You are on page 1of 46

KNPCC-06-Design and Construction of TBM Tunnel, Cut & Cover Tunnel and

underground ramp from Kanpur Central end of Nayaganj station to elevated ramp
after Transport Nagar and three underground metro stations (viz. Kanpur Central,
Jhakarkatti and Transport Nagar) including Architectural finishes, E & M, TVS, ECS
etc. on Corridor-1 of Kanpur MRTS Project at Kanpur, Uttar Pradesh, India.

FAN COIL UNITs


TDS &
GA DRAWINGs

Page 1 of 46
Page 2 of 46
Page 3 of 46
Page 4 of 46
Page 5 of 46
Page 6 of 46
Page 7 of 46
Page 8 of 46
Page 9 of 46
KNPCC06- Design and Construction of TBM Tunnel, Cut & Cover Tunnel and
underground ramp from Kanpur Central end of Nayaganj STATION to elevated ramp
after Transport Nagar and three underground metro STATIONs (viz. Kanpur Central,
Jhakarkatti and Transport Nagar) including Architectural finishes, E & M, TVS, ECS etc.
on Corridor-1 of Kanpur MRTS Project at Kanpur, Uttar Pradesh, India.

FCU Summary (TNG & JBT STN)

As Per BOQ As Per Actual

Piping Connections

Sn BOQ Sn TR CMH QTY TR CMH QTY Facing Filter


QTY
side

2 L.H.S

1 7 a) 1.5 1020 15 1.5 1020 8

6 R.H.S.

4 L.H.S.

2 7 b) 2.5 1700 65 2.5 1700 10

6 R.H.S.

3 L.H.S.

3 7 c) 3 2040 9 3 2040 6

3 R.H.S.

* Kanpur Central Station (CRS) FCU not included in above schedule due to latest Architectural drawings
are not issued us.

Page 10 of 46
KNPCC-06-Design and Construction of TBM Tunnel, Cut & Cover Tunnel and
underground ramp from Kanpur Central end of Nayaganj station to elevated ramp
after Transport Nagar and three underground metro stations (viz. Kanpur Central,
Jhakarkatti and Transport Nagar) including Architectural finishes, E & M, TVS, ECS
etc. on Corridor-1 of Kanpur MRTS Project at Kanpur, Uttar Pradesh, India.

TRANSPORT
NAGAR
STATION

Page 11 of 46
KNPCC 06_TNG Heat Load Summary
Equipment Tonnage Air Flow
Area Occupancy Selected Unit (FCU) QTY
S. No. Name of Area Room No. Load (TR) (CFM) Remarks
(Sqft) (Nos.) (kW) Summer Monsoon Summer Monsoon TR x Nos REMARKS

1 TOM U-05 105 2 1.5 0.97 1.00 418 352 1.5 x 2 1 W + 1S

2 EFO+SCR U-03/U-07 240 5 2.5 1.95 2.11 935 791 2.5 x 2 1 W + 1S

Technical Area
3 Security U-09 165 2 1 0.92 0.95 380 290 1.5 x 1 1W
Room

Selected the FCU to achive TR, not


4 SER + TER U-22&23 586 1 13.45 6.84 6.77 3689 3207 2.5 x 4 3W + 1S
cfm bcos occupancy is very less.

Comb. UPS Selected the FCU to achive TR, not


5 U-24&27 895 1 8.23 5.82 6.07 2965 2436 3.0 x 3 2 W + 1S
Room cfm bcos occupancy is very less.

* Equipment Load Details


1 TOM / EFO Room 1.5 KW load consider as per vendor confirmation mail copy attached.
2 In SCR Room, we Assumed 1.0 KW Equipment Load.

3 In SER/TER Room, 13.45 KW equipement Load cosider as confirmed by mail (attached)

4 In UPS Room, 8.23 KW equipement Load conisder as as confirmed by mail (attached)

FCU SELECTION AS PER HEAT LOAD


Connections
S.N. TR CMH QTY (Facing the
Filter)
1 1.5 1020 3 R.H.S.

2 2.5 1700 6 R.H.S.

3 3 2040 2 R.H.S.

4 3 2040 1 L.H.S.

* For Connection side refer the layout drawing attched .

Page 12 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - TRANSPORT NAGAR STATION (TNG) DATE: 20.05.23 Rev-0
LOCATION: U05 (TOM) at consourse level 29.07.23 Rev-1
AREA: 104.571648 Sq ft 1715 Cu ft (Volume) Summer Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 107.78 73.4 19 36.75 68.8
(Sq ft) (Btu/h.sq ft) ROOM 77 65.63 55 30.4 76.5
N - Glass 0.0 23 0.56 0 DIFFERENCE 30.78 XXXX XXXX -7.7
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 2 People X 17 CFM/Person 34
S - Glass 0.0 12 0.56 0 1715 Cu ft X 1 Air change per hour 29
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 34
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.96
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 20.70 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 418 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 2 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 W/sqft.
SE - Wall 0.0 24 0.31 0 Eq. Load = 1.5 KW
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0
NW - Wall 0.0 32 0.31 0 Summer Load:
Roof Sun 0 51 0.1 0 TR = 0.97 TR
Roof Shaded 39 0 DEHUMIDIFIED CFM = 418 CFM
TRANS. GAIN EXCEPT WALLS & ROOF FRESH AIR REQUIRED = 41.79941585 CFM
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)

All Glass 0 30.78 0.56 0

Partition 217.8576 25.78 0.36 2022

Ceiling 0 25.78 0.36 0


Floor 0 25.78 0.36 0
INTERNAL HEAT GAIN
People 2 Nos X 443.3 887
Light 105 W 3.41 357
Eq. Load 1500 WX 3.41 5115
Misc Load 0.0 WX 3.41 0
8380
OUTSIDE AIR
CFM °F BF FACTOR
34 30.78 0.1 1.08 113
ROOM SENSIBLE HEAT (RSH) 8493
Supply duct Supply duct leak. Heat gain from fan 2
2
heat gain + loss + HP(%)
Safety factor (%) 10.0 849

EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 9345


LATENT HEAT
People 2 Nos X 205 410
OUTSIDE AIR
CFM GR/LB BF FACTOR
34 -7.7 0.1 0.67 -18
392
Supply duct leakage loss + Safety factor % 10.0 39
EFFECTIVE ROOM LATENT HEAT (ERLH) 432
EFFECTIVE ROOM TOTAL HEAT (ERTH) 9776
OUTSIDE AIR HEAT (SENSIBLE)

CFM °F 1 - BF FACTOR
34 30.78 0.9 1.08 1017
OUTSIDE AIR HEAT (LATENT)

CFM GR/LB 1 - BF FACTOR


34 -7.7 0.9 0.68 -160
HEAT SUB TOTAL 10633
Return duct HP Pump + Dehum. & Pipe 10.0 1063
heat gain & loss (%)
TR 0.97 GRAND TOTAL HEAT 11697

Page 13 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - TRANSPORT NAGAR STATION (TNG) DATE: 20.05.23 Rev-0
LOCATION: U05 (TOM) at consourse level 29.07.23 Rev-1
AREA: 104.571648 Sq ft 1715 Cu ft (Volume) Monsoon Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 91.4 84.2 74.5 48.38 168
(Sq ft) (Btu/h.sq ft) ROOM 77 65.63 55 30.4 76.5
N - Glass 0.0 23 0.56 0 DIFFERENCE 14.4 XXXX XXXX 91.5
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 2 People X 17 CFM/Person 34
S - Glass 0.0 12 0.56 0 1715 Cu ft X 1 Air change per hour 29
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 34
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.92
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 20.70 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 352 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 2 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 W/sqft.
SE - Wall 0.0 24 0.31 0 Eq. Load = 1.5 KW
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0
NW - Wall 0.0 32 0.31 0 Monsoon Load:
Roof Sun 0 51 0.1 0 TR = 1.00 TR
Roof Shaded 39 0 DEHUMIDIFIED CFM = 352 CFM
TRANS. GAIN EXCEPT WALLS & ROOF FRESH AIR REQUIRED = 35.17705939 CFM
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)

All Glass 0 14.4 0.56 0

Partition 217.8576 9.4 0.36 737

Ceiling 0 9.4 0.36 0


Floor 0 9.4 0.36 0
INTERNAL HEAT GAIN
People 2 Nos X 443.3 887
Light 105 W 3.41 357
Eq. Load 1500 WX 3.41 5115
Misc Load 0.0 WX 3.41 0
7095
OUTSIDE AIR
CFM °F BF FACTOR
34 14.4 0.1 1.08 53
ROOM SENSIBLE HEAT (RSH) 7148
Supply duct Supply duct leak. Heat gain from fan 2
1
heat gain + loss + HP(%)
Safety factor (%) 10.0 715

EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 7864


LATENT HEAT
People 2 Nos X 205 410
OUTSIDE AIR
CFM GR/LB BF FACTOR
34 91.5 0.1 0.67 208
618
Supply duct leakage loss + Safety factor % 10.0 62
EFFECTIVE ROOM LATENT HEAT (ERLH) 680
EFFECTIVE ROOM TOTAL HEAT (ERTH) 8544
OUTSIDE AIR HEAT (SENSIBLE)

CFM °F 1 - BF FACTOR
34 14.4 0.9 1.08 476
OUTSIDE AIR HEAT (LATENT)

CFM GR/LB 1 - BF FACTOR


34 91.5 0.9 0.68 1904
HEAT SUB TOTAL 10924
Return duct HP Pump + Dehum. & Pipe 10.0 1092
heat gain & loss (%)
TR 1.00 GRAND TOTAL HEAT 12017

