You are on page 1of 202

TESTING & COMMISSIONING

INSPECTION REQUEST (T&C)

Aconex Transmittal No: HBKC-TRANSMIT-01


T&C Reference No.: MMC-HBK-AP-TC-MD-00151 Rev. No.: 0 Date: 23-Oct-2023
Engineering, Procurement and Construction (EPC / Turnkey) for Military Medical City Hospital at Tarek Bin
Project Name:
Zeyad Camp in Sailiyah (South of Doha)
Project Number: AA-103-01
Mr. Alaaddin Aktan Brig. (Eng./Air) Abdulrahman Ali Al-Abdulmalik
From: To:
Project Director /Contractor's Representative MMC Project Director

QATAR ARMED FORCES


Contractor: HBK Contracting Company Employer: Military Medical City Hospital
Project Management Office

Discipline: Architectural Civil Structural Electrical / ICT Mechanical Medical General

Supporting
Proposed Inspection Date: 24-Oct-2023 Inspection time: 10am
Documents

Location: Building: Zone: Level: Approved Drawing


B01 Z01 L0
Material Approval
MST / ITP
Room No.: ATTACHED LIST Room Name: CT ROOM Others

MST Reference No.: Drawing Reference No.:


MMC-HBK-ABAM-AP-MST-MD-0006
MAT Reference No.:
MMC-ABAM-AP-MAT-MD-0009 0
IR Reference No.:
MMC-HBK-AP-IR-MD-00087

Inspection Detailed Description:

MEQ Inspection of Imaging & Dental Package

Material IR Reference (MIR) MEQ Delivery No. Supplier Country of Origin

MMC-HBK-AP-MIR-MD-00136 MO-32199248 & MO-32061702 Ali Bin Ali Medical Germany

Cad ID Equipment Name Manufacturer Model Serial Number Quantity

CTX0152 CT Scanner, Multi-Slice, 64-320 Slice SIEMENS SOMATOM Drive ATTACHED LIST 2

SUB-CONTRACTOR CONTRACTOR
Engineer Engineer / CM QA/QC Representative Project Director
Requested by: Requested/Verified by: Verified by: Approved by:

Signature:
Company: Ali Bin Ali Medical Signature: Signature: Signature:
Name: Paulino Flores Name: Mr. Ibrahim Name: Mr. Rakesh NK Name: Mr. Alaaddin Aktan
Date: 23-Oct-2023 Date: 23-Oct-2023 Date: 23-Oct-2023 Date: 23-Oct-2023

EMPLOYER
Comments / Recommendation:

Employer Action Code: A (Approved) B (Approved with Comments) C (Revise & Resubmit) D (Rejected)

Note: To attach the Employer's comment response sheet after the inspection.
The approval and comments shall not in any ways relieve or absolve the Contractor from compliance of any obligations or liability under or in connection with the Contract, Project
Requirements and Specification.
MMC-HBK-QA-F024 Rev.0, Dated 12.09.2023 Page 1 of 1
MEDICAL EQUIPMENT
COMMISSIONING REPORT

Commissioning Report No.: MMC-HBK-AP-TC-MD-00151 Rev. No.: 0 Date: 23-Oct-23


Engineering, Procurement and Construction (EPC / Turnkey) for Military Medical City Hospital
Project Name:
at Tarek Bin Zeyad Camp in Sailiyah (South of Doha)
Project Number: AA-103-01
QATAR ARMED FORCES
Contractor: HBK Contracting Company Employer: Military Medical City Hospital
Project Management Office
MEQ Subcon: Ali Bin Ali Medical

Prot. n°: Real Property Tag No.:

Date: 23-Oct-23 Main Unit Tag No.: Real Property Tag


(in case of impossibility to attach on the item, it will be stick here)
Dept.: Imaging & Dental Package
Level: L0 Room No.: ATTACHED LIST

Item Code: CTX0152


Description: CT Scanner, Multi- Slice, 64-320 Slice (Somatom Drive)
Quantity: 2 Brand: Siemens
Serial No.: ATTACHED LIST Model: SOMATOM DRIVE
Acc. Description:

MEQ INSTALLATION AND TEST REPORT DETAILS (to attached approval copy)

Installation and Test Report No. (ITR): MMC-HBK-AP-IR-MD-00087 Rev. No.: 0 Date: 23-Oct-23

COMMISSIONING

STATUS
SN ACTIVITIES
PASSED FAILED N/A

1 Software Integration

Consumables Check
2
(to be applied to the Consumables NOT inspected during the Testing phase)

3 Performance Assurance Testing (Quality Check)

Legend: Passed (Successfully Performed) Failed (Not Successfully Performed) N/A (Not Applicable)

DOCUMENTATION

SN DOCUMENT DOCUMENT REFERENCE ACONEX WF REFERENCE TO BE SUBMITTED N/A


1 As-built Drawings
2 Operator Manual Uploaded on Aconex under following path:
3 Service Manual Uploaded on Aconex under following path:
4 Medical Equipment commissioning manufacturer check List attached
Software Package
5
(CD or USB)
Calibration (or) Cleaning Kit,
6
where applicable

Remarks:

Enclosures

MEQ Subcontractor Contractor Employer


Signature: Signature: Signature:

Name: Paulino Flores Name: Name:

Designation: Project Engineer Designation: Designation:

K‐P1‐QC‐F150 Rev.1,Dated 05.04.2023 Page 1 of 3


MEDICAL EQUIPMENT
COMMISSIONING REPORT

Date: 27-Aug-23 Date: Date:

K‐P1‐QC‐F150 Rev.1,Dated 05.04.2023 Page 2 of 3


MEDICAL EQUIPMENT
COMMISSIONING REPORT
MEDICAL EQUIPMENT COMMISSIONING CHECKLIST
STATUS
SN SECTION
PASSED FAILED N/A
1 IT Integration
1.a LIS
1.b RIS
1.c PIS
1.d PACS
1.e HIS / CIS
1.f Data Network connectivity
1.g Wireless Network connectivity
1.h Terminal Server integration
1.i Other #1:
1.j Other #2:
2 Software updated
3 Positioning

3.a Equipment positioned in the final location


3.b Equipment location is functional and operational
4 Accessories and consumables

4.a Expiry date of consumables subsequent commissioning date


4.b Accessories and consumables stored properly
5 Documents

5.a FDA/CE certification


5.b CoO (Country of origin) Certificate
5.c As-built Software configuration
5.d Operational and Service manuals uploaded on Aconex
6 Functional and Operational Verification

6.a Verification
6.b Image QA
6.c Functional and operational test as per the manufacture standards
6.d Test #1 not done in the RFIT:
6.e Test #2 not done in the RFIT:
Integration with other Medical equipment
7
Tag No. Item No. Item Description

7.a
7.b
7.c
7.d
7.e
8 Tags

8.a Electrical Safety Test Tag


8.b Inventory tag
8.c Battery check tag
9 ECRI/FDA recalls / clearance certificate to be attached
Legend: Passed (Successfully Performed) Failed (Not Successfully Performed) N/A (Not Applicable)

Notes

K‐P1‐QC‐F150 Rev.1,Dated 05.04.2023 Page 3 of 3


INSPECTION REQUEST (IR)

Aconex Transmittal No: HBKC-TRANSMIT-01


IR Reference No.: MMC-HBK-AP-IR-MD-00087 Rev. No.: 0 Date: 27-Sep-2023
Engineering, Procurement and Construction (EPC / Turnkey) for Military Medical City Hospital at Tarek
Project Name:
Bin Zeyad Camp in Sailiyah (South of Doha)
Project Number: AA-103-01
Mr. Alaaddin Aktan Brig. (Eng./Air) Abdulrahman Ali Al-Abdulmalik
From: To:
Project Director /Contractor's Representative MMC Project Director

QATAR ARMED FORCES


Contractor: HBK Contracting Company Employer: Military Medical City Hospital
Project Management Office

Discipline: Architectural Civil Structural Electrical / ICT Mechanical Medical General

Supporting
Proposed Inspection Date: 28-Sep-2023 Inspection time: 02:00pm
Documents
Location: Building: Zone: Level: Approved Drawing
B01 Z01 L0
Material Approval
MST / ITP
Room No.: Attached List Room Name: CT Room Others

MST Reference No.: MAT Reference No.: Type of Inspection:

MMC-HBK-ABAM-AP-MST-MD-0006 MMC-ABAM-AP-MAT-MD-0009 Hold

Inspection Detailed Description:

MEQ Inspection of 0

Material IR Reference (MIR) MEQ Delivery No. Supplier Country of Origin

MMC-HBK-AP-MIR-MD-00136 MO-32199248 & MO-32061702 Ali Bin Ali Medical GERMANY

Cad ID Equipment Name Manufacturer Model Serial Number Quantity

CT Scanner, Multi- Slice, 64-320 Slice


CTX0152 SIEMENS Somatom Drive Attached List 2
(Somatom Drive)

SUB-CONTRACTOR CONTRACTOR
Engineer Engineer / CM QA/QC Representative Project Director
Requested by: Requested/Verified by: Verified by: Approved by:

Signature:
Company: Ali Bin Ali Medical Signature: Signature: Signature:
Name: Mr. Paulino Flores Name: Mr. Ibrahim Name: Mr. Rakesh NK Name: Mr. Alaaddin Aktan
Date: 28-Sep-2023 Date: 28-Sep-2023 Date: 28-Sep-2023 Date: 28-Sep-2023

EMPLOYER
Comments / Recommendation:

Employer Action Code: A (Approved) B (Approved with Comments) C (Revise & Resubmit) D (Rejected)

Note: To attach the Employer's comment response sheet after the inspection.

The approval and comments shall not in any ways relieve or absolve the Contractor from compliance of any obligations or liability under or in connection with the Contract, Project
Requirements and Specification.
MMC-HBK-QA-F007 Rev.7, Dated 08.10.2022 Page 1 of 1
MATERIAL INSPECTION REQUEST (MIR)

Aconex Transmittal No.: HBKC-TRANSMIT-01


MIR Reference No.: MMC-HBK-AP-MIR-MD-00136 Rev. No.: 0 Date: 5-Jul-2023
Engineering, Procurement and Construction (EPC / Turnkey) for Military Medical City Hospital at
Project Name :
Tarek Bin Zeyad Camp in Sailiyah (South of Doha)
Project Number: AA-103-01
Mr. Alaaddin Aktan Brig. (Eng./Air) Abdulrahman Ali Al-Abdulmalik
From: To:
Project Director /Contractor's Representative MMC Project Director

QATAR ARMED FORCES


Contractor: HBK Contracting Company Employer: Military Medical City Hospital
Project Management Office

Discipline: Architectural Civil Structural Electrical / ICT Mechanical Medical General

Proposed Inspection Date: 9-Jul-2023 Inspection Time: 10:00 AM Location: HBK Site Store (On-site)

Supporting Documents: Material Approval Delivery Note Country of Origin Test Reports Others

Supplier: Ali Bin Ali Medical

Material Inspection Detailed Description:

MEQ Material Inspection of Radiology Package

MAT Reference MEQ Delivery No.

MMC-ABAM-AP-MAT-MD-0009_Rev.0 Code B MO-32199248 & MO-32061702

Country of
Cad ID MEQ Item Description Manufacturer Model Quantity
Origin

CAD ID -CTX0152 -CT Scanner, Multi-


CTX0152 Siemens Germany SOMATOM DRIVE 2
Slice, 64-320 Slice (Somatom Drive)

SUB-CONTRACTOR CONTRACTOR
Engineer Store QA/QC Representative Project Director
Requested by: Requested/Verified by: Verified by: Approved by:

Company: Ali Bin Ali MedicalSignature: Signature: Signature:


Name: Mr. Paulino Flores Name: Mr. Ghouse Name: Mr. Rakesh N.K. Name: Mr. Alaaddin Aktan
Date: 5-Jul-2023 Date: 5-Jul-2023 Date: 5-Jul-2023 Date: 5-Jul-2023

EMPLOYER
Comments / Recommendation:
1- Refer the attached Comments from HBK/SECO
2- Initially accepted as Boxes with SNs and PNs (Not assembled)
3- Final approval is subjected to final installation, testing & commissioning.

Employer Action Code: A (Approved)  B (Approved with Comments) C (Revise & Resubmit) D (Rejected)

Note: To attach the Employer's comment response sheet after the inspection.
This document shall not relieve Contractor of his liabilities under the Contract or constitute authorization of any change to Contract documents.

MMC-HBK-QA-F004 Rev.6, Dated 08.10.2022 Page 1 of 1


0ÿ !76ÿ(!"$)%$'*+ÿ2,-.ÿ/2422ÿÿ/01123ÿ6C )*B$'B)$)>
# - !-ÿ24/224 4!"#"24"$%&'%'

001
234
234
56789 ÿ76 

4ÿ2 4ÿ53 !#ÿ53


ÿ26788 4!"#"24"$%&'%' 4!"#"24"$%&'%'
!76ÿ(!"$)%$'*+ÿ2,-.ÿ/2422ÿÿ/01123ÿ688763ÿ29876 ÿ4
#77676 ÿÿ#25$*%)ÿ#2ÿ/#4ÿ67769ÿ"ÿ/8ÿ.7893ÿ9ÿ#2ÿÿ:*"
$"."$)*ÿ6 ÿ:*"$"."$)%
! ÿ0ÿÿ"ÿ#
2ÿ(;+ ÿ79 ÿ2ÿ"ÿ47ÿ376ÿ47ÿ9 76ÿ(A<ÿ9DDD+
#6ÿ(*<+ E76ÿ06969ÿ"ÿ,3 ÿ#686876 ÿ(A*&ÿ9DDD+
/968 27023ÿ)*ÿ/9189=9ÿ)$)>ÿ'?)$?)<ÿ4ÿ3/2ÿ(@2ÿA$*?$$+
/880 B4

ÿ.-#52ÿ4224#,2/ÿ(*+
(Fÿ99689 +

#",3 " 2,-.ÿ/2422ÿÿ/01123ÿ688763 3ÿ"ÿ41189


434"4"/2" ) 2987
6 ÿ
4ÿ # 7 7
67
6 ÿ 
ÿ#25$*%)ÿ
#2 ÿ/#4
$%B$'B)$)> 67769ÿ"ÿ/8ÿ.7893ÿ9ÿ#2ÿÿ:*"$"." 787
."$$$& $)*ÿ6 ÿ:*"$"."$)% #968

ÿ//4@
ÿ9879ÿ,782
279ÿ88679 ÿ60968ÿ789ÿ61989 ÿ879ÿG2,-.ÿ/2422ÿÿ/01123ÿ688763ÿ29876 ÿ4ÿ#77676 ÿÿ#25$*%)ÿ#2ÿ/#4
67769ÿ"ÿ/8ÿ.7893ÿ9ÿ#2ÿÿ:*"$"."$)*ÿ6 ÿ:*"$"."$)%Gÿÿ787ÿ879ÿ76 ÿ908ÿ?
HIJKÿMNOPKQJMMORÿSOKÿOTMUQOMJVORRWÿXYPYNOMYZ[

.6ÿ /891 8767168 9879ÿ-0869 #968


0012345264602672 3451ÿ0ÿ2ÿ ÿ6ÿ 4ÿ2ÿ6ÿ 0!!"ÿ6#!
08920 2 1! 1$ÿ%ÿ!!
9ÿ0ÿ8ÿ%
8#&'ÿ!'
9!"'ÿ
1!!"ÿ%
19( )*+ÿ19ÿ8$
0$'ÿ8ÿ'
ÿ19ÿ!ÿ,)2- 20 2
+)ÿÿ,)2- 20 2+*
!ÿÿÿÿ
%"ÿ$!ÿ
ÿÿ%ÿ
$!.ÿ9!"ÿ
4ÿ2ÿ6ÿ $!!"ÿ$#!
3451ÿ38ÿ2ÿ8& 8ÿ0#!! 1! ÿ-/9/ÿ$#!
ÿÿÿ!#0ÿ0#!
ÿÿÿ!ÿ
$$1!!ÿ%ÿ!ÿ$&0
ÿ6ÿÿ20ÿ3'ÿ$
ÿÿ$
!#!ÿ#!ÿ
ÿ%ÿ
$$#ÿ40
4!ÿÿÿ
$!'ÿ
ÿ&#ÿ
!ÿÿ2
ÿ$!0

3451ÿ61ÿ2ÿ6 6ÿ5! 4ÿ2ÿ6ÿ %ÿÿ345ÿ0


1! $0
001ÿ2ÿ8 8ÿ8 4ÿ2ÿ6ÿ )2ÿ!#ÿÿ0
1! $!ÿ
$'ÿ"'ÿ
!&$ÿ%ÿÿ$"
!0ÿ+2ÿ0ÿ$$
ÿ!ÿ!"ÿ
$ÿ$!#ÿ
!#ÿ%#$&ÿ%
!ÿ!$ÿ%ÿ
ÿ'ÿ
$$#ÿ"!ÿ!
ÿ#0ÿ62
1ÿ7#
ÿ%%ÿ!$
ÿÿ&ÿ!$$&
012ÿ415674ÿ8619 10 ÿ8
4ÿ50945ÿ01ÿ86674
2597401945ÿ012ÿ95
09ÿ ÿ4ÿ01
91709 75ÿ745 15 
ÿ4847ÿ ÿ5
9415ÿ012ÿ9

ÿÿ70247 ÿ0260 ÿÿ7!42ÿ 


 415

ÿÿ0 6 ÿ"00 ÿÿ7!42ÿ  "4054ÿ74847ÿ ÿ4ÿ0 !4


 415 9415
SITE PLAN

E
N
8 9
B07 B08

S
N
LA
.63
W
QIB
252
B14
P2.F Notes on preparations for installation B05

CORRIDOR
B09
B02 B03
B01
Contracts for performing and supervising on-site installation preparations should be concluded with technically
CONTRAST

B06
competent companies by the customer. The customer is responsible for timely and proper completion and B12 B13
B11

Z1-L0-IMC-004 AGENT supervision of all preparations for installation at the construction site in observance of all applicable legal regulations B04
B10

(e.g. X-ray regulations, radiation protection regulations) and all applicable general recognized rules of technology
PREP (e.g. VDE regulations, DIN standards).
Execution and supervision of installation preparations at the construction site and later observance of the standard
14.04 m² EQUIPMENT AT operating conditions are not included in our duties. The customer is responsible for checking the static calculations
CHANGE ROOM and, where applicable, the air conditioning in the building to be equipped.
Z1-L0-IMD-024 Z1-L0-IMD-027
Z1-L0-IMD-022 (M) GENERAL NOTES
Z1-L0-IMD-026 7.08 m² 1. PROJECT REFERENCE ELEVATION ±0.00 IS AT +27.50 QATAR NATIONAL DATUM. ELEVATIONS
SHOWN ARE WITH RESPECT TO THE PROJECT REFERENCE ELEVATION OF ±0.00 AT GROUND FLOOR.
2. ALL DIMENSIONS ARE IN MM UNLESS NOTED OTHERWISE.

4.77 m² above door


TS Room dimensioning
3.
4.
EQUIPMENT DIMENSIONS ARE SUBJECT TO CHANGE BASED ON MATERIAL SUBMISSION APPROVAL.
CONTRACTOR TO COORDINATE AS PER SITE CONDITIONS WHEREVER APPLICABLE.
5. SHOP DRAWINGS ARE ISSUED IN COORDINATION WITH APPROVED DETAILED DESIGN FF&E AND
SW MEDICAL EQUIPMENT SELECTIONS. SOME AREAS ARE SUBJECT TO CHANGE AFTER MATERIAL
SUBMITTALS APPROVAL .
The indicated room dimensions have to be checked on site. The planning department has to be informed about
possible deviations. Otherwise we cannot assume any guarantee for the accurate implementation of the dimensions
indicated in the planning documents.

P2.G
KEY PLAN 1
10 10.1 17 17.1
26

1046
A A

Room lighting
Z1 Z3
SBA
B Ambient lighting in rooms with diagnostics or with workstations must comply with the respective local and national
P2.1

F Z2 F
P3.1

CT ROOM 3131 regulations.

ISO CENTER
2.09
P2.A P3.A

EAT AT General requirements like the needed intensity of illumination - adjustable, reproducible, flicker-free or a limitation of
Z1-L0-IMD-025

2481
2480
dazzlings and reflections etc. have to be observed (EN 12464-1, DIN 5035-7).

440
P2.F P3.F

AT P2.1 P3.1

Z4 Z5
ISO CENTER ISO CENTER
5161 2760 V V

Display screen workstations


6 13 13.1 21
For setting up display screen workstations, take account of the guidelines in the Display Screen Workstation
directive as well as any national regulations (e.g. EN ISO 9241-5).
1862 REFERENCE DOCUMENTS
2.02 DOCUMENT NO TITLE REV
2.06
D 2.01 E BUILDINGS 1 - ALL ZONES - ALL PARTS - OVERALL -GROUND FLOOR -

5421
MMC-HBK-AP-DD-BAP-MEQ-L0-APO-1800 2
2500

MEDICAL EQUIPMENT PLAN


3131 3131 MMC-HBK-P1-DD-B01-MEQ-L0-P06-1806 BUILDING 1 - ZONE 01- PART 06- GROUND FLOOR MEDICAL EQUIPMENT PLAN 2

WORK / 2.07

CONTROL Safety distances


Z1-L0-IMD-023 C Distances from moving parts of the medical device to walls, furniture and other equipment have to be kept to avoid
2.11 3131 injuries by crushing in compliance with local regulations, e.g. a minimum distance of 50 cm according to EN 349. MILITARY MEDICAL CITY PROJECT - AL SAILIYAH
Approval Status
2.12 It is the customer's responsibility to ensure the above requirements are followed.

Approved as
Commented
ISO CENTER

Re-Submit
A Approved
This is to avoid the risk of injury.

D Rejected
Revise &
± 0.00 Authority Signature Date

2940
If safety distances are not maintained appropriate on-site safety measures have to be put in place.
-0.10

C
B
Clear visible markings according to national guidelines, e.g. crushing warning signs, hazard warning
AT 2.10 MMC-PMO
tape, hazard area cordon, safety mats, may be required.

2953
A
SW
3131 1
1100

2.05 The approval and comments shall not in any ways relieve or absolve the
Contractor from compliance of any obligations or liability under or in connection
Room height with the contract, project requirements and specifications.

400 Technically required minimum room height 2200 mm


160

Measured from the highest point of the finished floor (with covering) to the lowest point of the ceiling
2.08 2.04 2.03
00 ISSUED FOR CONSTRUCTION 31/10/2022 ABAM ABAM PR SG
REVISION DETAILS DATE DWN DES CHD APD
M Lead shielded wall EMPLOYER

QATAR ARMED FORCES


Transport technical cabinets and patient table MILITARY MEDICAL CITY HOSPITAL PROJECT
MANAGEMENT OFFICE P.O. BOX 2075 DOHA,
QATAR
The PDC is mounted and delivered on a transport pallet.
M.1 The IRSmx4d tower is delivered on a special shock-absorbing transport pallet. Moving through the building is not
MAIN CONTRACTOR:
permitted without this pallet.

Transport dimensions Length (mm) Width (mm) Height (mm) Weight (kg) HBK CONTRACTING CO. WLL
P.O. BOX 1362 DOHA, QATAR
PDC A with transport pallet - without UPS 1120 900 2070 ≤600 TEL: (974) 44451111 FAX: (974) 44451000
1 CT SCAN ROOM - EQUIPMENT ARRANGEMENT PLAN
MEQ-3130 SCALE: 1:30 PDC B with transport pallet 1120 900 2070 ≤450
Floor- and building vibrations LEAD CONSULTANT:

Fixpoints IRSmx4d tower with transport pallet 600 800 690 51.9
SOMATOM Drive - Equipment Legend
Floor- and building vibrations can reduce image quality! Therefore the gantry and the patient table must be
installed in an environment free of vibrations.
Fixpoint Components
MEINHARDT
IRSmx5d tower 645 175 450 25 14TH FLOOR AMWAL TOWER WESTBAY
Sources that produce vibrations are, e.g.: P.O. BOX 1362 DOHA, QATAR
Weight (kg), Heat dissipation to the air (W) Permissible acceleration for continuous vibration TEL: (974) 44117840 FAX: (974) 4411 7845
Railroad routes, subways, roads, road work and GR Gantry PHS 4n - with packing
construction sites, hospital power plants, mines, 2580 875 1570 700
Permissible acceleration rms-value [m/s²]

Pos. Description kg W Remark ARCHITECT & INTERIOR DESIGNER:


open-cast mines, quarries (explosions), ferry moorings, Operating console (controlbox, monitor, keyboard)
2.01 Gantry 2580 1000 #1, isocenter 1020 mm MPT 2n - with packing 2530 850 1430 850
any other sources of striking vibrations.
2.02 Patient table PHS 4n (2000 mm scannable range) 500 * * included in 1.01 Image Control System (Tower PC)
The CT system is not sensitive to common vibrations. If
2.03 PDC A cabinet with UPS 610 2000 the CT is away from vibrational sources, or the CT is
Power Distribution Cabinet A (incl. REPO contact)
2.04 PDC B cabinet 400 2000 replacing a CT system that to date has not shown image
MEDICAL PLANNER: MEDICAL EQUIPMENT : MEP SUBCONTRACTOR : SUBCONTRACTOR :
2.05 IRSmx5d Tower PC (Image Reconstruction System) 25 500 quality problems due to vibrations, it is usually not Power Distribution Cabinet B
necessary to execute vibrational measurements.
2.06 Control unit with monitor, control box, keyboard 10 100
If there are any doubts, the following thresholds have to be IRSmx (Image Reconstruction System Cabinet) Climatic conditions for transport and storage
2.07 ICS Tower 13 PC (syngo Acquisition Workplace) 25 500
verified by measurement:
2.08 Power Distributor BY HBK, not in scope of 1 10 100
AT Emergency off button with locking mechanism Transport / storage Temperature -20 to +50 °C
ABAM Delivery all components Relative humidity 10 to 90 % PROJECT TITLE:
2.09 Single Monitor Cart (Ondal 2018) 20 Patient Handling System PHS) must not exceed the On-off button with pilot lamp Barometric pressure 700 to 1060 hPa
2.10 I-Control trolley 20
thresholds as described in the above shown diagram.
SW Radiation warning lamp
Temperature gradient 10 K/h (non-condensing) ENGINEERING, PROCUREMENT AND
2.11 Medical Monitor (24") 10 Any transient vibration (shocks) has to be less than 0.5 m/s² peak-to-peak in the time domain.The vibrations have to Max. storage time 2 months
be measured with a sampling rate of 1000 Hz. Radiation ready indicator CONSTRUCTION (EPC/TURNKEY) FOR
2.12 syngo.via Ultramini Workstation Client 4 120 The data for transporting and storing the CT system apply only if the system is shipped free of damage in the
#1 additional heat dissipation up to 17 kW to water It is the customer's responsibility to contract a qualified specialist. The specialist must implement site
CV CARE Vision transport packaging provided by the manufacturer. All components have to be stored in the original transport
MILITARY MEDICAL CITY HOSPITAL
modifications to meet the specific limits, and to design structural solutions in case of deviations.
packaging. If the original packaging is no longer available, you have to use an equivalent packaging for intermediate (MMC) AT TAREK BIN ZEYAD CAMP
The system cable connections (power supply) between storage. After moving the CT system from a cold environment into a warm room, make sure that the entire CT
Transport Gantry not to scale Notes on preparations for installation Gantry and PDC must have a minimum length of 7 m.
system is dry before switching it ON.
IN SAILIYAH (SOUTH OF DOHA)
Place excess lengths in the cable duct.
Standard transport Transport through narrow passages Contracts for performing and supervising on-site installation preparations should be concluded with technically
4 Cable diameter 30 mm, minimum bending radius 148 mm.
competent companies by the customer. The customer is responsible for timely and proper completion and
Rollers swivelled out Rollers swivelled in
supervision of all preparations for installation at the construction site in observance of all applicable legal regulations PROJECT NO. AA-103-01
(e.g. X-ray regulations, radiation protection regulations) and all applicable general recognized rules of technology
1220 1220 DRAWING TITLE:
(e.g. VDE regulations, DIN standards).
1256 1256 Environmental conditions for operating
1 1 Execution and supervision of installation preparations at the construction site and later observance of the standard Network Integration BUILDING 01-ZONE 01, -PART 06 - GROUND FLOOR -
operating conditions are not included in our duties. The customer is responsible for checking the static calculations Entire CT System Air temperature range 18 to 28 °C
and, where applicable, the air conditioning in the building to be equipped. The Siemens Healthineers components are using TCP/IP Protocol, a 100/1000 Mbit/s switched Ethernet network CT SCAN ROOM (Z1-L0-IMD-025) - SOMATOM Drive
Relative humidity 20 to 75 %
min. 1999

min. 1999

and static IP addresses. PRE-INSTALLATION EQUIPMENT ARRANGEMENT PLAN


Barometric pressure 800 to 1060 hPa
3 3 Gantry with folded-up covers not to scale The required network cabling (min. CAT 5 TP) has to be provided on site. Media converters, which are needed for
Temperature gradient 6 K/h (non-condensing) THIS DRAWING HAS BEEN CHECKED FOR COMPLETENESS, ACCURACY, COORDINATION, AND
COMPLIANCE WITH THE CONTRACT DOCUMENTS. ALL DIMENSIONS AND FIELD CONDITIONS
using fibre optic cabling, are not in scope of delivery. HAVE BEEN VERIFIED.
FRONT VIEW SIDE VIEW Maintain the temperature range required to meet the needs of changing seasons. To prepare the implementation of the new system into the existing network environment, the availability
2 2 If it is not possible, an on-site room heating and air conditioning system is required. of the needed network data at least two weeks before starting the installation is mandatory.
264 1801 3331 4 4 When supplying air from the outside (fresh air), we recommend the on-site use of This is the only way to ensure a seamless integration of the new system into the workflow of the department.
5
Mr. ALAADDIN AKTAN 20 Sept 2022
6 coarse Filters, Filter class EU3 to EU4 for filtering dust particles up to > 10 μm CONTRACTOR'S REPRESENTATIVE: DATE:
5
(DIN 24185/Part 2). STATUS:
1 With touch panels on the rear (optional)
ISSUED FOR CONSTRUCTION

2 Covers must removed for mounting the transport device 2 SUBMISSION STAGE DATE
1
Smart Remote Services (SRS) Radiation protection
2100

2100

3 Transport device set to minimum floor clearance (7 mm) 2 17/10/2022


1992

WORKING DRAWING

4 TIPPING HAZARD! 3
Smart Remote Services (SRS) is used for remote diagnostics as well DRAWN DESIGN CHECKED
1022

as remote service to provide highest system availability. ABAM ABAM PRABHU


Attention:
Requirements:
DESIGNED SCALE A1
Gantry with transport device = 2865 kg, Transport device = 285 kg 2 MBit/s upstream) without time or volume limitations WORKING DRAWING REVISION NOTES MEINHARDT 1:30
If there is false floor in transportation route please check bearing capacity of this floor on-site! 1 Height of the gantry 2 Height with folded-up cover (for service) 3 Iso center
If necessary, cover the transport route with metal sheets to distribute the load. Data protection and security is defined in the Smart Remote : AS PER COMMENTS FROM OPERATOR; DRY WALL SHIFTED TO 400mm TO GAVE SPACE ON THE CT SCAN MACHINE AND TO RECESS ON THE WALL THE SUB
The maximum possible floor load (two-point load) per roller that may arise during gantry transport is 16 kN. 4 e.g. CARE Vision 5 Folded-up cover "hood right" 6 Folded-up cover "front ring" 1 DRAWING NO. REVISION NO.
Services security concept. EQUIPMENT (PDCa and PDCb) OF THE CT SCAN MACHINE.. MMC-HBK-P1-WD-B01-MEQ-L0-P06-3130 0
The door must have a final clearance of 1250 mm if bed entrance to the CT examination room is requested. Note the height of the folded-up covers if planning any technical equipment above the gantry !
BIM MODEL REFERENCE :
SITE PLAN

E
N
B07 B08

S
N
LA
.63
W
QIB
252
B14

B09 B05

8 9 P2.G M B02
B01
B03

B06
B12 B13
B11
+5.50 +5.50 B04
B10
+5.40 +5.40

CONCRETE SCREED
VINYL FLOOR FINISHED
5mm THK MS STEEL GENERAL NOTES
PLATE TRUNKING COVER 1. PROJECT REFERENCE ELEVATION ±0.00 IS AT +27.50 QATAR NATIONAL DATUM. ELEVATIONS
SHOWN ARE WITH RESPECT TO THE PROJECT REFERENCE ELEVATION OF ±0.00 AT GROUND FLOOR.
FLOOR CABLE 2. ALL DIMENSIONS ARE IN MM UNLESS NOTED OTHERWISE.
TRUNKING 3. EQUIPMENT DIMENSIONS ARE SUBJECT TO CHANGE BASED ON MATERIAL SUBMISSION APPROVAL.
4. CONTRACTOR TO COORDINATE AS PER SITE CONDITIONS WHEREVER APPLICABLE.
FFL: ±0.00 300
5. SHOP DRAWINGS ARE ISSUED IN COORDINATION WITH APPROVED DETAILED DESIGN FF&E AND
MEDICAL EQUIPMENT SELECTIONS. SOME AREAS ARE SUBJECT TO CHANGE AFTER MATERIAL
SUBMITTALS APPROVAL .

80
-0.10

KEY PLAN 1
10 10.1 17 17.1
26

+3.00
1 5 FLOOR TRUNKING DETAIL
A A

MEQ-3131 SCALE: 1:5 P2.1


Z1 Z3 P3.1

F Z2 F

CT ROOM P2.A P3.A


1000

1050
Z1-L0-IMD-025 POWER DISTRIBUTION
5160 2760 BOX BY HBK
P2.F P3.F

P2.1 P3.1

Fixpoints Z4 Z5
CT ROOM Fixpoint Components
AT
EMERGENCY STOP
SWITCH
Z1-L0-IMD-025 V V

GR Gantry

3000

3000
1000

1000
Operating console (controlbox, monitor, keyboard) 6 13 13.1 21

2.01 2.04
2.01 Image Control System (Tower PC)
REFERENCE DOCUMENTS
2480
1860 Power Distribution Cabinet A (incl. REPO contact) DOCUMENT NO TITLE REV
2.02

1950

1950
BUILDINGS 1 - ALL ZONES - ALL PARTS - OVERALL -GROUND FLOOR -
1800

3340 Power Distribution Cabinet B MMC-HBK-AP-DD-BAP-MEQ-L0-APO-1800


MEDICAL EQUIPMENT PLAN
2

2.02 IK 150x50mm OK FFL to IRSmx (Image Reconstruction System Cabinet)


MMC-HBK-P1-DD-B01-MEQ-L0-P06-1806 BUILDING 1 - ZONE 01- PART 06- GROUND FLOOR MEDICAL EQUIPMENT PLAN 2

FK 300x80mm @+500mm aFFL


1000

1000
AT Emergency off button with locking mechanism

995
FLOOR TRUNKING

WALL OUTLET
CV On-off button with pilot lamp
@+300mm aFFL
300 1900
FFL: ±0.00 FFL: ±0.00
2.05 SW Radiation warning lamp MILITARY MEDICAL CITY PROJECT - AL SAILIYAH
Approval Status

Approved as
Radiation ready indicator

Commented

Re-Submit
A Approved

D Rejected
Revise &
CV CARE Vision Authority Signature Date

C
B
FK 200x80mm The system cable connections (power supply) between
FLOOR TRUNKING MMC-PMO
Gantry and PDC must have a minimum length of 7 m.
Place excess lengths in the cable duct.
C CT SCAN ROOM - ELEVATION C Cable diameter 30 mm, minimum bending radius 148 mm.
A CT SCAN ROOM - ELEVATION A MEQ-3131 SCALE: 1:30
MEQ-3131 SCALE: 1:30

The approval and comments shall not in any ways relieve or absolve the
Contractor from compliance of any obligations or liability under or in connection
with the contract, project requirements and specifications.
WORKING DRAWING REVISION NOTES

1 : AS PER COMMENTS FROM OPERATOR; DRY WALL SHIFTED TO 400mm TO GAVE SPACE ON THE CT SCAN MACHINE AND TO RECESS ON THE WALL THE SUB
EQUIPMENT (PDCa and PDCb) OF THE CT SCAN MACHINE..

