Professional Documents
Culture Documents
underground ramp from Kanpur Central end of Nayaganj station to elevated ramp
after Transport Nagar and three underground metro stations (viz. Kanpur Central,
Jhakarkatti and Transport Nagar) including Architectural finishes, E & M, TVS, ECS
etc. on Corridor-1 of Kanpur MRTS Project at Kanpur, Uttar Pradesh, India.
Page 1 of 46
Page 2 of 46
Page 3 of 46
Page 4 of 46
Page 5 of 46
Page 6 of 46
Page 7 of 46
Page 8 of 46
Page 9 of 46
KNPCC06- Design and Construction of TBM Tunnel, Cut & Cover Tunnel and
underground ramp from Kanpur Central end of Nayaganj STATION to elevated ramp
after Transport Nagar and three underground metro STATIONs (viz. Kanpur Central,
Jhakarkatti and Transport Nagar) including Architectural finishes, E & M, TVS, ECS etc.
on Corridor-1 of Kanpur MRTS Project at Kanpur, Uttar Pradesh, India.
Piping Connections
2 L.H.S
6 R.H.S.
4 L.H.S.
6 R.H.S.
3 L.H.S.
3 7 c) 3 2040 9 3 2040 6
3 R.H.S.
* Kanpur Central Station (CRS) FCU not included in above schedule due to latest Architectural drawings
are not issued us.
Page 10 of 46
KNPCC-06-Design and Construction of TBM Tunnel, Cut & Cover Tunnel and
underground ramp from Kanpur Central end of Nayaganj station to elevated ramp
after Transport Nagar and three underground metro stations (viz. Kanpur Central,
Jhakarkatti and Transport Nagar) including Architectural finishes, E & M, TVS, ECS
etc. on Corridor-1 of Kanpur MRTS Project at Kanpur, Uttar Pradesh, India.
TRANSPORT
NAGAR
STATION
Page 11 of 46
KNPCC 06_TNG Heat Load Summary
Equipment Tonnage Air Flow
Area Occupancy Selected Unit (FCU) QTY
S. No. Name of Area Room No. Load (TR) (CFM) Remarks
(Sqft) (Nos.) (kW) Summer Monsoon Summer Monsoon TR x Nos REMARKS
Technical Area
3 Security U-09 165 2 1 0.92 0.95 380 290 1.5 x 1 1W
Room
3 3 2040 2 R.H.S.
4 3 2040 1 L.H.S.
Page 12 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - TRANSPORT NAGAR STATION (TNG) DATE: 20.05.23 Rev-0
LOCATION: U05 (TOM) at consourse level 29.07.23 Rev-1
AREA: 104.571648 Sq ft 1715 Cu ft (Volume) Summer Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 107.78 73.4 19 36.75 68.8
(Sq ft) (Btu/h.sq ft) ROOM 77 65.63 55 30.4 76.5
N - Glass 0.0 23 0.56 0 DIFFERENCE 30.78 XXXX XXXX -7.7
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 2 People X 17 CFM/Person 34
S - Glass 0.0 12 0.56 0 1715 Cu ft X 1 Air change per hour 29
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 34
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.96
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 20.70 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 418 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 2 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 W/sqft.
SE - Wall 0.0 24 0.31 0 Eq. Load = 1.5 KW
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0
NW - Wall 0.0 32 0.31 0 Summer Load:
Roof Sun 0 51 0.1 0 TR = 0.97 TR
Roof Shaded 39 0 DEHUMIDIFIED CFM = 418 CFM
TRANS. GAIN EXCEPT WALLS & ROOF FRESH AIR REQUIRED = 41.79941585 CFM
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
CFM °F 1 - BF FACTOR
34 30.78 0.9 1.08 1017
OUTSIDE AIR HEAT (LATENT)
Page 13 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - TRANSPORT NAGAR STATION (TNG) DATE: 20.05.23 Rev-0
LOCATION: U05 (TOM) at consourse level 29.07.23 Rev-1
AREA: 104.571648 Sq ft 1715 Cu ft (Volume) Monsoon Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 91.4 84.2 74.5 48.38 168
(Sq ft) (Btu/h.sq ft) ROOM 77 65.63 55 30.4 76.5
N - Glass 0.0 23 0.56 0 DIFFERENCE 14.4 XXXX XXXX 91.5
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 2 People X 17 CFM/Person 34
S - Glass 0.0 12 0.56 0 1715 Cu ft X 1 Air change per hour 29
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 34
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.92
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 20.70 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 352 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 2 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 W/sqft.