Page 14 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - TRANSPORT NAGAR STATION (TNG) DATE: 20.05.23 Rev-0
LOCATION: U03 &U07 (EFO/SCR) concourse Lvl 29.07.23 Rev-1
AREA: 239.535776 Sq ft 3928 Cu ft (Volume) Summer Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 107.78 73.4 19 36.75 68.8
(Sq ft) (Btu/h.sq ft) ROOM 73.4 63.916 60 29.175 74
N - Glass 0.0 23 0.56 0 DIFFERENCE 34.38 XXXX XXXX -5.2
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 5 People X 17 CFM/Person 85
S - Glass 0.0 12 0.56 0 3928 Cu ft X 1 Air change per hour 65
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 85
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.94
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 17.46 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 935 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 5 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 W/sqft.
SE - Wall 0.0 24 0.31 0 Eq. Load = 2.5 KW
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0
NW - Wall 0.0 32 0.31 0 Summer Load:
Roof Sun 0.0 51 0.1 0 TR = 1.95 TR
Roof Shaded 39 0 DEHUMIDIFIED CFM = 935 CFM
TRANS. GAIN EXCEPT WALLS & ROOF FRESH AIR REQUIRED = 93.5274 CFM
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)

All Glass 0 34.38 0.56 0

Partition 392.6816 29.38 0.36 4153

Ceiling 0 29.38 0.36 0


Floor 0 29.38 0.36 0
INTERNAL HEAT GAIN
People 5 Nos X 443.3 2217
Light 240 W 3.41 817
Eq. Load 2500 WX 3.41 8525
Misc Load 0.0 WX 3.41 0
15712
OUTSIDE AIR
CFM °F BF FACTOR
85 34.38 0.1 1.08 316
ROOM SENSIBLE HEAT (RSH) 16027
Supply duct Supply duct leak. Heat gain from fan 2
6
heat gain + loss + HP(%)
Safety factor (%) 10.0 1603

EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 17636


LATENT HEAT
People 5 Nos X 205 1025
OUTSIDE AIR
CFM GR/LB BF FACTOR
85 -5.2 0.1 0.67 -30
995
Supply duct leakage loss + Safety factor % 10.0 100
EFFECTIVE ROOM LATENT HEAT (ERLH) 1095
EFFECTIVE ROOM TOTAL HEAT (ERTH) 18731
OUTSIDE AIR HEAT (SENSIBLE)

CFM °F 1 - BF FACTOR
85 34.38 0.9 1.08 2840
OUTSIDE AIR HEAT (LATENT)

CFM GR/LB 1 - BF FACTOR


85 -5.2 0.9 0.68 -271
HEAT SUB TOTAL 21301
Return duct HP Pump + Dehum. & Pipe 10.0 2130
heat gain & loss (%)
TR 1.95 GRAND TOTAL HEAT 23431

Page 15 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - TRANSPORT NAGAR STATION (TNG) DATE: 20.05.23 Rev-0
LOCATION: U03 &U07 (EFO/SCR) concourse Lvl 29.07.23 Rev-1
AREA: 239.535776 Sq ft 3928 Cu ft (Volume) Monsoon Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 91.4 84.2 74.5 48.38 168
(Sq ft) (Btu/h.sq ft) ROOM 73.4 63.916 60 29.175 74
N - Glass 0.0 23 0.56 0 DIFFERENCE 18 XXXX XXXX 94
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 5 People X 17 CFM/Person 85
S - Glass 0.0 12 0.56 0 3928 Cu ft X 1 Air change per hour 65
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 85
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.90
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 17.46 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 791 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 5 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 W/sqft.
SE - Wall 0.0 24 0.31 0 Eq. Load = 2.5 KW
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0
NW - Wall 0.0 32 0.31 0 Monsoon Load:
Roof Sun 0.0 51 0.1 0 TR = 2.11 TR
Roof Shaded 39 0 DEHUMIDIFIED CFM = 791 CFM
TRANS. GAIN EXCEPT WALLS & ROOF FRESH AIR REQUIRED = 85 CFM
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)

All Glass 0 18 0.56 0

Partition 392.6816 13 0.36 1838

Ceiling 0 13 0.36 0
Floor 0 13 0.36 0
INTERNAL HEAT GAIN
People 5 Nos X 443.3 2217
Light 240 W 3.41 817
Eq. Load 2500 WX 3.41 8525
Misc Load 0.0 WX 3.41 0
13396
OUTSIDE AIR
CFM °F BF FACTOR
85 18 0.1 1.08 165
ROOM SENSIBLE HEAT (RSH) 13561
Supply duct Supply duct leak. Heat gain from fan 2
3
heat gain + loss + HP(%)
Safety factor (%) 10.0 1356

EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 14921


LATENT HEAT
People 5 Nos X 205 1025
OUTSIDE AIR
CFM GR/LB BF FACTOR
85 94 0.1 0.67 535
1560
Supply duct leakage loss + Safety factor % 10.0 156
EFFECTIVE ROOM LATENT HEAT (ERLH) 1716
EFFECTIVE ROOM TOTAL HEAT (ERTH) 16637
OUTSIDE AIR HEAT (SENSIBLE)

CFM °F 1 - BF FACTOR
85 18 0.9 1.08 1487
OUTSIDE AIR HEAT (LATENT)

CFM GR/LB 1 - BF FACTOR


85 94 0.9 0.68 4890
HEAT SUB TOTAL 23014
Return duct HP Pump + Dehum. & Pipe 10.0 2301
heat gain & loss (%)
TR 2.11 GRAND TOTAL HEAT 25316

Page 16 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - TRANSPORT NAGAR STATION (TNG) DATE: 20.05.23 Rev-0
LOCATION: U09 (Security Rm) concourse level 29.07.23 Rev-1
AREA: 166.1938482 Sq ft 2726 Cu ft (Volume) Summer Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 107.78 73.4 19 36.75 68.8
(Sq ft) (Btu/h.sq ft) ROOM 77 65.63 55 30.4 76.5
N - Glass 0.0 23 0.56 0 DIFFERENCE 30.78 XXXX XXXX -7.7
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 2 People X 17 CFM/Person 34
S - Glass 0.0 12 0.56 0 2726 Cu ft X 1 Air change per hour 45
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 45
W - Glass 0.0 163 0.56 0 s
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.95
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 20.70 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 380 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 2 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 W/sqft.
SE - Wall 0.0 24 0.31 0 Eq. Load = 1 KW
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0

NW - Wall 0.0 32 0.31 0 Summer Load:


Roof Sun 0 51 0.1 0 TR = 0.92 TR
Roof Shaded 39 0 DEHUMIDIFIED CFM = 380 CFM
TRANS. GAIN EXCEPT WALLS & ROOF FRESH AIR REQUIRED = 38.0144 CFM
ITEM Area Temp. diff. U

(Sq ft) (°F) (Btu/h.sq ft)

All Glass 0 30.78 0.56 0

Partition 291.875392 25.78 0.36 2709


Ceiling 0 25.78 0.36 0

Floor 0 25.78 0.36 0


INTERNAL HEAT GAIN
People 2 Nos X 443.3 887
Light 166 W 3.41 567
Eq. Load 1000 WX 3.41 3410
Misc Eq. Load 0 WX 3.41 0
7572
OUTSIDE AIR

CFM °F BF FACTOR
45 30.78 0.1 1.08 151
ROOM SENSIBLE HEAT (RSH) 7723
Supply duct Supply duct leak. Heat gain from fan 2
3
heat gain + loss + HP(%)
Safety factor (%) 10.0 772

EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 8499


LATENT HEAT
People 2 Nos X 205 410
OUTSIDE AIR
CFM GR/LB BF FACTOR
45 -7.7 0.1 0.67 -23
387
Supply duct leakage loss + Safety factor % 10.0 39
EFFECTIVE ROOM LATENT HEAT (ERLH) 425
EFFECTIVE ROOM TOTAL HEAT (ERTH) 8924
OUTSIDE AIR HEAT (SENSIBLE)

CFM °F 1 - BF FACTOR
45 30.78 0.9 1.08 1359
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
45 -7.7 0.9 0.68 -214
HEAT SUB TOTAL 10069
Return duct HP Pump + Dehum. & Pipe 10.0 1007
heat gain & loss (%)
TR 0.92 GRAND TOTAL HEAT 11076

Page 17 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - TRANSPORT NAGAR STATION (TNG) DATE: 20.05.23 Rev-0
LOCATION: U09 (Security Rm) concourse level 29.07.23 Rev-1
AREA: 165.356608 Sq ft 2712 Cu ft (Volume) Monsoon Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 91.4 84.2 74.5 48.38 168
(Sq ft) (Btu/h.sq ft) ROOM 77 65.63 55 30.4 76.5
N - Glass 0.0 23 0.56 0 DIFFERENCE 14.4 XXXX XXXX 91.5
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 2 People X 17 CFM/Person 34
S - Glass 0.0 12 0.56 0 2712 Cu ft X 1 Air change per hour 45
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 45
W - Glass 0.0 163 0.56 0 s
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.90
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 20.70 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 290 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 2 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 W/sqft.
SE - Wall 0.0 24 0.31 0 Eq. Load = 1 KW
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0

NW - Wall 0.0 32 0.31 0 Monsoon Load:


Roof Sun 0 51 0.1 0 TR = 0.95 TR
Roof Shaded 39 0 DEHUMIDIFIED CFM = 290 CFM
TRANS. GAIN EXCEPT WALLS & ROOF FRESH AIR REQUIRED = 34 CFM
ITEM Area Temp. diff. U