00 ISSUED FOR CONSTRUCTION 31/10/2022 ABAM ABAM PR SG


REVISION DETAILS DATE DWN DES CHD APD
EMPLOYER

9 8 P2.G M
QATAR ARMED FORCES
P2.G MILITARY MEDICAL CITY HOSPITAL PROJECT
MANAGEMENT OFFICE P.O. BOX 2075 DOHA,
QATAR
+5.50 +5.50 +5.50
+5.40 +5.40 +5.40 MAIN CONTRACTOR:

HBK CONTRACTING CO. WLL


P.O. BOX 1362 DOHA, QATAR
TEL: (974) 44451111 FAX: (974) 44451000

LEAD CONSULTANT:

MEINHARDT
14TH FLOOR AMWAL TOWER WESTBAY
P.O. BOX 1362 DOHA, QATAR
TEL: (974) 44117840 FAX: (974) 4411 7845

ARCHITECT & INTERIOR DESIGNER:

MEDICAL PLANNER: MEDICAL EQUIPMENT : MEP SUBCONTRACTOR : SUBCONTRACTOR :

+3.00

CT ROOM PROJECT TITLE:

2486 4993
Z1-L0-IMD-025 ENGINEERING, PROCUREMENT AND
1000
1050

SW
POWER DISTRIBUTION
BOX BY HBK
WORK / CONTROL POWER DISTRIBUTION EMERGENCY STOP
AT SWITCH
EMERGENCY STOP AT CONSTRUCTION (EPC/TURNKEY) FOR
BOX BY HBK SWITCH
PDC A CABINET
WITH UPS
PDC B
CABINET
EMERGENCY STOP
SWITCH
AT SBA
Z1-L0-IMD-023 MILITARY MEDICAL CITY HOSPITAL
CT ROOM (MMC) AT TAREK BIN ZEYAD CAMP
Z1-L0-IMD-025 AT IN SAILIYAH (SOUTH OF DOHA)
3000

1000

1000
50mmØ OPEN PVC PIPE PROJECT NO. AA-103-01
PROVISION FOR INJECTOR
2.08 THRU CONTROL ROOM EAT
ISO CENTER DRAWING TITLE:
2.03 2.04 1860 2480
2.02 BUILDING 01-ZONE 01, -PART 06 - GROUND FLOOR -
2050
1950

1800

CT SCAN ROOM (Z1-L0-IMD-025) - SOMATOM Drive

1800
1800

IK 200x60mm 50mmØ OPEN PVC PIPE


1600

OK FFL to UK PDB PROVISION FOR INJECTOR


ISO CENTER PRE-INSTALLATION ELEVATION DETAILS
2.05 3252 THIS DRAWING HAS BEEN CHECKED FOR COMPLETENESS, ACCURACY, COORDINATION, AND
1000

1000

1000
COMPLIANCE WITH THE CONTRACT DOCUMENTS. ALL DIMENSIONS AND FIELD CONDITIONS
130 130

IK 150x50mm OK FFL to 2.01 HAVE BEEN VERIFIED.


@+500mm aFFL
546

560
500

300500

2.05
300

FFL: ±0.00 FFL: ±0.00 FFL: ±0.00 FFL: ±0.00


Mr. ALAADDIN AKTAN 20 Sept 2022
CONTRACTOR'S REPRESENTATIVE: DATE:

STATUS:

ISSUED FOR CONSTRUCTION

OPC ICS IK 200x60mm FK 200x80mm SUBMISSION STAGE DATE


@300 aFFL to UK ABGD FLOOR TRUNKING
17/10/2022
PVC WALL TRUNKING
E CONTROL ROOM - ELEVATION E WORKING DRAWING

B CT SCAN ROOM - ELEVATION B D CONTROL ROOM - ELEVATION D MEQ-3131 SCALE: 1:30


DRAWN DESIGN CHECKED
MEQ-3131 SCALE: 1:30 MEQ-3131 SCALE: 1:30 PRABHU
ABAM ABAM

DESIGNED SCALE A1

MEINHARDT 1:30

DRAWING NO. REVISION NO.

MMC-HBK-P1-WD-B01-MEQ-L0-P06-3131 0

BIM MODEL REFERENCE :


SITE PLAN

E
N
B07 B08

S
N
LA
.63
W
QIB
252
8 9 I-Control with wall bracket (schematic) not to scale
SOMATOM Drive - Equipment Legend B14

B09 B05

B02 B03
4 Weight (kg), Heat dissipation to the air (W) B01
400
Pos. Description kg W Remark

B06
B12 B13
B11
1.01 Gantry 2580 1000 #1, isocenter 1020 mm B04
B10

1.02 Patient table PHS 4n (2000 mm scannable range) 500 * * included in 1.01
130 1.03 PDC A cabinet with UPS 610 2000

15
10 3
1.04 PDC B cabinet 400 2000
1.05 IRSmx5d Tower PC (Image Reconstruction System) 25 500

00
0
x. 1
1.06 Control unit with monitor, control box, keyboard 10 100

119

90
2

ma
9 4 1.07 ICS Tower 13 PC (syngo Acquisition Workplace) 25 500 GENERAL NOTES

1300
1. PROJECT REFERENCE ELEVATION ±0.00 IS AT +27.50 QATAR NATIONAL DATUM. ELEVATIONS
1 1.08 Power Distributor by customer, not in scope SHOWN ARE WITH RESPECT TO THE PROJECT REFERENCE ELEVATION OF ±0.00 AT GROUND FLOOR.
of delivery 2. ALL DIMENSIONS ARE IN MM UNLESS NOTED OTHERWISE.
6

1531

1530
3. EQUIPMENT DIMENSIONS ARE SUBJECT TO CHANGE BASED ON MATERIAL SUBMISSION APPROVAL.
1 4. CONTRACTOR TO COORDINATE AS PER SITE CONDITIONS WHEREVER APPLICABLE.

800 - 900
7 159 5. SHOP DRAWINGS ARE ISSUED IN COORDINATION WITH APPROVED DETAILED DESIGN FF&E AND
5 MEDICAL EQUIPMENT SELECTIONS. SOME AREAS ARE SUBJECT TO CHANGE AFTER MATERIAL
SUBMITTALS APPROVAL .
2663 8
1400 1263 1910
Floor- and building vibrations
Floor- and building vibrations can reduce image quality! Therefore the gantry and the patient table must be
3347 installed in an environment free of vibrations.

563
1 Wall bracket (thickness 35 mm) with wall mounting holes Ø 6.6 mm 2 Locking lever for locking/unlocking
KEY PLAN 1
10 10.1 17 17.1
26

Sources that produce vibrations are, e.g.:


Permissible acceleration for continuous vibration
500mm safety distance
3 Control unit 4 Minimum area requirements and dimensions for wall installation and handling Railroad routes, subways, roads, road work and A A

construction sites, hospital power plants, mines,

Permissible acceleration rms-value [m/s²]


5 24 V DC plug-in power supply and cable Z1 Z3
open-cast mines, quarries (explosions), ferry moorings, P2.1

Z2
P3.1

1790
F F
Input Output

1900
any other sources of striking vibrations.

787
- Voltage: 100 V AC - 240 V AC - Voltage: +24 V DC ± 5 % P2.A P3.A

- Line frequency: 50-60 Hz - Current: 1.25 A The CT system is not sensitive to common vibrations. If
- Current: 0.7 A - Cable length: 1.5 m
- Stand-by: 0.5 W the CT is away from vibrational sources, or the CT is P2.F P3.F

WORK / replacing a CT system that to date has not shown image P2.1 P3.1
728

6 7 Z4 Z5
quality problems due to vibrations, it is usually not
CONTROL
549

550 8 IVP control cable 9 Strain relief for power supply cable 10 Connection for power supply cable
necessary to execute vibrational measurements.
Z1-L0-IMD-023 V V
If there are any doubts, the following thresholds have to be

105
Delivery volume: - Control unit and a wall bracket for wall mounting (standard installation)
verified by measurement:

cabling
- Drilling template
1 10 100
- Installation material: 3x Fischer dowels 6 13 13.1 21

water
(Type: UX 8x50; nominal drill hole diameter: 8 mm; Drill hole depth: min. 60 mm
- 3x screws M6x80, 3x screw head caps grey REFERENCE DOCUMENTS
Patient Handling System PHS) must not exceed the
thresholds as described in the above shown diagram. DOCUMENT NO TITLE REV

BUILDINGS 1 - ALL ZONES - ALL PARTS - OVERALL -GROUND FLOOR -


MMC-HBK-AP-DD-BAP-MEQ-L0-APO-1800 2
963 Any transient vibration (shocks) has to be less than 0.5 m/s² peak-to-peak in the time domain.The vibrations have to MEDICAL EQUIPMENT PLAN

CT ROOM 300 Statics not to scale


be measured with a sampling rate of 1000 Hz. MMC-HBK-P1-DD-B01-MEQ-L0-P06-1806 BUILDING 1 - ZONE 01- PART 06- GROUND FLOOR MEDICAL EQUIPMENT PLAN 2
1990

1990
Z1-L0-IMD-025 4 3
The floor construction has to be performed solid and free of
vibration, e.g. concrete flooring C20/25 to C50/60 corresponding to
It is the customer's responsibility to contract a qualified specialist. The specialist must implement site
Center of DIN EN 206-1, according to the maximum values as specified in the
modifications to meet the specific limits, and to design structural solutions in case of deviations.
gravity textblock “Floor and building vibrations”.

256
Concrete fill-up, concrete class It is recommended to test the weight capacity of the concrete or MILITARY MEDICAL CITY PROJECT - AL SAILIYAH
1 2
C20/25 to C50/60 composite flooring by a stress analyst.
Fastening the gantry on the floor is possible but only necessary in
Approval Status

Approved as
Commented
Join with the solid concrete.

Re-Submit
A Approved
94 countries prone to earthquakes or according to local regulations.

D Rejected
Revise &
Securing the patient table to the floor is mandatory.
Authority Signature Date
PDC - Power Distribution Cabinet not to scale

C
B
Total weight of Gantry: 2580 kg : F stat total 25 kN
MMC-PMO
FRONT VIEW ILLUSTRATION for the cable inlet (Isometry)
Partial load on gantry foot 1 2 3 4
M
Nominal static load after levelling:
5.7 7.6 7.9 6.7
F stat nom [kN]

±0.7 ±0.7 ±0.8 ±0.8


F dyn max [kN] The approval and comments shall not in any ways relieve or absolve the
Contractor from compliance of any obligations or liability under or in connection
Outer diameter gantry foot [mm] 80 80 80 80 with the contract, project requirements and specifications.
M.1
Floor contact area gantry foot [cm²] 52.1 52.1 52.1 52.1

During gantry installation and leveling, the maximum possible load on one gantry foot can be 14 kN (the gantry is
1 CT SCAN ROOM - CONCRETE FILL-UP PLAN standing on two diagonal feet). Design access floors for a weight capacity of min. 400 kg per slab/plate. During

1850
1950
gantry transport, the load may be higher at certain individual points (3-point load, e.g. due to uneven flooring).
MEQ-3132 SCALE: 1:30 00 ISSUED FOR CONSTRUCTION 31/10/2022 ABAM ABAM PR SG
REVISION DETAILS DATE DWN DES CHD APD
EMPLOYER

6 1 QATAR ARMED FORCES


Floor mounting and cable inlet with standard table PHS 4n not to scale MILITARY MEDICAL CITY HOSPITAL PROJECT
MANAGEMENT OFFICE P.O. BOX 2075 DOHA,
QATAR

1 Adjustable gantry feet (Ø 80 mm); mounting holes (Ø 17 mm) ICS Tower 13 not to scale
MAIN CONTRACTOR:

100
2
Adjustable patient table feet with mounting holes (inner: Ø 20.5 mm); minimum extraction force: 2.03 kN at the two mounting points bearing
the greatest load at maximum patient travel path and a 230-kg load. According to IEC 60601-1, it is mandatory that the 4-fold safety factor be observed. 840 488
FRONT VIEW SIDE VIEW
7
TOP VIEW
2
570 0
HBK CONTRACTING CO. WLL
50 43
900 P.O. BOX 1362 DOHA, QATAR
2 Alternative floor mounting holes (Ø 18 mm), if position 2a is not usable 1252 4
2 TEL: (974) 44451111 FAX: (974) 44451000

120
1070 5 2 6
LEAD CONSULTANT:
3 Floor-inlet for cable/hose connection: 49/97 x 488 mm
890 TOP VIEW ILLUSTRATION for floor mounting
3
MEINHARDT

420
175 420 (top view of pedestal)
4 No floor cut-out permitted in this defined area (Ø 190 mm) around each adjustable gantry foot 1435 900 500 900 14TH FLOOR AMWAL TOWER WESTBAY
8 P.O. BOX 1362 DOHA, QATAR
Alternative to 3 : 689.5 745.5

40
TEL: (974) 44117840 FAX: (974) 4411 7845
5 Core hole: max. Ø 100 mm for HV cables and other system cabling 5 6 3

395
2 1
3 1 ARCHITECT & INTERIOR DESIGNER:
8
6 Core hole: max. Ø 80 mm for system cabling
10 3 3
1

691.5

650
570
7 Core hole: max. Ø 160 mm for water hoses 1 1 4

25
8 Gantry footprint 4
1 Air intake 2 Air exhaust (primary) 3 Air exhaust (secondary) 3 3 14 MEDICAL PLANNER: MEDICAL EQUIPMENT : MEP SUBCONTRACTOR : SUBCONTRACTOR :
7 Ø
4 Air must not exhaust directly to the air intake 5 e.g. a wall
9 "Electronics cover" for cabling between gantry and patient table (in scope of delivery)

100

40
6 Minimum distance for cable routing and air circulation 7 Minimum distance for air circulation
100 700 100
9 7
Floor requirements: Gantry and patient table orientation point
PROJECT TITLE:
CT
The floor construction has to be performed solid and free of vibration, e.g. concrete flooring C20/25 to C50/60 scan plane

950
corresponding to DIN EN 206-1, according to the maximum values as specified in the textblock
ILLUSTRATION for the cable inlet
(top view of pedestal)
ENGINEERING, PROCUREMENT AND
service area
“Floor and building vibrations”. Anti-static flooring is recommended for the examination room. ESD flooring is also suitable. 1 1 900 CONSTRUCTION (EPC/TURNKEY) FOR
NOTE: A solid and vibration-free floor is needed to avoid a negative influence on the vibration characteristic of the gantry. IRSmx5 tower not to scale

An incorrect vibration characteristic of the gantry can cause problems with balancing and image quality.
MILITARY MEDICAL CITY HOSPITAL
6 (MMC) AT TAREK BIN ZEYAD CAMP

max.120
Permissible tolerance for floor levelness is at maximum 10 mm, based on the area of the adjustable feet of the
4
gantry and the patient table. 9 175
SIDE VIEW of socle IN SAILIYAH (SOUTH OF DOHA)
orientation point

650
25
On-site subconstruction have to fulfill the flooring conditions. It is recommended to test the weight capacity of 5
PHS 4n

82.5
175 120
the concrete or composite flooring by a stress analyst. 645 PROJECT NO. AA-103-01
Floor mounting, as well as principally every kind of CT system component mounting, must be performed in 2 2 1 4 3 DRAWING TITLE:
accordance with country-specific guidelines in countries prone to earthquakes.The gantry and the patient

645
table have to be on the same (isocentric) plane.
55 790 55 BUILDING 01-ZONE 01, -PART 06 - GROUND FLOOR -
450

450
2a 2a CT SCAN ROOM (Z1-L0-IMD-025) - SOMATOM Drive
An "Installation Template" with footprint information for the gantry and patient table is optional available. 9 650 32.5
2 PRE-INSTALLATION CONCRETE FILL-UP PLAN
May not be used as a drilling template. A drilling template is not necessary. 7

150
205 5 THIS DRAWING HAS BEEN CHECKED FOR COMPLETENESS, ACCURACY, COORDINATION, AND
COMPLIANCE WITH THE CONTRACT DOCUMENTS. ALL DIMENSIONS AND FIELD CONDITIONS
Floor mounting Gantry 1 System cables HAVE BEEN VERIFIED.

- Possible through four mounting holes, but not required in principle (only in areas prone to earthquakes). FRONT VIEW SIDE VIEW TOP VIEW
2a 2a Cable inlets (cut-outs in the base) when cables are routed on the floor; if not used, the cut-outs are covered
Mounting materials must be provided on-site. 2
with dummy plates; feed lines are possible from all four sides
1 Front side with grid for air intake (cooling) 2 Support feet 3 Air intake 4 Air exhaust
- Leveling tolerance: in Z-direction ± 0.2 deg, in X-direction ± 0.5 deg Mr. ALAADDIN AKTAN 20 Sept 2022
2 2 3 Floor mounting holes (all Ø=14 mm) 4 PDC base (footprint) CONTRACTOR'S REPRESENTATIVE: DATE:
- Leveling with four adjustable feet. 5 Minimum distance for air circulation 6 Air must not exhaust directly to the air intake
STATUS:
Ø 5 Cable inlet in PDC base; opening is adjustable 6 Air exhaust for system cooling; must not be covered
7 Sliding door or similar ISSUED FOR CONSTRUCTION
For example, the sliding door of a wall For example, a wall; no safety distance for
Floor mounting patient table 280 The safety distances for air circulation (system cooling) must be maintained. Openings for air circulation in the 7 closet, and so on 8
air circulation (cooling) required SUBMISSION STAGE DATE
393 tower housing must not be covered. Air must not exhaust directly into the air intake (a closed air loop).
- The patient table MUST be secured to the floor (4 mounting holes). 9 Safety distance for air circulation (cooling) required 10 Top exhaust for system cooling; must not be covered 17/10/2022
WORKING DRAWING
- Installation material for floor mounting in concrete is in scope of delivery. Therefor min.140 mm thickness of concrete is required:
Anchor bolts type 1: 4x HSL-4G M 10/60 heavy-duty sleeve (used without bonded screed) or DRAWN DESIGN CHECKED

Anchor bolts type 2: 4x HSL-4G M 10/120 heavy-duty sleeve (used with up to 60 mm thick bonded screed) PRABHU
ABAM ABAM
- Leveling with four adjustable feet.
- Remove the floor cover in the entire footprint area of the table base.The support plate is equal to the footprint DESIGNED SCALE A1

of the patient table base and is used as a help to cut out the floor covering. MEINHARDT 1:30

DRAWING NO. REVISION NO.

MMC-HBK-P1-WD-B01-MEQ-L0-P06-3132 0

BIM MODEL REFERENCE :


SITE PLAN

E
N
B07 B08
8 9

S
AGENT Line impedance related to measured line voltage

N
LA
.63
W
QIB
252
B14

PREP EQUIPMENT B09 B05

ROOM 1 Minimum measured line voltage [ VAC ] B02 B03


2 B01

14.04 m²

B06
B12

CHANGE
B13
300 B11

Z1-L0-IMD-024 2 Maximum allowed line impedance [ mΩ ] B04


B10

(M) 250
Z1-L0-IMD-026 7.08 m² 250
The maximum allowed line impedance
depends on the actual measured lowest line
4.77 m² 200
voltage.
SW We recommend monitoring the voltage over
TS GENERAL NOTES
150 a period of 24 hours preferable on work days 1. PROJECT REFERENCE ELEVATION ±0.00 IS AT +27.50 QATAR NATIONAL DATUM. ELEVATIONS
to specify the minimum. 2.
SHOWN ARE WITH RESPECT TO THE PROJECT REFERENCE ELEVATION OF ±0.00 AT GROUND FLOOR.
ALL DIMENSIONS ARE IN MM UNLESS NOTED OTHERWISE.
3. EQUIPMENT DIMENSIONS ARE SUBJECT TO CHANGE BASED ON MATERIAL SUBMISSION APPROVAL.
100 85 4. CONTRACTOR TO COORDINATE AS PER SITE CONDITIONS WHEREVER APPLICABLE.
5. SHOP DRAWINGS ARE ISSUED IN COORDINATION WITH APPROVED DETAILED DESIGN FF&E AND
MEDICAL EQUIPMENT SELECTIONS. SOME AREAS ARE SUBJECT TO CHANGE AFTER MATERIAL
P2.G SUBMITTALS APPROVAL .
50

0 1
SBA
CT ROOM 360 380 400 420 440
KEY PLAN
+1600mm aFFL EAT AT +1800mm aFFL Z1-L0-IMD-025 1
10 10.1 17 17.1
26

2481
A A
+1800mm aFFL AT
P2.1
Z1 Z3 P3.1
CONCRETE SCREED F Z2 F

VINYL FLOOR FINISHED P2.A P3.A

2 x BK 130x70mm Fixpoints 5mm THK MS STEEL


@300mm aFFL PLATE TRUNKING COVER

Fixpoint Components FLOOR CABLE


P2.F P3.F

2760 TRUNKING P2.1 P3.1

300
Z4 Z5
D GR Gantry FFL: ±0.00

3131
Operating console (controlbox, monitor, keyboard) V V

ICS

80
Image Control System (Tower PC) 6 13 13.1 21
-0.10
WORK / Power Distribution Cabinet A (incl. REPO contact)
GR REFERENCE DOCUMENTS
CONTROL
50mmØ OPEN PVC PIPE Power Distribution Cabinet B DOCUMENT NO TITLE REV
Z1-L0-IMD-023 PROVISION FOR INJECTOR 1911
MMC-HBK-AP-DD-BAP-MEQ-L0-APO-1800
BUILDINGS 1 - ALL ZONES - ALL PARTS - OVERALL -GROUND FLOOR -
2
MEDICAL EQUIPMENT PLAN

*2 THRU CONTROL ROOM DRAIN PIPE FOR IRSmx (Image Reconstruction System Cabinet)

cabling
MMC-HBK-P1-DD-B01-MEQ-L0-P06-1806 BUILDING 1 - ZONE 01- PART 06- GROUND FLOOR MEDICAL EQUIPMENT PLAN 2
CONDENSATION OF THE 3 SECTION DETAIL

water
OPC MACHINE BY HBK AT Emergency off button with locking mechanism MEQ-3133 SCALE: 1:5

2615
IK 200x60mm OK FFL

FK 300x80mm
On-off button with pilot lamp
to @3000mm aFFL
AT +1800mm aFFL 2 MILITARY MEDICAL CITY PROJECT - AL SAILIYAH

1775
WATER COOLING SW Radiation warning lamp
3 Approval Status

Approved as
Commented
3133

Re-Submit
A Approved
Radiation ready indicator
1300

D Rejected
Revise &
6050 FK 300x80

135
Authority Signature Date

200 CV CARE Vision

C
B
SW 1204
2529 3321 MMC-PMO

85
above The system cable connections (power supply) between
door Cut-out in cable duct

80
FK 200x80mm Gantry and PDC must have a minimum length of 7 m.
Place excess lengths in the cable duct.

300
280

WD *3

h= 450mm
IK 200x60mm Cable diameter 30 mm, minimum bending radius 148 mm.

849
305
OK FFL to *2
845

The approval and comments shall not in any ways relieve or absolve the
@300mm AFFL 485 Contractor from compliance of any obligations or liability under or in connection
with the contract, project requirements and specifications.

549
M

Gantry contour
CV IRS PDCA PDCB Notes
IK 200x60mm
OK FFL to UK PDB 150x300 300x300 300x300 For service purposes; only required if there is no existing
WALL OUTLET
300mm AFFL *3 socket or none is planned by the electrician
00 ISSUED FOR CONSTRUCTION 31/10/2022 ABAM ABAM PR SG
(consult the Siemens Healthineers project management) Scan plane REVISION DETAILS DATE DWN DES CHD APD
M.1 EMPLOYER
*4 Grounded socket for I-control unit.
QATAR ARMED FORCES
2 DETAIL - A MILITARY MEDICAL CITY HOSPITAL PROJECT
MANAGEMENT OFFICE P.O. BOX 2075 DOHA,
MEQ-3133 SCALE: NTS QATAR

1 CT SCAN ROOM - FLOOR and WALL TRUNKING LAYOUT MAIN CONTRACTOR:


MEQ-3133 SCALE: 1:25
Legend HBK CONTRACTING CO. WLL
WORKING DRAWING REVISION NOTES Available cable and water hose sets P.O. BOX 1362 DOHA, QATAR
cut-out, LxW (i. e. in FK or raised floor) TEL: (974) 44451111 FAX: (974) 44451000

2 : ADJUSTMENT ON FLOOR TRUNKING AS PER THE NEW DRY WALL LOCATION Cable set Water hose set
cut-out, Ø in mm (i.e. in suspended ceiling) LEAD CONSULTANT:
* 10 m 10 m

Power supply SOMATOM Drive


16 m
25 m
20 m
30 m
KB core hole, Ø in mm (minimum inner clearance required)
MEINHARDT
Legend electrical installation *For the shown installation the selected options have to be used. BD floor opening, top view LxW (break-throughs and openings, which delimit the 14TH FLOOR AMWAL TOWER WESTBAY
P.O. BOX 1362 DOHA, QATAR
Mains TN-S 3/N/PE AC 50/60 Hz ± 2Hz Line impedance Power consumption 1 To external conductive parts * The length of the water hoses depends on the position of the cooling water connection. fireproof area, must be closed on site after the installation is finished). TEL: (974) 44117840 FAX: (974) 4411 7845
The final lenghts must be determined on site with the Siemens project manager!
Voltage 400 V ± 10 % Only copper cables are allowed DD ceiling opening in ceiling above LxW (break-throughs and openings, which ARCHITECT & INTERIOR DESIGNER:
2 Test jack 4 mm pin plug delimite the fireproof area, must be closed on site after the installation is finished).
Line to line unbalanced max. 2 % Connection value 173kVA Stand-by 16kVA Additional electrical connectivity for the customer at
WD wall break WxH (break-throughs and openings, which delimit the
Cable cross section is to be determined by national regulations. System off 1kVA 3f Circuit breaker 125A Siemens 3VA1112-4ED46-0AA0
Siemens Customer fireproof area, must be closed on site after the installation is finished).
The size of the terminals in the PDC are designed for. 25 / 95 mm² for time up to < 2 s 293kVA Healthineers
3a Circuit breaker 32A Siemens 3VA1132-4EE46-0AA0 name of a fixpoint or a connection point
PE N L1 L2 L3 Electrical installation according to IEC 60364-7-710, national regulations must be observed 2 4.4
MEDICAL PLANNER: MEDICAL EQUIPMENT : MEP SUBCONTRACTOR : SUBCONTRACTOR :

4 Overvoltage protection intern 1m


cable fixing point
Power supply for CT-System Minimum requirement for the on site
max. 2,5 mm² flexible
4.3
max.
Power distributor residual current device RCD Siemens 3VA9114-0RL21 250 VAC / 2 A
electrical installation 3Rc
Room Group 1 30mA, Room Group 2 30mA 24 VDC / 2 A Access hatch in suspended ceiling not required if the ceiling tiles are easily removable
4 residual current device RCD Siemens 3VA9114-0RL21 Size and position depending on structural conditions on site.
3R
Room Group 1 300mA, Room Group 2 30mA 2 4.2
PROJECT TITLE:
PE intern 1m
+ 5 24V DC power supply SITOP 6EP1436-2BA10
max. 2,5 mm² flexible switch, installation according to national guidelines
min. Auxiliary switch changeover contacts per Circuit breaker Siemens
max.
250 VAC / 2 A
4.1
ENGINEERING, PROCUREMENT AND
24 VDC / 2 A grounded socket, installation according to national guidelines
AUX 3 VA

6
16 □
Cu
1.4 13 13 13 21 T1 T2 3VA9988-0AA12 CONSTRUCTION (EPC/TURNKEY) FOR
K2 K3 K1 K1 80% 20% Side mounted motor per Circuit breaker 3VA 24V DC grounded socket, switchable, installation according to national guidelines
PA 1.1 14 14 14 22
10s 1s 7
3VA9117-0HB10 intern 1m 2
max. 2,5 mm² flexible
2.4 MILITARY MEDICAL CITY HOSPITAL
1 K K
Undervoltage release for MCCB per Circuit breaker Siemens Drain pipe provision 25-50mm Ø
6 33 K4 9 10
8
3VA9908-0BB11
max.
250 VAC / 2 A
24 VDC / 2 A
2.3

warning lamp / indicator,


(MMC) AT TAREK BIN ZEYAD CAMP
18 43 TP telephone socket
K1 2 9 Timing relay 3RP2505-1AB30-0AC1 ceiling mounted, wall mounted IN SAILIYAH (SOUTH OF DOHA)
PE
L1
L2
L3

T2 K1
~
24 23
34 15 44 2.2 network socket
2
5 18 K6 10 Timing relay Siemens 3RP2505-1AB30-0AC1 intern 1m
max. 2,5 mm² flexible

T1
4
1.1 1.4
12 Contactor relay 24V DC 3RH2131-2BB40
max.
250 VAC / 2 A
2.1
UK bottom edge OK top edge PROJECT NO. AA-103-01
15 AUX 3 VA 19 24 VDC / 2 A
DRAWING TITLE:
6A - Contactor relay 24V DC 3RH2131-2BB40 bottom edge suspended ceiling OK FFL top edge finished floor
13 UK ABGD
4 3 B1 F1 E1 K6 intern 1m 2 1.6 BUILDING 01-ZONE 01, -PART 06 - GROUND FLOOR -
5 Priorität 1 20 14a Impulse switch Eltako ES 12Z-200-UC
max. 2,5 mm² flexible
Q3 Q2 Q1 MODE 1
M 3VA <U T1 T2 K2 K3 ZE + ZA K4 K1 + max. 1.5
UK RHD
bottom edge bare ceiling OK RFB top edge unfinished floor CT SCAN ROOM (Z1-L0-IMD-025) - SOMATOM Drive
- 250 VAC / 2 A
4 32A 4 125A 4 125A
7
7
8 9 10 12 13
A2 E2
16 16 Contactor relay 24V DC 3RH2131-2BB40 24 VDC / 2 A PRE-INSTALLATION ELECTRICAL PLAN
RHD bare ceiling RFB unfinished floor level
3a 3f 3f - 13 THIS DRAWING HAS BEEN CHECKED FOR COMPLETENESS, ACCURACY, COORDINATION, AND
K8 19 Auxiliary switch changeover contacts Siemens 3VA9988-0AA12 Power Distribution Cabinet (PDC) ABGD suspended ceiling FFL finished floor level COMPLIANCE WITH THE CONTRACT DOCUMENTS. ALL DIMENSIONS AND FIELD CONDITIONS
3R 3R K6 HAVE BEEN VERIFIED.
+ EQUIPMENT
K8 23 14 20 Contactor relay 24VDC 3RT1017-1BB44-3MA0 (K6) aABGD above suspended ceiling AFFL above finished floor level
ROOM

1 23 Contactor relay 24V DC 3RH2131-2BB40 (K8)


aD on ceiling / suspended ceiling aFFL on finished floor / raised floor CONTRACTOR'S REPRESENTATIVE:
Mr. ALAADDIN AKTAN
DATE:
20 Sept 2022

2 AT Emergency off button with locking mechanism


EXAMINA-
BRH parapet height UZ downstand beam STATUS:

BY HBK TION On-off button with pilot lamp


ISSUED FOR CONSTRUCTION
ROOM External cooling system FK cable duct WxD (minimum inner clearance required), accessible flush floor trunking system,
SUBMISSION STAGE DATE
EQUIPMENT heat exchanger water/air - split floating ground contact, 250VAC / 2A oder 24VDC / 2A. moisture-proof, grounded
ROOM L The need for the installation has to be clarified with the customer. WORKING DRAWING 17/10/2022
L IK cable trunking WxD, WALL surface mounted
Do not connect external components to the CT power supply line. Room light
[1.0m] [0.7m] [0.7m]
CONTROL floating ground contact, 250VAC / 2A oder 24VDC / 2A. BK parapet channel WxD, surface mounted (for power and network sockets, etc.) DRAWN DESIGN CHECKED
Energy cables which do not belong to the system must be separated
X20 5.1

X20 5.2
X20 2.3
X20 2.4

PE L1/L2/L3 PE L1/L2/L3/N PE L1/L2/L3/N ROOM


prior to fitting The need for the installation has to be clarified with the customer. ABAM ABAM PRABHU
Siemens X20 5.4 - KW cable tray WxD (i. e. in ceiling void)
Healthineers 25 - 95 mm² the unit cables (distance >100 cm), or they must also be metallically
25 - 24V Output SCALE A1
10 mm² shielded. For LR ductwork, Ø in mm (minimum inner clearance required)
DESIGNED
95 mm² REPO X20 5.3+
USA: PE is equivalent to Protective-GND and PA is equivalent to MEINHARDT 1:25
Transient-GND The installations for cable routing depicted in the drawing need to be reserved for the exclusive
4 POWER DISTRIBUTION DIAGRAM use by SIEMENS Healthineers.
DRAWING NO. REVISION NO.

MEQ-3133 SCALE: NTS MMC-HBK-P1-WD-B01-MEQ-L0-P06-3133 0

BIM MODEL REFERENCE :


SITE PLAN

E
N
B07 B08

S
14.04 m²

N
LA
.63
W
Connection of cooling system (schematic)

QIB
252
not to scale
CHANGE Scope of delivery - Cooling system B14

Z1-L0-IMD-024 1. Standard:
B09
B02 B03
B05

B01
- Flexible water hoses (Ø 34 mm) with thermal insulation (Ø 58 mm); available lenghts 10, 20 and 30 m;
Z1-L0-IMD-026 7.08 m² min. bending radius: 150 mm, shorten excess cable lengths; preordering is possible

B06
B12 B13
- Thermal insulation of water hoses: B11
B10
• Length delivered depends on water hose length ordered.
4.77 m²
B04

Recommended: • Suitable for cable ducts up to 60 mm height and on-site water temperature in the range of ≥ 8° C to 16° C.
SW Please note:
TS Shut-off valve necessary. In this case the outer diameter of the thermal insulation won't fit the standard cable
duct heights of 60 mm.
- Accessories: contains all required parts for the water connection:
Pressure regulator • 2x flexible fabric hoses for water connection (Gantry side) with preinstalled shut-off valves
• Adapters for M36x2 metric to G1" inside thread (see also "Water connection pieces with shut-off valve") GENERAL NOTES
1. PROJECT REFERENCE ELEVATION ±0.00 IS AT +27.50 QATAR NATIONAL DATUM. ELEVATIONS
- Water drain for condensation (produced from the water-cooled gantry during system cooling): SHOWN ARE WITH RESPECT TO THE PROJECT REFERENCE ELEVATION OF ±0.00 AT GROUND FLOOR.
p Diff. pressure gauge • Length 10 m; (outer diameter Ø 10 mm; inner diameter Ø 6 mm) 2. ALL DIMENSIONS ARE IN MM UNLESS NOTED OTHERWISE.
• Min. bending radius: 30 mm 3. EQUIPMENT DIMENSIONS ARE SUBJECT TO CHANGE BASED ON MATERIAL SUBMISSION APPROVAL.
4. CONTRACTOR TO COORDINATE AS PER SITE CONDITIONS WHEREVER APPLICABLE.
• Shorten excess cable length to size.
5. SHOP DRAWINGS ARE ISSUED IN COORDINATION WITH APPROVED DETAILED DESIGN FF&E AND
TI Thermometer • Extension up to 20 m possible; extension material must be provided on-side. MEDICAL EQUIPMENT SELECTIONS. SOME AREAS ARE SUBJECT TO CHANGE AFTER MATERIAL
TI TI • Minimum flow rate: 2 l/h at 75% relative humidity SUBMITTALS APPROVAL .

SBA
CT ROOM On-site 2. Option
cooling Feed water flow meter - Fixed piping kit:
EAT AT Z1-L0-IMD-025 p p water supply • includes the installation material to connect the delivered flexible cooling hoses with on-site fixed piping
• 4x connection pieces (DKOL DN25 VA)

2481
AT • 4x adaptors M36x2 metric to G1" internal thread

KEY PLAN 1
10 10.1 17 17.1
26

A A

Water return Water inlet


P2.1
Z1 Z3 P3.1

2760 F Z2 F

Water connection pieces with shut-off valve not to scale P2.A P3.A

on-site
(in scope of delivery)
P2.F P3.F

Flexible fabric hose - unbent Flexible fabric hose - bent


ICS Supply provided by customer G1" external thread P2.1

Z4 Z5
P3.1

WORK /

150
2 V V

CONTROL GR
Z1-L0-IMD-023 1911 Adapter fitting for hose G1" internal thread
1 6 13 13.1 21

in scope of delivery
*2 DRAIN PIPE FOR

cabling
CONDENSATION OF THE m REFERENCE DOCUMENTS
in.

water
OPC MACHINE BY HBK 80 DOCUMENT NO TITLE REV

2615

534
3 MMC-HBK-AP-DD-BAP-MEQ-L0-APO-1800
BUILDINGS 1 - ALL ZONES - ALL PARTS - OVERALL -GROUND FLOOR -
MEDICAL EQUIPMENT PLAN
2

FK 300x80mm
MMC-HBK-P1-DD-B01-MEQ-L0-P06-1806 BUILDING 1 - ZONE 01- PART 06- GROUND FLOOR MEDICAL EQUIPMENT PLAN 2
4
AT

1775
WATER COOLING The cooling water hoses Ø 34 mm
(with insulation Ø 58 mm) from the gantry
1300

for water connection are in scope of


6050 delivery and available in 10, 20 or 30 m.
MILITARY MEDICAL CITY PROJECT - AL SAILIYAH
200 1204 Approval Status
2529 3321

Approved as
Commented
1

Re-Submit
A Approved

D Rejected
Revise &
FK 200x80mm Condensed water hose to Authority Signature Date

557
e.g. a sink or a siphon 1 Hexagon coupling nut 2 Shut-off valve 3 Flexible fabric hose 4

C
B
280

WD

h= 450mm
MMC-PMO
Suitable for installation in surface mounted trunking, cable duct or false floor.
845

GR

CV IRS PDCA PDCB Water connection pieces


with shut-off valve
Example for installation of water drain for condensed water not to scale The approval and comments shall not in any ways relieve or absolve the
Contractor from compliance of any obligations or liability under or in connection
150x300 300x300 300x300
(schematic) with the contract, project requirements and specifications.

