 30 s
Body Comp 3 min Body Comp 6 min Body Comp 6 min

Hi-Definition Vertebral Hi-Definition Vertebral Hi-Definition Vertebral


Fracture Assessment Fracture Assessment Fracture Assessment
with Abdominal Aortic with Abdominal Aortic with Abdominal Aortic
Calcification detection Calcification detection Calcification detection

Atypical Femur Atypical Femur Atypical Femur


Fracture Assessment Fracture Assessment Fracture Assessment

Advanced Body Advanced Body Advanced Body


Composition Composition Composition™
Assessment with Assessment with Assessment with
InnerCore InnerCore InnerCore™
Visceral Fat Assess- Visceral Fat Assess- Visceral Fat Assess-
ment ment ment

Lumbar Spine Lumbar Spine Lumbar Spine Lumbar Spine Lumbar Spine

Supine Lateral BMD Decubitus Lateral BMD Decubitus Lateral BMD Decubitus Lateral BMD Decubitus Lateral BMD

Dual Hip Dual Hip Dual Hip Dual Hip Dual Hip

Proximal Femur Proximal Femur Proximal Femur Proximal Femur Proximal Femur

Forearm Forearm Forearm Forearm Forearm

Hip Structure Analysis Hip Structure Analysis Hip Structure Analysis Hip Structure Analysis Hip Structure Analysis

Custom Region Custom Region Custom Region Custom Region Custom Region
of Interest of Interest of Interest of Interest of Interest

Research package option


• Prosthetic hip*
• Small Animal
• Infant Whole Body with Body Composition Assessment and subregional analysis
(Wi, W and A models)*

* Not available in all markets pending regulatory clearance


Horizon DXA system footprint

HORIZON A EQUIPMENT PLAN HORIZON C EQUIPMENT PLAN


MINIMUM RECOMMENDED ROOM SIZE MINIMUM RECOMMENDED ROOM SIZE

The Horizon DXA system packs a lot of performance into a small footprint. Operating from existing dedicated
power sources, the system fits comfortably in an 8’ X 8’ exam room (8’ X 10’ for whole body models) and
requires no protective shielding or special room preparations.*

*Installation requirements for X-ray equipment vary. Check with local regulatory authorities.

References
1. K023398, K041226, K042480, K130277 (AFF), K113356(VAT), K103265(Whole Body), K072847 (AAC), K060111 (AAC) 2. K023398 3. Hangartner, TN. A study
of long-term precision of dual energy X-ray absorptiometry bone densitometers and implications for the validity of the least-significant-change calculation.
Osteoporosis Int. 2007

www.hologic.com | BSHSalesSupportUS@hologic.com | +1.508.263.2471

North America / Latin America Europe Asia Pacific Australia


250 Campus Drive The Corporate Village 7th Floor, Biotech Centre 2 Suite 402, Level 4
Marlborough, MA 01752 Da Vincilaan 5 No. 11 Science Park West Avenue 2 Lyon Park Road
USA Building Caprese, 8th floor Hong Kong Science Park Macquarie Park NSW 2113
hologic.com 1935 Zaventem Shatin, New Territories Australia
Belgium Hong Kong

DS-00382 Rev. 006 © 2019 Hologic Inc. All rights reserved. Printed in USA. Specifications are subject to change without prior notice. Hologic, Advanced Body Composition, APEX, Dual Hip, Dynamic Calibration,
Express Exam, Hip Structure Analysis, Horizon, InnerCore, IRIS, IVA, MXApro, OnePage, OnePass, OneTime, Physicians Report Writer DX, Physicians Viewer, QDR, The Science of Sure and associated logos are
trademarks and/or registered trademarks of Hologic, Inc. and/or its subsidiaries in the United States and/or other countries. All other trademarks and registered trademarks are the property of their respective
owners. This information is intended for medical professionals in the U.S. and other markets and is not intended as a product solicitation or promotion where such activities are prohibited. Because Hologic
materials are distributed through websites, eBroadcasts and tradeshows, it is not always possible to control where such materials appear. For
specific information on what products are available for sale in a particular country, please contact your local Hologic representative or
write to womenshealth@hologic.com.

You might also like