(Sq ft) (°F) (Btu/h.sq ft)

All Glass 0 14.4 0.56 0

Partition 285.0976 9.4 0.36 965


Ceiling 0 9.4 0.36 0

Floor 0 9.4 0.36 0


INTERNAL HEAT GAIN
People 2 Nos X 443.3 887
Light 165 W 3.41 564
Eq. Load 1000 WX 3.41 3410
Misc Eq. Load 0 WX 3.41 0
5825
OUTSIDE AIR

CFM °F BF FACTOR
45 14.4 0.1 1.08 70
ROOM SENSIBLE HEAT (RSH) 5896
Supply duct Supply duct leak. Heat gain from fan 2
1
heat gain + loss + HP(%)
Safety factor (%) 10.0 590

EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 6486


LATENT HEAT
People 2 Nos X 205 410
OUTSIDE AIR
CFM GR/LB BF FACTOR
45 91.5 0.1 0.67 277
687
Supply duct leakage loss + Safety factor % 10.0 69
EFFECTIVE ROOM LATENT HEAT (ERLH) 756
EFFECTIVE ROOM TOTAL HEAT (ERTH) 7242
OUTSIDE AIR HEAT (SENSIBLE)

CFM °F 1 - BF FACTOR
45 14.4 0.9 1.08 633
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
45 91.5 0.9 0.68 2531
HEAT SUB TOTAL 10406
Return duct HP Pump + Dehum. & Pipe 10.0 1041
heat gain & loss (%)
TR 0.95 GRAND TOTAL HEAT 11446

Page 18 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - TRANSPORT NAGAR STATION (TNG) DATE: 20.05.23 Rev-0
LOCATION: U22 & U23 (SER+TER) Platform level 29.07.23 Rev-1
AREA: 586.010048 Sq ft 9611 Cu ft Summer Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 107.78 73.4 19 36.75 68.8
(Sq ft) (Btu/h.sq ft) ROOM 73.4 63.916 60 29.175 74
N - Glass 0.0 23 0.56 0 DIFFERENCE 34.38 XXXX XXXX -5.2
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 1 People X 16 CFM/Person 16
S - Glass 0.0 12 0.56 0 9611 Cu ft X 1 Air change per hour 160
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 160
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 1.00
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 17.46 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 3689 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 1 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 KW
SE - Wall 0.0 24 0.31 0 Eq. Load = 13.45 KW Misc Load 0.3
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0

NW - Wall 0.0 32 0.31 0 Summer Load:


Roof Sun 0 51 0.1 0 TR = 6.84 TR
Roof Shaded 39 0 DEHUMIDIFIED CFM = 3689 CFM
TRANS. GAIN EXCEPT WALLS & ROOF FRESH AIR REQUIRED = 368.933 CFM
ITEM Area Temp. diff. U

(Sq ft) (°F) (Btu/h.sq ft)


All Glass 0 34.38 0.56 0

Partition 1251.20192 29.38 0.36 13234

Ceiling 0 29.38 0.36 0


Floor 0 29.38 0.36 0
INTERNAL HEAT GAIN
People 1 Nos X 443.3 443
Light 586 W X 1.25 3.41 2498
Eq. Load 13450 WX 3.41 45865
Misc Load 175.8 WX 3.41 599
62639
OUTSIDE AIR

CFM °F BF FACTOR
160 34.38 0.1 1.08 595
ROOM SENSIBLE HEAT (RSH) 63234
Supply duct Supply duct leak. Heat gain from fan 2
12
heat gain + loss + HP(%)
Safety factor (%) 10.0 6323

EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 69569


LATENT HEAT
People 1 Nos X 205 205
OUTSIDE AIR
CFM GR/LB BF FACTOR
160 -5.2 0.1 0.67 -56
149
Supply duct leakage loss + Safety factor % 10.0 15
EFFECTIVE ROOM LATENT HEAT (ERLH) 164
EFFECTIVE ROOM TOTAL HEAT (ERTH) 69733
OUTSIDE AIR HEAT (SENSIBLE)

CFM °F 1 - BF FACTOR
160 34.38 0.9 1.08 5353
OUTSIDE AIR HEAT (LATENT)

CFM GR/LB 1 - BF FACTOR


160 -5.2 0.9 0.68 -510
HEAT SUB TOTAL 74576
Return duct HP Pump + Dehum. & Pipe 10.0 7458
heat gain & loss (%)
TR 6.84 GRAND TOTAL HEAT 82033

Page 19 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - TRANSPORT NAGAR STATION (TNG) DATE: 20.05.23 Rev-0
LOCATION: U22 & U23 (SER+TER) Platform level 29.07.23 Rev-1
AREA: 586.010048 Sq ft 9611 Cu ft Monsoon Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 91.4 84.2 74.5 48.38 168
(Sq ft) (Btu/h.sq ft) ROOM 73.4 63.916 60 29.175 74
N - Glass 0.0 23 0.56 0 DIFFERENCE 18 XXXX XXXX 94
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 1 People X 16 CFM/Person 16
S - Glass 0.0 12 0.56 0 9611 Cu ft X 1 Air change per hour 160
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 160
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.98
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 17.46 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 3207 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 1 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 KW
SE - Wall 0.0 24 0.31 0 Eq. Load = 13.45 KW
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0

NW - Wall 0.0 32 0.31 0 Monsoon Load:


Roof Sun 0 51 0.1 0 TR = 6.77 TR
Roof Shaded 39 0 DEHUMIDIFIED CFM = 3207 CFM
TRANS. GAIN EXCEPT WALLS & ROOF FRESH AIR REQUIRED = 320.713 CFM
ITEM Area Temp. diff. U

(Sq ft) (°F) (Btu/h.sq ft)


All Glass 0 18 0.56 0

Partition 1251.20192 13 0.36 5856

Ceiling 0 13 0.36 0
Floor 0 13 0.36 0
INTERNAL HEAT GAIN
People 1 Nos X 443.3 443
Light 586 W X 1.25 3.41 2498
Eq. Load 13450 WX 3.41 45865
Misc Load 0.0 WX 3.41 0
54661
OUTSIDE AIR

CFM °F BF FACTOR
160 18 0.1 1.08 311
ROOM SENSIBLE HEAT (RSH) 54973
Supply duct Supply duct leak. Heat gain from fan 2
6
heat gain + loss + HP(%)
Safety factor (%) 10.0 5497

EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 60476


LATENT HEAT
People 1 Nos X 205 205
OUTSIDE AIR
CFM GR/LB BF FACTOR
160 94 0.1 0.67 1009
1214
Supply duct leakage loss + Safety factor % 10.0 121
EFFECTIVE ROOM LATENT HEAT (ERLH) 1335
EFFECTIVE ROOM TOTAL HEAT (ERTH) 61811
OUTSIDE AIR HEAT (SENSIBLE)

CFM °F 1 - BF FACTOR
160 18 0.9 1.08 2802
OUTSIDE AIR HEAT (LATENT)

CFM GR/LB 1 - BF FACTOR


160 94 0.9 0.68 9215
HEAT SUB TOTAL 73828
Return duct HP Pump + Dehum. & Pipe 10.0 7383
heat gain & loss (%)
TR 6.77 GRAND TOTAL HEAT 81211

Page 20 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - TRANSPORT NAGAR STATION (TNG) DATE: 20.05.23 Rev-0
LOCATION: U24 & U27 (UPS Rm) at platform level 29.07.23 Rev-1
AREA: 895.475424 Sq ft 14686 Cu ft (Volume) Summer Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 107.78 73.4 19 36.75 68.8
(Sq ft) (Btu/h.sq ft) ROOM 73.4 63.916 60 29.175 74
N - Glass 0.0 23 0.56 0 DIFFERENCE 34.38 XXXX XXXX -5.2
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 1 People X 16 CFM/Person 16
S - Glass 0.0 12 0.56 0 14686 Cu ft X 1 Air change per hour 245
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 245
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 1.00
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 17.46 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 2965 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 1 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 KW
SE - Wall 0.0 24 0.31 0 Eq. Load = 8.23 KW Misc load 0.55
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0

NW - Wall 0.0 32 0.31 0 Summer Load:


Roof Sun 0 51 0.1 0 TR = 5.82 TR
Roof Shaded 39 0 DEHUMIDIFIED CFM = 2965 CFM
TRANS. GAIN EXCEPT WALLS & ROOF FRESH AIR REQUIRED = 296.482 CFM
ITEM Area Temp. diff. U

(Sq ft) (°F) (Btu/h.sq ft)

All Glass 0 34.38 0.56 0

Partition 1463.1424 29.38 0.36 15475

Ceiling 0 29.38 0.36 0

Floor 0 29.38 0.36 0


INTERNAL HEAT GAIN
People 1 Nos X 443.3 443
Light 895 W X 1.25 3.41 3817
Eq. Load 8230 WX 3.41 28064
Misc Eq Load 493 WX 3.41 2099
49899
OUTSIDE AIR

CFM °F BF FACTOR

245 34.38 0.1 1.08 909


ROOM SENSIBLE HEAT (RSH) 50808
Supply duct Supply duct leak. Heat gain from fan 2
18
heat gain + loss + HP(%)
Safety factor (%) 10.0 5081

EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 55907


LATENT HEAT
People 1 Nos X 205 205
OUTSIDE AIR
CFM GR/LB BF FACTOR
245 -5.2 0.1 0.67 -85
120
Supply duct leakage loss + Safety factor % 10.0 12
EFFECTIVE ROOM LATENT HEAT (ERLH) 132
EFFECTIVE ROOM TOTAL HEAT (ERTH) 56039
OUTSIDE AIR HEAT (SENSIBLE)

CFM °F 1 - BF FACTOR
245 34.38 0.9 1.08 8179
OUTSIDE AIR HEAT (LATENT)

CFM GR/LB 1 - BF FACTOR


245 -5.2 0.9 0.68 -779
HEAT SUB TOTAL 63439
Return duct HP Pump + Dehum. & Pipe 10.0 6344
heat gain & loss (%)
TR 5.82 GRAND TOTAL HEAT 69783

Page 21 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - TRANSPORT NAGAR STATION (TNG) DATE: 20.05.23 Rev-0
LOCATION: U24 & U27 (UPS Rm) at platform level 29.07.23 Rev-1
AREA: 895.475424 Sq ft 14686 Cu ft (Volume) Monsoon Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 91.4 84.2 74.5 48.38 168
(Sq ft) (Btu/h.sq ft) ROOM 73.4 63.916 60 29.175 74
N - Glass 0.0 23 0.56 0 DIFFERENCE 18 XXXX XXXX 94
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 1 People X 16 CFM/Person 16
S - Glass 0.0 12 0.56 0 14686 Cu ft X 1 Air change per hour 245
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 245
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.96
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 17.46 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 2436 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 1 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 KW
SE - Wall 0.0 24 0.31 0 Eq. Load = 8.23 KW Misc load 0.55
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0

NW - Wall 0.0 32 0.31 0 Monsoon Load:


Roof Sun 0 51 0.1 0 TR = 6.07 TR
Roof Shaded 39 0 DEHUMIDIFIED CFM = 2436 CFM
TRANS. GAIN EXCEPT WALLS & ROOF FRESH AIR REQUIRED = 243.58 CFM
ITEM Area Temp. diff. U

(Sq ft) (°F) (Btu/h.sq ft)

All Glass 0 18 0.56 0

Partition 1463.1424 13 0.36 6848

Ceiling 0 13 0.36 0

Floor 0 13 0.36 0
INTERNAL HEAT GAIN
People 1 Nos X 443.3 443
Light 895 W X 1.25 3.41 3817
Eq. Load 8230 WX 3.41 28064
Misc Eq Load 493 WX 3.41 2099
41271
OUTSIDE AIR

CFM °F BF FACTOR

245 18 0.1 1.08 476


ROOM SENSIBLE HEAT (RSH) 41747
Supply duct Supply duct leak. Heat gain from fan 2
10
heat gain + loss + HP(%)
Safety factor (%) 10.0 4175

EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 45931


LATENT HEAT
People 1 Nos X 205 205
OUTSIDE AIR
CFM GR/LB BF FACTOR
245 94 0.1 0.67 1542
1747
Supply duct leakage loss + Safety factor % 10.0 175
EFFECTIVE ROOM LATENT HEAT (ERLH) 1921
EFFECTIVE ROOM TOTAL HEAT (ERTH) 47853
OUTSIDE AIR HEAT (SENSIBLE)

CFM °F 1 - BF FACTOR
245 18 0.9 1.08 4282
OUTSIDE AIR HEAT (LATENT)

CFM GR/LB 1 - BF FACTOR


245 94 0.9 0.68 14081
HEAT SUB TOTAL 66216
Return duct HP Pump + Dehum. & Pipe 10.0 6622
heat gain & loss (%)
TR 6.07 GRAND TOTAL HEAT 72837

Page 22 of 46
U-factor calculation for Platform roof 750mm thickness RCC block
S.No. Description Roof Thermal Resistance - R Reference
R1 Outside Air Resistance 0.25 ISHRAE edision 2017, Table 1.20
R2 Cement plaster 1/2 Inch thick above the 0.15 ISHRAE edision 2017, Table 1.20
roof
R3 Cement plaster 1/2 Inch thick below the 0.15 ISHRAE edision 2017, Table 1.20
roof
R4 750 mm heavy weight concrete slab 5.91 ISHRAE edision 2017, Table 1.20

Total - R 6.46
U - Factor = 1/R
0.15

U-factor calculation for concourse roof 1200mm thickness RCC block


S.No. Description Roof Thermal Resistance - R Reference
R1 Outside Air Resistance 0.25 ISHRAE edision 2017, Table 1.20
R2 Cement plaster 1/2 Inch thick above the 0.15 ISHRAE edision 2017, Table 1.20
roof
R3 Cement plaster 1/2 Inch thick below the 0.15 ISHRAE edision 2017, Table 1.20
roof
R4 1200 mm heavy weight concrete slab 9.45 ISHRAE edision 2017, Table 1.20

Total - R 10.00
U - Factor = 1/R
0.10

U-factor calculation for walls


S.No. Description Roof Thermal Resistance - R Reference
R1 Outside Air Resistance 0.25 ISHRAE edision 2017, Table 1.20
R2 Cement plaster 1/2 Inch thick above the 0.15 ISHRAE edision 2017, Table 1.20
roof
R3 Cement plaster 1/2 Inch thick below the 0.15 ISHRAE edision 2017, Table 1.20
roof
R4 wall 2 cell deep of 8 Inch thickness 1.85 ISHRAE edision 2017, Table 1.20
R5 Internal air resistance (vertical) 0.86 ISHRAE edision 2017, Table 1.20
Total - R 3.26
U - Factor = 1/R
0.31

Page 23 of 46
Interface KNPCC06 <interfaceknpcc06@samindia.com>

Inputs required for Interface -KNPCC06 Project.


Interface KNPCC06 <interfaceknpcc06@samindia.com> Sun, Feb 19, 2023 at 10:14 AM
To: MEP Kanpur <mepkanpur@samindia.com>

for your reference

---------- Forwarded message ---------


From: Umendra Malik <umendra.malik@aurionpro.com>
Date: Fri, Feb 17, 2023 at 2:56 PM
Subject: Re: Inputs required for Interface -KNPCC06 Project.
To: interfaceknpcc06@samindia.com <interfaceknpcc06@samindia.com>,
Akshay Goel <akshay.goel@aurionpro.com>
Cc: amit n <amit.n@typsaitalferrgc.com>, mansi upmrc
<mansi.upmrc@gmail.com>, Sudeep Katiyar
<sudeep.katiyar@aurionpro.com>, Deepak Sharma
<Deepak.Sharma9@in.ey.com>, Pramod Kumar <pramod.kumar@aurionpro.com>,
PADMAKAR SHUKLA <padmakar.shukla@upmrcl.co.in>, Pankaj Yadav
<pankaj.yadav@upmrcl.co.in>, Pushkar Arora
<pushkar.arora@aurionpro.com>, Anurag Mishra
<anurag.m@typsaitalferrgc.com>
[Quoted text hidden]

2 attachments
Interface Specifications UPMRC.pdf
949K
AFC Electrical Load & Heat Load..xlsx
14K

Page 24 of 46
Typical Power Requirement for AFC Equipment at Station (Elevated) Entry & Exit Single Array)

Total KVA = Additional 25%


TR, N/W Switch Total
Type ITEM AG with Validator TOM/EFO TVM SC Kwatt/power for future
& Others Power
factor Equipments
Number of Equipment 7 3 4 1 LS
Watt/Per Equipment 300 250 600 600 300
Station
Total Watt = Watt * no of equipment 2100 750 2400 600 300
Kw=Watt/1000 2.1 0.75 2.4 0.6 0.3 6.15 7.6875 10
1Watt = 3.415BTU/hr 7.1715 2.5612 8.196 2.049 1.0245 21.0022 N/A 26.25275
Heat Dissipation per unit in BTU/Hr

Typical Power Requirement for AFC Equipment at Station (Underground) Entry & Exit - Double Array)
Total KVA = Additional 25%
TR, N/W Switch Total
Type ITEM AG with Validator TOM/EFO TVM SC Kwatt/power for future
& Others Power
factor Equipments
Number of Equipment 14 6 3 1 LS
Watt/Per Equipment 300 250 600 600 300
Station Total Watt = Watt * no of equipment 4200 1500 1800 600 300
Kw=Watt/1000 4.2 1.5 1.8 0.6 0.3 8.4 10.5 13
1Watt = 3.415BTU/hr 14.343 5.1225 6.147 2.049 1.0245 28.686 N/A 35.8575
Heat Dissipation per unit in BTU/Hr
1 amp is equal to 120 W. ... At 220V, 1 amp is equal to 220 watts. Here is

Page 25 of 46
ECSTVS Design <ecstvsdesign@samindia.com>

Discrepancy in Heat load for KNPCC06


Nasir Abdullah <nasir.a@typsaitalferrgc.com> Tue, Sep 5, 2023 at 11:21 AM
To: ECSTVS Design <ecstvsdesign@samindia.com>, E&M KNPCC06 <enmknpcc06@samindia.co>
Cc: Daniel Beshah <daniel.b@typsaitalferrgc.com>, Dhiman Majumdar <dhiman.m@typsaitalferrgc.com>, Sudhanshu
Shekhar Joshi <sudhanshu.j@typsaitalferrgc.com>, Shyamal Kanti Biswas <shyamal.b@typsaitalferrgc.com>, Divakar
Jha <divakar.j@typsaitalferrgc.com>, Ashutosh Kumar <ashutosh.k@typsaitalferrgc.com>, Shiva Seth
<shiva.s@typsaitalferrgc.com>, Arun Kumar Katiyar <arun.k@typsaitalferrgc.com>, Gaurav Rastogi
<gaurav.rastogi@hfcl.com>, Raushan Kumar <raushan.k@typsaitalferrgc.com>, Ashwani Gautam
<ashwani.g@typsaitalferrgc.com>

Dear Sir,

In continuation of trailing mail, a meeting has been conducted & the following points finalized.