SE - Wall 0.0 24 0.31 0 Eq. Load = 1.5 KW
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0
NW - Wall 0.0 32 0.31 0 Monsoon Load:
Roof Sun 0 51 0.1 0 TR = 1.00 TR
Roof Shaded 39 0 DEHUMIDIFIED CFM = 352 CFM
TRANS. GAIN EXCEPT WALLS & ROOF FRESH AIR REQUIRED = 35.17705939 CFM
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
CFM °F 1 - BF FACTOR
34 14.4 0.9 1.08 476
OUTSIDE AIR HEAT (LATENT)
Page 14 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - TRANSPORT NAGAR STATION (TNG) DATE: 20.05.23 Rev-0
LOCATION: U03 &U07 (EFO/SCR) concourse Lvl 29.07.23 Rev-1
AREA: 239.535776 Sq ft 3928 Cu ft (Volume) Summer Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 107.78 73.4 19 36.75 68.8
(Sq ft) (Btu/h.sq ft) ROOM 73.4 63.916 60 29.175 74
N - Glass 0.0 23 0.56 0 DIFFERENCE 34.38 XXXX XXXX -5.2
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 5 People X 17 CFM/Person 85
S - Glass 0.0 12 0.56 0 3928 Cu ft X 1 Air change per hour 65
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 85
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.94
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 17.46 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 935 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 5 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 W/sqft.
SE - Wall 0.0 24 0.31 0 Eq. Load = 2.5 KW
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0
NW - Wall 0.0 32 0.31 0 Summer Load:
Roof Sun 0.0 51 0.1 0 TR = 1.95 TR
Roof Shaded 39 0 DEHUMIDIFIED CFM = 935 CFM
TRANS. GAIN EXCEPT WALLS & ROOF FRESH AIR REQUIRED = 93.5274 CFM
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
CFM °F 1 - BF FACTOR
85 34.38 0.9 1.08 2840
OUTSIDE AIR HEAT (LATENT)
Page 15 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - TRANSPORT NAGAR STATION (TNG) DATE: 20.05.23 Rev-0
LOCATION: U03 &U07 (EFO/SCR) concourse Lvl 29.07.23 Rev-1
AREA: 239.535776 Sq ft 3928 Cu ft (Volume) Monsoon Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 91.4 84.2 74.5 48.38 168
(Sq ft) (Btu/h.sq ft) ROOM 73.4 63.916 60 29.175 74
N - Glass 0.0 23 0.56 0 DIFFERENCE 18 XXXX XXXX 94
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 5 People X 17 CFM/Person 85
S - Glass 0.0 12 0.56 0 3928 Cu ft X 1 Air change per hour 65
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 85
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.90
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 17.46 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 791 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 5 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 W/sqft.
SE - Wall 0.0 24 0.31 0 Eq. Load = 2.5 KW
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0
NW - Wall 0.0 32 0.31 0 Monsoon Load:
Roof Sun 0.0 51 0.1 0 TR = 2.11 TR
Roof Shaded 39 0 DEHUMIDIFIED CFM = 791 CFM
TRANS. GAIN EXCEPT WALLS & ROOF FRESH AIR REQUIRED = 85 CFM
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
Ceiling 0 13 0.36 0
Floor 0 13 0.36 0
INTERNAL HEAT GAIN
People 5 Nos X 443.3 2217
Light 240 W 3.41 817
Eq. Load 2500 WX 3.41 8525
Misc Load 0.0 WX 3.41 0
13396
OUTSIDE AIR
CFM °F BF FACTOR
85 18 0.1 1.08 165
ROOM SENSIBLE HEAT (RSH) 13561
Supply duct Supply duct leak. Heat gain from fan 2
3
heat gain + loss + HP(%)
Safety factor (%) 10.0 1356
CFM °F 1 - BF FACTOR
85 18 0.9 1.08 1487
OUTSIDE AIR HEAT (LATENT)
Page 16 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - TRANSPORT NAGAR STATION (TNG) DATE: 20.05.23 Rev-0
LOCATION: U09 (Security Rm) concourse level 29.07.23 Rev-1
AREA: 166.1938482 Sq ft 2726 Cu ft (Volume) Summer Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 107.78 73.4 19 36.75 68.8
(Sq ft) (Btu/h.sq ft) ROOM 77 65.63 55 30.4 76.5
N - Glass 0.0 23 0.56 0 DIFFERENCE 30.78 XXXX XXXX -7.7
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 2 People X 17 CFM/Person 34
S - Glass 0.0 12 0.56 0 2726 Cu ft X 1 Air change per hour 45
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 45
W - Glass 0.0 163 0.56 0 s
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.95
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 20.70 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 380 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 2 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 W/sqft.
