GENERAL NOTES & SPECIFICATIONS

SCHEDULE OF LOADS
LIGHTING AND POWER PANEL - LP PANEL
CIRCUIT CIRCUIT BREAKERS
NO. LOAD DESCRIPTION VOLTS VA AMPERES CONDUCTORS (mm2) CONDUIT Φ (mm)
AT AF POLE
1 LIGHTING RECEPTACLE: 10-36W 230 360 1.55 20 50 2P 2-3.5mm2. THHN; +1- 3.5 mm2. GW THHN 20 mmΦ
2 2 20 mmΦ
2 LIGHTING RECEPTACLE: 8-36W 230 288 1.25 20 50 2P 2-3.5mm . THHN; +1- 3.5 mm . GW THHN
3 CONVENIENCE OUTLET: 6-180VA 230 1080 4.69 20 50 2P 2-3.5mm2. THHN; +1- 3.5 mm2. GW THHN 20 mmΦ
4 CONVENIENCE OUTLET: 4-180VA 230 720 3.13 20 50 2P 2-3.5mm2. THHN; +1- 3.5 mm2. GW THHN 20 mmΦ
2 2 20 mmΦ
5 CONVENIENCE OUTLET: 5-180VA 230 900 3.91 20 50 2P 2-3.5mm . THHN; +1- 3.5 mm . GW THHN
2 2 20 mmΦ
6 CONVENIENCE OUTLET: 5-180VA 230 900 3.91 20 50 2P 2-3.5mm . THHN; +1- 3.5 mm . GW THHN
7 ACU - 0.5 HP 230 1127 4.90 20 50 2P 2-3.5mm2. THHN; +1- 3.5 mm2. GW THHN 20 mmΦ
8 ACU - 0.5 HP 230 1127 4.90 20 50 2P 2-3.5mm2. THHN; +1- 3.5 mm2. GW THHN 20 mmΦ
9 ACU - 0.5 HP 230 1127 4.90 20 50 2P 2-3.5mm2. THHN; +1- 3.5 mm2. GW THHN 20 mmΦ
10 SPARE 230 - - 20 50 2P ----------------------------------------------------- --------------------
TOTAL SEE DESIGN ANAYSIS - - ----------------------------------------------------- --------------------

DESIGN ANALYSIS/ LOAD COMPUTATION: * SIZE OF SERVICE CONDUCTOR:


= IFL X 1.25
· MOTOR LOADS (AIR-CONDITIONING UNITS) = 22.19 X 1.25
- 3 UNITS - ACU, 0.5 HP, 1ɸ 230V @ 4.9 FLC - - - - - - - - - - - - - - - - - - - - - 3,381 VA = 27.74 AMP

· OTHER LOADS: THEREFORE,


- LIGHTING & CONVENIENCE RECEPTACLE LOAD @100% D.F:
30.015 m2 X 2 X 24VA/m2 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1,440.72 VA SIZE OF SERVICE CONDUCTOR:
SUB - TOTAL - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4,821.72 VA
2 - 8.0mm2 THHN WIRE + 1 - 5.5mm2 THHN G.W
APPLICATION OF DEMAND FACTORS: in 25mm ɸ RIGID STEEL CONDUIT (RSC)
FIRST 10,000 VA @ 100% D.F - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4,821.72 VA
TOTAL NET COMPUTED VA - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4,821.72 VA SIZE OF OVERCURRENT PROTECTION:

TOTAL FULL LOAD CURRENT (IFL) = TOTAL NET COMPUTED VA + HIGHEST HP CURRENT(0.25) USE: 40AT, 1ɸ, 2P, 230V, 60HZ
PHASE VOLTAGE

TOTAL FULL LOAD CURRENT (IFL) = 4,821.72 VA + 17(0.25) = 22.19 AMP


230V

2 -8.0m²THHN
230 V , 1ɸ +1-5.5 mm² GW THHN
L-L Source, 60 Hz
2 -14mm²THHN
in 25 mm Ø RSC +1-8.0 mm² GW THHN
in 25 mm Ø RSC
L1
L2 M
GW