1. Heat load in TER:- 13.45 kW.


2. Heat Load in UPS Room: 8.23 kW (Non-Interlocking station).

This is for your information & record.

Thanks and Regards,

Nasir Abdullah | Sr System Interface Expert-K2 | Kanpur & Agra Metro Projects | TYPSA-ITALFERR JV |
Phone: +91 9899664537 | Email address: nasir.a@typsaitalferrgc.com |

710 & 711, Levana Cyber Height, Vibhuti Khand, Gomti Nagar, Lucknow | Uttar Pradesh - 226010 | India |

-----Original Appointment-----
From: Nasir Abdullah
Sent: Tuesday, September 5, 2023 10:52 AM
To: Nasir Abdullah; ECSTVS Design; E&M KNPCC06; Divakar Jha; Ashutosh Kumar; Shiva Seth; Arun Kumar Katiyar;
Gaurav Rastogi; Raushan Kumar
Cc: Daniel Beshah; Dhiman Majumdar; Sudhanshu Shekhar Joshi
Subject: Discrepancy in Heat load for KNPCC06
When: 05 September 2023 11:00-12:00 (UTC+05:30) Chennai, Kolkata, Mumbai, New Delhi.
Where: Microsoft Teams Meeting
[Quoted text hidden]

Page 26 of 46
12 13

Page 27 of 46
CONCOURSE LEVEL
1
Page 28 of 46
9
CONCOURSE LEVEL
1
13

Page 29 of 46
TR
C
CONCOURSE LEVEL
1
B
19500

9800
1
PLATFORM LEVEL

LOOP FRAME
F F
F

LOOP FRAME

15
OKS

ACDB
ACS Panel

DCDB
ACS Panel

MDF
IDF

OKS
LOOP BOX 3 & 4 LOOP BOX 1 & 2

INCOMMER INCOMMER SPARE CELL


01 02 FOR SMPS
BATTERY-1
SMPS
SPARE CELL
FOR SMPS
CHARGER

BATTERY-2
SMPS

13595
O/P PANEL

SPARE CELL UPS SPARE


FOR UPS CELL CHARGER
SMPS-2
SMPS-1
OAIT

ATS
BATTERY RACK- 2/2

SCVS
BATTERY RACK- 1/2

UPS-2
45 KVA

UPS-1 BATTERY RACK- 2/2


45 KVA

20KVA BATTERY RACK- 1/2


IT
16

BCB-2 BCB-1

Page 30 of 46
KNPCC-06-Design and Construction of TBM Tunnel, Cut & Cover Tunnel and
underground ramp from Kanpur Central end of Nayaganj station to elevated ramp
after Transport Nagar and three underground metro stations (viz. Kanpur Central,
Jhakarkatti and Transport Nagar) including Architectural finishes, E & M, TVS, ECS
etc. on Corridor-1 of Kanpur MRTS Project at Kanpur, Uttar Pradesh, India.

JHAKAR KATTI
BUS TERMINAL
STATION

Page 31 of 46
KNPCC 06_JBT Heat Load Summary For FCU
Equipment Tonnage Air Flow
Area Occupancy Selected Unit (FCU) QTY
S. No. Name of Area Room No. Load (TR) (CFM) Remarks
(Sqft) (Nos.) (kW) Summer Monsoon Summer Monsoon TR x Nos REMARKS

1 TOM U-05 108 2 1.5 0.74 1.41 275 514 1.5 x 2 1 W + 1S

2 SCR / EFO U-03 & U07 269 5 2.1 1.37 1.46 566 427 1.5 x 2 1 W + 1S

Technical Area
3 Security Rm U-09 97 6 1 0.93 0.73 285 220 1.5 x 1 1W
Room
Selected the FCU to achive TR, not
4 SER+TER U-22&23 520 1 13.45 7.13 6.95 3593 3310 2.5 x 4 3W + 1S
cfm bcos occupancy is very less.
Comb. UPS Selected the FCU to achive TR, not
5 U-24&27 692 1 8.23 5.72 5.63 2789 2403 3.0 x 3 2 W + 1S
Room cfm bcos occupancy is very less.

Equipment Load Details


1 TOM /EFO Room 1.5 KW load for reference vendor confirmation mail copy attached.
2 In SCR Room, we Assumed 1.0 KW Equipment Load.

3 In SER/TER Room, 13.45 KW equipement Load cosider as confirmed by mail (attached)

4 In UPS Room, 8.23 KW equipement Load conisder as as confirmed by mail (attached)

* We are Referred the latest architectural drawing received via letter no Kanpur-LET-JVTI-ARC-00834-E01 on dated 12.09.23.

FCU SELECTION AS PER HEAT LOAD


Connections
S.N. TR CMH QTY (Facing the
Filter)

1 1.5 1020 2 L.H.S.

2 1.5 1020 3 R.H.S.

3 2.5 1700 3 L.H.S.

4 2.5 1700 1 R.H.S.

5 3 2040 2 L.H.S.

6 3 2040 1 R.H.S.

* For Connection side refer the layout drawing attched .

Page 32 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - JHAKAR KATI BUS TERMINAL (JBT) Date 17.05.23 Rev-1
LOCATION: U 05 (TOM) at Concourse 29.07.23 Rev-2
AREA: 107.6 Sq ft 2120 Cu ft (Volume) Summer Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 107.78 73.4 19 36.75 68.8
(Sq ft) (Btu/h.sq ft) ROOM 80.6 68.675 55 32.87 86.3
N - Glass 0.0 23 0.56 0 DIFFERENCE 27.18 XXXX XXXX -17.5
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 2 People X 17 CFM/Person 34
S - Glass 0.0 12 0.56 0 2120 Cu ft X 1 Air change per hour 35
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 35
W - Glass 0.0 163 0.56 0 s
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.95
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 23.94 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 275 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 2 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 W/sqft.
SE - Wall 0.0 24 0.31 0 Eq. Load = 1.5 KW
S - Wall 0.0 34 0.31 0 Height = 19.7 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0

NW - Wall 0.0 32 0.31 0 Summer Load:


Roof Sun 0 51 0.1 0 TR = 0.74 TR
Roof Shaded 39 0 DEHUMIDIFIED CFM = 275 CFM
TRANS. GAIN EXCEPT WALLS & ROOF FRESH AIR REQUIRED = 34 CFM
ITEM Area Temp. diff. U

(Sq ft) (°F) (Btu/h.sq ft)

All Glass 0 27.18 0.56 0

Partition 0 22.18 0.31 0

Ceiling 0 22.18 0.36 0

Floor 0 22.18 0.36 0


INTERNAL HEAT GAIN
People 2 Nos X 443.3 887
Light 108 W 3.41 367
Eq. Load 1500 WX 3.41 5115
Misc Eq. Load 0 WX 3.41 0
6369
OUTSIDE AIR

CFM °F BF FACTOR

35 27.18 0.1 1.08 104


ROOM SENSIBLE HEAT (RSH) 6472
Supply duct Supply duct leak. loss Heat gain from fan 2
2
heat gain + + HP(%)
Safety factor (%) 10.0 647

EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 7122


LATENT HEAT
People 2 Nos X 205 410
OUTSIDE AIR
CFM GR/LB BF FACTOR
35 -17.5 0.1 0.67 -41
369
Supply duct leakage loss + Safety factor % 10.0 37
EFFECTIVE ROOM LATENT HEAT (ERLH) 405
EFFECTIVE ROOM TOTAL HEAT (ERTH) 7527
OUTSIDE AIR HEAT (SENSIBLE)

CFM °F 1 - BF FACTOR
35 27.18 0.9 1.08 933
OUTSIDE AIR HEAT (LATENT)

CFM GR/LB 1 - BF FACTOR


35 -17.5 0.9 0.68 -378
HEAT SUB TOTAL 8082
Return duct HP Pump + Dehum. & Pipe 10.0 808
heat gain & loss (%)
TR 0.74 GRAND TOTAL HEAT 8890

Page 33 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - JHAKAR KATI BUS TERMINAL (JBT) Date 17.05.23 Rev-1
LOCATION: U 05 (TOM) at Concourse 29.07.23 Rev-2
AREA: 107.6 Sq ft 2120 Cu ft (Volume) Monsoon Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 91.4 84.2 74.5 48.38 168
(Sq ft) (Btu/h.sq ft) ROOM 80.6 68.675 55 32.87 86.3
N - Glass 0.0 23 0.56 0 DIFFERENCE 10.8 XXXX XXXX 81.7
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 2 People X 17 CFM/Person 34
S - Glass 0.0 12 0.56 0 2120 Cu ft X 1 Air change per hour 35
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 35
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.95
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 23.94 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 514 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 2 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 W/sqft.
SE - Wall 0.0 24 0.31 0 Eq. Load = 3 KW
S - Wall 0.0 34 0.31 0 Height = 19.7 FT
SW - Wall 0.0 48 0.31 0
Calculated Load Summary
W - Wall 0.0 48 0.31 0

NW - Wall 0.0 32 0.31 0 Monsoon Condition


Roof Sun 107.6 51 0.1 549 TR = 1.41 TR
Roof Shaded 39 0 DEHUMIDIFIED CFM = 514 CFM
TRANS. GAIN EXCEPT WALLS & ROOF FRESH AIR REQUIRED = 51.3694 CFM
ITEM Area Temp. diff. U