6
1 DRAIN and COOLING WATER LOCATION 0 ISSUED FOR CONSTRUCTION
REVISION DETAILS
31/10/2022
DATE
ABAM ABAM
DWN DES
PR
CHD
SG
APD
MEQ-3134 SCALE: 1:30
1 EMPLOYER

On-site requirements for the integrated cooling system


QATAR ARMED FORCES
2 MILITARY MEDICAL CITY HOSPITAL PROJECT
The heat dissipation of the water-cooled gantry depends on the utilisation of the operator. MANAGEMENT OFFICE P.O. BOX 2075 DOHA,

max.
QATAR

4m
Utilisation of the CT system [%] 100 75 50 25 0 7 4 5 MAIN CONTRACTOR:
(Max. power) (stand-by)
Technical data of the interface heat exchanger 3
HBK CONTRACTING CO. WLL
Heat dissipation to cooling water [kW] 17 14 11 8 5
Primary circuit components: Shut-off devices, filters, flow indicators, fill and drain valves, plate heat P.O. BOX 1362 DOHA, QATAR
Heat dissipation (Gantry and patient table) to air [kW] 1 1 1 1 1 exchanger, pressure gauge 1 E.g. a sink 2 Water drain; flow rate capability: min. 20 l/h 3 E.g. cable duct TEL: (974) 44451111 FAX: (974) 44451000

Coolant: Water / glycol mixture with a maximum glycol concentration of 40%


Temperature gradient (cooling water) max. 1 K/min Temperature range:
4 Condensed water hose 5 Outlet for condensed water hose at the gantry
2° - 8° C LEAD CONSULTANT:

Operating pressure nominal: 2 bar to 6 bar, max. 10 bar Flow rate: 4 m³/h 6 Gantry rear view 7 Max. installation height (for hose routing; water drain connection etc.)
NOTE: To guarantee the limit of the maximum water pressure of 10 bar, Pressure loss: 0.5 bar MEINHARDT
the on-site cooling water system must provide a suitable safety device, e. Operating pressure: max. 10 bar 14TH FLOOR AMWAL TOWER WESTBAY
P.O. BOX 1362 DOHA, QATAR
TEL: (974) 44117840 FAX: (974) 4411 7845
g. a pressure relief valve.
Secondary circuit components: Fill and drain valve, shut-off device, diaphragm-type expansion vessel, GR Gantry - connection water, power and datalines
Water quality Potable water quality with particle size ≤ 0,25mm safety valve, circulating pump with fill and drain valve, permanent bleed, ARCHITECT & INTERIOR DESIGNER:

(filters/heat exchangers - see detail "Interface heat exchanger" - pressure gauge


must be provided by customer if necessary) Coolant: Water
On-site water connection (schematical) not to scale

Anti-freeze may be added to the on-site circuit. Max. mixing ratio up to -25°C: 40 % Connections: M36x2 / DN25
Adding anti-freeze reduces the cooling output and requires higher cooling water flow rate. Heat up brine to at least Internal pressure loss: ca. 0.5 bar 3 MEDICAL PLANNER: MEDICAL EQUIPMENT : MEP SUBCONTRACTOR : SUBCONTRACTOR :

+4 °C if the internal cooling system is connected to an existing on-site cooling system! Only then on-site water can Operating voltage: 3/N/PE ~400 VAC / ±10% - 50 Hz / ±1%
flow through the Gantry integrated cooling system. 3/N/PE ~460 VAC / ±10% - 60 Hz / ±1% 1 6 7

Switching off when the CT system is not in operation Power consumption, overall system: max. 0.6 kVA at 50 Hz
For purposes of saving energy the on-site water circulation can be switched off with: max. 0.9 kVA at 60 Hz 2 4 5 PROJECT TITLE:

- On-site installation of a solenoid valve or switch-off feed pump via contactor Fuse protection (provided by client): 10 A
- On-site feed pump 1 Water hose 2 M36 x 2 external thread 3 Adapter (in scope of delivery) ENGINEERING, PROCUREMENT AND
- Optional water/air-split cooling system
General information 4 G1" internal thread 5 G1" external thread 6 On-site water connection 7 e. g. wall CONSTRUCTION (EPC/TURNKEY) FOR
A floating relay contact assembly is included in the PDC:
Maximum 277 VAC/2 A; utilization category AC-14/15 For the gantry-integrated cooling system a on-site cooling water system has to be provided. MILITARY MEDICAL CITY HOSPITAL
Maximum 24 VDC/2 A; utilization category DC-12/13 The cooling water system will be connected via:
- Flexible water hoses (in scope of delivery, orderable lengths 10, 20 or 30 m) and special water connection pieces.
(MMC) AT TAREK BIN ZEYAD CAMP
Minimum flow rate - On-site cooling circuit Piping material
- On-site fixed pipes (PVC, copper, high-grade steel). Therefore a "Fixed piping kit" can be ordered. For vibration
Recommended Not recommended
IN SAILIYAH (SOUTH OF DOHA)
reduction the flexible water connection pieces have to be installed between the fixed piping and the water
Barometric pressure 700 to 1060 hPa
Pressure loss - On-site cooling circuit 2 connection points of the gantry. The direct connection of fixed piping and gantry water connection points is not
Stainless steel (V2A; V4A) Aluminium
permitted!
Non-ferrous metal (e.g. copper, brass) Iron, carbon steel
PROJECT NO. AA-103-01
Barometric pressure 700 to 1060 hPa 3500 l/h For service and filling procedure a water faucet with screw connection and a water drain (e.g. a sink or a siphon) in
2 3 Synthetic materials, plastics Zinc-plated steel
DRAWING TITLE:
4 3200 vicinity of the gantry is necessary.
3 3000 BUILDING 01-ZONE 01, -PART 06 - GROUND FLOOR -
3000 l/h Brazing solder, hard solder Zinc
2.2 bar
CT SCAN ROOM (Z1-L0-IMD-025) - SOMATOM Drive
2.0 bar Fitting solder types 3 and 4 Standard steel pipes PRE-INSTALLATION ELECTRICAL PLAN
2.05
1.8 bar 2050 THIS DRAWING HAS BEEN CHECKED FOR COMPLETENESS, ACCURACY, COORDINATION, AND
2000 l/h COMPLIANCE WITH THE CONTRACT DOCUMENTS. ALL DIMENSIONS AND FIELD CONDITIONS
HAVE BEEN VERIFIED.
1.6 bar 1800
1.45 1600
1.4 bar
1120
1300 1300 Legend
1.2 bar 970 1030 Mr. ALAADDIN AKTAN 20 Sept 2022
1000 l/h CONTRACTOR'S REPRESENTATIVE: DATE:
0.95 740 850
1.0 bar 650 cut-out, LxW (i. e. in FK or raised floor) STATUS:

0.8 bar 500 l/h 1 ISSUED FOR CONSTRUCTION


cut-out, Ø in mm (i.e. in suspended ceiling)
4°C 6°C 8°C 10°C 12°C 14°C 16°C
0.6 bar 0.65 SUBMISSION STAGE DATE
0.45
0.4 bar Drain pipe provision 32-50mm Ø WORKING DRAWING 17/10/2022
1 Water temperature 2 Flow rate volume 3 Without anti-freeze 4 With 40% anti freeze
0.2 bar 0.3 FK cable duct WxD (minimum inner clearance required), accessible flush floor trunking system, DRAWN DESIGN CHECKED
NOTE: Additional pump is required if flow rate of water supply is too low. moisture-proof, grounded
0 bar 1 ABAM ABAM PRABHU
IK cable trunking WxD, WALL surface mounted
1000 l / h

1500 l / h
500 l / h

3000 l / h
2000 l / h

2500 l / h

DESIGNED SCALE A1

MEINHARDT 1:25

DRAWING NO. REVISION NO.


1 Water flow per hour 2 Pressure loss 3 With and without anti-freeze
MMC-HBK-P1-WD-B01-MEQ-L0-P06-3133 0

BIM MODEL REFERENCE :


01231245ÿ72893ÿ 


!"
!"
#ÿ$%

&'ÿ!( ) &'ÿ.# ")/ /)1)/).3)ÿ.# ")/


*+,-ÿ!+ 0 12 32*!/ .2492449 0 12 32*!/ .2492449
1ÿ5*124736768ÿ3!ÿ93 .ÿ/:: ÿ5;72'42& <24278ÿ2ÿ9: !: ÿ<+=ÿ/)2
&.9! '' !&:.ÿ2ÿ*:/$&.>ÿ</ *&.>9
1+ ÿ ÿÿ2ÿ 3
!ÿ508 +ÿ ÿ)?ÿ2ÿÿ"ÿÿ 
+ÿÿ>-ÿ2ÿ@"$ÿ3+%
+ÿA=ÿ$ÿ2ÿ@"$ÿ3+%
+ÿ+ÿ/+Bÿ2ÿ@"$ÿ3+%
+ÿÿ>++ÿ2ÿ@"$ÿ3+%
+ÿ&+ÿÿ/ÿ2ÿ@"$ÿ3+%
ÿ ÿÿ2ÿ 3
+ÿ"+%+5)%1+8+ÿÿ2ÿ 3
+ÿ9+ÿ9++ÿ2ÿ 3
3 ÿ5748 +ÿ.</:)ÿ1+ÿ2ÿ@"$ÿ3+%
Cÿ ÿ2ÿ@"$ÿ3+%
+ÿÿÿ2ÿ@"$ÿ3+%
+ÿ.ÿ#ÿ2ÿ@"$ÿ3+%
+ÿ/Bÿÿ2ÿ@"$ÿ3+%
+ÿ/?ÿ+??ÿ2ÿ@"$ÿ3+%
+ÿÿ>,+ÿ2ÿ@"$ÿ3+%
+ÿ@ÿ"ÿ2ÿ@"$ÿ3+%
+ÿ*ÿ D+ÿ2ÿ@"$ÿ3+%
9ÿ>%ÿ2ÿ@"$ÿ3+%
ÿ/ÿ&ÿ2ÿ 3
1++ÿ?ÿ2ÿ 3
+ÿ@?ÿ&+%ÿ2ÿ 3
9 !+?5ÿ29ÿ.=+ÿ2422

ÿ )99 >)
811711 7177
01231245ÿ72893ÿ 
!"ÿ#$"ÿ%&
'ÿÿÿ$ÿÿÿ()'ÿ*) +ÿ#,, ÿ-.7/01/2 3/1274ÿ/ÿ*, ', ÿ3$ÿ#5/2+*' 00 '2,+ÿ/ÿ,#62+7
3# 2+7*(ÿ"!"ÿ"ÿÿ!"8ÿÿ8
9:;<ÿ>?@A<B;>>@CÿD@<ÿ@E>FB@>;G@CCHÿIJAJ?@>JKL

3ÿ+ *  #$"ÿ, )


-74ÿ*Qÿÿ*
'ÿ$ÿ-24/"
3ÿÿÿ
ÿ&ÿM ÿ-44'
ÿÿÿ
) 3ÿ23ÿ!ÿÿ
ÿÿÿ5
8ÿ!ÿ"ÿ&
ÿ-94ÿÿ+ÿ-
710/7724ÿÿ"ÿ
)/%M6/7/3/M17/ %M6)ÿ/ÿ  ÿ5Rÿ08ÿ-P4
5N/01/1O/472P 2ÿÿ# #$"ÿ"ÿ) *ÿÿÿÿ
5Rÿÿ!
5ÿÿ
ÿ888ÿÿ!
$ÿÿ
-O4ÿ2ÿÿ
&ÿÿ
ÿÿÿ
ÿ
8ÿÿ"8
ÿÿ&ÿ
 8&
7/ÿÿ"ÿ
"ÿÿÿ$ÿ
!ÿ8ÿÿ8
"ÿM ÿ2/ÿ#ÿ!
8ÿÿ"ÿÿ
ÿ8ÿ"ÿM ÿ$
ÿÿ4717112122ÿ4/
%M6)ÿ/ÿ  ÿ7" #$"ÿ"ÿ) $$ÿ8
8
ÿÿ
!ÿÿ
ÿ8ÿ9/
ÿ"ÿ
ÿÿ"
ÿRÿ&
M ÿ"ÿÿÿ
$ÿ8

811711 2177
01231245ÿ72893ÿ 
7*ÿÿ+%),ÿÿ
ÿÿ)%
+%%ÿÿ%ÿ-ÿ !
. ÿÿÿÿ
%ÿ-ÿ ÿ. ÿ-
)%ÿ2ÿÿ
ÿ%ÿ/%ÿ+,ÿ)
(ÿ420ÿ%ÿ1 2
*%ÿ)ÿÿ(
"1ÿ. ÿ%ÿÿ3%ÿ
 !"ÿ#ÿ$% &ÿ! '()ÿ)ÿ" *%ÿ/,,ÿ)ÿ
%ÿ-ÿ ÿ. ÿ-
)%ÿ4ÿ.45ÿ. ÿ5
1.ÿ%ÿÿÿ%ÿ-
ÿÿ-ÿ)%ÿ9
1ÿ%%,ÿ-
)%ÿ+%ÿÿ
,ÿ)ÿ+,
+%),ÿ6ÿ*ÿ%
3%ÿ1%,ÿÿ&"
ÿ%%,ÿ)
ÿ%ÿ-ÿ ÿ
7ÿÿÿ
ÿ%ÿ)ÿ
ÿÿÿ%
 !"ÿ#ÿ*"11$7& ÿ8%% '()ÿ)ÿ" %(ÿ+,ÿ2ÿ1
.%ÿÿ%ÿ-
9ÿÿ%ÿ,
ÿÿÿ
7ÿ'-%ÿÿ%
ÿÿ
%9ÿ-ÿ2ÿ
%ÿÿ5ÿ%
ÿ#ÿ%(ÿ) )%ÿÿÿ ÿ
 !"ÿ#ÿ% ÿ'%: " 4ÿ$;ÿ
%9ÿÿ%ÿ
),ÿ9ÿ(ÿ%,ÿÿ)
ÿÿ)ÿ,ÿ6
< <"ÿÿÿ-ÿ=
* ÿ ÿ5ÿ24"ÿ
"ÿ#ÿ.% .ÿ.%% ÿ#ÿ%(ÿ) 7#ÿ"%%ÿÿ%
" -%ÿÿ $ ÿ-%
%;%ÿÿ)%
(9ÿ2#
"%ÿ%;%
)ÿ--%
811711 4177
01231245ÿ72893ÿ 
ÿ !ÿ
"ÿ#ÿ#ÿ
ÿ$#ÿ$ÿ
ÿ4%ÿ&ÿ
ÿ$ÿ
ÿ  'ÿ
(ÿÿ
!#ÿ
&ÿ%ÿ)! )ÿ *" ÿÿ&

&ÿ%ÿ  ÿ )ÿ%ÿ"ÿ ÿ$ÿÿÿ"


& 
74ÿ56ÿÿ5
&%')+%7%,-%).7% ')+&ÿ%ÿ  3ÿÿ* *" ÿÿ& 7ÿ"ÿ24
/0%1.%.2%4722 8"ÿ 9
ÿÿÿ
7%ÿÿÿ
ÿÿÿ"ÿ
$ÿ!ÿÿ!
ÿ) ÿ2%ÿ*ÿ$
!ÿÿÿÿ
ÿ!ÿÿ) ÿ"
ÿÿ4717.12.22ÿ4%
')+&ÿ%ÿ  ÿ:  *" ÿÿ& ""ÿ!
!
ÿÿ
$ÿÿ
ÿ!ÿ9%
ÿÿ
ÿÿ
ÿ(ÿ#
) ÿÿÿÿ
"ÿ!
')+&ÿ%ÿ/ ;ÿ+ *" ÿÿ& 73ÿÿ- !ÿÿ
ÿÿ 
-ÿÿÿ$ÿ')+
5 ÿ)ÿÿÿ
ÿ$ÿ) ÿ5 ÿ$
ÿ2ÿÿ
ÿÿ8ÿ-!ÿ
"ÿ42.ÿÿ7 <
3ÿÿÿ"
&7ÿ5 ÿÿÿ=ÿ
3ÿ8!!ÿÿ
ÿ$ÿ) ÿ5 ÿ$
ÿ4ÿ5,5ÿ5) ÿ>
75ÿÿÿÿÿ$
811711 9177
01231245ÿ72893ÿ 
ÿÿ!ÿ"#ÿ9
$ÿ##%ÿ!
"#ÿ&#ÿÿ
%ÿ"ÿ&%
&#"%ÿÿ'ÿ#
(#ÿ$#%ÿÿ)*
ÿ##%ÿ"
ÿ#ÿ!ÿ ÿ
7ÿÿÿ
ÿ#ÿ"ÿ
ÿÿÿ#
+ ,*ÿ-ÿ'*$1./) ÿ0## 12"ÿ"ÿ* #2ÿ&%ÿ2ÿ$
3#ÿÿ#ÿ!
4ÿÿ#ÿ%
ÿÿÿ
7ÿ1!#ÿÿ#
ÿÿ
#4ÿ!ÿ2ÿ
#ÿÿ6ÿ#
ÿ-ÿ#2ÿ" "#ÿÿÿ ÿ
+ ,*ÿ-ÿ# ÿ1#5 * 4ÿ.7ÿ
#4ÿÿ#ÿ
"%ÿ9ÿ2ÿ#%ÿÿ"
ÿÿ"ÿ%ÿ
8 8*ÿÿÿ!ÿ9
' ÿ ÿ6ÿ:;*ÿ
7-ÿ*##ÿÿ#
!#ÿÿ . ÿ!#
#7#ÿÿ"#
24ÿ2-
*#ÿ#7#
"ÿ!!#
*ÿ-ÿ3# 3ÿ3## ÿ-ÿ#2ÿ" ÿ#"%ÿ
* 2ÿ4ÿ#4ÿ
#ÿ!4ÿ!ÿ
ÿ4-ÿ*##ÿ
#ÿ!ÿ
"ÿ  +ÿ#
#7#ÿÿ#
#%#4ÿ#
*ÿ-ÿ#%# ÿ 12"ÿ"ÿ*

*ÿ-ÿ  ÿ ÿ-ÿ#2ÿ" ÿ#!#ÿÿÿ2


* 

811711 177
01231245ÿ72893ÿ 
7ÿ(0ÿ,
!"#$!7!%&!#'7! "#$ ÿ!ÿ  +ÿ,-- +./ÿ/ÿ ÿÿÿÿÿ,ÿ/
ÿ
()!*'!'!4723 1
ÿ,ÿÿ
7!ÿÿ/,ÿ
/ÿÿÿ.ÿ
3ÿ1ÿÿ1,
/ÿ# ÿ2!ÿ+ÿ3,
,1ÿÿ/ÿÿ
ÿ1,ÿ/ÿ# ÿ.
ÿÿ4717'12'22ÿ4!
"#$ ÿ!ÿ  ÿ2/ +./ÿ/ÿ .,,.ÿ1
1
ÿÿ
3,,ÿÿ
,ÿ1ÿ9!
ÿ/,ÿ
ÿ,ÿ/,
ÿ,0ÿ-
# ÿ/,ÿÿ,ÿ
,.ÿ1
75ÿÿ&,/1ÿÿ
ÿÿ/,
&,,ÿÿ,ÿ3ÿ"#$
6 ÿ#ÿÿÿ
,ÿ3ÿ# ÿ6 ÿ3
/,ÿ2ÿÿ
ÿ,ÿ7,ÿ&1ÿ/
.ÿ42'ÿ,ÿ8 9
5,ÿ/ÿÿ.
8ÿ6 ÿ,ÿÿ:,ÿ
"#$ ÿ!ÿ(, 4ÿ$ +./ÿ/ÿ 5,ÿ711ÿ/ÿ
,ÿ3ÿ# ÿ6 ÿ3
/,ÿ4ÿ6%5ÿ6# ÿ;
86ÿ,ÿÿÿ,ÿ3
# ÿÿ3ÿ/,ÿ9
8ÿ,,1ÿ3
/,ÿ&,ÿÿ
1ÿ/ÿ&1
&,/1ÿ<ÿ5ÿ,
:,ÿ8,1ÿÿ4
ÿ,,1ÿ/
ÿ,ÿ3ÿ# ÿ
"#$ ÿ!ÿ581(*4 ÿ2,, +./ÿ/ÿ 7ÿÿÿ
ÿ,ÿ/ÿ
ÿÿÿ,
,.ÿ&1ÿ2ÿ8
811711 177
01231245ÿ72893ÿ 
ÿÿÿ!
"ÿÿÿ#
ÿÿÿ
7ÿ)!ÿÿ
ÿÿ
"ÿ!ÿ2ÿ
ÿÿ-ÿ
%ÿ(ÿ+ÿ, ,ÿÿÿ% ÿ
$%&'ÿ(ÿ  ÿ)* ' 4ÿ./ÿ
"ÿÿÿ
,#ÿ9ÿ+ÿ#ÿÿ,
ÿÿ,ÿ#ÿ0
1 1'ÿÿÿ!ÿ2
%3 ÿ ÿ-ÿ45'ÿ
7(ÿ'ÿÿ
!ÿÿ . ÿ!
/ÿÿ,
+"ÿ2(
'ÿ/
,ÿ!!
'ÿ(ÿ ÿ %ÿ(ÿ+ÿ, ÿ,#ÿ
' +ÿ"ÿ "ÿ
ÿ!"ÿ!ÿ
ÿ4(ÿ'ÿ
ÿ!ÿ
,ÿ  $ÿ
/ÿÿ
#"ÿ
'ÿ(ÿ%# %ÿ )+,ÿ,ÿ'

'ÿ(ÿ  ÿ %ÿ(ÿ+ÿ, ÿ!ÿÿÿ+


' 
'($%&(7(56(%77( $%&'ÿ(ÿ  3ÿÿ) )+,ÿ,ÿ' *ÿÿ$%&'ÿ.
.1(87(72(4729 +
$%&'ÿ(ÿ  ÿ:, )+,ÿ,ÿ' 7(ÿÿ,ÿ
,ÿÿÿ+ÿ
!ÿ#ÿÿ#
,ÿ% ÿ2(ÿ)ÿ!
#ÿÿ,ÿÿ
ÿ#ÿ,ÿ% ÿ+
ÿÿ4717712722ÿ4(
++ÿ#
 #ÿÿ
!ÿÿ
ÿ#ÿ9(
811711 3177
01231245ÿ72893ÿ 
ÿ!ÿ
ÿ!ÿ!
ÿ!"ÿ#
$ ÿ!ÿÿ!ÿ
!%ÿ&
7.ÿÿ/! &ÿÿ
ÿÿ !
/!!ÿÿ!ÿ0ÿ'$(
1 ÿ$ÿÿÿ
!ÿ0ÿ$ ÿ1 ÿ0
!ÿ2ÿÿ
ÿ!ÿ2!ÿ/&ÿ
%ÿ423ÿ!ÿ4 5
.!ÿÿÿ%
)4ÿ1 ÿ!ÿÿ6!ÿ
'$()ÿ*ÿ+! ,ÿ( -% ÿÿ) .!ÿ2&&ÿÿ
!ÿ0ÿ$ ÿ1 ÿ0
!ÿ4ÿ175ÿ1$ ÿ8
41ÿ!ÿÿÿ!ÿ0
$ ÿÿ0ÿ!ÿ9
4ÿ!!&ÿ0
 !ÿ/!ÿÿ
&ÿÿ/&
/! &ÿ9ÿ.ÿ!
6!ÿ4!&ÿÿ,)
ÿ!!&ÿ
ÿ!ÿ0ÿ$ ÿ
7ÿÿÿ
ÿ!ÿÿ
ÿÿÿ!
'$()ÿ*ÿ.)41+:, ÿ;!! -% ÿÿ) !%ÿ/&ÿ2ÿ4
1!ÿÿ!ÿ0
#ÿÿ!ÿ&
ÿÿÿ
7ÿ-0!ÿÿ!
ÿÿ
!#ÿ0ÿ2ÿ
!ÿÿ8ÿ!
$ÿ*ÿ!%ÿ !ÿÿÿ$ ÿ
'$()ÿ*ÿ! ÿ-!< ) 4ÿ+"ÿ
!#ÿÿ!ÿ
 &ÿ9ÿ%ÿ!&ÿÿ
ÿÿÿ&ÿ9
= =)ÿÿÿ0ÿ>
$. ÿ ÿ8ÿ57)ÿ

811711 177
01231245ÿ72893ÿ 
7ÿ""ÿÿ"
&"ÿÿ ' ÿ&"
"("ÿÿ%"
$)ÿ2
"ÿ"("
%ÿ&&"
ÿÿ!" !ÿ!"" #ÿÿ"$ÿ% ÿ"%*ÿ
 $ÿ)ÿ")ÿ
"ÿ&)ÿ&ÿ
ÿ4ÿ""ÿ
"ÿ&ÿ
%ÿ  +ÿ"
"("ÿÿ"
"*")ÿ"
ÿÿ#"*" #ÿ ,$%ÿ%ÿ

ÿÿ  ÿ #ÿÿ"$ÿ% ÿ"&"ÿÿÿ$


 
576,&"ÿÿ+#-7
ÿÿ&"
ÿ8)ÿ"ÿ"ÿ
ÿ5ÿ9ÿ:ÿ
+#- 7./#07 +#-ÿÿ  %"ÿ$ÿ&"ÿ;
'1 20 034720 4ÿÿ, ,$%ÿ%ÿ (ÿ"ÿ"$
*95ÿ5264ÿÿ
)ÿ"5ÿ&"ÿÿ;
"5ÿ"ÿ%ÿ
"("5ÿ!"ÿÿ"&)
ÿ"
7ÿÿ%"ÿ
%ÿÿÿ$ÿ
&ÿ*ÿÿ*"
%ÿ# ÿ2ÿ,ÿ&"
"*ÿÿ%ÿÿ
ÿ*"ÿ%ÿ# ÿ$
ÿÿ4717012022ÿ4
+#-ÿÿ  ÿ<% ,$%ÿ%ÿ $""$ÿ*
*
ÿÿ
&""ÿÿ
"ÿ*ÿ9
ÿ%"ÿ
ÿ"ÿ%"
ÿ"(ÿ)
# ÿ%"ÿÿ"ÿ
"$ÿ*

811711 0177
01231245ÿ72893ÿ 
7+ÿÿ,&*-ÿÿ
ÿÿ*&
,&&ÿÿ&ÿ.ÿ!"
/ ÿ!ÿÿÿ
&ÿ.ÿ! ÿ/ ÿ.
*&ÿ2ÿÿ
ÿ&ÿ0&ÿ,-ÿ*
)ÿ42ÿ&ÿ1 2
+&ÿ*ÿÿ)
#1ÿ/ ÿ&ÿÿ3&ÿ
!"#ÿ$ÿ%& 'ÿ" ()*ÿ*ÿ# +&ÿ0--ÿ*ÿ
&ÿ.ÿ! ÿ/ ÿ.
*&ÿ4ÿ/45ÿ/! ÿ5
1/ÿ&ÿÿÿ&ÿ.
! ÿÿ.ÿ*&ÿ9
1ÿ&&-ÿ.
*&ÿ,&ÿÿ
-ÿ*ÿ,-
,&*-ÿ6ÿ+ÿ&
3&ÿ1&-ÿÿ'#
ÿ&&-ÿ*
ÿ&ÿ.ÿ! ÿ
7ÿÿÿ
ÿ&ÿ*ÿ
ÿÿÿ&
!"#ÿ$ÿ+#11%7' ÿ8&& ()*ÿ*ÿ# &)ÿ,-ÿ2ÿ1
/&ÿÿ&ÿ.
9ÿÿ&ÿ-
ÿÿÿ
7ÿ(.&ÿÿ&
ÿÿ
&9ÿ.ÿ2ÿ
&ÿÿ5ÿ&
!ÿ$ÿ&)ÿ* *&ÿÿÿ! ÿ
!"#ÿ$ÿ& ÿ(&: # 4ÿ%;ÿ
&9ÿÿ&ÿ
*-ÿ9ÿ)ÿ&-ÿÿ*
ÿÿ*ÿ-ÿ6
< <#ÿÿÿ.ÿ=
!+ ÿ ÿ5ÿ24#ÿ
#ÿ$ÿ/& /ÿ/&& !ÿ$ÿ&)ÿ* 7$ÿ#&&ÿÿ&
# .&ÿÿ % ÿ.&
&;&ÿÿ*&
)9ÿ2$
#&ÿ&;&
*ÿ..&
811711 7177
01231245ÿ72893ÿ 
ÿ !ÿ
"ÿ#ÿ#ÿ
ÿ$#ÿ$ÿ
ÿ4%ÿ&ÿ
ÿ$ÿ
ÿ  'ÿ
(ÿÿ
!#ÿ
&ÿ%ÿ)! )ÿ *" ÿÿ&

&ÿ%ÿ  ÿ )ÿ%ÿ"ÿ ÿ$ÿÿÿ"


& 

811711 77177
SITE PLAN

E
7

N
Z1-L0-IMD-020
CHANGE B07 B08

S
18.65 m² (F)

N
7.59 m²

LA
.63
W
(M)

QIB
252
Z1-L0-IMD-022
B14

Z4-L0-IMD-068 Notes on preparations for installation B09 B05

Z1-L0-IMD-026 B02 B03

4.78 m² Contracts for performing and supervising on-site installation preparations should be concluded with technically
B01

4.77 m²

B06
competent companies by the customer. The customer is responsible for timely and proper completion and B12 B13

7.16 m² SW supervision of all preparations for installation at the construction site in observance of all applicable legal regulations
B11

B04
B10

TS (e.g. X-ray regulations, radiation protection regulations) and all applicable general recognized rules of technology
(e.g. VDE regulations, DIN standards).
Execution and supervision of installation preparations at the construction site and later observance of the standard
operating conditions are not included in our duties. The customer is responsible for checking the static calculations
and, where applicable, the air conditioning in the building to be equipped.

P2.G
GENERAL NOTES
1. PROJECT REFERENCE ELEVATION ±0.00 IS AT +27.50 QATAR NATIONAL DATUM. ELEVATIONS
AT SHOWN ARE WITH RESPECT TO THE PROJECT REFERENCE ELEVATION OF ±0.00 AT GROUND FLOOR.
2. ALL DIMENSIONS ARE IN MM UNLESS NOTED OTHERWISE.
3. EQUIPMENT DIMENSIONS ARE SUBJECT TO CHANGE BASED ON MATERIAL SUBMISSION APPROVAL.

1486
1550
Room dimensioning 4.
5.
CONTRACTOR TO COORDINATE AS PER SITE CONDITIONS WHEREVER APPLICABLE.
SHOP DRAWINGS ARE ISSUED IN COORDINATION WITH APPROVED DETAILED DESIGN FF&E AND
SBA MEDICAL EQUIPMENT SELECTIONS. SOME AREAS ARE SUBJECT TO CHANGE AFTER MATERIAL
SUBMITTALS APPROVAL .
The indicated room dimensions have to be checked on site. The planning department has to be informed about
EAT possible deviations. Otherwise we cannot assume any guarantee for the accurate implementation of the dimensions
2760 5161 indicated in the planning documents.
AT
A
2981

2981
3126
± 0.00
KEY PLAN
-0.10
10 10.1 17 17.1
1 26

A A

1.11 Room lighting


CT ROOM P2.1
Z1 Z3 P3.1

1.12 Ambient lighting in rooms with diagnostics or with workstations must comply with the respective local and national Z2
Z1-L0-IMD-021
1860
D regulations. P2.A
F F

P3.A

3126
General requirements like the needed intensity of illumination - adjustable, reproducible, flicker-free or a limitation of
1.07 dazzlings and reflections etc. have to be observed (EN 12464-1, DIN 5035-7).

2500
P2.F P3.F

1.06
WORK /
5821

P2.1 P3.1

1.02 C Z4 Z5
± 0.00
3126
-0.10 CONTROL V V

1929 1.01
Z1-L0-IMD-023 Display screen workstations
6 13 13.1 21
For setting up display screen workstations, take account of the guidelines in the Display Screen Workstation
directive as well as any national regulations (e.g. EN ISO 9241-5).
REFERENCE DOCUMENTS
1.09
DOCUMENT NO TITLE REV

1.10 AT MMC-HBK-AP-DD-BAP-MEQ-L0-APO-1800
BUILDINGS 1 - ALL ZONES - ALL PARTS - OVERALL -GROUND FLOOR -
MEDICAL EQUIPMENT PLAN
2

2440
MMC-HBK-P1-DD-B01-MEQ-L0-P06-1806 BUILDING 1 - ZONE 01- PART 06- GROUND FLOOR MEDICAL EQUIPMENT PLAN 2
2840

B Safety distances
1 3126

1435
SW Distances from moving parts of the medical device to walls, furniture and other equipment have to be kept to avoid
injuries by crushing in compliance with local regulations, e.g. a minimum distance of 50 cm according to EN 349.
1871

MILITARY MEDICAL CITY PROJECT - AL SAILIYAH

1.05 It is the customer's responsibility to ensure the above requirements are followed.
Approval Status

Approved as
Commented

Re-Submit
A Approved
This is to avoid the risk of injury.

D Rejected
Revise &
Authority Signature Date
If safety distances are not maintained appropriate on-site safety measures have to be put in place.

C
B
1.04 1.03 Clear visible markings according to national guidelines, e.g. crushing warning signs, hazard warning
1.08 AT tape, hazard area cordon, safety mats, may be required.
MMC-PMO

M Lead shielded wall

The approval and comments shall not in any ways relieve or absolve the
Contractor from compliance of any obligations or liability under or in connection

M.1
Room height with the contract, project requirements and specifications.

Technically required minimum room height 2200 mm


Measured from the highest point of the finished floor (with covering) to the lowest point of the ceiling
1 ISSUED FOR CONSTRUCTION 31/10/2022 ABAM ABAM PR SG

1 CT SCAN ROOM - EQUIPMENT ARRANGEMENT PLAN 00 ISSUED FOR CONSTRUCTION


REVISION DETAILS
20/09/2022
DATE
ABAM ABAM
DWN DES
PR
CHD
SG
APD
MEQ-3125 SCALE: 1:30
Fixpoints EMPLOYER

Floor- and building vibrations Fixpoint Components QATAR ARMED FORCES


Floor- and building vibrations can reduce image quality! Therefore the gantry and the patient table must be Transport technical cabinets and patient table MILITARY MEDICAL CITY HOSPITAL PROJECT
installed in an environment free of vibrations. GR Gantry MANAGEMENT OFFICE P.O. BOX 2075 DOHA,
QATAR
The PDC is mounted and delivered on a transport pallet.
SOMATOM Drive - Equipment Legend Sources that produce vibrations are, e.g.:
Permissible acceleration for continuous vibration Operating console (controlbox, monitor, keyboard) The IRSmx4d tower is delivered on a special shock-absorbing transport pallet. Moving through the building is not
Railroad routes, subways, roads, road work and permitted without this pallet. MAIN CONTRACTOR:
construction sites, hospital power plants, mines,
Permissible acceleration rms-value [m/s²]

Weight (kg), Heat dissipation to the air (W)


open-cast mines, quarries (explosions), ferry moorings,
Image Control System (Tower PC)
Transport dimensions Length (mm) Width (mm) Height (mm) Weight (kg) HBK CONTRACTING CO. WLL
Pos. Description kg W Remark any other sources of striking vibrations. Power Distribution Cabinet A (incl. REPO contact) P.O. BOX 1362 DOHA, QATAR
PDC A with transport pallet - without UPS 1120 900 2070 ≤600 TEL: (974) 44451111 FAX: (974) 44451000

1.01 Gantry 2580 1000 #1, isocenter 1020 The CT system is not sensitive to common vibrations. If
the CT is away from vibrational sources, or the CT is Power Distribution Cabinet B PDC B with transport pallet 1120 900 2070 ≤450
mm LEAD CONSULTANT:

1.02 Patient table PHS 4n (2000 mm scannable range) 500 * * included in 1.01 replacing a CT system that to date has not shown image IRSmx4d tower with transport pallet 600 800 690 51.9
quality problems due to vibrations, it is usually not
IRSmx (Image Reconstruction System Cabinet)
MEINHARDT
necessary to execute vibrational measurements. IRSmx5d tower 645 175 450 25 14TH FLOOR AMWAL TOWER WESTBAY
1.03 PDC A cabinet with UPS 610 2000 AT Emergency off button with locking mechanism P.O. BOX 1362 DOHA, QATAR
TEL: (974) 44117840 FAX: (974) 4411 7845
1.04 PDC B cabinet 400 2000 If there are any doubts, the following thresholds have to be PHS 4n - with packing 2580 875 1570 700
verified by measurement: On-off button with pilot lamp ARCHITECT & INTERIOR DESIGNER:
1.05 IRSmx5d Tower PC (Image Reconstruction System) 25 500 1 10 100
MPT 2n - with packing 2530 850 1430 850
1.06 Control unit with monitor, control box, keyboard 10 100 SW Radiation warning lamp
1.07 ICS Tower 13 PC (syngo Acquisition Workplace) 25 500 Patient Handling System PHS) must not exceed the
1.08 Power Distributor BY HBK, not in thresholds as described in the above shown diagram. Radiation ready indicator
MEDICAL PLANNER: MEDICAL EQUIPMENT : MEP SUBCONTRACTOR : SUBCONTRACTOR :
scope of delivery Any transient vibration (shocks) has to be less than 0.5 m/s² peak-to-peak in the time domain.The vibrations have to CV CARE Vision
be measured with a sampling rate of 1000 Hz.
Climatic conditions for transport and storage
It is the customer's responsibility to contract a qualified specialist. The specialist must implement site The system cable connections (power supply) between
Gantry and PDC must have a minimum length of 7 m. Transport / storage Temperature -20 to +50 °C
modifications to meet the specific limits, and to design structural solutions in case of deviations.
Place excess lengths in the cable duct. all components Relative humidity 10 to 90 % PROJECT TITLE:

Cable diameter 30 mm, minimum bending radius 148 mm. Barometric pressure 700 to 1060 hPa
Transport Gantry not to scale Notes on preparations for installation Temperature gradient 10 K/h (non-condensing) ENGINEERING, PROCUREMENT AND
Max. storage time 2 months
Standard transport Transport through narrow passages 4
Contracts for performing and supervising on-site installation preparations should be concluded with technically CONSTRUCTION (EPC/TURNKEY) FOR
competent companies by the customer. The customer is responsible for timely and proper completion and The data for transporting and storing the CT system apply only if the system is shipped free of damage in the
Rollers swivelled out Rollers swivelled in supervision of all preparations for installation at the construction site in observance of all applicable legal regulations Environmental conditions for operating transport packaging provided by the manufacturer. All components have to be stored in the original transport
MILITARY MEDICAL CITY HOSPITAL
1220 1220
(e.g. X-ray regulations, radiation protection regulations) and all applicable general recognized rules of technology
Entire CT System Air temperature range 18 to 28 °C
packaging. If the original packaging is no longer available, you have to use an equivalent packaging for intermediate (MMC) AT TAREK BIN ZEYAD CAMP
(e.g. VDE regulations, DIN standards). storage. After moving the CT system from a cold environment into a warm room, make sure that the entire CT
1
1256 1
1256 Execution and supervision of installation preparations at the construction site and later observance of the standard Relative humidity 20 to 75 % system is dry before switching it ON.
IN SAILIYAH (SOUTH OF DOHA)
operating conditions are not included in our duties. The customer is responsible for checking the static calculations Barometric pressure 800 to 1060 hPa
and, where applicable, the air conditioning in the building to be equipped. Temperature gradient 6 K/h (non-condensing)
PROJECT NO. AA-103-01
min. 1999

min. 1999

Maintain the temperature range required to meet the needs of changing seasons.
3 3 Gantry with folded-up covers not to scale If it is not possible, an on-site room heating and air conditioning system is required. DRAWING TITLE:

When supplying air from the outside (fresh air), we recommend the on-site use of Network Integration BUILDING 01-ZONE 01, -PART 06 - GROUND FLOOR -
FRONT VIEW SIDE VIEW coarse Filters, Filter class EU3 to EU4 for filtering dust particles up to > 10 μm CT SCAN ROOM (Z1-L0-IMD-021) - SOMATOM Drive
The Siemens Healthineers components are using TCP/IP Protocol, a 100/1000 Mbit/s switched Ethernet network
(DIN 24185/Part 2). PRE-INSTALLATION EQUIPMENT ARRANGEMENT PLAN
2 2 and static IP addresses.
264 3331 4 4 The required network cabling (min. CAT 5 TP) has to be provided on site. Media converters, which are needed for THIS DRAWING HAS BEEN CHECKED FOR COMPLETENESS, ACCURACY, COORDINATION, AND
5 1801 COMPLIANCE WITH THE CONTRACT DOCUMENTS. ALL DIMENSIONS AND FIELD CONDITIONS
using fibre optic cabling, are not in scope of delivery. HAVE BEEN VERIFIED.
6
5 To prepare the implementation of the new system into the existing network environment, the availability
1 With touch panels on the rear (optional) Smart Remote Services (SRS) of the needed network data at least two weeks before starting the installation is mandatory.
This is the only way to ensure a seamless integration of the new system into the workflow of the department.
Mr. ALAADDIN AKTAN 20 Sept 2022
CONTRACTOR'S REPRESENTATIVE: DATE:
2 Covers must removed for mounting the transport device 2 Smart Remote Services (SRS) is used for remote diagnostics as well
1 as remote service to provide highest system availability. STATUS:
2100

2100

3 Transport device set to minimum floor clearance (7 mm) 2


1992

ISSUED FOR CONSTRUCTION


Requirements:
3 SUBMISSION STAGE DATE
4 TIPPING HAZARD! 2 MBit/s upstream) without time or volume limitations Radiation protection
1022

WORKING DRAWING 09/08/2022


Data protection and security is defined in the Smart Remote
Attention: Services security concept. DRAWN DESIGN CHECKED

PRABHU
ABAM ABAM
Gantry with transport device = 2865 kg, Transport device = 285 kg
1 Height of the gantry 2 Height with folded-up cover (for service) 3 Iso center WORKING DRAWING REVISION NOTES DESIGNED SCALE A1
If there is false floor in transportation route please check bearing capacity of this floor on-site!
MEINHARDT 1:30
If necessary, cover the transport route with metal sheets to distribute the load. 1 : AS PER COMMENTS FROM OPERATOR; DRY WALL SHIFTED TO 400mm TO GAVE SPACE ON THE CT SCAN MACHINE AND TO RECESS ON THE WALL THE SUB
4 e.g. CARE Vision 5 Folded-up cover "hood right" 6 Folded-up cover "front ring"
The maximum possible floor load (two-point load) per roller that may arise during gantry transport is 16 kN. EQUIPMENT (PDCa and PDCb) OF THE CT SCAN MACHINE.. DRAWING NO. REVISION NO.