SE - Wall 0.0 24 0.31 0 Eq. Load = 1 KW
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0
CFM °F BF FACTOR
45 30.78 0.1 1.08 151
ROOM SENSIBLE HEAT (RSH) 7723
Supply duct Supply duct leak. Heat gain from fan 2
3
heat gain + loss + HP(%)
Safety factor (%) 10.0 772
CFM °F 1 - BF FACTOR
45 30.78 0.9 1.08 1359
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
45 -7.7 0.9 0.68 -214
HEAT SUB TOTAL 10069
Return duct HP Pump + Dehum. & Pipe 10.0 1007
heat gain & loss (%)
TR 0.92 GRAND TOTAL HEAT 11076
Page 17 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - TRANSPORT NAGAR STATION (TNG) DATE: 20.05.23 Rev-0
LOCATION: U09 (Security Rm) concourse level 29.07.23 Rev-1
AREA: 165.356608 Sq ft 2712 Cu ft (Volume) Monsoon Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 91.4 84.2 74.5 48.38 168
(Sq ft) (Btu/h.sq ft) ROOM 77 65.63 55 30.4 76.5
N - Glass 0.0 23 0.56 0 DIFFERENCE 14.4 XXXX XXXX 91.5
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 2 People X 17 CFM/Person 34
S - Glass 0.0 12 0.56 0 2712 Cu ft X 1 Air change per hour 45
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 45
W - Glass 0.0 163 0.56 0 s
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.90
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 20.70 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 290 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 2 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 W/sqft.
SE - Wall 0.0 24 0.31 0 Eq. Load = 1 KW
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0
CFM °F BF FACTOR
45 14.4 0.1 1.08 70
ROOM SENSIBLE HEAT (RSH) 5896
Supply duct Supply duct leak. Heat gain from fan 2
1
heat gain + loss + HP(%)
Safety factor (%) 10.0 590
CFM °F 1 - BF FACTOR
45 14.4 0.9 1.08 633
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
45 91.5 0.9 0.68 2531
HEAT SUB TOTAL 10406
Return duct HP Pump + Dehum. & Pipe 10.0 1041
heat gain & loss (%)
TR 0.95 GRAND TOTAL HEAT 11446
Page 18 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - TRANSPORT NAGAR STATION (TNG) DATE: 20.05.23 Rev-0
LOCATION: U22 & U23 (SER+TER) Platform level 29.07.23 Rev-1
AREA: 586.010048 Sq ft 9611 Cu ft Summer Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 107.78 73.4 19 36.75 68.8
(Sq ft) (Btu/h.sq ft) ROOM 73.4 63.916 60 29.175 74
N - Glass 0.0 23 0.56 0 DIFFERENCE 34.38 XXXX XXXX -5.2
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 1 People X 16 CFM/Person 16
S - Glass 0.0 12 0.56 0 9611 Cu ft X 1 Air change per hour 160
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 160
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 1.00
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 17.46 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 3689 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 1 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 KW
SE - Wall 0.0 24 0.31 0 Eq. Load = 13.45 KW Misc Load 0.3
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0
CFM °F BF FACTOR
160 34.38 0.1 1.08 595
ROOM SENSIBLE HEAT (RSH) 63234
Supply duct Supply duct leak. Heat gain from fan 2
12
heat gain + loss + HP(%)
Safety factor (%) 10.0 6323
CFM °F 1 - BF FACTOR
160 34.38 0.9 1.08 5353
OUTSIDE AIR HEAT (LATENT)
Page 19 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - TRANSPORT NAGAR STATION (TNG) DATE: 20.05.23 Rev-0
LOCATION: U22 & U23 (SER+TER) Platform level 29.07.23 Rev-1
AREA: 586.010048 Sq ft 9611 Cu ft Monsoon Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 91.4 84.2 74.5 48.38 168
(Sq ft) (Btu/h.sq ft) ROOM 73.4 63.916 60 29.175 74
N - Glass 0.0 23 0.56 0 DIFFERENCE 18 XXXX XXXX 94
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 1 People X 16 CFM/Person 16
S - Glass 0.0 12 0.56 0 9611 Cu ft X 1 Air change per hour 160
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 160
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.98
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 17.46 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 3207 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 1 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 KW
SE - Wall 0.0 24 0.31 0 Eq. Load = 13.45 KW
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0
Ceiling 0 13 0.36 0
Floor 0 13 0.36 0
INTERNAL HEAT GAIN
People 1 Nos X 443.3 443
Light 586 W X 1.25 3.41 2498