(Sq ft) (°F) (Btu/h.sq ft)

All Glass 0 10.8 0.56 0

Partition 0 5.8 0.31 0

Ceiling 0 5.8 0.36 0

Floor 0 5.8 0.36 0


INTERNAL HEAT GAIN
People 2 Nos X 443.3 887
Light 108 W 3.41 367
Eq. Load 3000 WX 3.41 10230
Misc Eq. Load 0 WX 3.41 0
12032
OUTSIDE AIR

CFM °F BF FACTOR

35 10.8 0.1 1.08 41


ROOM SENSIBLE HEAT (RSH) 12073
Supply duct Supply duct leak. loss Heat gain from fan 2
1
heat gain + + HP(%)
Safety factor (%) 10.0 1207

EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 13282


LATENT HEAT
People 2 Nos X 205 410
OUTSIDE AIR
CFM GR/LB BF FACTOR
35 81.7 0.1 0.67 193
603
Supply duct leakage loss + Safety factor % 10.0 60
EFFECTIVE ROOM LATENT HEAT (ERLH) 664
EFFECTIVE ROOM TOTAL HEAT (ERTH) 13945
OUTSIDE AIR HEAT (SENSIBLE)

CFM °F 1 - BF FACTOR
35 10.8 0.9 1.08 371
OUTSIDE AIR HEAT (LATENT)

CFM GR/LB 1 - BF FACTOR


35 81.7 0.9 0.68 1766
HEAT SUB TOTAL 16083
Return duct HP Pump + Dehum. & Pipe 5.0 804
heat gain & loss (%)
TR 1.41 GRAND TOTAL HEAT 16887

Page 34 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - JHAKAR KATI BUS TERMINAL (JBT) Date 17.05.23 Rev-1
LOCATION: U 03/U07 (SCR/EFO) at Concourse 29.07.23 Rev-2
AREA: 269 Sq ft 5299 Cu ft (Volume) Summer Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 107.78 73.4 19 36.75 68.8
(Sq ft) (Btu/h.sq ft) ROOM 75.2 65.475 60 30.348 78.7
N - Glass 0.0 23 0.56 0 DIFFERENCE 32.58 XXXX XXXX -9.9
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 5 People X 17 CFM/Person 85
S - Glass 0.0 12 0.56 0 5299 Cu ft X 1 Air change per hour 88
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 88
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.92
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 19.08 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 566 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 5 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 W/sqft.
SE - Wall 0.0 24 0.31 0 Eq. Load = 2.1 KW
S - Wall 0.0 34 0.31 0 Height = 19.7 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0

NW - Wall 0.0 32 0.31 0 Summer Load:


Roof Sun 0 51 0.1 0 TR = 1.37 TR
Roof Shaded 39 0 DEHUMIDIFIED CFM = 566 CFM
TRANS. GAIN EXCEPT WALLS & ROOF FRESH AIR REQUIRED = 85 CFM
ITEM Area Temp. diff. U

(Sq ft) (°F) (Btu/h.sq ft)

All Glass 0 32.58 0.56 0

Partition 0 27.58 0.31 0

Ceiling 0 27.58 0.36 0

Floor 0 27.58 0.36 0


INTERNAL HEAT GAIN
People 5 Nos X 443.3 2217
Light 269 W 3.41 917
Eq. Load 2100 WX 3.41 7161
Misc Load 0.0 WX 3.41 0
10295
OUTSIDE AIR

CFM °F BF FACTOR

88 32.58 0.1 1.08 311


ROOM SENSIBLE HEAT (RSH) 10606
Supply duct Supply duct leak. loss Heat gain from fan 2
6
heat gain + + HP(%)
Safety factor (%) 10.0 1061

EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 11672


LATENT HEAT
People 5 Nos X 205 1025
OUTSIDE AIR
CFM GR/LB BF FACTOR
88 -9.9 0.1 0.67 -59
966
Supply duct leakage loss + Safety factor % 10.0 97
EFFECTIVE ROOM LATENT HEAT (ERLH) 1063
EFFECTIVE ROOM TOTAL HEAT (ERTH) 12735
OUTSIDE AIR HEAT (SENSIBLE)

CFM °F 1 - BF FACTOR
88 32.58 0.9 1.08 2797
OUTSIDE AIR HEAT (LATENT)

CFM GR/LB 1 - BF FACTOR


88 -9.9 0.9 0.68 -535
HEAT SUB TOTAL 14997
Return duct HP Pump + Dehum. & Pipe 10.0 1500
heat gain & loss (%)
TR 1.37 GRAND TOTAL HEAT 16497

Page 35 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - JHAKAR KATI BUS TERMINAL (JBT) Date 17.05.23 Rev-1
LOCATION: U 03/U07 (SCR/EFO) at Concourse 29.07.23 Rev-2
AREA: 269 Sq ft 5299 Cu ft (Volume) Monsoon Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 91.4 84.2 74.5 48.38 168
(Sq ft) (Btu/h.sq ft) ROOM 75.2 65.475 60 30.348 78.7
N - Glass 0.0 23 0.56 0 DIFFERENCE 16.2 XXXX XXXX 89.3
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 5 People X 17 CFM/Person 85
S - Glass 0.0 12 0.56 0 5299 Cu ft X 1 Air change per hour 88
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 88
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.84
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 19.08 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 427 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 5 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 W/sqft.
SE - Wall 0.0 24 0.31 0 Eq. Load = 1 KW
S - Wall 0.0 34 0.31 0 Height = 19.7 FT
SW - Wall 0.0 48 0.31 0
Calculated Load Summary
W - Wall 0.0 48 0.31 0

NW - Wall 0.0 32 0.31 0 Monsoon Condition


Roof Sun 253.5 51 0.1 1293 TR = 1.46 TR
Roof Shaded 39 0 DEHUMIDIFIED CFM = 427 CFM
TRANS. GAIN EXCEPT WALLS & ROOF FRESH AIR REQUIRED = 85 CFM
ITEM Area Temp. diff. U

(Sq ft) (°F) (Btu/h.sq ft)

All Glass 0 16.2 0.56 0

Partition 0 11.2 0.31 0

Ceiling 0 11.2 0.36 0

Floor 0 11.2 0.36 0


INTERNAL HEAT GAIN
People 5 Nos X 443.3 2217
Light 269 W 3.41 917
Eq. Load 1000 WX 3.41 3410
Misc Load 0.0 WX 3.41 0
7837
OUTSIDE AIR

CFM °F BF FACTOR

88 16.2 0.1 1.08 155


ROOM SENSIBLE HEAT (RSH) 7991
Supply duct Supply duct leak. loss Heat gain from fan 2
3
heat gain + + HP(%)
Safety factor (%) 10.0 799

EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 8793


LATENT HEAT
People 5 Nos X 205 1025
OUTSIDE AIR
CFM GR/LB BF FACTOR
88 89.3 0.1 0.67 528
1553
Supply duct leakage loss + Safety factor % 10.0 155
EFFECTIVE ROOM LATENT HEAT (ERLH) 1709
EFFECTIVE ROOM TOTAL HEAT (ERTH) 10502
OUTSIDE AIR HEAT (SENSIBLE)

CFM °F 1 - BF FACTOR
88 16.2 0.9 1.08 1391
OUTSIDE AIR HEAT (LATENT)

CFM GR/LB 1 - BF FACTOR


88 89.3 0.9 0.68 4827
HEAT SUB TOTAL 16720
Return duct HP Pump + Dehum. & Pipe 5.0 836
heat gain & loss (%)
TR 1.46 GRAND TOTAL HEAT 17556

Page 36 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - JHAKAR KATI BUS TERMINAL (JBT) Date 17.05.23 Rev-1
LOCATION: U 09 (Security) at Concourse 29.07.23 Rev-2
AREA: 96.84 Sq ft 1908 Cu ft (Volume) Summer Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 107.78 73.4 19 36.75 68.8
(Sq ft) (Btu/h.sq ft) ROOM 80.6 68.675 55 32.87 86.3
N - Glass 0.0 23 0.56 0 DIFFERENCE 27.18 XXXX XXXX -17.5
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 6 People X 17 CFM/Person 102
S - Glass 0.0 12 0.56 0 1908 Cu ft X 1 Air change per hour 32
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 102
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.86
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 23.94 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 285 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 6 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 W/sqft.
SE - Wall 0.0 24 0.31 0 Eq. Load = 1 KW
S - Wall 0.0 34 0.31 0 Height = 19.7 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0

NW - Wall 0.0 32 0.31 0 Summer Load:


Roof Sun 0 51 0.1 0 TR = 0.93 TR
Roof Shaded 39 0 DEHUMIDIFIED CFM = 285 CFM
TRANS. GAIN EXCEPT WALLS & ROOF FRESH AIR REQUIRED = 102 CFM
ITEM Area Temp. diff. U

(Sq ft) (°F) (Btu/h.sq ft)

All Glass 0 27.18 0.56 0

Partition 0 22.18 0.31 0

Ceiling 0 22.18 0.36 0

Floor 0 22.18 0.36 0


INTERNAL HEAT GAIN
People 6 Nos X 443.3 2660
Light 97 W 3.41 330
Eq. Load 1000 WX 3.41 3410
Misc Load 0.0 WX 3.41 0
6400
OUTSIDE AIR