The door must have a final clearance of 1250 mm if bed entrance to the CT examination room is requested. Note the height of the folded-up covers if planning any technical equipment above the gantry ! MMC-HBK-P1-WD-B01-MEQ-L0-P06-3125 1

BIM MODEL REFERENCE :


SITE PLAN

E
N
7
M P2.G B07 B08

S
+5.50

N
LA
.63
+5.40

W
+5.50

QIB
252
B14

+5.40 B09 B05

B02 B03
B01

B06
B12 B13
B11
B10
B04

GENERAL NOTES
1. PROJECT REFERENCE ELEVATION ±0.00 IS AT +27.50 QATAR NATIONAL DATUM. ELEVATIONS
SHOWN ARE WITH RESPECT TO THE PROJECT REFERENCE ELEVATION OF ±0.00 AT GROUND FLOOR.
1 2.
3.
ALL DIMENSIONS ARE IN MM UNLESS NOTED OTHERWISE.
EQUIPMENT DIMENSIONS ARE SUBJECT TO CHANGE BASED ON MATERIAL SUBMISSION APPROVAL.
4. CONTRACTOR TO COORDINATE AS PER SITE CONDITIONS WHEREVER APPLICABLE.
5. SHOP DRAWINGS ARE ISSUED IN COORDINATION WITH APPROVED DETAILED DESIGN FF&E AND
MEDICAL EQUIPMENT SELECTIONS. SOME AREAS ARE SUBJECT TO CHANGE AFTER MATERIAL
SUBMITTALS APPROVAL .

+3.00 CT ROOM KEY PLAN 1


10 10.1 17 17.1
26

1200
PDC A CABINET Z1-L0-IMD-021
A A
WITH UPS

P2.1
Z1 Z3 P3.1

F Z2 F

EMERGENCY STOP EMERGENCY STOP


P2.A P3.A
1000

POWER DISTRIBUTION

1050
AT
SWITCH SWITCH AT
BOX BY HBK

3000
P2.F P3.F

EMERGENCY STOP AT PDC A CABINET PDC B PDB - POWER 1.01 P2.1 P3.1
SWITCH WITH UPS CABINET DISTRIBUTION Z4 Z5
BOX

CT ROOM 2980
V V

EMERGENCY STOP
Z1-L0-IMD-021

1800

1800

1800
AT
SWITCH
IK 200x60mm
1.02
6 13 13.1 21
OK FFL to UK PDB

3000
1000

WALL TRUNKING

1000
50mmØ OPEN PVC PIPE REFERENCE DOCUMENTS
PROVISION FOR INJECTOR
THRU CONTROL ROOM 5.07 1.05
DOCUMENT NO

BUILDINGS 1 - ALL ZONES - ALL PARTS - OVERALL -GROUND FLOOR -


TITLE REV

MMC-HBK-AP-DD-BAP-MEQ-L0-APO-1800 2

1860 1.03 1.04 FFL: ±0.00


MMC-HBK-P1-DD-B01-MEQ-L0-P06-1806
MEDICAL EQUIPMENT PLAN

BUILDING 1 - ZONE 01- PART 06- GROUND FLOOR MEDICAL EQUIPMENT PLAN 2
1.02

1950
1800

1800
IK 200x60mm
OK FFL to FK 200x80mm
UK PDB
1.05 FLOOR TRUNKING
1000

1000
MILITARY MEDICAL CITY PROJECT - AL SAILIYAH
Approval Status

Approved as
Commented
C CT SCAN ROOM - ELEVATION C

Re-Submit
A Approved

D Rejected
500
494

Revise &
500

CV
MEQ-3126 SCALE: 1:30 Fixpoints Authority Signature Date
FFL: ±0.00
Fixpoint Components

C
B
MMC-PMO
GR Gantry

Operating console (controlbox, monitor, keyboard)

FK 300x80mm Image Control System (Tower PC)


CONCRETE SCREED
FLOOR TRUNKING
VINYL FLOOR FINISHED Power Distribution Cabinet A (incl. REPO contact) The approval and comments shall not in any ways relieve or absolve the
5mm THK MS STEEL Contractor from compliance of any obligations or liability under or in connection

A CT SCAN ROOM - ELEVATION A


PLATE TRUNKING COVER Power Distribution Cabinet B with the contract, project requirements and specifications.
WORKING DRAWING REVISION NOTES FLOOR CABLE
MEQ-3126 SCALE: 1:25 TRUNKING IRSmx (Image Reconstruction System Cabinet)
1 : AS PER COMMENTS FROM OPERATOR; DRY WALL SHIFTED TO 400mm TO GAVE SPACE ON THE CT SCAN MACHINE AND TO RECESS ON THE WALL THE SUB FFL: ±0.00 300
EQUIPMENT (PDCa and PDCb) OF THE CT SCAN MACHINE.. AT Emergency off button with locking mechanism 1 ISSUED FOR CONSTRUCTION 31/10/2022 ABAM ABAM PR SG

On-off button with pilot lamp


00 ISSUED FOR CONSTRUCTION 20/09/2022 ABAM ABAM PR SG
7

80
REVISION DETAILS DATE DWN DES CHD APD
SW Radiation warning lamp
EMPLOYER
-0.10
+5.50 Radiation ready indicator
QATAR ARMED FORCES
+5.40 CV CARE Vision
MILITARY MEDICAL CITY HOSPITAL PROJECT
MANAGEMENT OFFICE P.O. BOX 2075 DOHA,
The system cable connections (power supply) between QATAR
Gantry and PDC must have a minimum length of 7 m.

5 FLOOR TRUNKING DETAIL Place excess lengths in the cable duct.


Cable diameter 30 mm, minimum bending radius 148 mm.
MAIN CONTRACTOR:

MEQ-3126 SCALE: 1:5


HBK CONTRACTING CO. WLL
P.O. BOX 1362 DOHA, QATAR
P2.G TEL: (974) 44451111 FAX: (974) 44451000
M
+5.50
LEAD CONSULTANT:
+5.40
MEINHARDT
14TH FLOOR AMWAL TOWER WESTBAY
P.O. BOX 1362 DOHA, QATAR
TEL: (974) 44117840 FAX: (974) 4411 7845

ARCHITECT & INTERIOR DESIGNER:

MEDICAL PLANNER: MEDICAL EQUIPMENT : MEP SUBCONTRACTOR : SUBCONTRACTOR :

+3.00
PROJECT TITLE:

ENGINEERING, PROCUREMENT AND


CT ROOM CONSTRUCTION (EPC/TURNKEY) FOR
1000

2510
1200

Z1-L0-IMD-021 MILITARY MEDICAL CITY HOSPITAL


EMERGENCY STOP
AT
SWITCH (MMC) AT TAREK BIN ZEYAD CAMP
IN SAILIYAH (SOUTH OF DOHA)
SW SBA

WORK / CONTROL SBA PROJECT NO. AA-103-01


Z1-L0-IMD-023
DRAWING TITLE:
1000

BUILDING 01-ZONE 01, -PART 06 - GROUND FLOOR -


AT
2760 5161 CT SCAN ROOM (Z1-L0-IMD-021) - SOMATOM Drive
PRE-INSTALLATION ELEVATION DETAILS
1.01 1860
1.02 THIS DRAWING HAS BEEN CHECKED FOR COMPLETENESS, ACCURACY, COORDINATION, AND
COMPLIANCE WITH THE CONTRACT DOCUMENTS. ALL DIMENSIONS AND FIELD CONDITIONS
1800

EAT HAVE BEEN VERIFIED.

2050
1800
1000

Mr. ALAADDIN AKTAN 20 Sept 2022

1600
CONTRACTOR'S REPRESENTATIVE: DATE:
1035
50mmØ OPEN STATUS:
PVC PIPE
PROVISION FOR ISSUED FOR CONSTRUCTION

130 130
INJECTOR
SUBMISSION STAGE DATE
FFL: ±0.00

560
WORKING DRAWING 09/08/2022

300
FFL: ±0.00 FFL: ±0.00
DRAWN DESIGN CHECKED

PRABHU
ABAM ABAM

IK 200x60mm DESIGNED SCALE A1


OPC ICS 2 x BK 130x70mm
@300 aFFL to UK ABGD
B CT SCAN ROOM - ELEVATION B PVC WALL TRUNKING
PVC WALL TRUNKING MEINHARDT 1:30
MEQ-3126 SCALE: 1:25
1 CONTROL ROOM - ELEVATION D DRAWING NO. REVISION NO.

MEQ-3126 SCALE: 1:30 MMC-HBK-P1-WD-B01-MEQ-L0-P06-3126 1

BIM MODEL REFERENCE :


SITE PLAN

E
N
B07 B08

S
N
LA
.63
W
QIB
252
I-Control with wall bracket (schematic) not to scale
SOMATOM Drive - Equipment Legend B14

B09 B05

B02 B03
4 Weight (kg), Heat dissipation to the air (W) B01

7.16 m² 400
Pos. Description kg W Remark

B06
B12 B13
B11
1.01 Gantry 2580 1000 #1, isocenter 1020 mm B04
B10

1.02 Patient table PHS 4n (2000 mm scannable range) 500 * * included in 1.01
130 1.03 PDC A cabinet with UPS 610 2000

15
10 3
1.04 PDC B cabinet 400 2000
1.05 IRSmx5d Tower PC (Image Reconstruction System) 25 500

00
0
x. 1
1.06 Control unit with monitor, control box, keyboard 10 100

119

90
2

ma
9 4 1.07 ICS Tower 13 PC (syngo Acquisition Workplace) 25 500 GENERAL NOTES

1300
1. PROJECT REFERENCE ELEVATION ±0.00 IS AT +27.50 QATAR NATIONAL DATUM. ELEVATIONS
1 1.08 Power Distributor by customer, not in scope SHOWN ARE WITH RESPECT TO THE PROJECT REFERENCE ELEVATION OF ±0.00 AT GROUND FLOOR.
of delivery 2. ALL DIMENSIONS ARE IN MM UNLESS NOTED OTHERWISE.
6 3. EQUIPMENT DIMENSIONS ARE SUBJECT TO CHANGE BASED ON MATERIAL SUBMISSION APPROVAL.
1 4. CONTRACTOR TO COORDINATE AS PER SITE CONDITIONS WHEREVER APPLICABLE.

800 - 900
7 159 5. SHOP DRAWINGS ARE ISSUED IN COORDINATION WITH APPROVED DETAILED DESIGN FF&E AND

1821
5 MEDICAL EQUIPMENT SELECTIONS. SOME AREAS ARE SUBJECT TO CHANGE AFTER MATERIAL
SUBMITTALS APPROVAL .

300 Concrete fill-up, concrete class 8


1911 963 C20/25 to C50/60
Floor- and building vibrations
Join with the solid concrete.
Floor- and building vibrations can reduce image quality! Therefore the gantry and the patient table must be
installed in an environment free of vibrations.
water

1 Wall bracket (thickness 35 mm) with wall mounting holes Ø 6.6 mm 2 Locking lever for locking/unlocking
KEY PLAN 1
10 10.1 17 17.1
26
cabling

Sources that produce vibrations are, e.g.:


110

Permissible acceleration for continuous vibration


3 Control unit 4 Minimum area requirements and dimensions for wall installation and handling Railroad routes, subways, roads, road work and A A

construction sites, hospital power plants, mines,

550

Permissible acceleration rms-value [m/s²]


5 24 V DC plug-in power supply and cable Z1 Z3
open-cast mines, quarries (explosions), ferry moorings, P2.1

Z2
P3.1

728
549

± 0.00 WORK / Input Output


any other sources of striking vibrations.
F F

- Voltage: 100 V AC - 240 V AC - Voltage: +24 V DC ± 5 % P2.A P3.A

-0.10 CONTROL - Line frequency: 50-60 Hz - Current: 1.25 A The CT system is not sensitive to common vibrations. If
- Current: 0.7 A - Cable length: 1.5 m
Z1-L0-IMD-023 - Stand-by: 0.5 W the CT is away from vibrational sources, or the CT is P2.F P3.F

800
1790

replacing a CT system that to date has not shown image P2.1 P3.1

6 7 Z4 Z5
quality problems due to vibrations, it is usually not
8 IVP control cable 9 Strain relief for power supply cable 10 Connection for power supply cable
necessary to execute vibrational measurements.
V V

Delivery volume: - Control unit and a wall bracket for wall mounting (standard installation) If there are any doubts, the following thresholds have to be
- Drilling template verified by measurement:

550
1 10 100
- Installation material: 3x Fischer dowels 6 13 13.1 21

(Type: UX 8x50; nominal drill hole diameter: 8 mm; Drill hole depth: min. 60 mm
- 3x screws M6x80, 3x screw head caps grey REFERENCE DOCUMENTS
Patient Handling System PHS) must not exceed the
thresholds as described in the above shown diagram. DOCUMENT NO TITLE REV

BUILDINGS 1 - ALL ZONES - ALL PARTS - OVERALL -GROUND FLOOR -


MMC-HBK-AP-DD-BAP-MEQ-L0-APO-1800 2
Any transient vibration (shocks) has to be less than 0.5 m/s² peak-to-peak in the time domain.The vibrations have to MEDICAL EQUIPMENT PLAN

1263 1400 3347 Statics not to scale MMC-HBK-P1-DD-B01-MEQ-L0-P06-1806 BUILDING 1 - ZONE 01- PART 06- GROUND FLOOR MEDICAL EQUIPMENT PLAN 2
be measured with a sampling rate of 1000 Hz.
The floor construction has to be performed solid and free of It is the customer's responsibility to contract a qualified specialist. The specialist must implement site
1490

1490
1911 4 3 vibration, e.g. concrete flooring C20/25 to C50/60 corresponding to
Center of DIN EN 206-1, according to the maximum values as specified in the
modifications to meet the specific limits, and to design structural solutions in case of deviations.
gravity textblock “Floor and building vibrations”.

256
It is recommended to test the weight capacity of the concrete or MILITARY MEDICAL CITY PROJECT - AL SAILIYAH
1 2 composite flooring by a stress analyst. Approval Status
Fastening the gantry on the floor is possible but only necessary in

Approved as
Commented

Re-Submit
A Approved
94 countries prone to earthquakes or according to local regulations.

D Rejected
Revise &
Securing the patient table to the floor is mandatory.
Authority Signature Date
PDC - Power Distribution Cabinet not to scale

C
B
Total weight of Gantry: 2580 kg : F stat total 25 kN
MMC-PMO
FRONT VIEW ILLUSTRATION for the cable inlet (Isometry)
Lead shielded wall Partial load on gantry foot 1 2 3 4

Nominal static load after levelling:


5.7 7.6 7.9 6.7
F stat nom [kN]

±0.7 ±0.7 ±0.8 ±0.8


F dyn max [kN] The approval and comments shall not in any ways relieve or absolve the
Contractor from compliance of any obligations or liability under or in connection
Outer diameter gantry foot [mm] 80 80 80 80 with the contract, project requirements and specifications.

Floor contact area gantry foot [cm²] 52.1 52.1 52.1 52.1

During gantry installation and leveling, the maximum possible load on one gantry foot can be 14 kN (the gantry is
1 CT SCAN ROOM - CONCRETE FILL-UP PLAN 1 ISSUED FOR CONSTRUCTION 31/10/2022 ABAM ABAM PR SG
standing on two diagonal feet). Design access floors for a weight capacity of min. 400 kg per slab/plate. During

1850
1950
gantry transport, the load may be higher at certain individual points (3-point load, e.g. due to uneven flooring).
MEQ-3127 SCALE: 1:30 00 ISSUED FOR CONSTRUCTION 20/09/2022 ABAM ABAM PR SG
REVISION DETAILS DATE DWN DES CHD APD
EMPLOYER

6 1 QATAR ARMED FORCES


Floor mounting and cable inlet with standard table PHS 4n not to scale MILITARY MEDICAL CITY HOSPITAL PROJECT
MANAGEMENT OFFICE P.O. BOX 2075 DOHA,
QATAR

1 Adjustable gantry feet (Ø 80 mm); mounting holes (Ø 17 mm) ICS Tower 13 not to scale
MAIN CONTRACTOR:

100
2
Adjustable patient table feet with mounting holes (inner: Ø 20.5 mm); minimum extraction force: 2.03 kN at the two mounting points bearing
the greatest load at maximum patient travel path and a 230-kg load. According to IEC 60601-1, it is mandatory that the 4-fold safety factor be observed. 840 488
FRONT VIEW SIDE VIEW
7
TOP VIEW
2
570 0
HBK CONTRACTING CO. WLL
50 43
900 P.O. BOX 1362 DOHA, QATAR
2 Alternative floor mounting holes (Ø 18 mm), if position 2a is not usable 1252 4
2 TEL: (974) 44451111 FAX: (974) 44451000

120
1070 5 2 6
LEAD CONSULTANT:
3 Floor-inlet for cable/hose connection: 49/97 x 488 mm
890 TOP VIEW ILLUSTRATION for floor mounting
3
MEINHARDT

420
175 420 (top view of pedestal)
4 No floor cut-out permitted in this defined area (Ø 190 mm) around each adjustable gantry foot 1435 900 500 900 14TH FLOOR AMWAL TOWER WESTBAY
8 P.O. BOX 1362 DOHA, QATAR
Alternative to 3 : 689.5 745.5

40
TEL: (974) 44117840 FAX: (974) 4411 7845
5 Core hole: max. Ø 100 mm for HV cables and other system cabling 5 6 3

395
2 1
3 1 ARCHITECT & INTERIOR DESIGNER:
8
6 Core hole: max. Ø 80 mm for system cabling
10 3 3
1

691.5

650
570
7 Core hole: max. Ø 160 mm for water hoses 1 1 4

25
8 Gantry footprint 4
1 Air intake 2 Air exhaust (primary) 3 Air exhaust (secondary) 3 3 14 MEDICAL PLANNER: MEDICAL EQUIPMENT : MEP SUBCONTRACTOR : SUBCONTRACTOR :
7 Ø
4 Air must not exhaust directly to the air intake 5 e.g. a wall
9 "Electronics cover" for cabling between gantry and patient table (in scope of delivery)

100

40
6 Minimum distance for cable routing and air circulation 7 Minimum distance for air circulation
100 700 100
9 7
Floor requirements: Gantry and patient table orientation point
PROJECT TITLE:
CT
The floor construction has to be performed solid and free of vibration, e.g. concrete flooring C20/25 to C50/60 scan plane

950
corresponding to DIN EN 206-1, according to the maximum values as specified in the textblock
ILLUSTRATION for the cable inlet
(top view of pedestal)
ENGINEERING, PROCUREMENT AND
service area
“Floor and building vibrations”. Anti-static flooring is recommended for the examination room. ESD flooring is also suitable. 1 1 900 CONSTRUCTION (EPC/TURNKEY) FOR
NOTE: A solid and vibration-free floor is needed to avoid a negative influence on the vibration characteristic of the gantry. IRSmx5 tower not to scale

An incorrect vibration characteristic of the gantry can cause problems with balancing and image quality.
MILITARY MEDICAL CITY HOSPITAL
6 (MMC) AT TAREK BIN ZEYAD CAMP

max.120
Permissible tolerance for floor levelness is at maximum 10 mm, based on the area of the adjustable feet of the
4
gantry and the patient table. 9 175
SIDE VIEW of socle IN SAILIYAH (SOUTH OF DOHA)
orientation point

650
25
On-site subconstruction have to fulfill the flooring conditions. It is recommended to test the weight capacity of 5
PHS 4n

82.5
175 120
the concrete or composite flooring by a stress analyst. 645 PROJECT NO. AA-103-01
Floor mounting, as well as principally every kind of CT system component mounting, must be performed in 2 2 1 4 3 DRAWING TITLE:
accordance with country-specific guidelines in countries prone to earthquakes.The gantry and the patient

645
table have to be on the same (isocentric) plane.
55 790 55 BUILDING 01-ZONE 01, -PART 06 - GROUND FLOOR -
450

450
2a 2a CT SCAN ROOM (Z1-L0-IMD-021) - SOMATOM Drive
An "Installation Template" with footprint information for the gantry and patient table is optional available. 9 650 32.5
2 PRE-INSTALLATION CONCRETE FILL-UP PLAN
May not be used as a drilling template. A drilling template is not necessary. 7

150
205 5 THIS DRAWING HAS BEEN CHECKED FOR COMPLETENESS, ACCURACY, COORDINATION, AND
COMPLIANCE WITH THE CONTRACT DOCUMENTS. ALL DIMENSIONS AND FIELD CONDITIONS
Floor mounting Gantry 1 System cables HAVE BEEN VERIFIED.

- Possible through four mounting holes, but not required in principle (only in areas prone to earthquakes). FRONT VIEW SIDE VIEW TOP VIEW
2a 2a Cable inlets (cut-outs in the base) when cables are routed on the floor; if not used, the cut-outs are covered
Mounting materials must be provided on-site. 2
with dummy plates; feed lines are possible from all four sides
1 Front side with grid for air intake (cooling) 2 Support feet 3 Air intake 4 Air exhaust
- Leveling tolerance: in Z-direction ± 0.2 deg, in X-direction ± 0.5 deg Mr. ALAADDIN AKTAN 20 Sept 2022
2 2 3 Floor mounting holes (all Ø=14 mm) 4 PDC base (footprint) CONTRACTOR'S REPRESENTATIVE: DATE:
- Leveling with four adjustable feet. 5 Minimum distance for air circulation 6 Air must not exhaust directly to the air intake
STATUS:
Ø 5 Cable inlet in PDC base; opening is adjustable 6 Air exhaust for system cooling; must not be covered
7 Sliding door or similar ISSUED FOR CONSTRUCTION
For example, the sliding door of a wall For example, a wall; no safety distance for
Floor mounting patient table 280 The safety distances for air circulation (system cooling) must be maintained. Openings for air circulation in the 7 closet, and so on 8
air circulation (cooling) required SUBMISSION STAGE DATE
393 tower housing must not be covered. Air must not exhaust directly into the air intake (a closed air loop).
- The patient table MUST be secured to the floor (4 mounting holes). 9 Safety distance for air circulation (cooling) required 10 Top exhaust for system cooling; must not be covered 09/08/2022
WORKING DRAWING
- Installation material for floor mounting in concrete is in scope of delivery. Therefor min.140 mm thickness of concrete is required:
Anchor bolts type 1: 4x HSL-4G M 10/60 heavy-duty sleeve (used without bonded screed) or DRAWN DESIGN CHECKED

Anchor bolts type 2: 4x HSL-4G M 10/120 heavy-duty sleeve (used with up to 60 mm thick bonded screed) PRABHU
ABAM ABAM
- Leveling with four adjustable feet.
- Remove the floor cover in the entire footprint area of the table base.The support plate is equal to the footprint DESIGNED SCALE A1

of the patient table base and is used as a help to cut out the floor covering. MEINHARDT 1:30

DRAWING NO. REVISION NO.

MMC-HBK-P1-WD-B01-MEQ-L0-P06-3127 1

BIM MODEL REFERENCE :


SITE PLAN

E
7

N
B07 B08

Line impedance related to measured line voltage

S
N
7.16 m²

LA
.63
W
QIB
252
B14
SW TS B09 B05
1 Minimum measured line voltage [ VAC ]
2 B02
B01
B03

B06
B12
300 B11
B13

2 Maximum allowed line impedance [ mΩ ] B04


B10

250
250
800 The maximum allowed line impedance
P2.G depends on the actual measured lowest line
200
voltage.
+1800mm aFFL AT We recommend monitoring the voltage over
DRAIN PIPE FOR 150 a period of 24 hours preferable on work days GENERAL NOTES
1. PROJECT REFERENCE ELEVATION ±0.00 IS AT +27.50 QATAR NATIONAL DATUM. ELEVATIONS
CONDENSATION OF THE to specify the minimum.

1640

1670
SHOWN ARE WITH RESPECT TO THE PROJECT REFERENCE ELEVATION OF ±0.00 AT GROUND FLOOR.

440
2. ALL DIMENSIONS ARE IN MM UNLESS NOTED OTHERWISE.
1842

MACHINE BY HBK SBA 100 85 3. EQUIPMENT DIMENSIONS ARE SUBJECT TO CHANGE BASED ON MATERIAL SUBMISSION APPROVAL.
4. CONTRACTOR TO COORDINATE AS PER SITE CONDITIONS WHEREVER APPLICABLE.
300 EAT
5. SHOP DRAWINGS ARE ISSUED IN COORDINATION WITH APPROVED DETAILED DESIGN FF&E AND
MEDICAL EQUIPMENT SELECTIONS. SOME AREAS ARE SUBJECT TO CHANGE AFTER MATERIAL
1910 5710 50
SUBMITTALS APPROVAL .

WATER COOLING AT

150 ± 0.00 0 1
1760 360 380 400 420 440
-0.10 2 x BK 130x70mm
CT ROOM @300mm aFFL KEY PLAN

500
10 10.1 17 17.1

water
1 26
300

FK 300x80

cabling
A A

Z1-L0-IMD-021 P2.1
Z1 Z3 P3.1
CONCRETE SCREED F Z2 F

VINYL FLOOR FINISHED P2.A P3.A

2
549

Fixpoints 5mm THK MS STEEL


WORK /

840
728

PLATE TRUNKING COVER


3128 ICS Fixpoint Components
50mmØ OPEN PVC PIPE
P2.F P3.F
FLOOR CABLE
CONTROL
FK 300x80mm

2220
TRUNKING P2.1 P3.1

PROVISION FOR INJECTOR FFL: ±0.00 300


Z4 Z5
GR THRU CONTROL ROOM Z1-L0-IMD-023 GR Gantry

Operating console (controlbox, monitor, keyboard) V V

80
Image Control System (Tower PC) 6 13 13.1 21
-0.10

*3 Power Distribution Cabinet A (incl. REPO contact) REFERENCE DOCUMENTS


OPC
3093
3693

2310 Power Distribution Cabinet B DOCUMENT NO TITLE REV

BUILDINGS 1 - ALL ZONES - ALL PARTS - OVERALL -GROUND FLOOR -

3 IK 200x60mm OK FFL MMC-HBK-AP-DD-BAP-MEQ-L0-APO-1800


MEDICAL EQUIPMENT PLAN
2

IRSmx (Image Reconstruction System Cabinet) 2


1960

MMC-HBK-P1-DD-B01-MEQ-L0-P06-1806 BUILDING 1 - ZONE 01- PART 06- GROUND FLOOR MEDICAL EQUIPMENT PLAN
3128 to @3000mm aFFL 3 SECTION DETAIL
180 AFFL AT AT Emergency off button with locking mechanism MEQ-3128 SCALE: 1:5

150x300mm IRS On-off button with pilot lamp


2810 MILITARY MEDICAL CITY PROJECT - AL SAILIYAH
2 WALL OUTLET
SW Radiation warning lamp Approval Status

1530

Approved as
1900 3100

Commented
CV @ +300mm aFFL

Re-Submit
A Approved
Radiation ready indicator

D Rejected
Revise &
AT +1800mm aFFL SW FK 300x80

135
Authority Signature Date
CV CARE Vision

C
B
MMC-PMO

85
FK 200x80mm The system cable connections (power supply) between
Cut-out in cable duct

80
*4 Gantry and PDC must have a minimum length of 7 m.
IK 200x60mm Place excess lengths in the cable duct.
300

OK FFL to Cable diameter 30 mm, minimum bending radius 148 mm.

849
305
1.08 @300mm aFFL
*3 The approval and comments shall not in any ways relieve or absolve the
275

485 Contractor from compliance of any obligations or liability under or in connection


with the contract, project requirements and specifications.

549
M

Gantry contour
Lead shielded wall
Notes
For service purposes; only required if there is no existing 1 ISSUED FOR CONSTRUCTION 31/10/2022 ABAM ABAM PR SG

*3 socket or none is planned by the electrician


00 ISSUED FOR CONSTRUCTION 20/09/2022 ABAM ABAM PR SG
(consult the Siemens Healthineers project management) Scan plane REVISION DETAILS DATE DWN DES CHD APD
EMPLOYER
M.1 *4 Grounded socket for I-control unit.
WORKING DRAWING REVISION NOTES
QATAR ARMED FORCES
PDCB IK 200x60mm 1 : AS PER COMMENTS FROM OPERATOR; WALL SHIFTED TO 400mm TO GAVE SPACE AND RECESS ON THE WALL THE SUB MACHINE OF THE CT SCAN
PDCA
OK FFL to 1 2 : ADJUSTMENT ON FLOOR TRUNKING AS PER THE NEW DRY WALL LOCATION
2 DETAIL - A MILITARY MEDICAL CITY HOSPITAL PROJECT
MANAGEMENT OFFICE P.O. BOX 2075 DOHA,
300x300mm 300x300mm MEQ-3128 SCALE: NTS QATAR
UK PDB
MAIN CONTRACTOR:

1 CT SCAN ROOM - FLOOR and WALL TRUNKING LAYOUT


SCALE: 1:25
Available cable and water hose sets Legend HBK CONTRACTING CO. WLL
MEQ-3128
P.O. BOX 1362 DOHA, QATAR
Cable set Water hose set cut-out, LxW (i. e. in FK or raised floor) TEL: (974) 44451111 FAX: (974) 44451000

* 10 m 10 m
cut-out, Ø in mm (i.e. in suspended ceiling)
16 m 20 m LEAD CONSULTANT:

25 m 30 m
Power supply SOMATOM Drive *For the shown installation the selected options have to be used.
KB core hole, Ø in mm (minimum inner clearance required)
MEINHARDT
Legend electrical installation BD floor opening, top view LxW (break-throughs and openings, which delimit the
* The length of the water hoses depends on the position of the cooling water connection. 14TH FLOOR AMWAL TOWER WESTBAY
P.O. BOX 1362 DOHA, QATAR
Mains TN-S 3/N/PE AC 50/60 Hz ± 2Hz Line impedance Power consumption 1 To external conductive parts
The final lenghts must be determined on site with the Siemens project manager! fireproof area, must be closed on site after the installation is finished). TEL: (974) 44117840 FAX: (974) 4411 7845

Voltage 400 V ± 10 % Only copper cables are allowed DD ceiling opening in ceiling above LxW (break-throughs and openings, which ARCHITECT & INTERIOR DESIGNER:
2 Test jack 4 mm pin plug Additional electrical connectivity for the customer at delimite the fireproof area, must be closed on site after the installation is finished).
Line to line unbalanced max. 2 % Connection value 173kVA Stand-by 16kVA
WD wall break WxH (break-throughs and openings, which delimit the
Cable cross section is to be determined by national regulations. System off 1kVA 3f Circuit breaker 125A Siemens 3VA1112-4ED46-0AA0 Siemens Customer
Healthineers fireproof area, must be closed on site after the installation is finished).
The size of the terminals in the PDC are designed for. 25 / 95 mm² for time up to < 2 s 293kVA
3a Circuit breaker 32A Siemens 3VA1132-4EE46-0AA0 name of a fixpoint or a connection point
PE N L1 L2 L3 Electrical installation according to IEC 60364-7-710, national regulations must be observed intern 1m 2 4.4
MEDICAL PLANNER: MEDICAL EQUIPMENT : MEP SUBCONTRACTOR : SUBCONTRACTOR :

4 Overvoltage protection max. 2,5 mm² flexible cable fixing point


Power supply for CT-System Minimum requirement for the on site max. 4.3
Power distributor residual current device RCD Siemens 3VA9114-0RL21 250 VAC / 2 A
electrical installation 3Rc
Room Group 1 30mA, Room Group 2 30mA 24 VDC / 2 A Access hatch in suspended ceiling not required if the ceiling tiles are easily removable
4 residual current device RCD Siemens 3VA9114-0RL21 Size and position depending on structural conditions on site.
3R
Room Group 1 300mA, Room Group 2 30mA PROJECT TITLE:
PE 2 4.2
intern 1m switch, installation according to national guidelines
+ 5 24V DC power supply SITOP 6EP1436-2BA10 max. 2,5 mm² flexible

min. Auxiliary switch changeover contacts per Circuit breaker Siemens


max.
250 VAC / 2 A
4.1 ENGINEERING, PROCUREMENT AND
grounded socket, installation according to national guidelines
AUX 3 VA

6
16 □
Cu
1.4 13 13 13 21 T1 T2 3VA9988-0AA12 24 VDC / 2 A
CONSTRUCTION (EPC/TURNKEY) FOR
K2 K3 K1 K1 80% 20% Side mounted motor per Circuit breaker 3VA 24V DC grounded socket, switchable, installation according to national guidelines
PA 1.1 14 14 14 22
10s 1s 7
3VA9117-0HB10
2 2.4
MILITARY MEDICAL CITY HOSPITAL
1 K K
Undervoltage release for MCCB per Circuit breaker Siemens intern 1m Drain pipe provision 32-50mm Ø
6 33 K4 9 10
8
3VA9908-0BB11 max.
max. 2,5 mm² flexible
2.3 warning lamp / indicator,
(MMC) AT TAREK BIN ZEYAD CAMP
18 43
TP telephone socket
K1 2 9 Timing relay 3RP2505-1AB30-0AC1
250 VAC / 2 A
ceiling mounted, wall mounted IN SAILIYAH (SOUTH OF DOHA)
PE
L1
L2
L3

T2 K1 24 VDC / 2 A

~
24 23
34 15 44 network socket
5 18 K6 10 Timing relay Siemens 3RP2505-1AB30-0AC1
T1
4
1.1 1.4
12 Contactor relay 24V DC 3RH2131-2BB40
intern 1m 2
max. 2,5 mm² flexible
2.2
UK bottom edge
OK top edge PROJECT NO. AA-103-01
15 AUX 3 VA 19 2.1
max.
DRAWING TITLE:
6A - Contactor relay 24V DC 3RH2131-2BB40
250 VAC / 2 A bottom edge suspended ceiling OK FFL top edge finished floor
13 24 VDC / 2 A UK ABGD
4 3 B1 F1 E1 K6 BUILDING 01-ZONE 01, -PART 06 - GROUND FLOOR -
5 Priorität 1 20 14a Impulse switch Eltako ES 12Z-200-UC
Q3 Q2 Q1 MODE 1
M 3VA <U T1 T2 K2 K3 ZE + ZA K4 K1 +
UK RHD
bottom edge bare ceiling OK RFB top edge unfinished floor CT SCAN ROOM (Z1-L0-IMD-021) - SOMATOM Drive
- 2 1.6
4 32A 4 125A 4 125A
7
7
8 9 10 12 13
A2 E2
16 16 Contactor relay 24V DC 3RH2131-2BB40
intern 1m
max. 2,5 mm² flexible PRE-INSTALLATION ELECTRICAL PLAN
1.5
RHD bare ceiling RFB unfinished floor level
3a 3f 3f - 13
max.
THIS DRAWING HAS BEEN CHECKED FOR COMPLETENESS, ACCURACY, COORDINATION, AND
250 VAC / 2 A
K8 19 Auxiliary switch changeover contacts Siemens 3VA9988-0AA12 24 VDC / 2 A ABGD suspended ceiling FFL finished floor level COMPLIANCE WITH THE CONTRACT DOCUMENTS. ALL DIMENSIONS AND FIELD CONDITIONS
3R 3R K6 HAVE BEEN VERIFIED.
+ EQUIPMENT
K8 23 14 20 Contactor relay 24VDC 3RT1017-1BB44-3MA0 (K6) aABGD above suspended ceiling AFFL above finished floor level
ROOM
Power Distribution Cabinet (PDC)
1 23 Contactor relay 24V DC 3RH2131-2BB40 (K8)
aD on ceiling / suspended ceiling aFFL on finished floor / raised floor CONTRACTOR'S REPRESENTATIVE:
Mr. ALAADDIN AKTAN
DATE:
20 Sept 2022

2 AT Emergency off button with locking mechanism


EXAMINA-
BRH parapet height UZ downstand beam STATUS:

BY HBK TION On-off button with pilot lamp


ISSUED FOR CONSTRUCTION
ROOM FK cable duct WxD (minimum inner clearance required), accessible flush floor trunking system,
SUBMISSION STAGE DATE
EQUIPMENT heat exchanger water/air - split moisture-proof, grounded
ROOM L WORKING DRAWING 09/08/2022
L IK cable trunking WxD, WALL surface mounted
Do not connect external components to the CT power supply line.
[1.0m] [0.7m] [0.7m] External cooling system
CONTROL
BK parapet channel WxD, surface mounted (for power and network sockets, etc.) DRAWN DESIGN CHECKED
Energy cables which do not belong to the system must be separated floating ground contact, 250VAC / 2A oder 24VDC / 2A.
X20 5.1

X20 5.2
X20 2.3
X20 2.4

PE L1/L2/L3 PE L1/L2/L3/N PE L1/L2/L3/N ROOM PRABHU


prior to fitting The need for the installation has to be clarified with the customer. ABAM ABAM
Siemens X20 5.4 - KW cable tray WxD (i. e. in ceiling void)
Healthineers 25 - 95 mm² the unit cables (distance >100 cm), or they must also be metallically
25 - 24V Output Room light SCALE A1
10 mm² shielded. For LR ductwork, Ø in mm (minimum inner clearance required)
DESIGNED
95 mm² REPO X20 5.3+ floating ground contact, 250VAC / 2A oder 24VDC / 2A.
USA: PE is equivalent to Protective-GND and PA is equivalent to MEINHARDT 1:25
Transient-GND The need for the installation has to be clarified with the customer.
The installations for cable routing depicted in the drawing need to be reserved for the exclusive
4 POWER DISTRIBUTION DIAGRAM use by SIEMENS Healthineers.
DRAWING NO. REVISION NO.