LEGEND: 40AT

20AT 20AT
SYMBOL DESCRIPTION 1 2
LIGHTING RECEPTACLE - 36W ECB in NEMA-4X 20AT 20AT
SX ONE GANG SWITCH - SPST 40AT, 1Ø, 2P 3 4
SXX TWO GANG SWITCH - SPST 230V, 60Hz 20AT 20AT
SXXX THREE GANG SWITCH - SPST 5 6 PANELBOARD
S3We' THREE WAY SWITCH 20AT 20AT in NEMA-1
SINGLE CONVENIENCE OUTLET 7 8 ENCLOSURE
20AT 20AT
DUPLEX CONVENIENCE OUTLET
9 10
DUPLEX CONVENIENCE OUTLET (GFCI)
GFCI 20AT 20AT

LOCATION MAP
WP WEATHERPROOF DUPLEX C.O
GB
LIGHTING & POWER PANEL BOARD
CONDUIT RUN
LP
1 CIRCUIT HOME RUN NO. SINGLE LINE DIAGRAM

ENGINEER : PTR No. : PREPARED BY : KATHRINA L. MORELOS, REE, RME OWNER : PROJECT TITLE : REVISION : SHEET CONTENTS : SHEET NO. :

PLACE : DRAWN BY : ARJUNA G. CHUA, REE, RME CARMENCITA IYANA SASAPAN GENERAL NOTES & SPECIFICATIONS, LEGEND
OWNER REPRESENTATIVE
CHECKED BY : ADDRESS :
PROPOSED 2 STOREY RESIDENCE
HENROD AMANTILLO, RME
SCHEDULE OF LOADS
DESIGN ANALYSIS
EE
DATE :

PRC No. : TIN No. : DATE :


BLK C, LOT 37, IRAYA ST. PH.5, ACM WOODSTOCK
HOMES , ALAPAN I-A, IMUS, CAVITE
OWNER SINGLE LINE DIAGRAM
LOCATION MAP 1 3
4.14 4.14
1.17 2.97 2.16

CABINET
REF

T&B a a
1.80 d 1.80 a'
Se

b'
2.88
Sa'
Sabc LP b
S3We' Se 1 S3We' Sb'

3 e 3 e'
4 2 1 4 2 1 LP
2
5 5
6 c 6
7 7
8 e 8 e'
SHOWER
7.25 9 Sc' c' AREA 1.35
4.05 4.05 10
11
12
c
13
Sd'
14 e'
f
15

Sfg
Sg'
d' 3.11
g'
g g BALCONY
MASTER'S
BEDROOM
1.31 1.31
WARDROBE
CABINET

1.53 2.52

ENGINEER : PTR No. : PREPARED BY : KATHRINA L. MORELOS, REE, RME OWNER : PROJECT TITLE : REVISION : SHEET CONTENTS : SHEET NO. :

PLACE : DRAWN BY : ARJUNA G. CHUA, REE, RME CARMENCITA IYANA SASAPAN

CHECKED BY : ADDRESS :
PROPOSED 2 STOREY RESIDENCE GROUND FLOOR LIGHTING LAYOUT EE
DATE : SECOND FLOORLLIGHTING LAYOUT

PRC No. : TIN No. : DATE :


BLK C, LOT 37, IRAYA ST. PH.5, ACM WOODSTOCK
HOMES , ALAPAN I-A, IMUS, CAVITE
2 3
4.14 4.14
1.17 2.97 2.16

GFCI CABINET
REF

T&B
1.80 1.80
LP
3
2.88
GFCI

LP
5
3 3
4 2 1 4 2 1
5 5
6 6
7 7
8 8
SHOWER
LP
7.25 9 AREA 1.35
4 GFCI
4.05 4.05 10
11
12
13
14
15

MASTER'S
BEDROOM

3.11
WP
BALCONY

1.31 1.31 LP
6

WARDROBE
CABINET

1.53 2.52

ENGINEER : PTR No. : PREPARED BY : KATHRINA L. MORELOS, REE, RME OWNER : PROJECT TITLE : REVISION : SHEET CONTENTS : SHEET NO. :

PLACE : DRAWN BY : ARJUNA G. CHUA, REE, RME CARMENCITA IYANA SASAPAN

CHECKED BY : ADDRESS :
PROPOSED 2 STOREY RESIDENCE GROUND FLOOR POWER LAYOUT EE
DATE : SECOND FLOOR POWER LAYOUT

PRC No. : TIN No. : DATE :


BLK C, LOT 37, IRAYA ST. PH.5, ACM WOODSTOCK
HOMES , ALAPAN I-A, IMUS, CAVITE
3 3

You might also like