CFM °F BF FACTOR

102 27.18 0.1 1.08 299


ROOM SENSIBLE HEAT (RSH) 6699
Supply duct Supply duct leak. loss Heat gain from fan 2
6
heat gain + + HP(%)
Safety factor (%) 10.0 670

EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 7375


LATENT HEAT
People 6 Nos X 205 1230
OUTSIDE AIR
CFM GR/LB BF FACTOR
102 -17.5 0.1 0.67 -120
1110
Supply duct leakage loss + Safety factor % 10.0 111
EFFECTIVE ROOM LATENT HEAT (ERLH) 1221
EFFECTIVE ROOM TOTAL HEAT (ERTH) 8597
OUTSIDE AIR HEAT (SENSIBLE)

CFM °F 1 - BF FACTOR
102 27.18 0.9 1.08 2695
OUTSIDE AIR HEAT (LATENT)

CFM GR/LB 1 - BF FACTOR


102 -17.5 0.9 0.68 -1092
HEAT SUB TOTAL 10199
Return duct HP Pump + Dehum. & Pipe 10.0 1020
heat gain & loss (%)
TR 0.93 GRAND TOTAL HEAT 11219

Page 37 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - JHAKAR KATI BUS TERMINAL (JBT) Date 17.05.23 Rev-1
LOCATION: U 09 (Security) at Concourse 29.07.23 Rev-2
AREA: 96.84 Sq ft 1908 Cu ft (Volume) Monsoon Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 91.4 84.2 74.5 48.38 168
(Sq ft) (Btu/h.sq ft) ROOM 80.6 68.675 55 32.87 86.3
N - Glass 0.0 23 0.56 0 DIFFERENCE 10.8 XXXX XXXX 81.7
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 2 People X 17 CFM/Person 34
S - Glass 0.0 12 0.56 0 1908 Cu ft X 1 Air change per hour 32
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 34
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.90
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 23.94 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 220 CFM
N - Wall 0.0 22 0.31 0 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 2 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 W/sqft.
SE - Wall 0.0 24 0.31 0 Eq. Load = 1 KW
S - Wall 0.0 34 0.31 0 Height = 19.7 FT
SW - Wall 0.0 48 0.31 0
Calculated Load Summary
W - Wall 0.0 48 0.31 0

NW - Wall 0.0 32 0.31 0 Monsoon Condition


Roof Sun 96.84 51 0.1 494 TR = 0.73 TR
Roof Shaded 39 0 DEHUMIDIFIED CFM = 220 CFM
TRANS. GAIN EXCEPT WALLS & ROOF FRESH AIR REQUIRED = 34 CFM
ITEM Area Temp. diff. U

(Sq ft) (°F) (Btu/h.sq ft)

All Glass 0 10.8 0.56 0

Partition 0 5.8 0.31 0

Ceiling 0 5.8 0.36 0

Floor 0 5.8 0.36 0


INTERNAL HEAT GAIN
People 2 Nos X 443.3 887
Light 97 W 3.41 330
Eq. Load 1000 WX 3.41 3410
Misc Load 0.0 WX 3.41 0
5121
OUTSIDE AIR

CFM °F BF FACTOR

34 10.8 0.1 1.08 40


ROOM SENSIBLE HEAT (RSH) 5160
Supply duct Supply duct leak. loss Heat gain from fan 2
1
heat gain + + HP(%)
Safety factor (%) 10.0 516

EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 5677


LATENT HEAT
People 2 Nos X 205 410
OUTSIDE AIR
CFM GR/LB BF FACTOR
34 81.7 0.1 0.67 186
596
Supply duct leakage loss + Safety factor % 10.0 60
EFFECTIVE ROOM LATENT HEAT (ERLH) 656
EFFECTIVE ROOM TOTAL HEAT (ERTH) 6333
OUTSIDE AIR HEAT (SENSIBLE)

CFM °F 1 - BF FACTOR
34 10.8 0.9 1.08 357
OUTSIDE AIR HEAT (LATENT)

CFM GR/LB 1 - BF FACTOR


34 81.7 0.9 0.68 1700
HEAT SUB TOTAL 8390
Return duct HP Pump + Dehum. & Pipe 5.0 419
heat gain & loss (%)
TR 0.73 GRAND TOTAL HEAT 8809

Page 38 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - JHAKAR KATI BUS TERMINAL (JBT) Date 17.05.23 Rev-1
LOCATION: U 22 & 23 (SCR+TER) at ground floor 29.07.23 Rev-2
AREA: 520 Sq ft 8528 Cu ft Summer Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 107.78 73.4 19 36.75 68.8
(Sq ft) (Btu/h.sq ft) ROOM 75.2 65.475 60 30.348 78.7
N - Glass 0.0 23 0.56 0 DIFFERENCE 32.58 XXXX XXXX -9.9
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 1 People X 16 CFM/Person 16
S - Glass 0.0 12 0.56 0 8528 Cu ft X 1 Air change per hour 142
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 142
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 1.00
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 19.08 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 3593 CFM
N - Wall 398.1 22 0.31 2715 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 1 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 KW
SE - Wall 0.0 24 0.31 0 Eq. Load = 13.45 KW
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0

NW - Wall 0.0 32 0.31 0 Summer Load:


Roof Sun 520 51 0.15 3978 TR = 7.13 TR
Roof Shaded 39 0 DEHUMIDIFIED CFM = 3593 CFM
TRANS. GAIN EXCEPT WALLS & ROOF FRESH AIR REQUIRED = 359.343 CFM
ITEM Area Temp. diff. U

(Sq ft) (°F) (Btu/h.sq ft)

All Glass 0 32.58 0.56 0

Partition 1355.5584 27.58 0.31 11590

Ceiling 0 27.58 0.36 0

Floor 0 27.58 0.36 0


INTERNAL HEAT GAIN
People 1 Nos X 443.3 443
Light 520 W X 1.25 3.41 2217
Eq. Load 13450 WX 3.41 45865
Misc Load 0.0 WX 3.41 0
66807
OUTSIDE AIR

CFM °F BF FACTOR

142 32.58 0.1 1.08 500


ROOM SENSIBLE HEAT (RSH) 67307
Supply duct Supply duct leak. loss Heat gain from fan 2
10
heat gain + + HP(%)
Safety factor (%) 10.0 6731

EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 74048


LATENT HEAT
People 1 Nos X 205 205
OUTSIDE AIR
CFM GR/LB BF FACTOR
142 -9.9 0.1 0.67 -94
111
Supply duct leakage loss + Safety factor % 10.0 11
EFFECTIVE ROOM LATENT HEAT (ERLH) 122
EFFECTIVE ROOM TOTAL HEAT (ERTH) 74169
OUTSIDE AIR HEAT (SENSIBLE)

CFM °F 1 - BF FACTOR
142 32.58 0.9 1.08 4501
OUTSIDE AIR HEAT (LATENT)

CFM GR/LB 1 - BF FACTOR


142 -9.9 0.9 0.68 -861
HEAT SUB TOTAL 77809
Return duct HP Pump + Dehum. & Pipe 10.0 7781
heat gain & loss (%)
TR 7.13 GRAND TOTAL HEAT 85590

Page 39 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - JHAKAR KATI BUS TERMINAL (JBT) Date 17.05.23 Rev-1
LOCATION: U 22 & 23 (SCR+TER) at Ground 29.07.23 Rev-2
AREA: 520 Sq ft 8528 Cu ft Monsoon Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 91.4 84.2 74.5 48.38 168
(Sq ft) (Btu/h.sq ft) ROOM 75.2 65.475 60 30.348 78.7
N - Glass 0.0 23 0.56 0 DIFFERENCE 16.2 XXXX XXXX 89.3
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 1 People X 16 CFM/Person 16
S - Glass 0.0 12 0.56 0 8528 Cu ft X 1 Air change per hour 142
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 142
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.98
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 19.08 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 3310 CFM
N - Wall 473.4 22 0.31 3228 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 1 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 KW
SE - Wall 0.0 24 0.31 0 Eq. Load = 13.45 KW
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0
Calculated Load Summary
W - Wall 0.0 48 0.31 0

NW - Wall 0.0 32 0.31 0 Monsoon Condition


Roof Sun 692 51 0.15 5294 TR = 6.95 TR
Roof Shaded 39 0 DEHUMIDIFIED CFM = 3310 CFM
TRANS. GAIN EXCEPT WALLS & ROOF FRESH AIR REQUIRED = 330.998 CFM
ITEM Area Temp. diff. U

(Sq ft) (°F) (Btu/h.sq ft)

All Glass 0 16.2 0.56 0

Partition 1355.5584 11.2 0.31 4706

Ceiling 0 11.2 0.36 0

Floor 0 11.2 0.36 0


INTERNAL HEAT GAIN
People 1 Nos X 443.3 443
Light 520 W X 1.25 3.41 2217
Eq. Load 13450 WX 3.41 45865
Misc Eq Load 0 WX 3.41 0
61753
OUTSIDE AIR

CFM °F BF FACTOR

142 16.2 0.1 1.08 249


ROOM SENSIBLE HEAT (RSH) 62002
Supply duct Supply duct leak. loss Heat gain from fan 2
5
heat gain + + HP(%)
Safety factor (%) 10.0 6200

EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 68207


LATENT HEAT
People 1 Nos X 205 205
OUTSIDE AIR
CFM GR/LB BF FACTOR
142 89.3 0.1 0.67 850
1055
Supply duct leakage loss + Safety factor % 10.0 106
EFFECTIVE ROOM LATENT HEAT (ERLH) 1161
EFFECTIVE ROOM TOTAL HEAT (ERTH) 69368
OUTSIDE AIR HEAT (SENSIBLE)