MEQ-3128 SCALE: NTS MMC-HBK-P1-WD-B01-MEQ-L0-P06-3128 1

BIM MODEL REFERENCE :


SITE PLAN

E
N
B07 B08

S
N
LA
.63
W
Connection of cooling system (schematic)

QIB
252
not to scale
B14

B09 B05
Scope of delivery - Cooling system B02
B01
B03

1. Standard:

B06
B12
800 - Flexible water hoses (Ø 34 mm) with thermal insulation (Ø 58 mm); available lenghts 10, 20 and 30 m; B11
B13

min. bending radius: 150 mm, shorten excess cable lengths; preordering is possible B04
B10

Recommended: - Thermal insulation of water hoses:


AT • Length delivered depends on water hose length ordered.
• Suitable for cable ducts up to 60 mm height and on-site water temperature in the range of ≥ 8° C to 16° C.
DRAIN PIPE FOR Shut-off valve Please note:
CONDENSATION OF THE

1640

1670
necessary. In this case the outer diameter of the thermal insulation won't fit the standard cable
1842

duct heights of 60 mm.


MACHINE BY HBK Pressure regulator
- Accessories: contains all required parts for the water connection: GENERAL NOTES
300 • 2x flexible fabric hoses for water connection (Gantry side) with preinstalled shut-off valves 1. PROJECT REFERENCE ELEVATION ±0.00 IS AT +27.50 QATAR NATIONAL DATUM. ELEVATIONS
1910 5710 p Diff. pressure gauge • Adapters for M36x2 metric to G1" inside thread (see also "Water connection pieces with shut-off valve") SHOWN ARE WITH RESPECT TO THE PROJECT REFERENCE ELEVATION OF ±0.00 AT GROUND FLOOR.
2. ALL DIMENSIONS ARE IN MM UNLESS NOTED OTHERWISE.
- Water drain for condensation (produced from the water-cooled gantry during system cooling):
WATER COOLING • Length 10 m; (outer diameter Ø 10 mm; inner diameter Ø 6 mm)
3.
4.
EQUIPMENT DIMENSIONS ARE SUBJECT TO CHANGE BASED ON MATERIAL SUBMISSION APPROVAL.
CONTRACTOR TO COORDINATE AS PER SITE CONDITIONS WHEREVER APPLICABLE.
• Min. bending radius: 30 mm 5. SHOP DRAWINGS ARE ISSUED IN COORDINATION WITH APPROVED DETAILED DESIGN FF&E AND

150 ± 0.00 TI TI
TI Thermometer
• Shorten excess cable length to size. MEDICAL EQUIPMENT SELECTIONS. SOME AREAS ARE SUBJECT TO CHANGE AFTER MATERIAL
SUBMITTALS APPROVAL .
1760 On-site • Extension up to 20 m possible; extension material must be provided on-side.
-0.10 cooling Feed water flow meter • Minimum flow rate: 2 l/h at 75% relative humidity
CT ROOM 2. Option

500
water supply

water
p p - Fixed piping kit:
300

FK 300x80

cabling
• includes the installation material to connect the delivered flexible cooling hoses with on-site fixed piping
Z1-L0-IMD-021 • 4x connection pieces (DKOL DN25 VA)
• 4x adaptors M36x2 metric to G1" internal thread
KEY PLAN 1
10 10.1 17 17.1
26

A A
549

840
Water return Water inlet Z1 Z3
728

P2.1 P3.1

Z2
FK 300x80mm

F F

2220
P2.A P3.A

GR

on-site
Water connection pieces with shut-off valve not to scale P2.F P3.F

Supply provided by customer G1" external thread (in scope of delivery) P2.1

Z4 Z5
P3.1

Flexible fabric hose - unbent Flexible fabric hose - bent


V V
1
3693

3093

2310

150
Adapter fitting for hose G1" internal thread 2 6 13 13.1 21

in scope of delivery
1960

1
REFERENCE DOCUMENTS
DOCUMENT NO TITLE REV
AT m BUILDINGS 1 - ALL ZONES - ALL PARTS - OVERALL -GROUND FLOOR -
in. MMC-HBK-AP-DD-BAP-MEQ-L0-APO-1800
MEDICAL EQUIPMENT PLAN
2

80
150x300mm IRS MMC-HBK-P1-DD-B01-MEQ-L0-P06-1806 BUILDING 1 - ZONE 01- PART 06- GROUND FLOOR MEDICAL EQUIPMENT PLAN 2

534
3
2810
The cooling water hoses Ø 34 mm 4

1530
1900 3100 (with insulation Ø 58 mm) from the gantry
for water connection are in scope of
AT CV delivery and available in 10, 20 or 30 m.
PDCB PDCA
MILITARY MEDICAL CITY PROJECT - AL SAILIYAH
Approval Status

Approved as
Commented
FK 200x80mm

Re-Submit
A Approved

D Rejected
Revise &
Condensed water hose to Authority Signature Date
e.g. a sink or a siphon 1

C
B
300

MMC-PMO
1 Hexagon coupling nut 2 Shut-off valve 3 Flexible fabric hose 4
275

GR Suitable for installation in surface mounted trunking, cable duct or false floor.

Lead shielded wall

Water connection pieces The approval and comments shall not in any ways relieve or absolve the
with shut-off valve Contractor from compliance of any obligations or liability under or in connection
with the contract, project requirements and specifications.

Example for installation of water drain for condensed water not to scale

(schematic)

1 DRAIN and COOLING WATER LOCATION 0 ISSUED FOR CONSTRUCTION


REVISION DETAILS
31/10/2022
DATE
ABAM ABAM
DWN DES
PR
CHD
SG
APD
MEQ-3129 SCALE: 1:30 EMPLOYER
6

On-site requirements for the integrated cooling system


QATAR ARMED FORCES
1
MILITARY MEDICAL CITY HOSPITAL PROJECT
The heat dissipation of the water-cooled gantry depends on the utilisation of the operator. MANAGEMENT OFFICE P.O. BOX 2075 DOHA,
QATAR

Utilisation of the CT system [%] 100 75 50 25 0 2


MAIN CONTRACTOR:
(Max. power) (stand-by)

max.
Technical data of the interface heat exchanger

4m
Heat dissipation to cooling water [kW] 17 14 11 8 5 7 4 5
HBK CONTRACTING CO. WLL
Primary circuit components: Shut-off devices, filters, flow indicators, fill and drain valves, plate heat P.O. BOX 1362 DOHA, QATAR
Heat dissipation (Gantry and patient table) to air [kW] 1 1 1 1 1 exchanger, pressure gauge 3
TEL: (974) 44451111 FAX: (974) 44451000

Coolant: Water / glycol mixture with a maximum glycol concentration of 40%


Temperature gradient (cooling water) max. 1 K/min Temperature range: 2° - 8° C LEAD CONSULTANT:
Flow rate: 1 E.g. a sink 2 Water drain; flow rate capability: min. 20 l/h 3 E.g. cable duct
Operating pressure nominal: 2 bar to 6 bar, max. 10 bar 4 m³/h
NOTE: To guarantee the limit of the maximum water pressure of 10 bar, Pressure loss: 0.5 bar 4 Condensed water hose 5 Outlet for condensed water hose at the gantry
MEINHARDT
the on-site cooling water system must provide a suitable safety device, e. Operating pressure: max. 10 bar 14TH FLOOR AMWAL TOWER WESTBAY
P.O. BOX 1362 DOHA, QATAR
g. a pressure relief valve. 6 Gantry rear view 7 Max. installation height (for hose routing; water drain connection etc.) TEL: (974) 44117840 FAX: (974) 4411 7845
Secondary circuit components: Fill and drain valve, shut-off device, diaphragm-type expansion vessel, GR Gantry - connection water, power and datalines
Water quality Potable water quality with particle size ≤ 0,25mm safety valve, circulating pump with fill and drain valve, permanent bleed, ARCHITECT & INTERIOR DESIGNER:

(filters/heat exchangers - see detail "Interface heat exchanger" - pressure gauge


must be provided by customer if necessary) Coolant: Water

Anti-freeze may be added to the on-site circuit. Max. mixing ratio up to -25°C: 40 % Connections: M36x2 / DN25 On-site water connection (schematical) not to scale

Adding anti-freeze reduces the cooling output and requires higher cooling water flow rate. Heat up brine to at least Internal pressure loss: ca. 0.5 bar MEDICAL PLANNER: MEDICAL EQUIPMENT : MEP SUBCONTRACTOR : SUBCONTRACTOR :

+4 °C if the internal cooling system is connected to an existing on-site cooling system! Only then on-site water can Operating voltage: 3/N/PE ~400 VAC / ±10% - 50 Hz / ±1% 3
flow through the Gantry integrated cooling system. 3/N/PE ~460 VAC / ±10% - 60 Hz / ±1%
Power consumption, overall system: max. 0.6 kVA at 50 Hz 1 6 7
Switching off when the CT system is not in operation
For purposes of saving energy the on-site water circulation can be switched off with: max. 0.9 kVA at 60 Hz PROJECT TITLE:

- On-site installation of a solenoid valve or switch-off feed pump via contactor Fuse protection (provided by client): 10 A
2 4 5
- On-site feed pump ENGINEERING, PROCUREMENT AND
- Optional water/air-split cooling system 1 Water hose 2 M36 x 2 external thread 3 Adapter (in scope of delivery)
General information CONSTRUCTION (EPC/TURNKEY) FOR
A floating relay contact assembly is included in the PDC:
Maximum 277 VAC/2 A; utilization category AC-14/15 For the gantry-integrated cooling system a on-site cooling water system has to be provided.
4 G1" internal thread 5 G1" external thread 6 On-site water connection 7 e. g. wall
MILITARY MEDICAL CITY HOSPITAL
Maximum 24 VDC/2 A; utilization category DC-12/13 The cooling water system will be connected via:
- Flexible water hoses (in scope of delivery, orderable lengths 10, 20 or 30 m) and special water connection pieces.
(MMC) AT TAREK BIN ZEYAD CAMP
Minimum flow rate - On-site cooling circuit - On-site fixed pipes (PVC, copper, high-grade steel). Therefore a "Fixed piping kit" can be ordered. For vibration IN SAILIYAH (SOUTH OF DOHA)
reduction the flexible water connection pieces have to be installed between the fixed piping and the water Piping material
Barometric pressure 700 to 1060 hPa
Pressure loss - On-site cooling circuit 2 connection points of the gantry. The direct connection of fixed piping and gantry water connection points is not Recommended Not recommended
permitted!
Stainless steel (V2A; V4A) Aluminium
PROJECT NO. AA-103-01
Barometric pressure 700 to 1060 hPa 3500 l/h For service and filling procedure a water faucet with screw connection and a water drain (e.g. a sink or a siphon) in
2 3 Non-ferrous metal (e.g. copper, brass) Iron, carbon steel DRAWING TITLE:
4 3200 vicinity of the gantry is necessary.
3 3000 Synthetic materials, plastics Zinc-plated steel
BUILDING 01-ZONE 01, -PART 06 - GROUND FLOOR -
3000 l/h
2.2 bar CT SCAN ROOM (Z1-L0-IMD-021) - SOMATOM Drive
Brazing solder, hard solder Zinc PRE-INSTALLATION CHILLED WATER and DRAIN DETAILS
2.0 bar
2.05
Fitting solder types 3 and 4 Standard steel pipes
1.8 bar 2050 THIS DRAWING HAS BEEN CHECKED FOR COMPLETENESS, ACCURACY, COORDINATION, AND
2000 l/h COMPLIANCE WITH THE CONTRACT DOCUMENTS. ALL DIMENSIONS AND FIELD CONDITIONS
HAVE BEEN VERIFIED.
1.6 bar 1800
1.45 1600
1.4 bar
1300 1300
1.2 bar 970
1120 Legend
1030 Mr. ALAADDIN AKTAN 20 Sept 2022
1000 l/h CONTRACTOR'S REPRESENTATIVE: DATE:
0.95 740 850
1.0 bar 650 cut-out, LxW (i. e. in FK or raised floor) STATUS:

0.8 bar 500 l/h 1 ISSUED FOR CONSTRUCTION


4°C 6°C 8°C 10°C 12°C 14°C 16°C cut-out, Ø in mm (i.e. in suspended ceiling)
0.6 bar 0.65 SUBMISSION STAGE DATE
0.45
0.4 bar Drain pipe provision 32-50mm Ø WORKING DRAWING 09/08/2022
1 Water temperature 2 Flow rate volume 3 Without anti-freeze 4 With 40% anti freeze
0.2 bar 0.3 FK cable duct WxD (minimum inner clearance required), accessible flush floor trunking system, DRAWN DESIGN CHECKED
NOTE: Additional pump is required if flow rate of water supply is too low. moisture-proof, grounded
0 bar 1 ABAM ABAM PRABHU
IK cable trunking WxD, WALL surface mounted
1000 l / h

1500 l / h
500 l / h

3000 l / h
2000 l / h

2500 l / h

DESIGNED SCALE A1

MEINHARDT 1:30

DRAWING NO. REVISION NO.


1 Water flow per hour 2 Pressure loss 3 With and without anti-freeze
MMC-HBK-P1-WD-B01-MEQ-L0-P06-3129 0

BIM MODEL REFERENCE :


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy


General Information

Equipment
Standard IEC 61223-2-6 (Ed.2) Customer Name Customer
Tester Name sm Customer ID Id
Manufacturer Siemens Healthcare GmbH Hospital Name 105781
Product Name SOMATOM Drive Street Street StreetNo
Software Version syngo CT VB20A Zip Code ZIP
Serial Number 105781 City City
Handed over 2023-01-25 District District
Country QAT
Customer Phone Number Phone

Serial Number
Component Serial Number Revision Level
Tube Assembly A 691022371 -
Tube Assembly B 684512271 -

2023-10-11 09:46:32 Page: 1 / 2


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy Lightmarker

Description
For the test of the lightmarkers the system phantom is centered and aligned, so that the lightmarkers hit the engraved
notches on the phantom. From image of the phantom, scanned with narrow collimation, the congruence of the
engraved notches with the scan plane as well as the saggital and coronal planes are tested.
Last IEC Constancy Reference measurement: 2023-10-11 09:27
(values stated in brackets)
Slice phantom -

Test:
Test Results OK
Result [mm]
0.00
Tolerance
-1.00 ... 1.00

2023-10-11 09:46:32 Page: 2 / 2


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy


General Information

Equipment
Standard IEC 61223-2-6 (Ed.2) Customer Name Customer
Tester Name sm Customer ID Id
Manufacturer Siemens Healthcare GmbH Hospital Name 105781
Product Name SOMATOM Drive Street Street StreetNo
Software Version syngo CT VB20A Zip Code ZIP
Serial Number 105781 City City
Handed over 2023-01-25 District District
Country QAT
Customer Phone Number Phone

Serial Number
Component Serial Number Revision Level
Tube Assembly A 691022371 -
Tube Assembly B 684512271 -

2023-10-11 10:09:18 Page: 1 / 2


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy Sag./Cor. Lightm.

Description
For the test of the lightmarkers the system phantom is centered and aligned, so that the lightmarkers hit the engraved
notches on the phantom. From image of the phantom, scanned with narrow collimation, the congruence of the
engraved notches with the scan plane as well as the saggital and coronal planes are tested.
Last IEC Constancy Reference measurement: 2023-10-11 09:30
(values stated in brackets)
Slice phantom -

Test:
Test Results OK

Result
Sagittal Light Marker Coronal Light Marker
Result 0.00 mm 0.00 mm
Tolerance -1.00 ... 1.00 mm -1.00 ... 1.00 mm

2023-10-11 10:09:18 Page: 2 / 2


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy


General Information

Equipment
Standard IEC 61223-2-6 (Ed.2) Customer Name Customer
Tester Name sm Customer ID Id
Manufacturer Siemens Healthcare GmbH Hospital Name 105781
Product Name SOMATOM Drive Street Street StreetNo
Software Version syngo CT VB20A Zip Code ZIP
Serial Number 105781 City City
Handed over 2023-01-25 District District
Country QAT
Customer Phone Number Phone

Serial Number
Component Serial Number Revision Level
Tube Assembly A 691022371 -
Tube Assembly B 684512271 -

2023-10-11 09:47:02 Page: 1 / 2


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy Topogram Pos.

Description
In the Topogram image of the system phantom the position of an tomogram scan with narrow collimation is selected
for the engraved notches in the phantom. From the recorded tomogram image of the phantom the congruence of
the engraved notches with the scan plane is inspected.
Last IEC Constancy Reference measurement: 2023-10-11 09:31
(values stated in brackets)
Slice phantom -

Test:
Test Results OK
Result [mm]
0.00
Tolerance
-2.00 ... 2.00

2023-10-11 09:47:02 Page: 2 / 2


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy


General Information

Equipment
Standard IEC 61223-2-6 (Ed.2) Customer Name Customer
Tester Name sm Customer ID Id
Manufacturer Siemens Healthcare GmbH Hospital Name 105781
Product Name SOMATOM Drive Street Street StreetNo
Software Version syngo CT VB20A Zip Code ZIP
Serial Number 105781 City City
Handed over 2023-01-25 District District
Country QAT
Customer Phone Number Phone

Serial Number
Component Serial Number Revision Level
Tube Assembly A 691022371 -
Tube Assembly B 684512271 -

2023-10-11 09:48:34 Page: 1 / 4


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy Slice

Description
The tomographic section thickness is evaluated by measuring the width of the image of an inclined aluminium ramp
at the intersection of the ramp with the slice. The width is defined as the Full Width at Half-Maximum (FWHM) of the
baseline corrected CT-value profile. The influence of the reconstruction kernel and the influence of the cone angle
on the measured width are taken into account. The measurement is performed for two sets of scan parameters,
representing a typical head- and a typical body mode. The evaluation is performed for at least the both outer and
one central slice. The measurement and evaluation is performed separately for system A and B.
Last IEC Constancy Reference measurement: 2023-10-11 09:33
(values stated in brackets)
Slice phantom -

Common Parameters
Scan Type Sequence
Voltage 120 kV
UHR no
Shaped filter Wide
Tin filter no
Window width 500 HU
Window center 50 HU
FoV 120 mm

Test: Typical head mode


Test Parameters Test Results OK
System A
Current 390 mA
Slice width reconstructed 4.8 mm
Number of images 3
Collimation 12x1.2 mm
Scan Time 1.0 s
Rotation time 1.0 s
Body Region Head
Kernel Or44s

Result
System A
Slice 1 4.69 mm (4.62)
Tolerance 3.80 ... 5.62 mm

Slice 2 4.75 mm (4.79)


Tolerance 3.80 ... 5.79 mm

Slice 3 4.64 mm (4.66)


Tolerance 3.80 ... 5.66 mm

2023-10-11 09:48:34 Page: 2 / 4


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Test: Typical body mode


Test Parameters Test Results OK
System A
Current 294 mA
Slice width reconstructed 5.0 mm
Number of images 7
Collimation 64x0.6 mm
Scan Time 0.5 s
Rotation time 0.5 s
Body Region Body
Kernel Or37f

Result
System A
Slice 1 5.11 mm (5.05)
Tolerance 4.05 ... 6.00 mm

Slice 2 5.09 mm (5.12)


Tolerance 4.12 ... 6.00 mm

Slice 4 5.22 mm (5.21)


Tolerance 4.21 ... 6.00 mm

Slice 6 5.04 mm (5.06)


Tolerance 4.06 ... 6.00 mm

Slice 7 5.09 mm (5.04)


Tolerance 4.04 ... 6.00 mm

Test: Typical body mode with dual tube System A and B


Test Parameters Test Results OK
System A System B
Current 147 mA 147 mA
Slice width
5.0 mm 5.0 mm
reconstructed
Number of
7 7
images
Collimation 64x0.6 mm 64x0.6 mm
Scan Time 0.5 s 0.5 s
Rotation time 0.5 s 0.5 s
Body Region Body Body
Kernel Or37f Or37f

2023-10-11 09:48:34 Page: 3 / 4


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Result
System A System B
Slice 1 5.08 mm (5.05) 5.02 mm (5.04)
Tolerance 4.05 ... 6.00 mm 4.04 ... 6.00 mm

Slice 2 4.94 mm (5.12) 5.13 mm (5.04)


Tolerance 4.12 ... 6.00 mm 4.04 ... 6.00 mm

Slice 4 5.19 mm (5.08) 5.12 mm (5.13)


Tolerance 4.08 ... 6.00 mm 4.13 ... 6.00 mm

Slice 6 5.01 mm (4.96) 5.00 mm (4.92)


Tolerance 4.00 ... 5.96 mm 4.00 ... 5.92 mm

Slice 7 5.08 mm (5.01) 5.02 mm (4.87)


Tolerance 4.01 ... 6.00 mm 4.00 ... 5.87 mm

2023-10-11 09:48:34 Page: 4 / 4


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy


General Information

Equipment
Standard IEC 61223-2-6 (Ed.2) Customer Name Customer
Tester Name sm Customer ID Id
Manufacturer Siemens Healthcare GmbH Hospital Name 105781
Product Name SOMATOM Drive Street Street StreetNo
Software Version syngo CT VB20A Zip Code ZIP
Serial Number 105781 City City
Handed over 2023-01-25 District District
Country QAT
Customer Phone Number Phone

Serial Number
Component Serial Number Revision Level
Tube Assembly A 691022371 -
Tube Assembly B 684512271 -

2023-10-11 09:50:03 Page: 1 / 6


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy Homogeneity / Water

Description
The measurement is performed for three sets of scan parameters, representing a typical head-mode, a typical body
mode and a body-dual-source mode. For the dual-source mode the evaluation is performed separately for system A
and B. The water value and homogeneity is evaluated by measuring the mean CT number in five Regions Of Interest
(ROI) in the image of a cylindrical water phantom with diameter 20 cm. The ROI are located in the center and near
the edge of the water phantom at 12 o'clock, 3 o'clock, 6 o'clock and 9 o'clock. The water value is the CT-number of
the central ROI, the homogeneity is the difference between the outer ROI and the central ROI each.
Last IEC Constancy Reference measurement: 2023-10-11 09:33
(values stated in brackets)
Water phantom -
Water phantom large -

Common Parameters
Scan Type Sequence
Voltage 120 kV
UHR no
Shaped filter Wide
Tin filter no
Window width 500 HU
Window center 0 HU
FoV 250 mm

Test: Typical body mode


Test Parameters Test Results OK
System A
Current 294 mA
Slice width reconstructed 5.0 mm
Number of images 7
Collimation 64x0.6 mm
Scan Time 0.5 s
Rotation time 0.5 s
Body Region Body
Kernel Or37f
Radius of central ROI 10.00 mm
Radius of peripheral ROI 10.00 mm

2023-10-11 09:50:03 Page: 2 / 6


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Water Value Results


Water Value Results for System A
Slice 1 1.64 HU (1.84)
Tolerance -2.16 ... 4.00 HU

Slice 2 1.75 HU (1.71)


Tolerance -2.29 ... 4.00 HU

Slice 3 2.10 HU (2.04)


Tolerance -1.96 ... 4.00 HU

Slice 4 2.47 HU (2.06)


Tolerance -1.94 ... 4.00 HU

Slice 5 1.85 HU (1.63)


Tolerance -2.37 ... 4.00 HU

Slice 6 1.88 HU (1.61)


Tolerance -2.39 ... 4.00 HU

Slice 7 2.03 HU (1.59)


Tolerance -2.41 ... 4.00 HU

Results for System A


System A
Center Diff.3 Diff.6 Diff.9 Diff.12
Slice 1 1.64 HU (1.84) 0.51 HU (0.40) 0.53 HU (0.11) 0.40 HU (0.23) 0.36 HU (0.19)
Tolerance -2.16 ... 4.00 HU -1.60 ... 2.40 HU -1.89 ... 2.11 HU -1.77 ... 2.23 HU -1.81 ... 2.19 HU

Slice 2 1.75 HU (1.71) 0.32 HU (0.44) 0.27 HU (0.33) 0.31 HU (0.42) -0.12 HU (-0.10)
Tolerance -2.29 ... 4.00 HU -1.56 ... 2.44 HU -1.67 ... 2.33 HU -1.58 ... 2.42 HU -2.10 ... 1.90 HU

Slice 3 2.10 HU (2.04) -0.24 HU (-0.12) -0.23 HU (0.15) -0.16 HU (-0.12) -0.16 HU (-0.31)
Tolerance -1.96 ... 4.00 HU -2.12 ... 1.88 HU -1.85 ... 2.15 HU -2.12 ... 1.88 HU -2.31 ... 1.69 HU

Slice 4 2.47 HU (2.06) -0.54 HU (-0.36) -0.43 HU (0.03) -0.37 HU (0.22) -0.60 HU (-0.09)
Tolerance -1.94 ... 4.00 HU -2.36 ... 1.64 HU -1.97 ... 2.03 HU -1.78 ... 2.22 HU -2.09 ... 1.91 HU

Slice 5 1.85 HU (1.63) 0.29 HU (0.47) 0.18 HU (0.35) 0.32 HU (0.52) 0.03 HU (0.35)
Tolerance -2.37 ... 4.00 HU -1.53 ... 2.47 HU -1.65 ... 2.35 HU -1.48 ... 2.52 HU -1.65 ... 2.35 HU

Slice 6 1.88 HU (1.61) 0.06 HU (0.14) 0.14 HU (0.37) 0.18 HU (0.38) -0.31 HU (0.13)
Tolerance -2.39 ... 4.00 HU -1.86 ... 2.14 HU -1.63 ... 2.37 HU -1.62 ... 2.38 HU -1.87 ... 2.13 HU

Slice 7 2.03 HU (1.59) -0.33 HU (-0.09) -0.13 HU (0.34) -0.12 HU (0.06) -0.45 HU (-0.09)
Tolerance -2.41 ... 4.00 HU -2.09 ... 1.91 HU -1.66 ... 2.34 HU -1.94 ... 2.06 HU -2.09 ... 1.91 HU

2023-10-11 09:50:03 Page: 3 / 6


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Test: Typical body mode with dual tube System A and B


Test Parameters Test Results OK
System A System B
Current 294 mA 294 mA
Slice width
5.0 mm 5.0 mm
reconstructed
Number of
7 7
images
Collimation 64x0.6 mm 64x0.6 mm
Scan Time 0.5 s 0.5 s
Rotation time 0.5 s 0.5 s
Body Region Body Body
Kernel Or37f Or37f
Radius of central ROI 10.00 mm
Radius of peripheral ROI 10.00 mm

Water Value Results


Water Value Results for System A Water Value Results for System B
Slice 1 2.61 HU (2.15) 0.43 HU (1.03)
Tolerance -3.85 ... 6.00 HU -4.97 ... 6.00 HU

Slice 2 1.84 HU (1.86) 1.01 HU (1.16)


Tolerance -4.14 ... 6.00 HU -4.84 ... 6.00 HU

Slice 3 2.80 HU (3.49) 1.09 HU (0.87)


Tolerance -2.51 ... 6.00 HU -5.13 ... 6.00 HU

Slice 4 3.00 HU (3.11) 0.55 HU (0.84)


Tolerance -2.89 ... 6.00 HU -5.16 ... 6.00 HU

Slice 5 3.45 HU (3.08) 0.15 HU (0.81)


Tolerance -2.92 ... 6.00 HU -5.19 ... 6.00 HU

Slice 6 3.09 HU (3.20) -0.10 HU (1.16)


Tolerance -2.80 ... 6.00 HU -4.84 ... 6.00 HU

Slice 7 2.33 HU (2.44) 0.32 HU (0.51)


Tolerance -3.56 ... 6.00 HU -5.49 ... 6.00 HU

2023-10-11 09:50:03 Page: 4 / 6


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Results for System A


System A
Center Diff.3 Diff.6 Diff.9 Diff.12
Slice 1 2.61 HU (2.15) -0.27 HU (0.40) -0.30 HU (-0.06) -0.17 HU (0.14) -0.06 HU (0.82)
Tolerance -3.85 ... 6.00 HU -3.60 ... 4.40 HU -4.06 ... 3.94 HU -3.86 ... 4.14 HU -3.18 ... 4.82 HU

Slice 2 1.84 HU (1.86) 0.47 HU (0.59) 0.81 HU (0.40) 0.79 HU (0.34) 0.97 HU (1.21)
Tolerance -4.14 ... 6.00 HU -3.41 ... 4.59 HU -3.60 ... 4.40 HU -3.66 ... 4.34 HU -2.79 ... 5.21 HU

Slice 3 2.80 HU (3.49) -0.06 HU (-0.93) -0.25 HU (-1.22) -0.38 HU (-1.01) 0.08 HU (-0.11)
Tolerance -2.51 ... 6.00 HU -4.93 ... 3.07 HU -5.22 ... 2.78 HU -5.01 ... 2.99 HU -4.11 ... 3.89 HU

Slice 4 3.00 HU (3.11) -0.52 HU (-0.37) -0.42 HU (-0.25) -0.11 HU (-0.54) -0.09 HU (-0.09)
Tolerance -2.89 ... 6.00 HU -4.37 ... 3.63 HU -4.25 ... 3.75 HU -4.54 ... 3.46 HU -4.09 ... 3.91 HU

Slice 5 3.45 HU (3.08) -0.63 HU (-0.45) -0.62 HU (-0.20) -0.51 HU (-0.56) -0.50 HU (0.09)
Tolerance -2.92 ... 6.00 HU -4.45 ... 3.55 HU -4.20 ... 3.80 HU -4.56 ... 3.44 HU -3.91 ... 4.09 HU

Slice 6 3.09 HU (3.20) -0.38 HU (-0.80) -0.37 HU (-0.85) -0.79 HU (-0.93) -0.36 HU (-0.49)
Tolerance -2.80 ... 6.00 HU -4.80 ... 3.20 HU -4.85 ... 3.15 HU -4.93 ... 3.07 HU -4.49 ... 3.51 HU

Slice 7 2.33 HU (2.44) -0.22 HU (-0.41) 0.16 HU (-0.41) 0.12 HU (-0.42) 0.54 HU (0.36)
Tolerance -3.56 ... 6.00 HU -4.41 ... 3.59 HU -4.41 ... 3.59 HU -4.42 ... 3.58 HU -3.64 ... 4.36 HU

Results for System B


System B
Center Diff.3 Diff.6 Diff.9 Diff.12
Slice 1 0.43 HU (1.03) 1.56 HU (0.92) 1.85 HU (1.27) 1.94 HU (1.33) 2.54 HU (1.86)
Tolerance -4.97 ... 6.00 HU -3.08 ... 4.92 HU -2.73 ... 5.27 HU -2.67 ... 5.33 HU -2.14 ... 5.86 HU

Slice 2 1.01 HU (1.16) 1.51 HU (1.52) 1.53 HU (1.47) 1.48 HU (1.21) 1.84 HU (2.21)
Tolerance -4.84 ... 6.00 HU -2.48 ... 5.52 HU -2.53 ... 5.47 HU -2.79 ... 5.21 HU -1.79 ... 6.00 HU

Slice 3 1.09 HU (0.87) 1.52 HU (1.90) 1.61 HU (1.82) 1.34 HU (1.90) 2.13 HU (2.05)
Tolerance -5.13 ... 6.00 HU -2.10 ... 5.90 HU -2.18 ... 5.82 HU -2.10 ... 5.90 HU -1.95 ... 6.00 HU

Slice 4 0.55 HU (0.84) 2.06 HU (1.96) 1.96 HU (2.09) 2.19 HU (1.89) 2.56 HU (2.31)
Tolerance -5.16 ... 6.00 HU -2.04 ... 5.96 HU -1.91 ... 6.00 HU -2.11 ... 5.89 HU -1.69 ... 6.00 HU

Slice 5 0.15 HU (0.81) 2.11 HU (1.65) 2.69 HU (1.72) 2.20 HU (1.61) 2.95 HU (2.42)
Tolerance -5.19 ... 6.00 HU -2.35 ... 5.65 HU -2.28 ... 5.72 HU -2.39 ... 5.61 HU -1.58 ... 6.00 HU

Slice 6 -0.10 HU (1.16) 2.58 HU (1.39) 2.66 HU (1.65) 2.75 HU (1.42) 3.06 HU (1.98)
Tolerance -4.84 ... 6.00 HU -2.61 ... 5.39 HU -2.35 ... 5.65 HU -2.58 ... 5.42 HU -2.02 ... 5.98 HU

Slice 7 0.32 HU (0.51) 2.18 HU (1.90) 2.10 HU (2.01) 2.22 HU (2.15) 2.52 HU (2.12)
Tolerance -5.49 ... 6.00 HU -2.10 ... 5.90 HU -1.99 ... 6.00 HU -1.85 ... 6.00 HU -1.88 ... 6.00 HU

2023-10-11 09:50:03 Page: 5 / 6


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Test: Typical head mode


Test Parameters Test Results OK
System A
Current 390 mA
Slice width reconstructed 4.8 mm
Number of images 3
Collimation 12x1.2 mm
Scan Time 1.0 s
Rotation time 1.0 s
Body Region Head
Kernel Or44s
Radius of central ROI 10.00 mm
Radius of peripheral ROI 10.00 mm

Water Value Results


Water Value Results for System A
Slice 1 1.43 HU (1.72)
Tolerance -2.28 ... 4.00 HU

Slice 2 1.58 HU (1.47)


Tolerance -2.53 ... 4.00 HU

Slice 3 1.84 HU (1.59)


