You are on page 1of 27

2023

ASL-173E
CH-87+430(INTERCHANGE)

GEOTECHNICAL REPORT
ISO/IEC 17025 Accredited Testing Laboratory by NABL

PROJECT
SUB SOIL INVESTIGATION FOR PROPOSED CONSTRUCTION
OF FOUR-LANE GREENFIELD AMRITSAR CONNECTIVITY FOR
CONNECTION OF AMRITSAR WITH DELHI-AMRITSAR-KATRA
EXPRESSWAY FROM JUNCTION WITH NH-3 AND TARAN
BYPASS NEAR MANNAWALA VILLAGE CH 70+950 TO
JUNCTION WITH NH-354 AJANALA ROAD NEAR HARSHA CHINA
VILLAGE CH 99+020 (KM 70+950 TO KM 99+020 OF AMRITSAR
CONNECTIVITY) ON EPC MODE UNDER BHARATMALA
PARIYOJNA IN THE STATE OF PUNJAB

ARUN SOIL LAB PRIVATE LIMITED


Geotech & Material Consultants For Civil Engineering Projects

Registered Office: E-11, First Floor, Lekhraj Market-I,


Indira Nagar, Lucknow- 226016
Main Laboratory: 636/110, Budh Vihar, Takrohi,
Indira Nagar, Lucknow-227105

arunsoillab.asl@gmail.com
9415025566, 9415501637
info@arunsoillab.com

"QUALITY CONSCIOUSNESS IS OUR CORE CONCEPT"


Copyright: wordexceltemplates.com
ISO/IEC 17025 Accredited Laboratory ARUN SOIL LAB PVT LTD
(NABL accredited lab) Geotech Investigation Report No. ASL 173E-2023

ACKNOWLEDGEMENT

Project: SUB SOIL INVESTIGATION FOR PROPOSED CONSTRUCTION OF FOUR-


LANE GREENFIELD AMRITSAR CONNECTIVITY FOR CONNECTION OF
AMRITSAR WITH DELHI-AMRITSAR-KATRA EXPRESSWAY FROM JUNCTION
WITH NH-3 AND TARAN BYPASS NEAR MANNAWALA VILLAGE CH 70+950 TO
JUNCTION WITH NH-354 AJANALA ROAD NEAR HARSHA CHINA VILLAGE CH
99+020 (KM 70+950 TO KM 99+020 OF AMRITSAR CONNECTIVITY) ON EPC MODE
UNDER BHARATMALA PARIYOJNA IN THE STATE OF PUNJAB

Client: - M/s D. P. S. Contractors Pvt. Ltd.

Subject: - Geotechnical Investigation Report

Dear Sir,
With reference to your Order DPS/ASR-KE/WO/2023/35 dated 10th May 2023,
Arun Soil Lab Pvt. Ltd. (ASL) is pleased to submit the report carried out for the
proposed site.

The investigation end up with conclusions and recommendations relevant to the


findings in addition to the laboratory test results, also attached herewith.

We look forward for further co-operation if any, whenever required. For any further
clarification concerning the report, please contact us at your convenience.

ARUN SOIL LAB PVT. LTD.


(Geotech & Material Consultants for Civil Engineering Projects)
E-11, First Floor, Lekhraj Market-I, Indira Nagar, Lucknow- 226016
Phone: 2341943; 4001043; Mobile: 9415025566, 9415501637, 38
arunsoillab.asl@gmail.com; info@arunsoillab.com
ISO/IEC 17025 Accredited Laboratory ARUN SOIL LAB PVT LTD
(NABL accredited lab) Geotech Investigation Report No. ASL 173E-2023

CONTENTS

1. INTRODUCTION 1
SUMMARY OF FIELD WORK 1
2. REFERENCES 2
3. METHODOLOGY OF FIELD INVESTIGATION 3
STANDARD PENETRATION TEST (SPT) 3
UNDISTURBED SOIL SAMPLES (UDS) 4
4. LABORATORY TESTS 5
CLASSIFICATION AND ABBREVIATIONS 6
5. INTERPRETATION OF LAB TEST RESULTS
a. GENERAL NATURE OF SOIL STRATA 7
b. SPT VALUES 7
c. WATER TABLE 7
d. HARMFUL SALTS TEST REPORT 8
6. RECOMMENDATIONS 9-10
7. SITE PLAN/GOOGLE EARTH IMAGE 11
8. SITE PHOTOGRAPHS 12
9. BEARING CAPACITY CALCULATIONS 13-16
10. RESULTS SHEETS 17-18
11. BORE-LOG CHARTS 19
12. TRIAXIAL SHEAR/DIRECT SHEAR GRAPHS 20-23
13. CONSOLIDATION TEST GRAPHS 24

ARUN SOIL LAB PVT. LTD.