Eq. Load 13450 WX 3.41 45865
Misc Load 0.0 WX 3.41 0
54661
OUTSIDE AIR
CFM °F BF FACTOR
160 18 0.1 1.08 311
ROOM SENSIBLE HEAT (RSH) 54973
Supply duct Supply duct leak. Heat gain from fan 2
6
heat gain + loss + HP(%)
Safety factor (%) 10.0 5497
CFM °F 1 - BF FACTOR
160 18 0.9 1.08 2802
OUTSIDE AIR HEAT (LATENT)
Page 20 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - TRANSPORT NAGAR STATION (TNG) DATE: 20.05.23 Rev-0
LOCATION: U24 & U27 (UPS Rm) at platform level 29.07.23 Rev-1
AREA: 895.475424 Sq ft 14686 Cu ft (Volume) Summer Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 107.78 73.4 19 36.75 68.8
(Sq ft) (Btu/h.sq ft) ROOM 73.4 63.916 60 29.175 74
N - Glass 0.0 23 0.56 0 DIFFERENCE 34.38 XXXX XXXX -5.2
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 1 People X 16 CFM/Person 16
S - Glass 0.0 12 0.56 0 14686 Cu ft X 1 Air change per hour 245
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 245
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 1.00
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 17.46 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 2965 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 1 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 KW
SE - Wall 0.0 24 0.31 0 Eq. Load = 8.23 KW Misc load 0.55
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0
CFM °F BF FACTOR
CFM °F 1 - BF FACTOR
245 34.38 0.9 1.08 8179
OUTSIDE AIR HEAT (LATENT)
Page 21 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - TRANSPORT NAGAR STATION (TNG) DATE: 20.05.23 Rev-0
LOCATION: U24 & U27 (UPS Rm) at platform level 29.07.23 Rev-1
AREA: 895.475424 Sq ft 14686 Cu ft (Volume) Monsoon Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 91.4 84.2 74.5 48.38 168
(Sq ft) (Btu/h.sq ft) ROOM 73.4 63.916 60 29.175 74
N - Glass 0.0 23 0.56 0 DIFFERENCE 18 XXXX XXXX 94
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 1 People X 16 CFM/Person 16
S - Glass 0.0 12 0.56 0 14686 Cu ft X 1 Air change per hour 245
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 245
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.96
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 17.46 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 2436 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 1 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 KW
SE - Wall 0.0 24 0.31 0 Eq. Load = 8.23 KW Misc load 0.55
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0
Ceiling 0 13 0.36 0
Floor 0 13 0.36 0
INTERNAL HEAT GAIN
People 1 Nos X 443.3 443
Light 895 W X 1.25 3.41 3817
Eq. Load 8230 WX 3.41 28064
Misc Eq Load 493 WX 3.41 2099
41271
OUTSIDE AIR
CFM °F BF FACTOR
CFM °F 1 - BF FACTOR
245 18 0.9 1.08 4282
OUTSIDE AIR HEAT (LATENT)
Page 22 of 46
U-factor calculation for Platform roof 750mm thickness RCC block
S.No. Description Roof Thermal Resistance - R Reference
R1 Outside Air Resistance 0.25 ISHRAE edision 2017, Table 1.20
R2 Cement plaster 1/2 Inch thick above the 0.15 ISHRAE edision 2017, Table 1.20
roof
R3 Cement plaster 1/2 Inch thick below the 0.15 ISHRAE edision 2017, Table 1.20
roof
R4 750 mm heavy weight concrete slab 5.91 ISHRAE edision 2017, Table 1.20
Total - R 6.46
U - Factor = 1/R
0.15
Total - R 10.00
U - Factor = 1/R
0.10
Page 23 of 46
Interface KNPCC06 <interfaceknpcc06@samindia.com>
2 attachments
Interface Specifications UPMRC.pdf
949K
AFC Electrical Load & Heat Load..xlsx
14K
Page 24 of 46
Typical Power Requirement for AFC Equipment at Station (Elevated) Entry & Exit Single Array)
Typical Power Requirement for AFC Equipment at Station (Underground) Entry & Exit - Double Array)
Total KVA = Additional 25%
TR, N/W Switch Total
Type ITEM AG with Validator TOM/EFO TVM SC Kwatt/power for future
& Others Power
factor Equipments
Number of Equipment 14 6 3 1 LS
Watt/Per Equipment 300 250 600 600 300
Station Total Watt = Watt * no of equipment 4200 1500 1800 600 300
Kw=Watt/1000 4.2 1.5 1.8 0.6 0.3 8.4 10.5 13
1Watt = 3.415BTU/hr 14.343 5.1225 6.147 2.049 1.0245 28.686 N/A 35.8575
Heat Dissipation per unit in BTU/Hr
1 amp is equal to 120 W. ... At 220V, 1 amp is equal to 220 watts. Here is
Page 25 of 46
ECSTVS Design <ecstvsdesign@samindia.com>
Dear Sir,
In continuation of trailing mail, a meeting has been conducted & the following points finalized.