Tolerance -2.41 ... 4.00 HU

Results for System A


System A
Center Diff.3 Diff.6 Diff.9 Diff.12
Slice 1 1.43 HU (1.72) 0.61 HU (0.71) 0.88 HU (0.63) 1.06 HU (0.78) 0.59 HU (0.41)
Tolerance -2.28 ... 4.00 HU -1.29 ... 2.71 HU -1.37 ... 2.63 HU -1.22 ... 2.78 HU -1.59 ... 2.41 HU

Slice 2 1.58 HU (1.47) 0.88 HU (1.07) 0.77 HU (1.04) 0.67 HU (0.95) 0.46 HU (0.67)
Tolerance -2.53 ... 4.00 HU -0.93 ... 3.07 HU -0.96 ... 3.04 HU -1.05 ... 2.95 HU -1.33 ... 2.67 HU

Slice 3 1.84 HU (1.59) 0.44 HU (0.58) 0.46 HU (0.98) 0.55 HU (0.87) 0.14 HU (0.63)
Tolerance -2.41 ... 4.00 HU -1.42 ... 2.58 HU -1.02 ... 2.98 HU -1.13 ... 2.87 HU -1.37 ... 2.63 HU

2023-10-11 09:50:03 Page: 6 / 6


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy


General Information

Equipment
Standard IEC 61223-2-6 (Ed.2) Customer Name Customer
Tester Name sm Customer ID Id
Manufacturer Siemens Healthcare GmbH Hospital Name 105781
Product Name SOMATOM Drive Street Street StreetNo
Software Version syngo CT VB20A Zip Code ZIP
Serial Number 105781 City City
Handed over 2023-01-25 District District
Country QAT
Customer Phone Number Phone

Serial Number
Component Serial Number Revision Level
Tube Assembly A 691022371 -
Tube Assembly B 684512271 -

2023-10-11 09:50:53 Page: 1 / 4


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy Noise

Description
The measurement is performed for three sets of scan parameters, representing a typical head-mode, a typical body
mode and a body dual-source mode. For the dual-source mode the evaluation is performed separately for system
A and B. The image noise is evaluated measuring the standard deviation of CT numbers in a Region Of Interest
(ROI) in the image of a cylindrical water phantom with diameter 20 cm. The ROI is located in the phantom center.
To suppress the influence of image inhomogeneity and ring artifacts, the evaluation is performed for the difference
image of two succeeding scans.
Last IEC Constancy Reference measurement: 2023-10-11 09:35
(values stated in brackets)
Water phantom -
Water phantom large -

Common Parameters
Scan Type Sequence
Voltage 120 kV
UHR no
Shaped filter Wide
Tin filter no
Window width 500 HU
Window center 0 HU
FoV 250 mm

Test: Typical head mode


Test Parameters Test Results OK
System A
Current 390 mA
Slice width reconstructed 4.8 mm
Number of images 3
Collimation 12x1.2 mm
Scan Time 1.0 s
Rotation time 1.0 s
Body Region Head
Kernel Hr38s
Radius of ROIs 40 mm

Result
Results for System A
Slice 1 3.29 HU (3.31)
Tolerance 2.98 ... 3.54 HU

Slice 2 3.18 HU (3.23)


Tolerance 2.91 ... 3.54 HU

Slice 3 3.29 HU (3.24)


Tolerance 2.92 ... 3.54 HU

2023-10-11 09:50:53 Page: 2 / 4


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Test: Typical body mode


Test Parameters Test Results OK
System A
Current 294 mA
Slice width reconstructed 5.0 mm
Number of images 7
Collimation 64x0.6 mm
Scan Time 0.5 s
Rotation time 0.5 s
Body Region Body
Kernel Br38f
Radius of ROIs 40 mm

Result
Results for System A
Slice 1 4.72 HU (4.80)
Tolerance 4.32 ... 5.23 HU

Slice 2 4.79 HU (4.72)


Tolerance 4.28 ... 5.19 HU

Slice 3 4.68 HU (4.75)


Tolerance 4.28 ... 5.23 HU

Slice 4 4.72 HU (4.71)


Tolerance 4.28 ... 5.18 HU

Slice 5 4.69 HU (4.62)


Tolerance 4.28 ... 5.08 HU

Slice 6 4.65 HU (4.74)


Tolerance 4.28 ... 5.21 HU

Slice 7 4.78 HU (4.76)


Tolerance 4.28 ... 5.23 HU

Test: Typical body mode with dual tube System A and B


Test Parameters Test Results OK
System A System B
Current 294 mA 294 mA
Slice width
5.0 mm 5.0 mm
reconstructed
Number of
7 7
images
Collimation 64x0.6 mm 64x0.6 mm
Scan Time 0.5 s 0.5 s
Rotation time 0.5 s 0.5 s
Body Region Body Body
Kernel Br38f Br38f
Radius of ROIs 40 mm

2023-10-11 09:50:53 Page: 3 / 4


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Result
Results for System A Results for System B
Slice 1 4.73 HU (4.68) 4.71 HU (4.80)
Tolerance 4.25 ... 5.15 HU 4.32 ... 5.19 HU

Slice 2 4.69 HU (4.72) 4.73 HU (4.71)


Tolerance 4.25 ... 5.19 HU 4.25 ... 5.18 HU

Slice 3 4.66 HU (4.71) 4.71 HU (4.69)


Tolerance 4.25 ... 5.18 HU 4.25 ... 5.16 HU

Slice 4 4.64 HU (4.76) 4.78 HU (4.70)


Tolerance 4.28 ... 5.19 HU 4.25 ... 5.17 HU

Slice 5 4.72 HU (4.74) 4.71 HU (4.68)


Tolerance 4.27 ... 5.19 HU 4.25 ... 5.15 HU

Slice 6 4.66 HU (4.70) 4.67 HU (4.63)


Tolerance 4.25 ... 5.17 HU 4.25 ... 5.09 HU

Slice 7 4.67 HU (4.78) 4.75 HU (4.76)


Tolerance 4.30 ... 5.19 HU 4.28 ... 5.19 HU

2023-10-11 09:50:53 Page: 4 / 4


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy


General Information

Equipment
Standard IEC 61223-2-6 (Ed.2) Customer Name Customer
Tester Name sm Customer ID Id
Manufacturer Siemens Healthcare GmbH Hospital Name 105781
Product Name SOMATOM Drive Street Street StreetNo
Software Version syngo CT VB20A Zip Code ZIP
Serial Number 105781 City City
Handed over 2023-01-25 District District
Country QAT
Customer Phone Number Phone

Serial Number
Component Serial Number Revision Level
Tube Assembly A 691022371 -
Tube Assembly B 684512271 -

2023-10-11 09:52:22 Page: 1 / 6


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy MTF

Description
The High Contrast Resolution is determined by evaluating the image of a thin tungsten wire placed in a plastic
rod, centered in the scan plane and aligned along the scanner axis. From the images of the wire the point spread
function is obtained and the Modulation Transfer Function (MTF) is calculated as the Fourier Transformation of the
point spread function. The 50% and 10% value of the MTF are evaluated. The measurement is performed for four
to five sets of scan parameters, representing a typical head-mode, a typical body mode, a dual-source mode, the
sharpest mode without UHR comb and, if available, the sharpest mode with UHR-comb. For the dual-source mode
the evaluation is performed separately for system A and B.
Last IEC Constancy Reference measurement: 2023-10-11 09:36
(values stated in brackets)
Wire phantom -
Wire Phantom Type Wire in air

Common Parameters
Scan Type Sequence
Voltage 120 kV
UHR no
Shaped filter Wide
Tin filter no
Window width 100 HU
Window center 30 HU
FoV 50 mm

Test: Typical body mode


Test Parameters Test Results OK
System A
Current 294 mA
Slice width reconstructed 5.0 mm
Number of images 7
Collimation 64x0.6 mm
Scan Time 0.5 s
Rotation time 0.5 s
Body Region Body
Kernel Br38f

2023-10-11 09:52:22 Page: 2 / 6


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Results for System A


System A
50% 10%
Slice 1 3.53 lp/cm (3.53) 5.86 lp/cm (5.86)
Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 2 3.53 lp/cm (3.53) 5.86 lp/cm (5.86)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 3 3.55 lp/cm (3.54) 5.87 lp/cm (5.87)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 4 3.53 lp/cm (3.54) 5.86 lp/cm (5.86)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 5 3.54 lp/cm (3.54) 5.86 lp/cm (5.87)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 6 3.57 lp/cm (3.57) 5.88 lp/cm (5.88)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 7 3.59 lp/cm (3.59) 5.89 lp/cm (5.89)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Test: Typical body mode with dual tube System A and B


Test Parameters Test Results OK
System A System B
Current 294 mA 294 mA
Slice width
5.0 mm 5.0 mm
reconstructed
Number of
7 7
images
Collimation 64x0.6 mm 64x0.6 mm
Scan Time 0.5 s 0.5 s
Rotation time 0.5 s 0.5 s
Body Region Body Body
Kernel Br38f Br38f

2023-10-11 09:52:22 Page: 3 / 6


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Results for System A


System A
50% 10%
Slice 1 3.53 lp/cm (3.51) 5.86 lp/cm (5.85)
Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 2 3.53 lp/cm (3.53) 5.86 lp/cm (5.86)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 3 3.54 lp/cm (3.53) 5.87 lp/cm (5.86)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 4 3.53 lp/cm (3.53) 5.86 lp/cm (5.86)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 5 3.54 lp/cm (3.53) 5.87 lp/cm (5.86)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 6 3.56 lp/cm (3.56) 5.88 lp/cm (5.88)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 7 3.59 lp/cm (3.58) 5.89 lp/cm (5.89)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Results for System B


System B
50% 10%
Slice 1 3.53 lp/cm (3.52) 5.86 lp/cm (5.86)
Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 2 3.53 lp/cm (3.53) 5.86 lp/cm (5.86)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 3 3.53 lp/cm (3.53) 5.86 lp/cm (5.86)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 4 3.53 lp/cm (3.53) 5.86 lp/cm (5.86)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 5 3.53 lp/cm (3.54) 5.86 lp/cm (5.87)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 6 3.57 lp/cm (3.57) 5.88 lp/cm (5.88)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 7 3.59 lp/cm (3.59) 5.89 lp/cm (5.89)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

2023-10-11 09:52:22 Page: 4 / 6


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Test: Typical head mode


Test Parameters Test Results OK
System A
Current 390 mA
Slice width reconstructed 4.8 mm
Number of images 3
Collimation 12x1.2 mm
Scan Time 1.0 s
Rotation time 1.0 s
Body Region Head
Kernel Hr38s

Results for System A


System A
50% 10%
Slice 1 3.08 lp/cm (3.07) 5.72 lp/cm (5.72)
Tolerance 2.84 ... 3.47 lp/cm 5.22 ... 6.38 lp/cm

Slice 2 3.10 lp/cm (3.10) 5.73 lp/cm (5.73)


Tolerance 2.84 ... 3.47 lp/cm 5.22 ... 6.38 lp/cm

Slice 3 3.14 lp/cm (3.14) 5.76 lp/cm (5.76)


Tolerance 2.84 ... 3.47 lp/cm 5.22 ... 6.38 lp/cm

Test: Sharpest mode (without option UHR)


Test Parameters Test Results OK
System A
Current 390 mA
Slice width reconstructed 4.8 mm
Number of images 3
Collimation 12x1.2 mm
Scan Time 1.0 s
Rotation time 1.0 s
Body Region Head
Kernel Hr68h

Results for System A


System A
50% 10%
Slice 1 11.67 lp/cm (11.63) 13.43 lp/cm (13.42)
Tolerance 10.24 ... 12.52 lp/cm 12.60 ... 15.40 lp/cm

Slice 2 11.67 lp/cm (11.66) 13.43 lp/cm (13.43)


Tolerance 10.24 ... 12.52 lp/cm 12.60 ... 15.40 lp/cm

Slice 3 11.72 lp/cm (11.73) 13.43 lp/cm (13.44)


Tolerance 10.24 ... 12.52 lp/cm 12.60 ... 15.40 lp/cm

2023-10-11 09:52:22 Page: 5 / 6


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

2023-10-11 09:52:22 Page: 6 / 6


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy


General Information

Equipment
Standard IEC 61223-2-6 (Ed.2) Customer Name Customer
Tester Name sm Customer ID Id
Manufacturer Siemens Healthcare GmbH Hospital Name 105781
Product Name SOMATOM Drive Street Street StreetNo
Software Version syngo CT VB20A Zip Code ZIP
Serial Number 105781 City City
Handed over 2023-01-25 District District
Country QAT
Customer Phone Number Phone

Serial Number
Component Serial Number Revision Level
Tube Assembly A 691022371 -
Tube Assembly B 684512271 -

2023-10-11 09:53:57 Page: 1 / 2


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy Table Position

Description
The patient table is automatically moved forward and backward over 30 cm in continuous movement and stepwise
movement. After each series of movements the distance is measured with a ruler.
Last IEC Constancy Reference measurement: 2023-10-11 09:39
(values stated in brackets)

Test:
Test Results OK

Continuous Move Stepwise Move


Position 1 -300.00 mm -300.00 mm
Tolerance -301.00 ... -299.00 mm -301.00 ... -299.00 mm

Position 2 0.00 mm 0.00 mm


Tolerance -1.00 ... 1.00 mm -1.00 ... 1.00 mm

Position 3 300.00 mm 300.00 mm


Tolerance 299.00 ... 301.00 mm 299.00 ... 301.00 mm

Position 4 0.00 mm 0.00 mm


Tolerance -1.00 ... 1.00 mm -1.00 ... 1.00 mm

2023-10-11 09:53:57 Page: 2 / 2


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy


General Information

Equipment
Standard IEC 61223-2-6 (Ed.2) Customer Name Customer
Tester Name sm Customer ID Id
Manufacturer Siemens Healthcare GmbH Hospital Name 105781
Product Name SOMATOM Drive Street Street StreetNo
Software Version syngo CT VB20A Zip Code ZIP
Serial Number 105781 City City
Handed over 2023-01-25 District District
Country QAT
Customer Phone Number Phone

Serial Number
Component Serial Number Revision Level
Tube Assembly A 691022371 -
Tube Assembly B 684512271 -

2023-10-12 09:48:48 Page: 1 / 3


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy CTDI-Air

Description
The CTDIfreeAir is evaluated from the measured Dose-Length-Product (over 10 cm) in a typical head-mode, a typical
body mode (A-System) and a scan with the typical body mode parameter in the B-system.
Last IEC Constancy Reference measurement: 2023-10-12 09:48
(values stated in brackets)
Dosimeter -
CT-Ionisation Chamber -

Common Parameters
Scan Type Sequence
UHR no

Test: Typical head mode


Test Parameters Test Results OK
System A DLP [mGycm] Result [mGy/100mAs]

Voltage 120 kV 122.10 21.74 (21.76)

Current 390 mA Tolerance


18.43 ... 26.11
Slice width reconstructed 4.8 mm
Number of images 3
Collimation 12x1.2 mm
Scan Time 1.0 s
Rotation time 1.0 s
Shaped filter Wide
Tin filter no
Body Region Head
Window width 350 HU
Window center 50 HU
FoV 250 mm
Kernel Hr38s

Test: Typical body mode


Test Parameters Test Results OK
System A DLP [mGycm] Result [mGy/100mAs]

Voltage 120 kV 106.20 18.81 (18.81)

Current 294 mA Tolerance


15.79 ... 22.57
Collimation 64x0.6 mm
Scan Time 0.5 s
Rotation time 0.5 s
Shaped filter Wide
Tin filter no
Body Region Body

2023-10-12 09:48:48 Page: 2 / 3


System Serial Number: 105781
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Test: Typ. body, but with system B


Test Parameters Test Results OK
System B DLP [mGycm] Result [mGy/100mAs]

Voltage 120 kV 106.70 18.90 (18.88)

Current 294 mA Tolerance


15.79 ... 22.66
Collimation 64x0.6 mm
Scan Time 0.5 s
Rotation time 0.5 s
Shaped filter Wide
Tin filter no
Body Region Body

Test:
Test Parameters Test Results OK
System A DLP [mGycm] Result [mGy/100mAs]

Voltage 100 kV 18.39 1.92 (1.92)

Current 500 mA Tolerance


1.58 ... 2.30
Collimation 64x0.6 mm
Scan Time 0.5 s
Rotation time 0.5 s
Shaped filter Tin
Tin filter yes
Body Region Body

Test:
Test Parameters Test Results OK
System B DLP [mGycm] Result [mGy/100mAs]

Voltage 100 kV 18.76 1.95 (1.95)

Current 500 mA Tolerance


1.58 ... 2.34
Collimation 64x0.6 mm
Scan Time 0.5 s
Rotation time 0.5 s
Shaped filter Tin
Tin filter yes
Body Region Body

2023-10-12 09:48:48 Page: 3 / 3


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy


General Information

Equipment
Standard IEC 61223-2-6 (Ed.2) Customer Name Customer
Tester Name AR Customer ID Id
Manufacturer Siemens Healthcare GmbH Hospital Name 105779
Product Name SOMATOM Drive Street Street StreetNo
Software Version syngo CT VB20A Zip Code ZIP
Serial Number 105779 City City
Handed over 2023-01-26 District District
Country QAT
Customer Phone Number Phone

Serial Number
Component Serial Number Revision Level
Tube Assembly A 647422271 -
Tube Assembly B 633412271 -

2023-10-12 09:04:49 Page: 1 / 2


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy Lightmarker

Description
For the test of the lightmarkers the system phantom is centered and aligned, so that the lightmarkers hit the engraved
notches on the phantom. From image of the phantom, scanned with narrow collimation, the congruence of the
engraved notches with the scan plane as well as the saggital and coronal planes are tested.
Last IEC Constancy Reference measurement: 2023-10-12 08:53
(values stated in brackets)
Slice phantom -

Test:
Test Results OK
Result [mm]
0.00
Tolerance
-1.00 ... 1.00

2023-10-12 09:04:49 Page: 2 / 2


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy


General Information

Equipment
Standard IEC 61223-2-6 (Ed.2) Customer Name Customer
Tester Name AR Customer ID Id
Manufacturer Siemens Healthcare GmbH Hospital Name 105779
Product Name SOMATOM Drive Street Street StreetNo
Software Version syngo CT VB20A Zip Code ZIP
Serial Number 105779 City City
Handed over 2023-01-26 District District
Country QAT
Customer Phone Number Phone

Serial Number
Component Serial Number Revision Level
Tube Assembly A 647422271 -
Tube Assembly B 633412271 -

2023-10-12 09:05:32 Page: 1 / 2


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy Sag./Cor. Lightm.

Description
For the test of the lightmarkers the system phantom is centered and aligned, so that the lightmarkers hit the engraved
notches on the phantom. From image of the phantom, scanned with narrow collimation, the congruence of the
engraved notches with the scan plane as well as the saggital and coronal planes are tested.
Last IEC Constancy Reference measurement: 2023-10-12 09:04
(values stated in brackets)
Slice phantom -

Test:
Test Results OK

Result
Sagittal Light Marker Coronal Light Marker
Result 0.00 mm 0.00 mm
Tolerance -1.00 ... 1.00 mm -1.00 ... 1.00 mm

2023-10-12 09:05:32 Page: 2 / 2


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy


General Information

Equipment
Standard IEC 61223-2-6 (Ed.2) Customer Name Customer
Tester Name AR Customer ID Id
Manufacturer Siemens Healthcare GmbH Hospital Name 105779
Product Name SOMATOM Drive Street Street StreetNo
Software Version syngo CT VB20A Zip Code ZIP
Serial Number 105779 City City
Handed over 2023-01-26 District District
Country QAT
Customer Phone Number Phone

Serial Number
Component Serial Number Revision Level
Tube Assembly A 647422271 -
Tube Assembly B 633412271 -

2023-10-12 09:05:52 Page: 1 / 2


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy Topogram Pos.

Description
In the Topogram image of the system phantom the position of an tomogram scan with narrow collimation is selected
for the engraved notches in the phantom. From the recorded tomogram image of the phantom the congruence of
the engraved notches with the scan plane is inspected.
Last IEC Constancy Reference measurement: 2023-10-12 08:55
(values stated in brackets)
Slice phantom -

Test:
Test Results OK
Result [mm]
0.00
Tolerance
-2.00 ... 2.00

2023-10-12 09:05:52 Page: 2 / 2


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy


General Information

Equipment
Standard IEC 61223-2-6 (Ed.2) Customer Name Customer
Tester Name AR Customer ID Id
Manufacturer Siemens Healthcare GmbH Hospital Name 105779
Product Name SOMATOM Drive Street Street StreetNo
Software Version syngo CT VB20A Zip Code ZIP
Serial Number 105779 City City
Handed over 2023-01-26 District District
Country QAT
Customer Phone Number Phone

Serial Number
Component Serial Number Revision Level
Tube Assembly A 647422271 -
Tube Assembly B 633412271 -

2023-10-12 09:07:24 Page: 1 / 4


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy Slice

Description
The tomographic section thickness is evaluated by measuring the width of the image of an inclined aluminium ramp
at the intersection of the ramp with the slice. The width is defined as the Full Width at Half-Maximum (FWHM) of the
baseline corrected CT-value profile. The influence of the reconstruction kernel and the influence of the cone angle
on the measured width are taken into account. The measurement is performed for two sets of scan parameters,
representing a typical head- and a typical body mode. The evaluation is performed for at least the both outer and
one central slice. The measurement and evaluation is performed separately for system A and B.
Last IEC Constancy Reference measurement: 2023-10-12 08:56
(values stated in brackets)
Slice phantom -

Common Parameters
Scan Type Sequence
Voltage 120 kV
UHR no
Shaped filter Wide
Tin filter no
Window width 500 HU
Window center 50 HU
FoV 120 mm

Test: Typical head mode


Test Parameters Test Results OK
System A
Current 390 mA
Slice width reconstructed 4.8 mm
Number of images 3
Collimation 12x1.2 mm
Scan Time 1.0 s
Rotation time 1.0 s
Body Region Head
Kernel Or44s

Result
System A
Slice 1 4.72 mm (4.73)
Tolerance 3.80 ... 5.73 mm

Slice 2 4.87 mm (4.84)


Tolerance 3.84 ... 5.80 mm

Slice 3 4.74 mm (4.73)


Tolerance 3.80 ... 5.73 mm

2023-10-12 09:07:24 Page: 2 / 4


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Test: Typical body mode


Test Parameters Test Results OK
System A
Current 294 mA
Slice width reconstructed 5.0 mm
Number of images 7
Collimation 64x0.6 mm
Scan Time 0.5 s
Rotation time 0.5 s
Body Region Body
Kernel Or37f

Result
System A
Slice 1 5.12 mm (5.17)
Tolerance 4.17 ... 6.00 mm

Slice 2 5.18 mm (5.09)


Tolerance 4.09 ... 6.00 mm

Slice 4 5.28 mm (5.18)


Tolerance 4.18 ... 6.00 mm

Slice 6 5.17 mm (5.12)


Tolerance 4.12 ... 6.00 mm

Slice 7 5.21 mm (5.20)


Tolerance 4.20 ... 6.00 mm

Test: Typical body mode with dual tube System A and B


Test Parameters Test Results OK
System A System B
Current 147 mA 147 mA
Slice width
5.0 mm 5.0 mm
reconstructed
Number of
7 7
images
Collimation 64x0.6 mm 64x0.6 mm
Scan Time 0.5 s 0.5 s
Rotation time 0.5 s 0.5 s
Body Region Body Body
Kernel Or37f Or37f

2023-10-12 09:07:24 Page: 3 / 4


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Result
System A System B
Slice 1 5.01 mm (5.02) 5.08 mm (5.20)
Tolerance 4.02 ... 6.00 mm 4.20 ... 6.00 mm

Slice 2 5.03 mm (4.98) 5.01 mm (5.09)


Tolerance 4.00 ... 5.98 mm 4.09 ... 6.00 mm

Slice 4 5.10 mm (5.14) 5.13 mm (5.18)


Tolerance 4.14 ... 6.00 mm 4.18 ... 6.00 mm

Slice 6 5.17 mm (5.10) 5.03 mm (5.04)


Tolerance 4.10 ... 6.00 mm 4.04 ... 6.00 mm

Slice 7 5.18 mm (5.09) 5.11 mm (5.20)


Tolerance 4.09 ... 6.00 mm 4.20 ... 6.00 mm

2023-10-12 09:07:24 Page: 4 / 4


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy


General Information

Equipment
Standard IEC 61223-2-6 (Ed.2) Customer Name Customer
Tester Name AR Customer ID Id
Manufacturer Siemens Healthcare GmbH Hospital Name 105779
Product Name SOMATOM Drive Street Street StreetNo
Software Version syngo CT VB20A Zip Code ZIP
Serial Number 105779 City City
Handed over 2023-01-26 District District
Country QAT
Customer Phone Number Phone

Serial Number
Component Serial Number Revision Level
Tube Assembly A 647422271 -
Tube Assembly B 633412271 -

2023-10-12 09:08:50 Page: 1 / 6


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy Homogeneity / Water

Description
The measurement is performed for three sets of scan parameters, representing a typical head-mode, a typical body
mode and a body-dual-source mode. For the dual-source mode the evaluation is performed separately for system A
and B. The water value and homogeneity is evaluated by measuring the mean CT number in five Regions Of Interest
(ROI) in the image of a cylindrical water phantom with diameter 20 cm. The ROI are located in the center and near
the edge of the water phantom at 12 o'clock, 3 o'clock, 6 o'clock and 9 o'clock. The water value is the CT-number of
the central ROI, the homogeneity is the difference between the outer ROI and the central ROI each.
Last IEC Constancy Reference measurement: 2023-10-12 08:57
(values stated in brackets)
Water phantom -
Water phantom large -

Common Parameters
Scan Type Sequence
Voltage 120 kV
UHR no
Shaped filter Wide
Tin filter no
Window width 500 HU
Window center 0 HU
FoV 250 mm

Test: Typical body mode


Test Parameters Test Results OK
System A
Current 294 mA
Slice width reconstructed 5.0 mm
Number of images 7
Collimation 64x0.6 mm
Scan Time 0.5 s
Rotation time 0.5 s
Body Region Body
Kernel Or37f
Radius of central ROI 10.00 mm
Radius of peripheral ROI 10.00 mm

2023-10-12 09:08:50 Page: 2 / 6


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Water Value Results


Water Value Results for System A
Slice 1 0.01 HU (0.31)
Tolerance -3.69 ... 4.00 HU

Slice 2 0.08 HU (-0.11)


Tolerance -4.00 ... 3.89 HU

Slice 3 0.86 HU (0.59)


Tolerance -3.41 ... 4.00 HU

Slice 4 0.65 HU (0.28)


Tolerance -3.72 ... 4.00 HU

Slice 5 0.58 HU (0.12)


Tolerance -3.88 ... 4.00 HU

Slice 6 0.62 HU (0.46)


Tolerance -3.54 ... 4.00 HU

Slice 7 0.58 HU (0.15)


Tolerance -3.85 ... 4.00 HU

Results for System A


System A
Center Diff.3 Diff.6 Diff.9 Diff.12
Slice 1 0.01 HU (0.31) 0.64 HU (0.44) 1.00 HU (0.38) 0.61 HU (0.58) 0.64 HU (0.35)
Tolerance -3.69 ... 4.00 HU -1.56 ... 2.44 HU -1.62 ... 2.38 HU -1.42 ... 2.58 HU -1.65 ... 2.35 HU

Slice 2 0.08 HU (-0.11) 0.35 HU (0.70) 0.87 HU (1.10) 0.37 HU (0.72) 0.49 HU (0.45)
Tolerance -4.00 ... 3.89 HU -1.30 ... 2.70 HU -0.90 ... 3.10 HU -1.28 ... 2.72 HU -1.55 ... 2.45 HU

Slice 3 0.86 HU (0.59) -0.35 HU (-0.21) -0.35 HU (-0.33) -0.61 HU (-0.02) -0.83 HU (-0.42)
Tolerance -3.41 ... 4.00 HU -2.21 ... 1.79 HU -2.33 ... 1.67 HU -2.02 ... 1.98 HU -2.42 ... 1.58 HU

Slice 4 0.65 HU (0.28) 0.09 HU (-0.04) 0.00 HU (0.36) -0.20 HU (0.31) -0.39 HU (-0.26)
Tolerance -3.72 ... 4.00 HU -2.04 ... 1.96 HU -1.64 ... 2.36 HU -1.69 ... 2.31 HU -2.26 ... 1.74 HU

Slice 5 0.58 HU (0.12) 0.19 HU (0.47) 0.19 HU (0.46) -0.01 HU (0.69) -0.02 HU (0.37)
Tolerance -3.88 ... 4.00 HU -1.53 ... 2.47 HU -1.54 ... 2.46 HU -1.31 ... 2.69 HU -1.63 ... 2.37 HU

Slice 6 0.62 HU (0.46) -0.30 HU (0.02) -0.22 HU (0.37) -0.10 HU (0.04) -0.19 HU (-0.23)
Tolerance -3.54 ... 4.00 HU -1.98 ... 2.02 HU -1.63 ... 2.37 HU -1.96 ... 2.04 HU -2.23 ... 1.77 HU

Slice 7 0.58 HU (0.15) -0.22 HU (0.53) 0.33 HU (0.48) -0.03 HU (0.37) -0.19 HU (0.20)
Tolerance -3.85 ... 4.00 HU -1.47 ... 2.53 HU -1.52 ... 2.48 HU -1.63 ... 2.37 HU -1.80 ... 2.20 HU

2023-10-12 09:08:50 Page: 3 / 6


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Test: Typical body mode with dual tube System A and B


Test Parameters Test Results OK
System A System B
Current 294 mA 294 mA
Slice width
5.0 mm 5.0 mm
reconstructed
Number of
7 7
images
Collimation 64x0.6 mm 64x0.6 mm
Scan Time 0.5 s 0.5 s
Rotation time 0.5 s 0.5 s
Body Region Body Body
Kernel Or37f Or37f
Radius of central ROI 10.00 mm
Radius of peripheral ROI 10.00 mm

Water Value Results


Water Value Results for System A Water Value Results for System B
Slice 1 1.86 HU (1.40) -0.33 HU (-0.46)
Tolerance -4.60 ... 6.00 HU -6.00 ... 5.54 HU

Slice 2 1.54 HU (1.23) -0.55 HU (-0.07)


Tolerance -4.77 ... 6.00 HU -6.00 ... 5.93 HU

Slice 3 1.69 HU (1.79) -0.19 HU (-0.14)


Tolerance -4.21 ... 6.00 HU -6.00 ... 5.86 HU

Slice 4 2.20 HU (1.57) -1.39 HU (-0.75)


Tolerance -4.43 ... 6.00 HU -6.00 ... 5.25 HU

Slice 5 1.94 HU (2.02) -1.01 HU (-1.04)


Tolerance -3.98 ... 6.00 HU -6.00 ... 4.96 HU

Slice 6 1.94 HU (2.02) -0.71 HU (-0.48)


Tolerance -3.98 ... 6.00 HU -6.00 ... 5.52 HU

Slice 7 1.46 HU (1.30) -0.54 HU (-1.22)


Tolerance -4.70 ... 6.00 HU -6.00 ... 4.78 HU

2023-10-12 09:08:50 Page: 4 / 6


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Results for System A


System A
Center Diff.3 Diff.6 Diff.9 Diff.12
Slice 1 1.86 HU (1.40) -0.53 HU (-0.22) -0.60 HU (-0.11) -0.71 HU (-0.18) -0.63 HU (0.04)
Tolerance -4.60 ... 6.00 HU -4.22 ... 3.78 HU -4.11 ... 3.89 HU -4.18 ... 3.82 HU -3.96 ... 4.04 HU

Slice 2 1.54 HU (1.23) -0.30 HU (0.18) -0.08 HU (0.37) -0.41 HU (0.31) 0.21 HU (0.24)
Tolerance -4.77 ... 6.00 HU -3.82 ... 4.18 HU -3.63 ... 4.37 HU -3.69 ... 4.31 HU -3.76 ... 4.24 HU

Slice 3 1.69 HU (1.79) -0.71 HU (-0.64) -0.68 HU (-0.45) -0.63 HU (-0.81) -0.57 HU (-0.44)
Tolerance -4.21 ... 6.00 HU -4.64 ... 3.36 HU -4.45 ... 3.55 HU -4.81 ... 3.19 HU -4.44 ... 3.56 HU

Slice 4 2.20 HU (1.57) -1.11 HU (-0.15) -1.13 HU (-0.21) -1.05 HU (-0.21) -1.01 HU (0.09)
Tolerance -4.43 ... 6.00 HU -4.15 ... 3.85 HU -4.21 ... 3.79 HU -4.21 ... 3.79 HU -3.91 ... 4.09 HU

Slice 5 1.94 HU (2.02) -0.59 HU (-0.47) -0.84 HU (-0.33) -0.86 HU (-0.70) -0.32 HU (-0.29)
Tolerance -3.98 ... 6.00 HU -4.47 ... 3.53 HU -4.33 ... 3.67 HU -4.70 ... 3.30 HU -4.29 ... 3.71 HU

Slice 6 1.94 HU (2.02) -0.87 HU (-0.84) -0.62 HU (-0.75) -0.77 HU (-0.78) -0.81 HU (-0.25)
Tolerance -3.98 ... 6.00 HU -4.84 ... 3.16 HU -4.75 ... 3.25 HU -4.78 ... 3.22 HU -4.25 ... 3.75 HU

Slice 7 1.46 HU (1.30) -0.50 HU (-0.28) -0.40 HU (-0.19) -0.50 HU (-0.43) -0.42 HU (0.09)
Tolerance -4.70 ... 6.00 HU -4.28 ... 3.72 HU -4.19 ... 3.81 HU -4.43 ... 3.57 HU -3.91 ... 4.09 HU

Results for System B


System B
Center Diff.3 Diff.6 Diff.9 Diff.12
Slice 1 -0.33 HU (-0.46) 2.03 HU (2.09) 2.12 HU (2.54) 2.00 HU (2.08) 1.99 HU (2.18)
Tolerance -6.00 ... 5.54 HU -1.91 ... 6.00 HU -1.46 ... 6.00 HU -1.92 ... 6.00 HU -1.82 ... 6.00 HU

Slice 2 -0.55 HU (-0.07) 2.55 HU (2.32) 2.46 HU (2.36) 2.44 HU (1.85) 2.75 HU (2.10)
Tolerance -6.00 ... 5.93 HU -1.68 ... 6.00 HU -1.64 ... 6.00 HU -2.15 ... 5.85 HU -1.90 ... 6.00 HU

Slice 3 -0.19 HU (-0.14) 1.83 HU (1.90) 2.14 HU (2.43) 2.09 HU (1.98) 2.42 HU (2.28)
Tolerance -6.00 ... 5.86 HU -2.10 ... 5.90 HU -1.57 ... 6.00 HU -2.02 ... 5.98 HU -1.72 ... 6.00 HU

Slice 4 -1.39 HU (-0.75) 2.92 HU (2.40) 3.23 HU (2.55) 2.81 HU (2.12) 3.42 HU (2.54)
Tolerance -6.00 ... 5.25 HU -1.60 ... 6.00 HU -1.45 ... 6.00 HU -1.88 ... 6.00 HU -1.46 ... 6.00 HU

Slice 5 -1.01 HU (-1.04) 2.57 HU (2.67) 3.02 HU (3.26) 2.69 HU (2.63) 3.16 HU (2.80)
Tolerance -6.00 ... 4.96 HU -1.33 ... 6.00 HU -0.74 ... 6.00 HU -1.37 ... 6.00 HU -1.20 ... 6.00 HU

Slice 6 -0.71 HU (-0.48) 2.36 HU (2.05) 2.43 HU (2.36) 2.33 HU (2.04) 2.89 HU (2.38)
Tolerance -6.00 ... 5.52 HU -1.95 ... 6.00 HU -1.64 ... 6.00 HU -1.96 ... 6.00 HU -1.62 ... 6.00 HU

Slice 7 -0.54 HU (-1.22) 1.74 HU (2.06) 1.74 HU (2.84) 1.82 HU (2.52) 2.11 HU (2.96)
Tolerance -6.00 ... 4.78 HU -1.94 ... 6.00 HU -1.16 ... 6.00 HU -1.48 ... 6.00 HU -1.04 ... 6.00 HU

2023-10-12 09:08:50 Page: 5 / 6


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Test: Typical head mode


Test Parameters Test Results OK
System A
Current 390 mA
Slice width reconstructed 4.8 mm
Number of images 3
Collimation 12x1.2 mm
Scan Time 1.0 s
Rotation time 1.0 s
Body Region Head
Kernel Or44s
Radius of central ROI 10.00 mm
Radius of peripheral ROI 10.00 mm

Water Value Results


Water Value Results for System A
Slice 1 -0.41 HU (-0.03)
Tolerance -4.00 ... 3.97 HU

Slice 2 -0.53 HU (-0.28)


Tolerance -4.00 ... 3.72 HU

Slice 3 0.14 HU (0.24)


Tolerance -3.76 ... 4.00 HU

Results for System A


System A
Center Diff.3 Diff.6 Diff.9 Diff.12
Slice 1 -0.41 HU (-0.03) 0.84 HU (0.57) 0.96 HU (0.85) 1.02 HU (0.43) 0.62 HU (0.35)
Tolerance -4.00 ... 3.97 HU -1.43 ... 2.57 HU -1.15 ... 2.85 HU -1.57 ... 2.43 HU -1.65 ... 2.35 HU