(Geotech & Material Consultants for Civil Engineering Projects)
E-11, First Floor, Lekhraj Market-I, Indira Nagar, Lucknow- 226016
Phone: 2341943; 4001043; Mobile: 9415025566, 9415501637, 38
arunsoillab.asl@gmail.com; info@arunsoillab.com
ISO/IEC 17025 Accredited Laboratory ARUN SOIL LAB PVT LTD
(NABL accredited lab) Geotech Investigation Report No. ASL 173E-2023

SUB SOIL INVESTIGATION FOR PROPOSED CONSTRUCTION OF FOUR-LANE


GREENFIELD AMRITSAR CONNECTIVITY FOR CONNECTION OF AMRITSAR
WITH DELHI-AMRITSAR-KATRA EXPRESSWAY FROM JUNCTION WITH NH-3
AND TARAN BYPASS NEAR MANNAWALA VILLAGE CH 70+950 TO JUNCTION
WITH NH-354 AJANALA ROAD NEAR HARSHA CHINA VILLAGE CH 99+020 (KM
70+950 TO KM 99+020 OF AMRITSAR CONNECTIVITY) ON EPC MODE UNDER
BHARATMALA PARIYOJNA IN THE STATE OF PUNJAB

INTRODUCTION
The work of sub-soil exploration was awarded to us by M/s D.P.S. Contractors Pvt. Ltd. The
object of the investigation was to study the geo-technical properties of soil both in field and
laboratory and determine safe allowable pressure for the foundation soil.

SUMMARY OF FIELD WORK


The boreholes of diameter 150 mm were made within the proposed layout of the structure. The
borehole was progressed using manually operated augers and further advanced by use of manually
operated shell casing to the desired depth. The locations of boreholes have been reported in
“BOREHOLE LOCATION PLAN”. Details of Bore holes are as follows:

Depth Field
Bore Easting Northing Field Investigation
Investigation
Hole (m) Completion Date
Start Date
1 35.00 489836.521 3507820.977 21/05/2023 22/05/2023

Field Test IS Code Referred


IS: 1892-2021 Field Work Including Existent Ground Water Table
IS: 2132-2021 Sampling in Undisturbed and Disturbed Form
IS: 2131-2021 Standard Penetration Test

ARUN SOIL LAB PVT. LTD.


(Geotech & Material Consultants for Civil Engineering Projects)
E-11, First Floor, Lekhraj Market-I, Indira Nagar, Lucknow- 226016
Phone: 2341943; 4001043; Mobile: 9415025566, 9415501637, 38
arunsoillab.asl@gmail.com; info@arunsoillab.com
Page 1 of 24
ISO/IEC 17025 Accredited Laboratory ARUN SOIL LAB PVT LTD
(NABL accredited lab) Geotech Investigation Report No. ASL 173E-2023

REFERENCES
Laboratory Test IS Code Referred
Bulk Density By calculations
Natural Moisture Content IS : 2720 (Part-2)-1973, RA-2010
Specific Gravity IS : 2720 (Part-3)-1980, RA-2007
Grain Size Analysis IS : 2720 (Part-4)-1985, RA-2010
Liquid Limit and Plastic Limit IS : 2720 (Part-5)-1985, RA-2010
Shrinkage Limit IS : 2720 (Part 6) -1972, RA-2007
Free Swell Index IS : 2720 (Part-40) -1977, RA-2007
Unconsolidated Undrained Triaxial Shear Test IS : 2720 (Part-11)-1993, RA-2007
Consolidation Test IS : 2720 (Part-15)-1986, RA-2007
pH value IS : 3025 (Part-11)-1983, RA-2006
Chemical Analysis
of Water* Sulphates IS : 3025 (Part-24)-1986, RA-2009
Chlorides IS : 3025 (Part-32)-1988, RA-2009
pH value IS : 2720 (Part 26)-1987, RA-2007
Chemical Analysis
of Soil* Sulphates IS : 2720 (Part-27)-1977, RA-2010
Chlorides IS : 3025 (Part-32)-1988, RA-2009

BEARING CAPACITY IS Code Referred


Bearing Capacity Calculation IS : 6403 - 1974
Settlement Analysis IS : 8009 (Part I) - 1976
Maximum Permissible Settlement, Differential IS : 1904 -1986
Settlement and Angular Distortion
Pile Capacity Calculations IS : 2911(Part 1/Sec 2), IRC 78

ARUN SOIL LAB PVT. LTD.