CFM °F 1 - BF FACTOR
142 16.2 0.9 1.08 2238
OUTSIDE AIR HEAT (LATENT)

CFM GR/LB 1 - BF FACTOR


142 89.3 0.9 0.68 7768
HEAT SUB TOTAL 79374
Return duct HP Pump + Dehum. & Pipe 5.0 3969
heat gain & loss (%)
TR 6.95 GRAND TOTAL HEAT 83342

Page 40 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - JHAKAR KATI BUS TERMINAL (JBT) Date 17.05.23 Rev-1
LOCATION: U 24 & 27 (Comb. UPS Rm) at Ground 29.07.23 Rev-2
AREA: 692 Sq ft 11349 Cu ft (Volume) Summer Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 107.78 73.4 19 36.75 68.8
(Sq ft) (Btu/h.sq ft) ROOM 75.2 65.475 60 30.348 78.7
N - Glass 0.0 23 0.56 0 DIFFERENCE 32.58 XXXX XXXX -9.9
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 1 People X 16 CFM/Person 16
S - Glass 0.0 12 0.56 0 11349 Cu ft X 1 Air change per hour 189
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 189
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 1.00
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 19.08 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 2789 CFM
N - Wall 473.4 22 0.31 3228 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 1 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 KW
SE - Wall 0.0 24 0.31 0 Eq. Load = 8.23 KW
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0 Load Summary
W - Wall 0.0 48 0.31 0

NW - Wall 0.0 32 0.31 0 Summer Load:


Roof Sun 692 51 0.15 5294 TR = 5.72 TR
Roof Shaded 39 0 DEHUMIDIFIED CFM = 2789 CFM
TRANS. GAIN EXCEPT WALLS & ROOF FRESH AIR REQUIRED = 278.901 CFM
ITEM Area Temp. diff. U

(Sq ft) (°F) (Btu/h.sq ft)

All Glass 0 32.58 0.56 0

Partition 1355.5584 27.58 0.31 11590

Ceiling 0 27.58 0.36 0

Floor 0 27.58 0.36 0


INTERNAL HEAT GAIN
People 1 Nos X 443.3 443
Light 692 W X 1.25 3.41 2950
Eq. Load 8230 WX 3.41 28064
Misc Eq Load 0 WX 3.41 0
51569
OUTSIDE AIR

CFM °F BF FACTOR

189 32.58 0.1 1.08 666


ROOM SENSIBLE HEAT (RSH) 52235
Supply duct Supply duct leak. loss Heat gain from fan 2
13
heat gain + + HP(%)
Safety factor (%) 10.0 5223

EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 57472


LATENT HEAT
People 1 Nos X 205 205
OUTSIDE AIR
CFM GR/LB BF FACTOR
189 -9.9 0.1 0.67 -125
80
Supply duct leakage loss + Safety factor % 10.0 8
EFFECTIVE ROOM LATENT HEAT (ERLH) 87
EFFECTIVE ROOM TOTAL HEAT (ERTH) 57559
OUTSIDE AIR HEAT (SENSIBLE)

CFM °F 1 - BF FACTOR
189 32.58 0.9 1.08 5990
OUTSIDE AIR HEAT (LATENT)

CFM GR/LB 1 - BF FACTOR


189 -9.9 0.9 0.68 -1146
HEAT SUB TOTAL 62403
Return duct HP Pump + Dehum. & Pipe 10.0 6240
heat gain & loss (%)
TR 5.72 GRAND TOTAL HEAT 68643

Page 41 of 46
HEAT LOAD SHEET
JOB NAME: KNPCC-06 - JHAKAR KATI BUS TERMINAL (JBT) Date 17.05.23 Rev-1
LOCATION: U 24 & 27 (Comb. UPS Rm) at Ground 29.07.23 Rev-2
AREA: 692 Sq ft 11349 Cu ft (Volume) Monsoon Condition
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH TH GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 91.4 84.2 74.5 48.38 168
(Sq ft) (Btu/h.sq ft) ROOM 75.2 65.475 60 30.348 78.7
N - Glass 0.0 23 0.56 0 DIFFERENCE 16.2 XXXX XXXX 89.3
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 1 People X 16 CFM/Person 16
S - Glass 0.0 12 0.56 0 11349 Cu ft X 1 Air change per hour 189
SW - Glass 0.0 85 0.56 0 CFM VENTILATION 189
W - Glass 0.0 163 0.56 0
NW - Glass 0.0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.97
Sky light 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 19.08 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 2403 CFM
N - Wall 473.4 22 0.31 3228 NOTES
NE - Wall 0.0 22 0.31 0 Occupancy = 1 Nos
E - Wall 0.0 22 0.31 0 Lighting = 1 KW
SE - Wall 0.0 24 0.31 0 Eq. Load = 8.23 KW
S - Wall 0.0 34 0.31 0 Height = 16.4 FT
SW - Wall 0.0 48 0.31 0
Calculated Load Summary
W - Wall 0.0 48 0.31 0

NW - Wall 0.0 32 0.31 0 Monsoon Condition


Roof Sun 692 51 0.15 5294 TR = 5.63 TR
Roof Shaded 39 0 DEHUMIDIFIED CFM = 2403 CFM
TRANS. GAIN EXCEPT WALLS & ROOF FRESH AIR REQUIRED = 240.339 CFM
ITEM Area Temp. diff. U

(Sq ft) (°F) (Btu/h.sq ft)

All Glass 0 16.2 0.56 0

Partition 1355.5584 11.2 0.31 4706

Ceiling 0 11.2 0.36 0

Floor 0 11.2 0.36 0


INTERNAL HEAT GAIN
People 1 Nos X 443.3 443
Light 692 W X 1.25 3.41 2950
Eq. Load 8230 WX 3.41 28064
Misc Eq Load 0 WX 3.41 0
44686
OUTSIDE AIR

CFM °F BF FACTOR

189 16.2 0.1 1.08 331


ROOM SENSIBLE HEAT (RSH) 45017
Supply duct Supply duct leak. loss Heat gain from fan 2
7
heat gain + + HP(%)
Safety factor (%) 10.0 4502

EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 49525


LATENT HEAT
People 1 Nos X 205 205
OUTSIDE AIR
CFM GR/LB BF FACTOR
189 89.3 0.1 0.67 1132
1337
Supply duct leakage loss + Safety factor % 10.0 134
EFFECTIVE ROOM LATENT HEAT (ERLH) 1470
EFFECTIVE ROOM TOTAL HEAT (ERTH) 50996
OUTSIDE AIR HEAT (SENSIBLE)

CFM °F 1 - BF FACTOR
189 16.2 0.9 1.08 2978
OUTSIDE AIR HEAT (LATENT)

CFM GR/LB 1 - BF FACTOR


189 89.3 0.9 0.68 10337
HEAT SUB TOTAL 64311
Return duct HP Pump + Dehum. & Pipe 5.0 3216
heat gain & loss (%)
TR 5.63 GRAND TOTAL HEAT 67527

Page 42 of 46
4
C
JBT-FCU-301 & 302
1.5 TR BOU +3200
600x1000 SP DUCT
BOD:3900 AFFL

U05
+120.760 FFL
+120.760
+120.660
2500x1200 SAD
BOD:3700 AFFL

JHAKAR KATI BUS TERMINAL STATION


CONCOURSE LEVEL U05 TOM ROOM
2 CONCOURSE LEVEL

Page 43 of 46
900x500
4 SAD 800x400 SED 5
BOD:4400 AFFL 2000 L/s BOD 4500

B
JBT-FCU-304 & 305
1.5 TR BOU +3660
# 750x250 SED BELLMOUTH
0 L/s EACH U03/U07
CONCOURSE LEVEL
3
JHAKAR KATI BUS TERMINAL STATION
U03/U07 SCR/EFO ROOM
CONCOURSE LEVEL

800x400 SED Page 44 of 46


2000 L/s BOD 4500
4
210 L/s
B.O.ATG +500 JBT-MFD-308
JBT-MFD-309

JBT-FCU-303
1.5 TR BOU +3660
U09

U18

A
CONCOURSE LEVEL 32Ø CH
JHAKAR KATI BUS TERMINAL STATION
1 U09 SEC. ROOM
CONCOURSE LEVEL
Page 45 of 46
09' 11'

Page 46 of 46
10' 12'
ACDB DCDB LOOP BOX 1 & 2 LOOP BOX 3 & 4
GSM
ACS Panel

E'
ACS Panel
IDF
MDF

U22 & U23


FIBRE OPTIC
LOOP BOX-2

+128.437 FFL
+127.987 TOC
FIBRE OPTIC
LOOP BOX-1

O/P OAIT C R EES


PANEL
D'
B SMPS SMPS
SPARE CELL
CHARGER
MAIN EARTH BUS BAR

FOR SMPS
B/B2 B/B1
SMPS SMPS SPARE CELL

OKS
2 1 FOR SMPS SPARE
UPS
CELL
SPARE FOR
CELL UPS
CHARGER
U24 & U27
BCB-2
ATS
+128.437 FFL 80 KVA

BCB-1

BATTERY RACK- 1/2

BATTERY RACK- 1/2


BATTERY RACK- 2/2

BATTERY RACK- 2/2


+127.987 TOC
SCVS
UPS-1
45 KVA
UPS-2
45 KVA
C'

LPD-01
LPD-02
IT
ANCILLARY BUILDING GROUND FLOOR LEVEL
1

You might also like