Slice 2 -0.53 HU (-0.28) 1.08 HU (0.82) 1.23 HU (0.96) 1.16 HU (1.08) 0.92 HU (0.40)
Tolerance -4.00 ... 3.72 HU -1.18 ... 2.82 HU -1.04 ... 2.96 HU -0.92 ... 3.08 HU -1.60 ... 2.40 HU

Slice 3 0.14 HU (0.24) 0.71 HU (0.43) 0.46 HU (0.52) 0.52 HU (0.37) 0.07 HU (0.29)
Tolerance -3.76 ... 4.00 HU -1.57 ... 2.43 HU -1.48 ... 2.52 HU -1.63 ... 2.37 HU -1.71 ... 2.29 HU

2023-10-12 09:08:50 Page: 6 / 6


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy


General Information

Equipment
Standard IEC 61223-2-6 (Ed.2) Customer Name Customer
Tester Name AR Customer ID Id
Manufacturer Siemens Healthcare GmbH Hospital Name 105779
Product Name SOMATOM Drive Street Street StreetNo
Software Version syngo CT VB20A Zip Code ZIP
Serial Number 105779 City City
Handed over 2023-01-26 District District
Country QAT
Customer Phone Number Phone

Serial Number
Component Serial Number Revision Level
Tube Assembly A 647422271 -
Tube Assembly B 633412271 -

2023-10-12 09:09:40 Page: 1 / 4


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy Noise

Description
The measurement is performed for three sets of scan parameters, representing a typical head-mode, a typical body
mode and a body dual-source mode. For the dual-source mode the evaluation is performed separately for system
A and B. The image noise is evaluated measuring the standard deviation of CT numbers in a Region Of Interest
(ROI) in the image of a cylindrical water phantom with diameter 20 cm. The ROI is located in the phantom center.
To suppress the influence of image inhomogeneity and ring artifacts, the evaluation is performed for the difference
image of two succeeding scans.
Last IEC Constancy Reference measurement: 2023-10-12 08:58
(values stated in brackets)
Water phantom -
Water phantom large -

Common Parameters
Scan Type Sequence
Voltage 120 kV
UHR no
Shaped filter Wide
Tin filter no
Window width 500 HU
Window center 0 HU
FoV 250 mm

Test: Typical head mode


Test Parameters Test Results OK
System A
Current 390 mA
Slice width reconstructed 4.8 mm
Number of images 3
Collimation 12x1.2 mm
Scan Time 1.0 s
Rotation time 1.0 s
Body Region Head
Kernel Hr38s
Radius of ROIs 40 mm

Result
Results for System A
Slice 1 3.20 HU (3.19)
Tolerance 2.90 ... 3.51 HU

Slice 2 3.17 HU (3.25)


Tolerance 2.93 ... 3.54 HU

Slice 3 3.26 HU (3.32)


Tolerance 2.99 ... 3.54 HU

2023-10-12 09:09:40 Page: 2 / 4


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Test: Typical body mode


Test Parameters Test Results OK
System A
Current 294 mA
Slice width reconstructed 5.0 mm
Number of images 7
Collimation 64x0.6 mm
Scan Time 0.5 s
Rotation time 0.5 s
Body Region Body
Kernel Br38f
Radius of ROIs 40 mm

Result
Results for System A
Slice 1 4.86 HU (4.86)
Tolerance 4.37 ... 5.23 HU

Slice 2 4.77 HU (4.82)


Tolerance 4.34 ... 5.23 HU

Slice 3 4.69 HU (4.82)


Tolerance 4.34 ... 5.23 HU

Slice 4 4.80 HU (4.76)


Tolerance 4.28 ... 5.23 HU

Slice 5 4.79 HU (4.78)


Tolerance 4.30 ... 5.23 HU

Slice 6 4.75 HU (4.84)


Tolerance 4.36 ... 5.23 HU

Slice 7 4.72 HU (4.81)


Tolerance 4.33 ... 5.23 HU

Test: Typical body mode with dual tube System A and B


Test Parameters Test Results OK
System A System B
Current 294 mA 294 mA
Slice width
5.0 mm 5.0 mm
reconstructed
Number of
7 7
images
Collimation 64x0.6 mm 64x0.6 mm
Scan Time 0.5 s 0.5 s
Rotation time 0.5 s 0.5 s
Body Region Body Body
Kernel Br38f Br38f
Radius of ROIs 40 mm

2023-10-12 09:09:40 Page: 3 / 4


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Result
Results for System A Results for System B
Slice 1 4.88 HU (4.91) 4.81 HU (4.84)
Tolerance 4.42 ... 5.19 HU 4.36 ... 5.19 HU

Slice 2 4.76 HU (4.74) 4.73 HU (4.71)


Tolerance 4.27 ... 5.19 HU 4.25 ... 5.18 HU

Slice 3 4.66 HU (4.77) 4.73 HU (4.73)


Tolerance 4.29 ... 5.19 HU 4.26 ... 5.19 HU

Slice 4 4.74 HU (4.65) 4.74 HU (4.67)


Tolerance 4.25 ... 5.12 HU 4.25 ... 5.14 HU

Slice 5 4.65 HU (4.80) 4.65 HU (4.75)


Tolerance 4.32 ... 5.19 HU 4.28 ... 5.19 HU

Slice 6 4.66 HU (4.71) 4.70 HU (4.65)


Tolerance 4.25 ... 5.18 HU 4.25 ... 5.12 HU

Slice 7 4.67 HU (4.76) 4.67 HU (4.63)


Tolerance 4.28 ... 5.19 HU 4.25 ... 5.09 HU

2023-10-12 09:09:40 Page: 4 / 4


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy


General Information

Equipment
Standard IEC 61223-2-6 (Ed.2) Customer Name Customer
Tester Name AR Customer ID Id
Manufacturer Siemens Healthcare GmbH Hospital Name 105779
Product Name SOMATOM Drive Street Street StreetNo
Software Version syngo CT VB20A Zip Code ZIP
Serial Number 105779 City City
Handed over 2023-01-26 District District
Country QAT
Customer Phone Number Phone

Serial Number
Component Serial Number Revision Level
Tube Assembly A 647422271 -
Tube Assembly B 633412271 -

2023-10-12 09:11:09 Page: 1 / 6


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy MTF

Description
The High Contrast Resolution is determined by evaluating the image of a thin tungsten wire placed in a plastic
rod, centered in the scan plane and aligned along the scanner axis. From the images of the wire the point spread
function is obtained and the Modulation Transfer Function (MTF) is calculated as the Fourier Transformation of the
point spread function. The 50% and 10% value of the MTF are evaluated. The measurement is performed for four
to five sets of scan parameters, representing a typical head-mode, a typical body mode, a dual-source mode, the
sharpest mode without UHR comb and, if available, the sharpest mode with UHR-comb. For the dual-source mode
the evaluation is performed separately for system A and B.
Last IEC Constancy Reference measurement: 2023-10-12 09:00
(values stated in brackets)
Wire phantom -
Wire Phantom Type Wire in air

Common Parameters
Scan Type Sequence
Voltage 120 kV
UHR no
Shaped filter Wide
Tin filter no
Window width 100 HU
Window center 30 HU
FoV 50 mm

Test: Typical body mode


Test Parameters Test Results OK
System A
Current 294 mA
Slice width reconstructed 5.0 mm
Number of images 7
Collimation 64x0.6 mm
Scan Time 0.5 s
Rotation time 0.5 s
Body Region Body
Kernel Br38f

2023-10-12 09:11:09 Page: 2 / 6


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Results for System A


System A
50% 10%
Slice 1 3.56 lp/cm (3.56) 5.88 lp/cm (5.88)
Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 2 3.56 lp/cm (3.55) 5.88 lp/cm (5.87)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 3 3.56 lp/cm (3.56) 5.89 lp/cm (5.89)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 4 3.56 lp/cm (3.57) 5.89 lp/cm (5.89)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 5 3.58 lp/cm (3.58) 5.90 lp/cm (5.90)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 6 3.60 lp/cm (3.60) 5.90 lp/cm (5.90)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 7 3.62 lp/cm (3.62) 5.91 lp/cm (5.92)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Test: Typical body mode with dual tube System A and B


Test Parameters Test Results OK
System A System B
Current 294 mA 294 mA
Slice width
5.0 mm 5.0 mm
reconstructed
Number of
7 7
images
Collimation 64x0.6 mm 64x0.6 mm
Scan Time 0.5 s 0.5 s
Rotation time 0.5 s 0.5 s
Body Region Body Body
Kernel Br38f Br38f

2023-10-12 09:11:09 Page: 3 / 6


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Results for System A


System A
50% 10%
Slice 1 3.55 lp/cm (3.56) 5.88 lp/cm (5.88)
Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 2 3.55 lp/cm (3.56) 5.87 lp/cm (5.88)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 3 3.55 lp/cm (3.56) 5.88 lp/cm (5.88)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 4 3.56 lp/cm (3.56) 5.89 lp/cm (5.89)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 5 3.57 lp/cm (3.57) 5.89 lp/cm (5.89)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 6 3.60 lp/cm (3.60) 5.90 lp/cm (5.90)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 7 3.62 lp/cm (3.62) 5.91 lp/cm (5.92)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Results for System B


System B
50% 10%
Slice 1 3.54 lp/cm (3.55) 5.87 lp/cm (5.87)
Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 2 3.55 lp/cm (3.55) 5.88 lp/cm (5.87)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 3 3.55 lp/cm (3.56) 5.88 lp/cm (5.88)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 4 3.56 lp/cm (3.55) 5.88 lp/cm (5.88)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 5 3.58 lp/cm (3.58) 5.89 lp/cm (5.89)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 6 3.59 lp/cm (3.59) 5.90 lp/cm (5.90)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

Slice 7 3.62 lp/cm (3.62) 5.91 lp/cm (5.91)


Tolerance 3.15 ... 3.85 lp/cm 5.31 ... 6.49 lp/cm

2023-10-12 09:11:09 Page: 4 / 6


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Test: Typical head mode


Test Parameters Test Results OK
System A
Current 390 mA
Slice width reconstructed 4.8 mm
Number of images 3
Collimation 12x1.2 mm
Scan Time 1.0 s
Rotation time 1.0 s
Body Region Head
Kernel Hr38s

Results for System A


System A
50% 10%
Slice 1 3.10 lp/cm (3.10) 5.75 lp/cm (5.74)
Tolerance 2.84 ... 3.47 lp/cm 5.22 ... 6.38 lp/cm

Slice 2 3.13 lp/cm (3.13) 5.77 lp/cm (5.76)


Tolerance 2.84 ... 3.47 lp/cm 5.22 ... 6.38 lp/cm

Slice 3 3.18 lp/cm (3.18) 5.80 lp/cm (5.80)


Tolerance 2.84 ... 3.47 lp/cm 5.22 ... 6.38 lp/cm

Test: Sharpest mode (without option UHR)


Test Parameters Test Results OK
System A
Current 390 mA
Slice width reconstructed 4.8 mm
Number of images 3
Collimation 12x1.2 mm
Scan Time 1.0 s
Rotation time 1.0 s
Body Region Head
Kernel Hr68h

Results for System A


System A
50% 10%
Slice 1 11.85 lp/cm (11.85) 13.46 lp/cm (13.46)
Tolerance 10.24 ... 12.52 lp/cm 12.60 ... 15.40 lp/cm

Slice 2 11.88 lp/cm (11.88) 13.47 lp/cm (13.46)


Tolerance 10.24 ... 12.52 lp/cm 12.60 ... 15.40 lp/cm

Slice 3 11.94 lp/cm (11.93) 13.47 lp/cm (13.47)


Tolerance 10.24 ... 12.52 lp/cm 12.60 ... 15.40 lp/cm

2023-10-12 09:11:09 Page: 5 / 6


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

2023-10-12 09:11:09 Page: 6 / 6


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy


General Information

Equipment
Standard IEC 61223-2-6 (Ed.2) Customer Name Customer
Tester Name AR Customer ID Id
Manufacturer Siemens Healthcare GmbH Hospital Name 105779
Product Name SOMATOM Drive Street Street StreetNo
Software Version syngo CT VB20A Zip Code ZIP
Serial Number 105779 City City
Handed over 2023-01-26 District District
Country QAT
Customer Phone Number Phone

Serial Number
Component Serial Number Revision Level
Tube Assembly A 647422271 -
Tube Assembly B 633412271 -

2023-10-12 09:12:41 Page: 1 / 2


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy Table Position

Description
The patient table is automatically moved forward and backward over 30 cm in continuous movement and stepwise
movement. After each series of movements the distance is measured with a ruler.
Last IEC Constancy Reference measurement: 2023-10-12 09:02
(values stated in brackets)

Test:
Test Results OK

Continuous Move Stepwise Move


Position 1 -300.00 mm -300.00 mm
Tolerance -301.00 ... -299.00 mm -301.00 ... -299.00 mm

Position 2 0.00 mm 0.00 mm


Tolerance -1.00 ... 1.00 mm -1.00 ... 1.00 mm

Position 3 300.00 mm 300.00 mm


Tolerance 299.00 ... 301.00 mm 299.00 ... 301.00 mm

Position 4 0.00 mm 0.00 mm


Tolerance -1.00 ... 1.00 mm -1.00 ... 1.00 mm

2023-10-12 09:12:41 Page: 2 / 2


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy


General Information

Equipment
Standard IEC 61223-2-6 (Ed.2) Customer Name Customer
Tester Name AR Customer ID Id
Manufacturer Siemens Healthcare GmbH Hospital Name 105779
Product Name SOMATOM Drive Street Street StreetNo
Software Version syngo CT VB20A Zip Code ZIP
Serial Number 105779 City City
Handed over 2023-01-26 District District
Country QAT
Customer Phone Number Phone

Serial Number
Component Serial Number Revision Level
Tube Assembly A 647422271 -
Tube Assembly B 633412271 -

2023-10-12 09:23:49 Page: 1 / 3


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Quality IEC Constancy CTDI-Air

Description
The CTDIfreeAir is evaluated from the measured Dose-Length-Product (over 10 cm) in a typical head-mode, a typical
body mode (A-System) and a scan with the typical body mode parameter in the B-system.
Last IEC Constancy Reference measurement: 2023-10-12 09:23
(values stated in brackets)
Dosimeter -
CT-Ionisation Chamber -

Common Parameters
Scan Type Sequence
UHR no

Test: Typical head mode


Test Parameters Test Results OK
System A DLP [mGycm] Result [mGy/100mAs]

Voltage 120 kV 119.70 21.31 (21.31)

Current 390 mA Tolerance


18.43 ... 25.57
Slice width reconstructed 4.8 mm
Number of images 3
Collimation 12x1.2 mm
Scan Time 1.0 s
Rotation time 1.0 s
Shaped filter Wide
Tin filter no
Body Region Head
Window width 350 HU
Window center 50 HU
FoV 250 mm
Kernel Hr38s

Test: Typical body mode


Test Parameters Test Results OK
System A DLP [mGycm] Result [mGy/100mAs]

Voltage 120 kV 104.10 18.44 (18.46)

Current 294 mA Tolerance


15.79 ... 22.15
Collimation 64x0.6 mm
Scan Time 0.5 s
Rotation time 0.5 s
Shaped filter Wide
Tin filter no
Body Region Body

2023-10-12 09:23:49 Page: 2 / 3


System Serial Number: 105779
SOMATOM Drive Quality IEC Constancy
Customer ID: Id

Test: Typ. body, but with system B


Test Parameters Test Results OK
System B DLP [mGycm] Result [mGy/100mAs]

Voltage 120 kV 105.40 18.67 (18.67)

Current 294 mA Tolerance


15.79 ... 22.40
Collimation 64x0.6 mm
Scan Time 0.5 s
Rotation time 0.5 s
Shaped filter Wide
Tin filter no
Body Region Body

Test:
Test Parameters Test Results OK
System A DLP [mGycm] Result [mGy/100mAs]

Voltage 100 kV 18.45 1.92 (1.92)

Current 500 mA Tolerance


1.58 ... 2.30
Collimation 64x0.6 mm
Scan Time 0.5 s
Rotation time 0.5 s
Shaped filter Tin
Tin filter yes
Body Region Body

Test:
Test Parameters Test Results OK
System B DLP [mGycm] Result [mGy/100mAs]

Voltage 100 kV 18.43 1.92 (1.92)

Current 500 mA Tolerance


1.58 ... 2.30
Collimation 64x0.6 mm
Scan Time 0.5 s
Rotation time 0.5 s
Shaped filter Tin
Tin filter yes
Body Region Body

2023-10-12 09:23:49 Page: 3 / 3


RASHID
Digitally signed by RASHID ASIM
DN: cn=RASHID ASIM, c=DE,
o=Siemens,

ASIM
email=asim.rashid@siemens-
healthineers.com
Date: 2023.10.16 12:54:23 +03'00'
105779
105779 16/10/2023
105779 16/10/2023
105779 16/10/2023
105779 16/10/2023
105779 16/10/2023
105779 16/10/2023
105779 16/10/2023

RASHID Digitally signed by RASHID ASIM


DN: cn=RASHID ASIM, c=DE,
o=Siemens,

ASIM
email=asim.rashid@siemens-
healthineers.com
Date: 2023.10.16 15:36:15 +03'00'
Miled
Digitally signed by Miled samir
DN: cn=Miled samir, c=DE,
o=Siemens,

samir
email=samir.miled@siemens-
healthineers.com
Date: 2023.10.15 23:06:30 +03'00'
Miled
Digitally signed by Miled samir
DN: cn=Miled samir, c=DE,
o=Siemens,

samir
email=samir.miled@siemens-
healthineers.com
Date: 2023.10.15 23:08:02 +03'00'
This is to confirm that

Prebin Alakadan

has successfully passed the test

CT Basic Certification
Contents:

• X-Ray fundamentals
• CT basic knowledge
• CT basic application
• Basic Tune up
• Preventive maintenenace
• Safety issues

Completion date: February 09, 2012


Identification number: AAELAFY
Test number: CTTCTBASIC

This certificate is automatically created by system on August 01, 2017 and requires no signature
www.siemens.com/healthineers

CERTIFICATE *
of Attendance

Mr. Asim Rashid


has attended the course

Somatom Definition, Definition AS/AS+,


Definition Flash System
CT2DEFFAM
from March 28, 2011 to April 13, 2011
at Erlangen, Training Center

with the following contents:

 System Overview Definition and Definition AS/AS+ and Definition Flash


 System Specific Safety Instructions
 Power Distribution Systems
 Gantry Stationary
 Gantry Rotating
 Data Measurement Systems
 Imaging Reconstruction Systems
 Patient Handling Systems
 Gantry Cooling Systems
 Service Software

Siemens Healthineers
Global Training Center
Intranet: https://intranet.training.healthcare.siemens.com/
Internet: https://training.healthcare.siemens.com/

* This attendance certificate is a reprint that was automatically created by system


on 2017-08-02 and requires no signature

Identification Number: AADWPCA - CSTC


www.siemens.com/healthineers

CERTIFICATE *
of Attendance

Mr. Samir Miled


has attended the course

Somatom Definition, Definition AS/AS+


System Course
CT2DEFFAM
from December 3, 2008 to December 19, 2008
at Cary, North Carolina, USA

with the following contents:

 System Overview Definition and Definition AS/AS+


 Power Distribution Systems
 Gantry Stationary
 Gantry Rotating
 Data Measurement Systems
 Imaging Reconstruction Systems
 Patient Handling Systems
 Gantry Cooling Systems
 Service Software
 Hands-on

Siemens Healthineers
Global Training Center
Intranet: https://intranet.training.healthcare.siemens.com/
Internet: https://training.healthcare.siemens.com/

* This attendance certificate is a reprint that was automatically created by system


on 2017-08-02 and requires no signature

Identification Number: AADDOHD - TDC


Mr. Vinay Aggarwal
has attended the course

CT BASICS
CT1CTBASIC

from April 19, 2010 to April 30, 2010


at India

with the following contents:

General safety information


X-ray fundamentals
CT Principle
CT basics
Overview main CT components
CT systems
Tune up
Image quality check
System operation

Siemens Healthineers
Global Training Center

Dr. Janina Beilner


Global Head of Education
Date: Apr 30, 2010
Identification Number: AADRSGX - CSTC

Intranet: https://intranet.training.healthcare.siemens.com
Internet: https://training.healthcare.siemens.com
www.siemens.com/healthineers

CERTIFICATE *
of Attendance

Mr. Asim Rashid


has attended the course

CT BASICS
CT1CTBASIC
from March 14, 2011 to March 25, 2011
at Erlangen, Training Center

with the following contents:

 General safety information


 X-ray fundamentals
 CT Principle
 CT basics
 Overview main CT components
 CT systems
 Tune up
 Image quality check
 System operation

Siemens Healthineers
Global Training Center
Intranet: https://intranet.training.healthcare.siemens.com/
Internet: https://training.healthcare.siemens.com/

* This attendance certificate is a reprint that was automatically created by system


on 2017-08-02 and requires no signature

Identification Number: AADWPBX - CSTC


Packages as Per MOD Packages as Per Packages as Per
Department Dept Ref ID Room Name Room # CAD ID Description ItemQty Arch Code Supplier Manufacturer Model Serial No.
Contract MAT RBR

Imaging & Dental Radiology Imaging Diagnostic Ground CT Scanner, Multi-Slice, 64-
CT ROOM Z1-L0-IMD-021 CTX0152 1 1-Fixed ABAM SIEMENS SOMATOM Drive 105781
Package Package Packages Imaging Floor 320 Slice

Imaging & Dental Radiology Imaging Diagnostic Ground CT Scanner, Multi-Slice, 64-
CT ROOM Z1-L0-IMD-025 CTX0152 1 1-Fixed ABAM SIEMENS SOMATOM Drive 105779
Package Package Packages Imaging Floor 320 Slice
Data sheet

SOMATOM Drive
Data sheet for syngo CT VB20
siemens-healthineers.com/somatom-drive

International version.
Not for distribution or use in the U.S.
SOMATOM Drive

Regardless of who walks through the door, your medical


imaging institution is constantly pressured to provide
state-of-the-art CT imaging – every day, every night,
and at every single moment.

This is why Siemens Healthineers, with its unique Dual


Source technology, is collaborating with you to expand
technological possibilities, simplify complex procedures,
and raise clinical standards.

After all, patients don’t always have an appointment.


Medical conditions often can’t wait for specialized staff.
And clinical trends are never constant. In today’s world,
you need to be prepared to aid your patients, to cope with
your environment, and to meet your business needs –
while driving precision every step of the way.

2
syngo CT VB20 · SOMATOM Drive

SOMATOM Drive boosts your performance, Drive precision


empowers your routines, and expands for your patients.
your capabilities. SOMATOM Drive provides reliable diagnostic results
Drive precision every day, every night, and at every across clinical disciplines as well as a new quality of
single moment with SOMATOM® Drive. patient care. Accept more patients than ever before
and master urgent care. This will improve the CT
experience for everyone involved.

Drive precision Drive precision


for your environment. for your business needs.
SOMATOM Drive lets you standardize your institution’s SOMATOM Drive allows you to implement unprecedented
quality of care to unseen levels. Promote optimum system management efficiency. Versatile and future-
performance at all times by simplifying routines and proof, this CT technology connects you to the CT practice
accelerating workflows. of tomorrow, advancing new clinical fields and new
technologies.

3
SOMATOM Drive · syngo CT VB20

Highlights

110
90

IR 130
70 140
A B

Dual Source Technology StellarInfinity detectors with Unique 10 kV Steps


Integrated Iterative Reconstruction
The Dual Source CT technology To provide more patients with the
allows you to achieve precise dose With the StellarInfinity detectors with most precise dose values for their
and superfast scanning, appropriate integrated iterative reconstruction, situation, SOMATOM Drive’s unique
to each patient’s needs regardless SOMATOM Drive is driving a new 10 kV Steps and CARE kV facilitate
of age, size or weight. The unique level of integration of software and higher power at lower kVs. They
Dual Source gantry and high-pitch hardware. The high resolution of the also provide more accurate kV
table introduce precise CT imaging StellarInfinity detectors create excellent settings, which makes it even easier
at unprecedented acquisition speed image quality with reduced noise. to achieve the right dose for each
and temporal resolution. individual patient. So now you
can scan patients at lower kVs
more often.

70 & 80 kV

Tin Filters Straton® MX Sigma X-ray Rapid Results


tubes & Sigma generators
This unique Siemens Healthineers Rapid Results Technology
feature prefilters and shapes the SOMATOM Drive is equipped with auto­matically calculates the images
X-ray spectrum, removing low- the new Straton MX Sigma X-ray and archives the evaluation results,
energy photons that significantly tubes, Sigma generators, and High for example Lung CAD in the
increase dose but not image quality Power 70 & High Power 80 that multi­modality oncology workflow
in non-contrast imaging. SOMATOM enables low-dose scanning while or Monoenergetic Images in CT Dual
Drive comes with two Tin Filters freezing motion at maximum speed. Energy. With no human interaction
that allow high pitch and Superfast It’s optimized for low kV imaging to in-between, you will be provided
Scanning to be performed. This reduce scan time, while maintaining the right series and the appropriate
reduces dose and motion artifacts, exceptional image quality. amount of information. Also, you
which is especially important for SOMATOM Drive uses the power don’t have to open the workflow in
lung cancer screening. Additionally, of both tubes for fast scanning. syngo.via since the calculated results
this technology aims to lower dose are automatically sent to your PACS.
while maintaining image quality
for sinus and extremity images,
coronary calcium scoring and
colonography.

4
syngo CT VB20 · SOMATOM Drive

Highlights

Superfast Scanning Adaptive 4D Spiral

Superfast Scanning helps eliminate motion artifacts The Adaptive 4D Spiral achieves whole-brain and
without increasing the dose, while breathing artifacts whole-organ coverage for perfusion imaging and
are removed with the most precise dose and the best enables low-dose CT angiography and dynamic CT.
in-plane temporal resolution. This also helps dose- Harness the potential to improve patient out­comes
sensitive patients, who need very low doses – but it does with 4D imaging that exceeds the detector width and
so without limiting scan speed and temporal resolution. allows you to act faster and be more confident than
ever in your treatment decisions. The new Adaptive
4D Spiral visualizes motion with a dynamic scan range
up to 480 mm on SOMATOM Drive.

FAST IRS FAST Integrated Workflow with FAST 3D Camera

In virtually all reconstructions, the FAST IRS (image The FAST 3D Camera captures the patient’s shape,
reconstruction system) can reduce wait time. For position, and height using three-dimensional data.
example, filtered back projection (FBP) reconstructions Thanks to infrared measurement, it also recognizes
are calculated with up to 70 fps (frames per second) and body contours: for example, patients are covered with
iterative reconstructions (IR) are calculated with 50 fps. blankets patient gowns. Algorithms utilize this data to
Using FAST IRS, the often numerous reconstructions in calculate the correct patient positioning. The zero­click
polytrauma and emergency exams can be performed solution runs unique algorithms to support accurate
fast, when time till diagnosis really counts. and reproducible positioning: With FAST Isocentering,
you get the right dose modulation and consistent
images; FAST Range supports scanning the right body
region with no truncation; FAST Direction helps
safeguard the right scan direction.

5
SOMATOM Drive · syngo CT VB20

System Configuration

Standard system hardware Standard system software


• 0.28 s rotation time • syngo Examination
• 2 x Straton MX Sigma X-ray tubes • syngo Viewing
and Sigma generators • syngo Filming
• z-Sharp technology • syngo Archiving & Network
• Adaptive Dose Shield • syngo Service Solution
• 2 x StellarInfinity detectors • Image Filter
• 200 kW (2 x 100 kW generators) • Video Capture and Editing Tool
• Cooling system water/water • Scan Protocol Assistant
• CT patient table (2,000 mm scan range, • e-Logbook
227 kg / 500 lbs table load) • syngo 3D Real Time MPR
• 20 fps IR, 60 fps FBP • syngo 3D SSD
(Surface Shaded Display)
Optional system hardware
• syngo Volume Calculation
• Multi-purpose patient table
• syngo Dynamic Evaluation
(307 kg / 676 lbs table load)
• syngo VRT
• Additional 19” (48 cm) flat screen monitor
(Volume Rendering Technique)
• Table side rails
• CT-Angiography
• 400 mm / 15.7” patient restraint strap
• Neuro BestContrast
• Table cover paper dispenser
• Adaptive Signal Boost
• Split cooling system water/air
• Dual 19” (48 cm) flat screen monitor with dual DistinCT Imaging
display functionality • SureView
• Advanced radiotranslucent ECG extensions for • X-CARE
uncompro­mised, metal artifact-free use in • FAST Adjust
Cardiac CT imaging • FAST Scan Assistant
• Respiratory Gating and Triggering CT • CARE Filter
(e.g., for support of Varian and Anzai devices) • CARE Bolus CT
• FAST IRS with 50 fps IR, 70 fps FBP • CARE Topo
• CARE Dose4D
Standard workplace
• CARE kV
• syngo® Acquisition Workplace
• CARE Child – Pediatric Protocols
• 19” (48 cm) flat screen monitor
• CARE Profile
• CD/DVD storage
• CARE Dashboard
Optional workplace
• syngo.via
• Additional 19” (48 cm) flat screen monitor
• Dual 19” (48 cm) flat screen monitor with dual
display functionality

6
syngo CT VB20 · SOMATOM Drive

System Configuration

DistinCT Imaging Advanced syngo Security


• Sigma High Power incl. High Power 70 & 80 • IT Security – Whitelisting
and 10 kV steps • syngo Security Package Basic
• Tin Filters • syngo Security Package Advanced
• CARE Contrast III1
Integrated Iterative Reconstruction
DistinCT Reading Advanced Modeled Iterative Reconstruction
• VRT (ADMIRE®)2
• WorkStream4D™ (direct 3D recon)
syngo Legacy 3D tools
• Extended FOV
• syngo Fly Through
DistinCT Reading – Advanced4 • syngo Image Fusion
• iMAR (iterative Metal Artifact Reduction)
Optional applications for CT Intervention
• FAST Spine
• Adapt. 3D Intervent. Suite Wired
• HD FOV Pro (Field of View)
• Adapt. 3D Intervent. Suite Wireless
• z-UHR incl. UHR (z Ultra High Resolution)
• Adaptive 3D Intervention Pro
DistinCT Function – DE
syngo.via
• Dual Energy Scanning with Tin Filter
• Wide range of individual applications
• FAST DE (direct Dual Energy 3D recon)
• CT Cardio-Vascular Engine
• FAST DE Results
• CT Acute Care Engine
DistinCT Function – Dynamic • CT Oncology Engine
• Heart Perfusion Scanning • CT Neuro Engine
• Adaptive 4D Spiral Plus • CT Dual Energy

DistinCT Function – Cardiac Remote tools


• syngo HeartView (incl. Turbo Flash Cardio3, • Expert-i
Cardio Sequence and Adaptive ECG-Pulsing)
• syngo Cardio BestPhase Plus
• syngo Calcium Scoring
• Fast Phase

1
CARE Contrast III supports injectors classes up to CANOpen standard class IV
2
In clinical practice, the use of ADMIRE may reduce CT patient dose depending on the clinical task, patient size, anatomical location, and clinical practice.
A radiologist and a physicist should be consulted to determine the appropriate dose to obtain diagnostic image quality for the particular clinical task.
3
Turbo Flash Cardio is the high pitch spiral mode (formerly called Flash Spiral Cardio). Availability of the mode depends on the system configuration
4
deconfigurable

7
SOMATOM Drive · syngo CT VB20

System Hardware

Gantry

Aperture
78 cm / 30.71”

Distance between gantry front to scan plane


• 35 cm / 13.77”
• The short distance from the gantry front to the
scan plane allows for easy operator access during
interventional procedures

Scan field
• 50 cm / 19.69”
• 78 cm / 30.71”
Generator
Rotation time
0.28, 0.33, 0.5, 1.0 s Max. power
200 kW (2 x 100 kW)
Temporal resolution
75 ms temporal resolution independent of the IEC Requested kV Accuracy
heart rate (down to 37.5 ms using 2-segment ± 10%
reconstruction)
Typical kV Accuracy
Three laser light markers ± 1%
Coronal, sagittal, transversal laser light showing
the isocenter position of the scan plane

Integrated touch panels


Four1 touch panels with anatomical positioning

Ring light
A gantry ring, mood light (LED) in different, preset
and adjustable colors. Create a relaxing atmosphere
for your patients.

Two continuously rotating tube-detector units


with optimized geometry for high-resolution
data acquisition across the entire scan field

1
2 standard, 4 optional

8
syngo CT VB20 · SOMATOM Drive

System Hardware

Tube Assembly System Focal spot size according to IEC 60336


• 0.7 x 0.7/7°
Tube
• 0.9 x 1.1/7°

z-Sharp technology

Straton tube 1 2 Alternating


focal spots 0.6 mm

Over-
sampling

0.6 mm

64-row detector
128-slice acquisition electronics
2 x Straton MX Sigma X-ray tubes and Sigma
generators
The unique Straton X-ray tube utilizes an electron
Tube current range
beam that is accurately and rapidly deflected,
• Single source 20–800 mA
creating two precise focal spots alternating 4,608
• Dual source 40–1600 mA
times per second. This doubles the X-ray projections
High Power 70 reaching each detector element. The two overlapping
650 mA (@ 70 kV) projections result in an oversampling in the z-direction
and allow acquiring twice the number of slices per
High Power 80 detector row. The resulting measurements interleave
750 mA (@ 80 kV) half a detector slice width, doubling the scan
Tube voltage information without a corresponding increase
• 70 –140 kV in 10 kV steps in dose. This provides a scan speed independent of
• Automatically selected through CARE kV based spatial resolution in the z-direction of up to 0.30 mm
on patient body habitus and examination type and a corre­sponding reduction of spiral artifacts in
the daily clinical routine at any position within the
Tube anode heat storage capacity scan field.
0 MHU (0.6 MHU capacity combined with
7.3 MHU/min (5,400 kJ/min) cooling rate is Multifan principle with Flying Focal Spot
comparable to the performance of a conventional Computer-controlled monitoring of anode
tube with approximately 50 MHU (37,000 kJ) temperature
anode heat storage capacity)

Cooling rate
7.3 MHU/min

9
SOMATOM Drive · syngo CT VB20

System Hardware

Adaptive Dose Shield CARE Filter

Permanent filtration (tube housing assembly)


Dose Shield
• Quality equivalent filtration 6.8 mm Al at
145 kV / Tube A and B

Permanent filtration (beam-limiting device)


• 0.3 mm titanium with aluminium 0.5 mm,
quality equivalent filtration 1.6 mm Al at
145 kV / Tube A and B (e.g., cardiac and
pediatric body protocols)

Dose Shield
Additional protocol-dependent filtration
• 0.5 mm Al / Tube A and B
• Tin Filter / Tube A and B

The first dynamic tube collimation that protects the


patient from clinically irrelevant radiation in Spiral CT

10
syngo CT VB20 · SOMATOM Drive

System Hardware

Data Acquisition System HiDynamics


The full electronic integration significantly extends
StellarInfinity Detector
the dynamic bandwidth, thus increasing the image
appearance, especially when high-contrast objects
are in close proximity to low-contrast objects.
HiDynamics is of significant relevance in low kV scans,
e.g., for enhancing the 80 kV dataset of Dual Energy
scans or pediatric imaging at 70 kV.

UFC (Ultra Fast Ceramics) detector

X-ray

Siemens Healthineers’ first fully integrated detector


with TrueSignal and Edge technology. Due to the UFC

full electronic integration of the StellarInfinity detector,


electronic components (microchips, conductors, etc.) Light
are integrated directly at the photo diode. This
reduces electronic noise coming from the detector
elements and thus significantly improves the
signal-to-noise ratio (SNR) for optimized dose Siemens Healthineers’ proprietary scintillator material
efficiency and image quality. with ultra-short decay, extremely low afterglow and
high absorption for optimized image quality and high
TrueSignal technology
dose efficiency
The full electronic integration significantly improves
the SNR, allowing a much better utilization especially Detector Scatter Collimator
of low signals at the detector, e.g., in bariatric For improved low-contrast resolution,
patients or low-dose imaging e.g., in neuro and abdominal imaging
Edge technology Max. number of slices/rotation
• 2 x 128 (acquired slices through z-Sharp technology)
• 2 x 384 (reconstructed slices)

Number of detector rows


2 x 64

Number of electronic detector channels utilized


for up to 2 x 128 slices/rotation acquisition
2 x 128

The full electronic integration of the Stellar detector


elements reduces electronic cross-talk between
neighboring detector rows. This significantly reduces
slice blurring, resulting in a more precise slice
profile. This enables the generation of 0.5 mm slices
delivering a spatial cross-plane resolution of 0.3 mm.