Nasir Abdullah | Sr System Interface Expert-K2 | Kanpur & Agra Metro Projects | TYPSA-ITALFERR JV |
Phone: +91 9899664537 | Email address: nasir.a@typsaitalferrgc.com |
710 & 711, Levana Cyber Height, Vibhuti Khand, Gomti Nagar, Lucknow | Uttar Pradesh - 226010 | India |
-----Original Appointment-----
From: Nasir Abdullah
Sent: Tuesday, September 5, 2023 10:52 AM
To: Nasir Abdullah; ECSTVS Design; E&M KNPCC06; Divakar Jha; Ashutosh Kumar; Shiva Seth; Arun Kumar Katiyar;
Gaurav Rastogi; Raushan Kumar
Cc: Daniel Beshah; Dhiman Majumdar; Sudhanshu Shekhar Joshi
Subject: Discrepancy in Heat load for KNPCC06
When: 05 September 2023 11:00-12:00 (UTC+05:30) Chennai, Kolkata, Mumbai, New Delhi.
Where: Microsoft Teams Meeting
[Quoted text hidden]
Page 26 of 46
12 13
Page 27 of 46
CONCOURSE LEVEL
1
Page 28 of 46
9
CONCOURSE LEVEL
1
13
Page 29 of 46
TR
C
CONCOURSE LEVEL
1
B
19500
9800
1
PLATFORM LEVEL
LOOP FRAME
F F
F
LOOP FRAME
15
OKS
ACDB
ACS Panel
DCDB
ACS Panel
MDF
IDF
OKS
LOOP BOX 3 & 4 LOOP BOX 1 & 2
BATTERY-2
SMPS
13595
O/P PANEL
ATS
BATTERY RACK- 2/2
SCVS
BATTERY RACK- 1/2
UPS-2
45 KVA
BCB-2 BCB-1
Page 30 of 46
KNPCC-06-Design and Construction of TBM Tunnel, Cut & Cover Tunnel and
underground ramp from Kanpur Central end of Nayaganj station to elevated ramp
after Transport Nagar and three underground metro stations (viz. Kanpur Central,
Jhakarkatti and Transport Nagar) including Architectural finishes, E & M, TVS, ECS
etc. on Corridor-1 of Kanpur MRTS Project at Kanpur, Uttar Pradesh, India.
JHAKAR KATTI
BUS TERMINAL
STATION
Page 31 of 46
KNPCC 06_JBT Heat Load Summary For FCU
Equipment Tonnage Air Flow
Area Occupancy Selected Unit (FCU) QTY
S. No. Name of Area Room No. Load (TR) (CFM) Remarks
(Sqft) (Nos.) (kW) Summer Monsoon Summer Monsoon TR x Nos REMARKS
2 SCR / EFO U-03 & U07 269 5 2.1 1.37 1.46 566 427 1.5 x 2 1 W + 1S
Technical Area
3 Security Rm U-09 97 6 1 0.93 0.73 285 220 1.5 x 1 1W
Room
Selected the FCU to achive TR, not
4 SER+TER U-22&23 520 1 13.45 7.13 6.95 3593 3310 2.5 x 4 3W + 1S
cfm bcos occupancy is very less.
Comb. UPS Selected the FCU to achive TR, not
5 U-24&27 692 1 8.23 5.72 5.63 2789 2403 3.0 x 3 2 W + 1S
Room cfm bcos occupancy is very less.
* We are Referred the latest architectural drawing received via letter no Kanpur-LET-JVTI-ARC-00834-E01 on dated 12.09.23.