11
SOMATOM Drive · syngo CT VB20

System Hardware

Number of detector elements Spiral acquisition modes


• 77,824 128 x 0.6 mm1, 64 x 0.6 mm1,
• (47,104 system A; 30,720 system B) 40 x 0.6 mm1, 20 x 0.6 mm1,
16 x 0.6 mm (UHR)1,
Number of detector channels/slice
16 x 0.3 mm1 (z-UHR),
• Detector A: 1472
16 x 0.6 mm1, 32 x 1.2 mm,
• Detector B: 960
32 x 0.6 mm
Number of projections
Sequence acquisition modes
Up to 4,608 (1/360°) on each data acquisition unit
128 x 0.6 mm1, 64 x 0.6 mm1,
Dual Source, cardio acquisition modes 16 x 0.6 mm1, 32 x 0.6 mm,
Acquisition of 2 x 128 x 0.6 mm1 with Dual Source 16 x 0.6 mm (UHR), 2 x 1 mm,
single segment reconstruction, resulting in heartrate- 32 x 1.2 mm, 12 x 1.2 mm,
independent temporal resolution of 75 ms; 1 x 5 mm, 1 x 10 mm
down to 37.5 ms using 2-segment reconstruction
Heart Perfusion mode
Dual Source, Turbo Flash modes2 Sequence shuttle mode to dynamically cover up to
Acquisition of 2 x 128 x 0.6 mm1 in Dual Source approximately twice the detector width for myocardial
acquisition mode, for increased scan speed up perfusion studies with sufficient temporal resolution
to 400 mm/s (458 mm/s when ECG-triggered), even for high heart rates
results in temporal resolution of 75 ms
Adaptive Signal Boost
Dual Source, Turbo Flash mode2, The Adaptive Signal Boost amplifies low signal areas
z-coverage/rotation of the CT data and further reduces streaks and noise
130 mm / 5.14” (at pitch 3.4) equals 458 mm/s in the image especially for larger patients
at the fastest rotation speed
Adaptive 4D Spiral Plus mode
Dual Source, dual power acquisition modes • Spiral scan mode for a larger perfusion and dynamic
Acquisition of up to 2 x 128 x 0.6 mm1 with the CTA acquisitions range than the detector width of
parallel utilization of two 100 kW sources, resulting up to 480 mm / 18.89“
in up to 128 slices/rotation with 200 kW of power • Enables 4D CT DSA
reserve
z-UHR (Ultra High Resolution)1
Dual Source Dual Energy acquisition modes1 • Siemens Healthineers’ proprietary z-UHR enables
Acquisition of up to 2 x 128 x 0.6 mm1 with the previously unachievable image detail with an
parallel utilization of two sources with different isotropic resolution of 24 lp/cm (± 10%) at 2% MTF
kV settings and Tin Filter, resulting in improved • The combination of z-Sharp technology and
spectral separation z-UHR offers isotropic detail in the range of
flat-panel or Micro CT technology

1
Acquisition modes driven by z-Sharp technology
2
Turbo Flash Cardio is the high pitch spiral mode (formerly called Flash Spiral Cardio). Availability of the mode depends on the system configuration.

12
syngo CT VB20 · SOMATOM Drive

System Hardware

Patient Table 2,000 mm Optional Multi-purpose Patient Table

Max. table load Max. table load


227 kg / 500 lbs 307 kg2 / 676 lbs2

Table feed speed Turbo Flash mode1 Table feed speed Turbo Flash mode1
Up to 400 mm/s / 15.75 inch/s Up to 400 mm/s / 15.75 inch/s

Table feed speed ECG-triggered Turbo Flash mode1 Table feed speed ECG-triggered Turbo Flash mode1
Up to 458 mm/s / 18.03 inch/s Up to 458 mm/s / 18.03 inch/s

Vertical patient load position Vertical patient load position


490 mm 550 mm

Vertical travel speed Vertical travel speed


20–50 mm/s 20–50 mm/s / 0.79–1.97 inch/s

Scannable range Scannable range


2,000 mm / 78.74” 2,000 mm / 78.74”

Distance between gantry front and table front Distance between gantry front and table front
386 mm / 15.2” 386 mm / 15.20”

Distance between Touch Panel front and Distance between Touch Panel front
table front and table front
348 mm / 13.7” 387 mm / 15.24”

Additional exchangeable
tabletops3
• High-capacity patient and trauma tabletop
• RTP tabletop

Optional Foot Pedals

Four pairs of foot pedals are provided on the bottom


edge of the patient table allowing table lifting and
lowering from various positions

1
Turbo Flash Cardio is the high pitch spiral mode (formerly called Flash Spiral Cardio). Availability of the mode depends on the system configuration.
2
Optional with high-capacity tabletop
3
Not available for standard 2,000 mm patient table

13
SOMATOM Drive · syngo CT VB20

Workplace Overview

syngo Acquisition Workplace (AWP)

The syngo Acquisition Workplace provides an


intelligent and reliable workflow for data acquisition,
image reconstruction, and routine postprocessing
at the CT scanner. Built on the unique syngo platform,
the syngo Acquisition Workplace is intuitive and
user-friendly

Image Reconstruction

Real-time display
Real-time image display (512 x 512) during
spiral acquisition
Raw Data
Slice thickness
0.4, 0.5 , 0.6–20 mm Capacity
(20 mm using dynamic multiscan) 4 TB

Recon field External USB 3.0 ports for quick and easy raw data
• 5–50 cm / 1.97”–16.69” storage are supported
• 5–78 cm / 1.97”–30.71”

Recon time
• Up to 70 fps with weighted filtered 3D
backprojection (WFBP) and z-Sharp technology
at full image quality
• Up to 50 fps1 with integrated Iterative
Reconstruction with z-Sharp technology
at full image quality

Recon matrix
512 x 512

HU scale
– 1,024 to + 3,071

Extended HU scale
– 10,240 to + 30,710

Wide range of freely selectable slice thicknesses


for prospective and/or retrospective reconstruction

1
Optional with FAST IRS

14
syngo CT VB20 · SOMATOM Drive

syngo Workplace
Technical Specifications
Workplace AWP Image storage
• 3 x 1,000 GB (1 TB) physical
High-performance computer
• ~ 2,100,000 images
Quad Core 3.60 GHz1
Additional storage
Graphics accelerator
• DVD DICOM drive:
NVIDIA Quadro K1200 for fast 3D postprocessing
4.7 GB DVD media
Standard monitor 8,000 images
• 19” (48 cm) flat screen • Write-RW/+RW/-DL/Read
• 1,280 x 1,024 resolution • CD-R: 700 MB
• 1,024 x 1,024 image display matrix 1,100 images
• 0.29 mm pixel size • External USB 3.0 ports for quick and easy raw data
storage are supported. External USB memory stick
Additional monitor2 for image data
Yes
DICOM viewer
Dual monitor3 Included on each CD; automatically started on the
Yes viewer’s PC
RAM storage
16 GB

1
Or equivalent
2
Optional. Additional monitor for replication of primary monitor at remote location. Distance from host up to 30 m.
3
Optional. Dual monitor enables the simultaneous display of two scans on two monitors within the 3D task card, ideally used for comparison of follow-up studies
or native and contrast-enhanced scans.

15
SOMATOM Drive · syngo CT VB20

Standard System Software and Applications


syngo Examination
Scan Protocol Assistant Sequence Acquisition

Up to 10,000 protocols can be edited, modified, Reconstructed slice widths


and stored 0.5, 0.6, 0.75, 1.0, 1.2, 1.5, 2.0, 2.4, 3.0, 4.0, 4.8,
5.0, 6.0, 7.0, 7.2, 8.0, 10.0, 14.4, 15.0, 20.0 mm
Easy and intuitive way to change and manage scan
protocols Partial scan times (260°)
0.20, 0.24, 0.36, 0.72 s
Automatic Patient Positioning
No. of uninter­rupted scans per range
Two user-configurable buttons on the gantry panel
100
One-touch, quick patient positioning for preselected
No. of ranges per protocol
clinical protocols – e.g., head, thorax
33
Topogram
Scan times (full scan)
Length 0.28, 0.33, 0.5, 1.0 s
20–2,000 mm / 0.8”–78.7”
Scan cycle time
Scan times (min. scan cycle time depending on rotation time)
2.0–20 s 0.75 s–60 s (± 10%)

Views Scan range


a.p., p.a., lateral max. 2,000 mm / 78.74”

Real-time topogram Acquisition with or without table feed

Tin Filter topograms available with license Automatic clustering of scans

Manual interruption possible once desired anatomy Dynamic Multiscan


has been imaged Multiple (continuous) sequence scanning without
table movement for fast dynamic contrast studies
Patient Communication with maximum coverage of 38.4 mm
Integrated patient intercom

Automatic Patient Instruction (API)


• Freely recordable
• 30 API text pairs
• Presets in nine languages available

16
syngo CT VB20 · SOMATOM Drive

Standard System Software and Applications


syngo Examination
Multislice Spiral Acquisition Patient Registration

Reconstructed slice widths Direct input of patient information on the Acquisition


0.42, 0.5, 0.6, 0.75, 1.0, 1.5, Workplace immediately prior to scan
2.0, 3.0, 4.0, 5.0, 6.0, 7.0, 8.0, 10.0 mm
Pre-registration of patients at any time prior to scan
Temporal resolution
Special emergency patient registration
• 75 ms, 88 ms, 134 ms, 268 ms
(allows examination without entering patient
• up to 37.5 ms with bi-segment reconstruction
data before scanning)
(with syngo HeartView CT1)
Transfer of patient information from HIS/RIS via
Scan times full scan (360°)
DICOM Get Worklist
0.28, 0.33, 0.5, 1.0 s
Transfer of examination information from scanner into
Slice increment
HIS/RIS via MPPS (Modality Performed Procedure Step)
0.1–10 mm
Auto Field of View Adaption
Pitch factor
• 0.35–3.2 up to 3.4 When positioning the scan range, the width of the
(ECG-triggered Turbo Flash mode3) range is automatically adapted to cover the whole
• Down to 0.3 (z-UHR)2 body of the patient
• Down to 0.17 (syngo HeartView)
• Down to 0.09 (Respiratory Gating and Triggering CT)1 CINE Display

Spiral scan time Display of image sequences


max. 80 s Automatic or interactive with mouse control
Scan length Max. image rate: 30 frames/s
Max. 1,840 mm / 77.44”
Neuro BestContrast
No. of ranges per protocol
33 Achieves a significant increase in contrast without an
increase in noise or dose for better gray-white matter
Automatic clustering of scans differentiation
Optimized special reconstruction algorithm e-Logbook
(PFO: Posterior Fossa Optimization) for reduction
of beam-hardening artifacts in head images Tool to collect patient information for statistics,
documen­tation, and research
WorkStream4D • View
4D workflow with direct generation of axial, sagittal, • Archive
coronal, or double-oblique images from standard • Print
scanning protocols • Export

Elimination of manual reconstruction steps syngo Dynamic Evaluation

Reduction of data volume, since virtually all Evaluation of contrast enhancement in organs
diagnostic information is captured in 3D slices and tissues

Calculation of
• Time-density curves (up to 5 ROIs)
• Peak-enhancement images
• Time-to-peak images
1
Optional
2
Deconfigurable
3
Turbo Flash Cardio is the high pitch spiral mode (formerly called Flash Spiral Cardio). Availability of the mode depends on the system configuration.

17
SOMATOM Drive · syngo CT VB20

Standard System Software and Applications


syngo Viewing, syngo Filming and syngo Archiving & Networking
Windowing Evaluation Tools

Window width and center freely selectable Parallel evaluation of more than
10 Regions of Interest
Single window
• Circle
Double window (e.g., bone/soft tissue) • Irregular
• Polygonal
Multiple window settings for multi-image display
Statistical evaluation
Organ-specific window settings, e.g., for soft tissue • Area/volume
and bones • Standard deviation
2D Postprocessing • Mean value
• Min./max. values
Image zoom and pan • Histogram
Image manipulations Profile cuts
• Averaging, subtraction • Horizontal
• Reversal of grayscale values • Vertical
• Mirroring • Oblique
Advanced image algorithms Distance measurement
• LCE: Low Contrast Enhancement for improving
low-contrast detectability Angle measurement
• HCE: High Contrast Enhancement for increased Online measurement of a 5 x 5 pixel size RoI
sharpness of high-contrast structures
• ASA: Advanced Smoothing Algorithm Freely selectable positioning of coordinate system
edge-preserving smoothing filter, dedicated
Crosshair
to cardiac exams
Image annotation and labeling

18
syngo CT VB20 · SOMATOM Drive

Standard System Software and Applications


syngo Viewing, syngo Filming and syngo Archiving & Networking
Filming IT Security
• Digital film documentation, connection Functionalities enabling SOMATOM Drive
to a suitable digital camera users to confront the primary IT risk factors,
• Connection via DICOM basic print including unauthorized access to protected
• Automatic filming health information or manipulation of the system.
• Interactive virtual film sheet
Network connection
• Customizable film formats with up to 64 images
Network communication is restricted to the clinically
• Filming in parallel with other activities
relevant DICOM nodes (for example, PACS and RIS).
• Independent scanning and documentation
• Freely selectable positioning of images Whitelisting (Microsoft Device Guard)
onto film sheet Marks all executable files to be used on the scanner
• Configurable image text and auto­matically prevents non approved executables
from being started.
Printing
Documentation on PostScript printer supported Malware protection (Microsoft EMET)
• Prevents software vulnerabilities from being
Video Capture and Editing Tool
exploited by termi­nating, blocking or otherwise
Integrated solution for imaging and visualization of
invalidating actions which might compromise
4D infor­mation, allowing the generation and editing
the scanner.
of video files for improved diagnoses, recording,
• Security patches will be provided on regular basis1
and teaching. A wide range of multimedia formats
to maintain the clinical function of the medical
are supported, e.g., AVI, Flash (SWF), GIF, QuickTime
device. Updates will be pushed via Smart Remote
(MOV), streaming video
Services (SRS) and have to be confirmed/executed
Image Transfer/Networking by the on-site user.2
Interface for transfer of medical images and
information using the DICOM standard. Facilitates
communication with devices from different
manufacturers
• DICOM Storage (Send/Receive)
• DICOM Query/Retrieve
• DICOM Basic Print
• DICOM Get Worklist (HIS/RIS)
• DICOM MPPS (Modality Performed Procedure Step)
• DICOM Storage Commitment
• DICOM Viewer on CD

1
Most recent scanner software has to be installed
2
If the security patch needs to be installed on site by Siemens Healthineers charges may result. Service conditions apply

19
SOMATOM Drive · syngo CT VB20

Optional System Soft­ Remote Tools


ware and Applications
teamplay syngo Virtual Cockpit4

syngo Virtual Cockpit4 is designed to assist scan


procedures – from a distance. Expert colleagues
receive access to the scanner and can support less-
experienced technologist – ensuring reproducible
results across your entire CT system fleet.

SOMATOM Drive with VB20 is ready for syngo


Virtual Cockpit.

For more information and experiences please visit:


https://www.healthcare.siemens.com/medical-
imaging-it/imaging-acquisition-solutions/syngo-
virtual-cockpit

teamplay is a cloud-based network that brings syngo Expert-i


together healthcare professionals in order to advance
Enables the physician to interact with the syngo CT
medicine and human health as a team effort. From
Workplace from virtually anywhere in your hospital
devices and protocols to partici­pating team members,
it provides precise starting points for enhancing
efficiency, competitiveness and quality of care.

teamplay Dose enables access to all dose related events


across the entire institution. Monitor applied radiation
levels to find the correct balance between image quality
and dose level. teamplay Dose helps enforcing dose
related quality assurance measures.

teamplay Usage helps to isolate workflow inefficiencies


and allows the user to explore the departments
productivity and efficiency. Identify the institution’s
scanner utilization by analyzing performed procedure
types, examined body regions or patient throughput.

teamplay Protocols1 enables the analysis of dose


reduction measures by comparing the applied radiation
of different protocol versions. Identify best-practice
protocols by comparing protocol parameters and dose
levels. Furthermore teamplay Protocols allows the
adaption2 and distribution of protocols remotely to
compatible scanners across the institution’s network.

teamplay Images Research3 allows the user to share and


comment imaging studies within the institution and
cross-institutional for research and education purposes.

SOMATOM Drive is ready for teamplay.


For more information and experiences please visit:
siemens.com/teamplay
1
teamplay Protocols supports selected Siemens Healthineers scanners. Please contact your Siemens representative for more details.
2
syngo Expert-i required
3
teamplay Images Research application is not intended for diagnostic use.
4
syngo Virtual Cockpit is not commercially available yet in all countries. Its future availability cannot be guaranteed.

20
syngo CT VB20 · SOMATOM Drive

DistinCT Imaging

FAST Adjust CARE Topo

Real-time topogram

Manual interruption possible once desired anatomy


has been imaged

CARE Dose4D

Scan with
constant mA

Reduced
dose level
based
on topogram
Direct scan param­eter adjustment at the push
of a button Real-time
angular dose
FAST Scan Assistant modulation

• Automated real-time tube current adjust­ment for


optimum diagnostic image quality at lowest possible
dose, depending on patient size and anatomy
• Fully automated dose management for
adults and children

CARE kV

Easy and intuitive scan parameter setting

CARE Filter

Specially designed X-ray exposure filters installed


at the tube and the collimator for protocol-specific
optimization of patient dose and image quality

CARE Bolus CT First automated, organ-sensitive voltage setting to


optimize contrast-to-noise ratio and reduce dose in
Scan mode for contrast bolus-triggered data
relation to the size of the patient
acquisition

Significant improvement of the planning procedure


by enabling an optimum spiral scan start after
contrast injection

The procedure is based on repetitive low dose


moni­toring scans at one slice level and analysis of
the time density curve in an ROI (Region of Interest)

21
SOMATOM Drive · syngo CT VB20

DistinCT Imaging

CARE Child – Pediatric Protocols CARE Dashboard

• Dedicated pediatric CT imaging, including 70 kV Visualization of activated dose reduction features and
scan modes and specific CARE Dose4D curves technologies for each scan range of an examination
and protocols
• Special clinical protocols with 70 or 80 kV X-CARE
selection and a wide range of mAs settings. Angular tube current modulation to reduce X-ray
The X-ray exposure is adapted to the child’s exposure (organ dose) of peripheral dose-sensitive
(and small adult’s) weight and age, substantially body regions, e.g., the breasts, thyroid gland or
reducing the effective patient dose eye lens

CARE Profile SureView

Pitch-independent image quality

Excellent for clinical workflow: Forget about


compro­mises in your clinical workflow. Just specify
the slice thickness in your protocols according to
Visualization of the dose distribution along the
your clinical needs. SureView automatically takes
topogram prior to the scan
care of providing excellent volume image quality –
with exceptional performance.

Multiply your clinical performance with SureView:


High-quality imaging at any scanning speed. SureView
allows the CT scanner to automatically select the
necessary pitch value to achieve the coverage and
scan time defined by you, while keeping selected
slice thickness and image quality

Includes advanced cone beam reconstruction


algorithms for elimination of cone beam artifacts
with 2 x 128-slice acquisition
22
syngo CT VB20 · SOMATOM Drive

DistinCT Imaging – DistinCT Reading –


Advanced1 Advanced1
CARE Contrast FAST Spine

SYNC.
START

Synchronized scanning and contrast injection through Accurate and auto­matically aligned preparation of
integration of CT scanner and injector facilitate spine recons with just a single click
enhanced CT examinations and improved workflow
iMAR (iterative Metal Artifact Reduction)

Input Image iMAR Image

Detail recovery Strong metal artifacts


removal method in areas
with severe artifacts

Soft metal artifacts removal


method in areas with less
Adaptive severe artifacts
Sinogram Mixing

Reduces metal artifacts in various body regions

Advanced metal artifact reduction with a combination


of beam hardening correction, normalized sinogram
inpainting, and frequency split

Adaptive Sinogram Mixing with iteratively refined


process for normalized sinogram inpainting and
mixing steps

Compatible with extended FOV, extended CT scale


and dose reduction features

Simple user interface

Requires the FAST IRS option

HD FOV Pro (Field of View)2

Designed to enable visualization of the human body


parts and skin line located outside of the 50 cm
1
Optional
2
The image quality for the area outside the 50 cm standard scan field of view
standard scan field of view up to the bore size,
does not meet the image quality of the area inside the 50 cm standard scan based on the algo­rithmic comple­ment of missing
field of view. Image artefacts may appear, depending on the patient setup detector data outside of the 50 cm standard scan FOV
and anatomy scanned.

23
SOMATOM Drive · syngo CT VB20

DistinCT Function – DistinCT Function –


Dynamic1 DE1
Adaptive 4D Spiral Plus FAST DE

Easy and intuitive direct 3D-­reconstruc­tion of acquired


Dual Energy data, such as with WorkStream4D

FAST DE Results1

Facilitates volume perfusion studies in head and


body applications for a perfusion range of up to
14 cm / 5.51”

Continuously repeated bi-directional table movement


Automatically gen­erates Dual Energy datasets on the
during spiral acquisition enables an extended range
AWP and the results are sent directly to the reading
for 4D information
environment for a straightforward Dual Energy
Facilitates dynamic studies up to a scan range of workflow
48.0 cm / 18.9”

1
Optional

24
syngo CT VB20 · SOMATOM Drive

DistinCT Function –
Cardiac1
syngo HeartView CT FAST Phase

syngo HeartView CT with ECG-synchronized true Intuitive solution fully integrated in the cardiac
isotro­pic volume acquisition using prospective work­flow for helping to quickly set up complex and
ECG-triggered or retrospective ECG-gating mode usually time-consuming cardiac procedures reliably
and repeatedly. By measuring of heart rate and
Basis for 3D cardiac scanning and reconstruction,
rhythm the system automatically chooses the most
e.g., CT angiography of the coronary and thoracic
appropriate phase of the heart cycle to scan and
vessels or calcium scoring
later to reconstruct based on fully configurable and
The ECG signal used for gating the CT images is customizable look up tables.
acquired by an integrated ECG device. The ECG signal
Reduction of complexity and standardization of
is displayed on the gantry front cover and the scan
cardiac acquisitions by making them more robust
interface
and less user-dependent
Dual Source acquisition mode with single-segment
syngo Cardio BestPhase Plus
recon­struction enables heart-rate-independent
temporal resolution of 75 ms (factor 2 x higher than Provides a proposal for the heart phase and 3D VRT
single-source acquisition with same parameters) visualization of the heart in several user-selectable
heart phases to help the physician choose the
Down to 37.5 ms temporal resolution combining
desired heart phase for image reconstruction
syngo HeartView acquisition with robust 2-segment
reconstruction (except Turbo Flash mode1)

Ultra-fast Turbo Flash mode2 Cardio scanning allows


for maximum dose saving

ECG-synchronized Cardio Sequence for dose-efficient


but versatile low-dose cardiac imaging, including high
heart rates and functional evaluation

Quality control tools enable retrospective ECG viewing


and interaction as well as computer-assisted heart
phase definition

Automatic detection of irregular heartbeats with


intuitive ECG editing functionality

1
Optional
2
Turbo Flash Cardio is the high pitch spiral mode (formerly called Flash Spiral Cardio). Availability of the mode depends on the system configuration.

25
SOMATOM Drive · syngo CT VB20

Optional FAST Applications


FAST Integrated Workflow
World’s first 3D Camera integrated in a CT FAST 3D Camera
positioning workflow is available as an option
and allows automatic patient positioning in
the examination room.

The FAST 3D Camera captures the patient’s shape,


position, and height in three dimensions. Using
infrared measurement, it even recognizes body
contours: for example, when people are wearing
masking clothes or blankets.

Specialized applications support accurate and


reproducible positioning:
• FAST Isocentering, at the push of a button, The 3D Camera is used to get data of the patient
provides the correct isocenter position, enabling structure in three dimensions and is equipped with
the right dose modulation and consistent images. an infrared light source and sensor as well as an
• FAST Range supports scanning the correct RGB camera.
body region in the topogram with no cut-off –
The 3D Camera system is positioned above the patient
by aligning the automatically identified anatomical
table and in front of the gantry.
position with the protocol.
• FAST Direction helps safeguard the right scan A live image of the patient is displayed on the Touch
direction of the topogram, which is crucial when Panel preparation screen and a planning image can
moving the table with infused patients. be taken and displayed.
• FAST Topo – enables faster scan speeds in topograms,
The FAST 3D Camera captures the patient’s shape,
which prevents breath-hold artifacts. It also has the
position, and height in three dimensions.
potential to decrease the topogram dose.
• FAST Planning – assists the scan and reconstruction Using infrared measurement, it even recognizes
planning, based on a topogram, to provide an easier, body contours: for example, when people are
faster and standardized workflow in CT scanning. wearing masking clothes or blankets.
• FAST 3D Align – automatically corrects misalignment
of anatomic structures, organs of the patient. Algorithms use the measured data to calculate
It aligns those to fit it to the selected reconstruction • The body regions in z-direction
plane for a highly automated reconstruction • The patient’s direction – “head-first versus feet-first”
workflow. Additionally it minimizes the black as well as “prone or supine”
area in the image through automatically adjusts • The table height and patient thickness
recon field of view selection.

1
Optional

26
syngo CT VB20 · SOMATOM Drive

Optional FAST Applications


Advanced Applications
Touch Panels FAST Topo

Enables faster scan speeds in topograms, which


prevents breath-hold artifacts. It also has the potential
to decrease the topogram dose.

FAST Planning

The future of patient positioning is at the touch


of a button. Improve your workflow and get closer
to the patient with our highly integrated Touch
Panels:
• Move away from plain push button interaction
with your scanner and patients
• Scan Selection and ECG monitoring on patient level Assists the scan and reconstruction planning,
• Simple user interface for ease of use based on a topogram, to provide an easier, faster and
• Touch Panels interface provides unique growth standardized workflow in CT scanning. FAST Planning
potential incl. video coupling1 features the selection of the anatomical region of
• Rear panel1 for greater patient interaction interest from a list prospectively defined scan and
• Sleek modern feel with reduced obsolescence reconstruction ranges, automatic detection of
the scan region(s) of interest and proposal of
corresponding scan range(s) in the topogram
(in a narrow or wide lateral FOV), optimized FOV
and automatic iso-center adap­tation for Head scans.

FAST 3D Align

Automatically corrects misalignment of anatomic


structures, organs of the patient. It aligns those to
fit it to the selected reconstruction plane for a highly
automated reconstruction workflow. Additionally
it minimizes the black area in the image through
automatically adjusts recon field of view selection.
Works in combination with WorkStream4D.
1
Optional

27
SOMATOM Drive · syngo CT VB20

syngo Security Integrated Iterative


Reconstruction
syngo System Security Advanced Modeled Iterative Reconstruction
(ADMIRE)1
syngo System Security provides IT security
functionalities to safeguard your SOMATOM Drive
ADMIRE FBP
against external threats. Raw data statistical
modeling

User management Artifact cancellation


Model-based noise
cancellation
Defines individual user accounts and passwords to
protect scanner access. Master
3D Validation
Current
image
volume
Raw data Final image
Password strength
(Advanced)
Enables the creation of strong user passwords in system modeling
Cancellation Cancellation

compliance with the institution’s password policy.

Artifacts

Noise
FBP

Audit trail
Enables the evaluation of who has conducted or
altered studies, for example deleting parts of exam In modern healthcare, patients deserve the lowest
studies. possible dose, and radiologists desire the best image
quality in their daily routine. This is known as ALARA –
Groups and role the paradigm to deliver diagnostic image quality at
Supports the creation of individual user privileges a dose As Low As Reasonably Achievable. But the big
and restricts scanner usage according to institution’s challenge is to realize this in the daily routine, e.g.,
defined users. time-critical settings like acute care, making many
institutions step away from iterative reconstruction.
Patient groups
Enables the creation of specific patient groups to ADMIRE – Siemens Healthineers’ Advanced Modeled
protect sensitive patient information (e.g. data Iterative Reconstruction – can reduce patient dose,
of VIP patients). and images will benefit from a higher resolution at
organ borders and improved delineation of edges,
Trusted nodes
e.g., to better localize lesions. Moreover, ADMIRE
Reduces the risk of data manipulation by
smoothly integrates iterative reconstruction into the
authenticating predefined secure medical devices in
daily routine. Thick slices are now reconstructed with
the institution’s network (for example, PACS servers).
an improved image impression, even from ultra-low
dose scans. With this, iteratively reconstructed low-
dose datasets can now easily be stored in PACS or
on film. Therefore, ADMIRE sets a new benchmark in
iterative reconstruction instead of limiting its potential
in the clinical routine.

1
In clinical practice, the use of ADMIRE may reduce CT patient dose depending on the clinical task, patient size, anatomical location, and clinical practice.
A radiologist and a physicist should be consulted to determine the appropriate dose to obtain diagnostic image quality for the particular clinical task.

28
syngo CT VB20 · SOMATOM Drive

syngo Legacy Optional Applications


3D Tools for CT Intervention
syngo Fly Through Adaptive 3D Intervention Pro

Virtual Endoscopy software enabling visualization of Spiral and sequential non-fluoroscopic interventional
vessels, airways, and the intestines procedures

syngo Image Fusion i-Sequence biopsy mode with user-configurable dose


and windowing display
Image Fusion is used for spatial alignment and
visuali­zation of image data of one patient where i-Spiral mode for complete organ coverage
image data has been generated at different points
Switching scan modes on the fly during intervention
in time or by different modalities
with one single click

Up to 8 image displays for better navigation in the


volume

Layout Editor with user-configurable screen layouts

Interventional Toolbar with measurement tools and


automatic table positioning via buttons or joystick
with auto-stop function

Switch between continuous and incremental table


movement with user-configurable increments

i-Precision view: increases or decreases the predefined


mAs value

HandCARE for i-Sequence: Real-time dose modulation


during the CT-guided intervention
avoids direct X-ray irradiation of the radiologist’s hand

Adaptive 3D Intervention Suite (Wired or Wireless)

Complete solution for non-fluoroscopic and


fluoro­scopic minimally invasive 3D volume
interventions. Includes Adaptive 3D Intervention,
Intervention Pro, i-Fluoro, i-Control (wireless or cable),
footswitch.

Near to real-time coronal, sagittal, and oblique image


guidance

3D Layout Editor: user-configurable screen layouts


in 3D

Display of coronal, axial, and sagittal MPRs and VRT

Interventional Toolbar with path planning tools such


as Auto Needle Detection

29
SOMATOM Drive · syngo CT VB20

Image Quality

Low-contrast Detectability Spatial Resolution (Standard)

Phantom x/y-plane
CATPHAN (20 cm) 2% MTF 16.4 lp/cm (± 10%)
10% MTF 14.0 lp/cm (± 10%)
Object size
50% MTF 11.4 lp/cm (± 10%)
5 mm
Technique
Contrast difference
Wire phantom
3 HU
Acquisition: 12 x 1.2 mm, 120 kV,
CTDIvol (32 cm) 320 mAs, 1.0 s, Kernel H70h
8.0 mGy at 120 eff. mAs
z-direction
Technique 2% MTF 16.9 lp/cm (± 10%)
10 mm slice, 120 kV (spiral body mode), IR 10% MTF 13.1 lp/cm (± 10%)
50% MTF 6.0 lp/cm (± 10%)
Spatial Resolution (UHR)
Technique
Isotropic spatial resolution in all three planes 128 x 0.6 mm, gold platelet, IR strength 5, 0.5 mm slice
(x, y, and z)
Homogeneity
x/y-plane
2% MTF 24.0 lp/cm (± 10%) Cross-field uniformity in a typical mode,
10% MTF 23.3 lp/cm (± 10%) 20 cm water phantom centered
50% MTF 18.7 lp/cm (± 10%) Max. ± 4 HU
Typ. ± 2 HU
Technique
Wire phantom
Acquisition: 16 x 0.6 mm, Kernel U95u

z-direction1
2% MTF 24.3 lp/cm (± 10%)
10% MTF 17.5 lp/cm (± 10%)
50% MTF 6.5 lp/cm (± 10%)

Technique
Gold platelet phantom
Acquisition: 16 x 0.3 mm, slice width 0.4 mm

1
Optional

30
syngo CT VB20 · SOMATOM Drive

Image Quality

Phantom Validation of z-Sharp Technology Phantom Validation of z-UHR1

CATPHAN measure­ment CATPHAN measurement


Demonstrates routine cross-plane resolution Results in isotropic resolution of 0.24 mm in all
of 0.33 mm three planes (x, y, and z)
• 0.33 mm x 0.33 mm x 0.33 mm • 0.24 mm x 0.24 mm x 0.24 mm
(x times y times z direction) • For ultra-high resolution bone imaging
• 0.30 mm High Resolution in z-direction with • Isotropic detail in the range of flat-panel or
Edge technology Micro CT technology
• in daily clinical routine • 0.3 mm collimation
• with variable pitch values

Pitch 0.55 0.6 1.0 1.5

z-axis

0.28 mm

0.29 mm

0.31 mm

0.33 mm

0.36 mm

Pitch 1.0 1.0


Center 100 mm off-center

z-axis

0.33 mm

0.36 mm

0.38 mm

0.42 mm

1
Optional with z-UHR

31
SOMATOM Drive · syngo CT VB20

Installation

Dimensions Height Width Length Weight


(mm / inch) (mm / inch) (mm / inch) (kg / lbs)

Components

Gantry, including water/ ≤ 1,990 / 78.3 ≤ 2,400 / 94.5 ≤ 1,300 / 51.2 ≤ 2,300 / 5,071
water cooling system

Patient table ≤ 850 / 33.5 ≤ 800 / 31.5 ≤ 2,480 / 97.6 ≤ 500 / 1,102

Multi-purpose table 1
≤ 1,000 / 39.4 ≤ 800 / 31.5 ≤ 2,480 / 97.6 ≤ 600 / 1,323

Operator’s console desk1 ≤ 720 / 28.3 ≤ 800 / 31.5 ≤ 1,200 / 47.2 ≤ 35 / 77

Power cabinet ≤ 1,960 / 77.2 ≤ 900 / 35.4 ≤ 700 / 27.6 ≤ 600 / 1,323

Water/air cooling system2


Indoor unit ≤ 1,960 / 77.2 ≤ 1,005 / 39.6 ≤ 710 / 28.0 ≤ 413 / 911
Outdoor unit ≤ 1,150 / 45.3 ≤ 1,150 / 45.3 ≤ 2,600 / 102.4 ≤ 185 / 408

Image Recon. System ≤ 550 / 21.7 ≤ 505 / 18.9 ≤ 765 / 30.1 ≤ 100 / 220

syngo Workplaces

syngo Acquisition Workplace ≤ 470 / 18.5 ≤ 250 / 9.8 ≤ 750 / 29.5 ≤ 30 / 66

syngo RR4D1 ≤ 368 / 14.5 ≤ 175 / 6.9 ≤ 475 / 18.7 ≤ 21 / 46

syngo.via1

syngo.via1 ≤ 379 / 14.9 ≤ 188 / 7.4 ≤ 492 / 19.4 ≤ 16 / 35


(server-based workstation)

1
Optional
2
Optional split cooling available

32
syngo CT VB20 · SOMATOM Drive

Installation

Power Supply Protection Against Input Power Instability

Nominal voltage 3/N~ Gantry with X-ray


380–480 V in 20 V steps ≤ 10 ms

Nominal line frequency Gantry without X-ray


50; 60 Hz ≤ 20 ms

Line impedance Image Reconstruction


80–125 mOhm dependent on voltage ≤ 180 s

Nominal power connection system2 System, syngo Acquisition Workplace,


150 + 135 kVA syngo CT Workplace
(water/water cooling) with UPS standard

Nominal power connection water/air split cooling Disabling of Dual Source mode for single-source
system1/2 acquisition
16 kVA
Electromagnetic Compatibility
Power Consumption
This product is in compliance with IEC 60601-1-2
Computer on and fulfills CISPR 11 Class A
3.0 kVA
Fluctuation
System on standby
Nominal voltage
6.0 kVA
+ 10 / –10%
System scanning
Nominal frequency
285 kVA
± 2 Hz
Water/air cooling when system scanning1
Electromagnetic Compatibility
295 kVA
This product is in compliance with IEC 60601-1-2
Water/air cooling on standby1
and fulfils CISPR 11 Class A
16 kVA
Emissions class according to IEC 601-1-2

1
Optional
2
Power consumption – Note: If pretransformer needed, at least 10% more power

33
SOMATOM Drive · syngo CT VB20

Installation

Cooling

Heat dissipation to cooling environment


(using standard water/water cooling system)
max. 15 kW

Heat dissipation to air cooling environment


(using optional water/air split cooling system)
max. 15 kW

Heat dissipation computing periphery only


max. 2.5 kW

Average gantry heat dissipation to air


max. 1 kW

Room Environment

Temperature range
18–28 °C

Max. temperature gradient


6 K/h

Relative air humidity without condensation


20–75%

Minimal Surface Area for Installation

Power supply installation space


• (1.71 m x 2.12 m) 3.6 m²
• (5.6 ft x 6.95 ft) 38.9 ft²

Control room size


• (1.50 m x 1.20 m) 1.8 m²
• (4.90 ft x 3.90 ft) 19.1 ft²

Scan room size


• (5.68 m x 3.11 m) 17.7 m²
• (18.64 ft x 10.20 ft) 190.2 ft²

34
International version.
Not for distribution or use in the U.S.

On account of certain regional limitations of sales rights Note: Any technical data contained in this document
and service availability, we cannot guarantee that all may vary within defined tolerances. Original images
products included in this brochure are available through always lose a certain amount of detail when reproduced.
the Siemens Healthineers sales organization worldwide.
The statements by Siemens Healthineers’ customers
Availability and packaging may vary by country and is
described herein are based on results that were achieved
subject to change without prior notice. Some/All of the
in the customers’ unique setting. Since there is no
features and products described herein may not be
“typical” hospital and many variables exist (e.g. hospital
available in the United States.
size, case mix, level of IT adoption) there can be no
The information in this document contains general guarantee that other customers will achieve the same
technical descriptions of specifications and options as results.
well as standard and optional features which do not
always have to be present in individual cases.

Siemens Healthineers reserves the right to modify the


design, packaging, specifications and options described
herein without prior notice. Please contact your local
Siemens Healthineers sales representative for the most
current information.

Siemens Healthineers Headquarters Legal Manufacturer


Siemens Healthcare GmbH Siemens Healthcare GmbH
Henkestr. 127 Henkestr. 127
91052 Erlangen, Germany 91052 Erlangen
Phone: +49 9131 84-0 Germany
siemens-healthineers.com

Published by Siemens Healthcare GmbH · Order No. CT-09591-28T2-7600 · Printed in Germany · 8510 1020 · © Siemens Healthcare GmbH, 2020