5 3 2040 2 L.H.S.
6 3 2040 1 R.H.S.
Page 32 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - JHAKAR KATI BUS TERMINAL (JBT) Date 17.05.23 Rev-1
LOCATION: U 05 (TOM) at Concourse 29.07.23 Rev-2
AREA: 107.6 Sq ft 2120 Cu ft (Volume) Summer Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 107.78 73.4 19 36.75 68.8
(Sq ft) (Btu/h.sq ft) ROOM 80.6 68.675 55 32.87 86.3
N - Glass 0.0 23 0.56 0 DIFFERENCE 27.18 XXXX XXXX -17.5
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 2 People X 17 CFM/Person 34
S - Glass 0.0 12 0.56 0 2120 Cu ft X 1 Air change per hour 35
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 35
W - Glass 0.0 163 0.56 0 s
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.95
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 23.94 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 275 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 2 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 W/sqft.
SE - Wall 0.0 24 0.31 0 Eq. Load = 1.5 KW
S - Wall 0.0 34 0.31 0 Height = 19.7 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0
CFM °F BF FACTOR
CFM °F 1 - BF FACTOR
35 27.18 0.9 1.08 933
OUTSIDE AIR HEAT (LATENT)
Page 33 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - JHAKAR KATI BUS TERMINAL (JBT) Date 17.05.23 Rev-1
LOCATION: U 05 (TOM) at Concourse 29.07.23 Rev-2
AREA: 107.6 Sq ft 2120 Cu ft (Volume) Monsoon Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 91.4 84.2 74.5 48.38 168
(Sq ft) (Btu/h.sq ft) ROOM 80.6 68.675 55 32.87 86.3
N - Glass 0.0 23 0.56 0 DIFFERENCE 10.8 XXXX XXXX 81.7
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 2 People X 17 CFM/Person 34
S - Glass 0.0 12 0.56 0 2120 Cu ft X 1 Air change per hour 35
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 35
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.95
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 23.94 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 514 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 2 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 W/sqft.
SE - Wall 0.0 24 0.31 0 Eq. Load = 3 KW
S - Wall 0.0 34 0.31 0 Height = 19.7 FT
SW - Wall 0.0 48 0.31 0
Calculated Load Summary
W - Wall 0.0 48 0.31 0
CFM °F BF FACTOR
CFM °F 1 - BF FACTOR
35 10.8 0.9 1.08 371
OUTSIDE AIR HEAT (LATENT)
Page 34 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - JHAKAR KATI BUS TERMINAL (JBT) Date 17.05.23 Rev-1
LOCATION: U 03/U07 (SCR/EFO) at Concourse 29.07.23 Rev-2
AREA: 269 Sq ft 5299 Cu ft (Volume) Summer Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 107.78 73.4 19 36.75 68.8
(Sq ft) (Btu/h.sq ft) ROOM 75.2 65.475 60 30.348 78.7
N - Glass 0.0 23 0.56 0 DIFFERENCE 32.58 XXXX XXXX -9.9
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 5 People X 17 CFM/Person 85
S - Glass 0.0 12 0.56 0 5299 Cu ft X 1 Air change per hour 88
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 88
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.92
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 19.08 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 566 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 5 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 W/sqft.
SE - Wall 0.0 24 0.31 0 Eq. Load = 2.1 KW
S - Wall 0.0 34 0.31 0 Height = 19.7 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0
CFM °F BF FACTOR
CFM °F 1 - BF FACTOR
88 32.58 0.9 1.08 2797
OUTSIDE AIR HEAT (LATENT)
Page 35 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - JHAKAR KATI BUS TERMINAL (JBT) Date 17.05.23 Rev-1
LOCATION: U 03/U07 (SCR/EFO) at Concourse 29.07.23 Rev-2
AREA: 269 Sq ft 5299 Cu ft (Volume) Monsoon Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 91.4 84.2 74.5 48.38 168
(Sq ft) (Btu/h.sq ft) ROOM 75.2 65.475 60 30.348 78.7
N - Glass 0.0 23 0.56 0 DIFFERENCE 16.2 XXXX XXXX 89.3
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 5 People X 17 CFM/Person 85
S - Glass 0.0 12 0.56 0 5299 Cu ft X 1 Air change per hour 88
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 88
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.84
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 19.08 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 427 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 5 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 W/sqft.
SE - Wall 0.0 24 0.31 0 Eq. Load = 1 KW
S - Wall 0.0 34 0.31 0 Height = 19.7 FT
SW - Wall 0.0 48 0.31 0
Calculated Load Summary
W - Wall 0.0 48 0.31 0
CFM °F BF FACTOR
CFM °F 1 - BF FACTOR
88 16.2 0.9 1.08 1391
OUTSIDE AIR HEAT (LATENT)
Page 36 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - JHAKAR KATI BUS TERMINAL (JBT) Date 17.05.23 Rev-1
LOCATION: U 09 (Security) at Concourse 29.07.23 Rev-2
AREA: 96.84 Sq ft 1908 Cu ft (Volume) Summer Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 107.78 73.4 19 36.75 68.8
(Sq ft) (Btu/h.sq ft) ROOM 80.6 68.675 55 32.87 86.3
N - Glass 0.0 23 0.56 0 DIFFERENCE 27.18 XXXX XXXX -17.5
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 6 People X 17 CFM/Person 102
S - Glass 0.0 12 0.56 0 1908 Cu ft X 1 Air change per hour 32
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 102
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.86
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 23.94 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 285 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 6 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 W/sqft.
SE - Wall 0.0 24 0.31 0 Eq. Load = 1 KW
S - Wall 0.0 34 0.31 0 Height = 19.7 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0
CFM °F BF FACTOR
CFM °F 1 - BF FACTOR
102 27.18 0.9 1.08 2695
OUTSIDE AIR HEAT (LATENT)
Page 37 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - JHAKAR KATI BUS TERMINAL (JBT) Date 17.05.23 Rev-1
LOCATION: U 09 (Security) at Concourse 29.07.23 Rev-2
AREA: 96.84 Sq ft 1908 Cu ft (Volume) Monsoon Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 91.4 84.2 74.5 48.38 168
(Sq ft) (Btu/h.sq ft) ROOM 80.6 68.675 55 32.87 86.3
N - Glass 0.0 23 0.56 0 DIFFERENCE 10.8 XXXX XXXX 81.7
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 2 People X 17 CFM/Person 34
S - Glass 0.0 12 0.56 0 1908 Cu ft X 1 Air change per hour 32
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 34
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.90
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 23.94 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 220 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 2 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 W/sqft.
SE - Wall 0.0 24 0.31 0 Eq. Load = 1 KW
S - Wall 0.0 34 0.31 0 Height = 19.7 FT
SW - Wall 0.0 48 0.31 0
Calculated Load Summary
W - Wall 0.0 48 0.31 0
CFM °F BF FACTOR
CFM °F 1 - BF FACTOR
34 10.8 0.9 1.08 357
OUTSIDE AIR HEAT (LATENT)
Page 38 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - JHAKAR KATI BUS TERMINAL (JBT) Date 17.05.23 Rev-1
LOCATION: U 22 & 23 (SCR+TER) at ground floor 29.07.23 Rev-2
AREA: 520 Sq ft 8528 Cu ft Summer Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 107.78 73.4 19 36.75 68.8
(Sq ft) (Btu/h.sq ft) ROOM 75.2 65.475 60 30.348 78.7
N - Glass 0.0 23 0.56 0 DIFFERENCE 32.58 XXXX XXXX -9.9
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 1 People X 16 CFM/Person 16
S - Glass 0.0 12 0.56 0 8528 Cu ft X 1 Air change per hour 142
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 142
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 1.00
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 19.08 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 3593 CFM
N - Wall 398.1 22 0.31 2715 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 1 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 KW
SE - Wall 0.0 24 0.31 0 Eq. Load = 13.45 KW
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0
CFM °F BF FACTOR
CFM °F 1 - BF FACTOR
142 32.58 0.9 1.08 4501
OUTSIDE AIR HEAT (LATENT)
Page 39 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - JHAKAR KATI BUS TERMINAL (JBT) Date 17.05.23 Rev-1
LOCATION: U 22 & 23 (SCR+TER) at Ground 29.07.23 Rev-2
AREA: 520 Sq ft 8528 Cu ft Monsoon Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 91.4 84.2 74.5 48.38 168
(Sq ft) (Btu/h.sq ft) ROOM 75.2 65.475 60 30.348 78.7
N - Glass 0.0 23 0.56 0 DIFFERENCE 16.2 XXXX XXXX 89.3
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 1 People X 16 CFM/Person 16
S - Glass 0.0 12 0.56 0 8528 Cu ft X 1 Air change per hour 142
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 142
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.98
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 19.08 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 3310 CFM
N - Wall 473.4 22 0.31 3228 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 1 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 KW
SE - Wall 0.0 24 0.31 0 Eq. Load = 13.45 KW
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0
Calculated Load Summary
W - Wall 0.0 48 0.31 0
CFM °F BF FACTOR
CFM °F 1 - BF FACTOR
142 16.2 0.9 1.08 2238
OUTSIDE AIR HEAT (LATENT)
Page 40 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - JHAKAR KATI BUS TERMINAL (JBT) Date 17.05.23 Rev-1
LOCATION: U 24 & 27 (Comb. UPS Rm) at Ground 29.07.23 Rev-2
AREA: 692 Sq ft 11349 Cu ft (Volume) Summer Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 107.78 73.4 19 36.75 68.8
(Sq ft) (Btu/h.sq ft) ROOM 75.2 65.475 60 30.348 78.7
N - Glass 0.0 23 0.56 0 DIFFERENCE 32.58 XXXX XXXX -9.9
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 1 People X 16 CFM/Person 16
S - Glass 0.0 12 0.56 0 11349 Cu ft X 1 Air change per hour 189
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 189
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 1.00
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 19.08 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 2789 CFM
N - Wall 473.4 22 0.31 3228 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 1 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 KW
SE - Wall 0.0 24 0.31 0 Eq. Load = 8.23 KW
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0
CFM °F BF FACTOR
CFM °F 1 - BF FACTOR
189 32.58 0.9 1.08 5990
OUTSIDE AIR HEAT (LATENT)
Page 41 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - JHAKAR KATI BUS TERMINAL (JBT) Date 17.05.23 Rev-1
LOCATION: U 24 & 27 (Comb. UPS Rm) at Ground 29.07.23 Rev-2
AREA: 692 Sq ft 11349 Cu ft (Volume) Monsoon Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 91.4 84.2 74.5 48.38 168
(Sq ft) (Btu/h.sq ft) ROOM 75.2 65.475 60 30.348 78.7
N - Glass 0.0 23 0.56 0 DIFFERENCE 16.2 XXXX XXXX 89.3
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 1 People X 16 CFM/Person 16
S - Glass 0.0 12 0.56 0 11349 Cu ft X 1 Air change per hour 189
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 189
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.97
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 19.08 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 2403 CFM
N - Wall 473.4 22 0.31 3228 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 1 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 KW
SE - Wall 0.0 24 0.31 0 Eq. Load = 8.23 KW
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0
Calculated Load Summary
W - Wall 0.0 48 0.31 0
CFM °F BF FACTOR
CFM °F 1 - BF FACTOR
189 16.2 0.9 1.08 2978
OUTSIDE AIR HEAT (LATENT)
Page 42 of 46
4
C
JBT-FCU-301 & 302
1.5 TR BOU +3200
600x1000 SP DUCT
BOD:3900 AFFL
U05
+120.760 FFL
+120.760
+120.660
2500x1200 SAD
BOD:3700 AFFL
Page 43 of 46
900x500
4 SAD 800x400 SED 5
BOD:4400 AFFL 2000 L/s BOD 4500
B
JBT-FCU-304 & 305
1.5 TR BOU +3660
# 750x250 SED BELLMOUTH
0 L/s EACH U03/U07
CONCOURSE LEVEL
3
JHAKAR KATI BUS TERMINAL STATION
U03/U07 SCR/EFO ROOM
CONCOURSE LEVEL
JBT-FCU-303
1.5 TR BOU +3660
U09
U18
A
CONCOURSE LEVEL 32Ø CH
JHAKAR KATI BUS TERMINAL STATION
1 U09 SEC. ROOM
CONCOURSE LEVEL
Page 45 of 46
09' 11'
Page 46 of 46
10' 12'
ACDB DCDB LOOP BOX 1 & 2 LOOP BOX 3 & 4
GSM
ACS Panel
E'
ACS Panel
IDF
MDF
+128.437 FFL
+127.987 TOC
FIBRE OPTIC
LOOP BOX-1
FOR SMPS
B/B2 B/B1
SMPS SMPS SPARE CELL
OKS
2 1 FOR SMPS SPARE
UPS
CELL
SPARE FOR
CELL UPS
CHARGER
U24 & U27
BCB-2
ATS
+128.437 FFL 80 KVA
BCB-1
LPD-01
LPD-02
IT
ANCILLARY BUILDING GROUND FLOOR LEVEL
1