(Geotech & Material Consultants for Civil Engineering Projects)
E-11, First Floor, Lekhraj Market-I, Indira Nagar, Lucknow- 226016
Phone: 2341943; 4001043; Mobile: 9415025566, 9415501637, 38
arunsoillab.asl@gmail.com; info@arunsoillab.com
Page 2 of 24
ISO/IEC 17025 Accredited Laboratory ARUN SOIL LAB PVT LTD
(NABL accredited lab) Geotech Investigation Report No. ASL 173E-2023

METHODOLOGY OF FIELD INVESTIGATION


Standard Penetration Test (SPT) was conducted
in the boreholes at every 1.50 m interval and
change of strata as per specifications.
Standard split spoon sampler attached to lower end
of drill rods was driven in the boreholes by means of
standard hammer of 63.50 kg falling freely from a
height of 75 cm. The sampler was driven 45 cm as
per specifications and number of blows required
for each 15 cm penetration was recorded.
The number of blows for the first 15 cm
penetration was not taken into account as it is
considered seating drive. The number of blows
for next 30 cm penetration was designated as SPT ‘N’ value. Wherever the total penetration was
less than 45 cm, the number of blows & the depth penetrated is incorporated in respective bore
logs. Disturbed Soil samples obtained from standard split spoon sampler were collected in
polythene bags of suitable size. These samples were properly sealed, labeled, recorded and
carefully transported to laboratory for testing.
CONSISTENCY / RELATIVE DENSITY OF SOIL WITH SPT VALUES AS
PER IRC: 75-2015
SPT Value Consistency SPT Value Density Descriptor
0-2 Very Soft
0-4 Very Loose
2-4 Soft
4-8 Medium 4-10 Loose
8-16 Stiff 10-30 Medium Dense
16-32 Very Stiff
30-50 Dense
>32 Hard
>50 Very Dense

ARUN SOIL LAB PVT. LTD.


(Geotech & Material Consultants for Civil Engineering Projects)
E-11, First Floor, Lekhraj Market-I, Indira Nagar, Lucknow- 226016
Phone: 2341943; 4001043; Mobile: 9415025566, 9415501637, 38
arunsoillab.asl@gmail.com; info@arunsoillab.com
Page 3 of 24
ISO/IEC 17025 Accredited Laboratory ARUN SOIL LAB PVT LTD
(NABL accredited lab) Geotech Investigation Report No. ASL 173E-2023

Undisturbed Soil Samples (UDS) were collected from the boreholes at every 1.50
m interval & change of strata as per sampling specifications, in thin-walled sampling
tubes of 100 mm dia. and 450 mm length. These sampling tubes after retrieval from
the boreholes were properly waxed and sealed at both ends. These were carefully
labeled and transported to the laboratory for testing. UDS wherever slipped during
lifting, were duly marked in the bore logs as well in the soil profile.

SPT Split Spoon Soil Sampling (DS)


Disturbed soil collected in the SPT sampler was preserved in polythene covers and
transported to the laboratory. One more polythene cover was provided to prevent the
loss of moisture during the transit period.

ARUN SOIL LAB PVT. LTD.


(Geotech & Material Consultants for Civil Engineering Projects)
E-11, First Floor, Lekhraj Market-I, Indira Nagar, Lucknow- 226016
Phone: 2341943; 4001043; Mobile: 9415025566, 9415501637, 38
arunsoillab.asl@gmail.com; info@arunsoillab.com
Page 4 of 24
ISO/IEC 17025 Accredited Laboratory ARUN SOIL LAB PVT LTD
(NABL accredited lab) Geotech Investigation Report No. ASL 173E-2023

LABORATORY TESTS:
The following laboratory tests were conducted to determine the engineering characteristics of sub-
soils:

Natural moisture contents were determined by oven drying method as per IS 2720 (Part II)-1973.
The results have been reported in result sheet attached.

Dry and Bulk density of soil strata were obtained using Shelby tubes in accordance with IS 2720
(Part XXIX)-1975. The results have been reported in result sheet attached.

Particle size analysis test by hydrometer method were performed in accordance with IS 2720
(Part IV) - 1965 on the part of soil samples obtained after the sieve analysis. The results have been
reported in result sheet attached.

Atterberg Limits’ tests were performed in accordance with IS 2720 (Part V) - 1985 and results
have been reported in result sheet attached.

Specific gravity tests were performed in accordance with IS 2720 (Part III Section1) -1980 and
the results have been reported in result sheet attached.

Triaxial Compression Test under Unconsolidated Un-drained (UU) condition as per IS: 2720
(Part-XI)-2011 were performed on the undisturbed soil samples obtained during the field
investigation. The results have been reported in result sheet attached.

Direct shear tests were performed as per IS 2720 (Part XIII)-2015, on the undisturbed soil
samples obtained during the field investigation. The results and the density of samples have been
reported in result sheet attached.

Consolidation tests were performed as per IS 2720 (Part XV)-1986, on the undisturbed soil
samples obtained during the field investigation. The result in the form of compression index (Cc)
is reported in result sheet attached.

ARUN SOIL LAB PVT. LTD.


(Geotech & Material Consultants for Civil Engineering Projects)
E-11, First Floor, Lekhraj Market-I, Indira Nagar, Lucknow- 226016
Phone: 2341943; 4001043; Mobile: 9415025566, 9415501637, 38
arunsoillab.asl@gmail.com; info@arunsoillab.com
Page 5 of 24
ISO/IEC 17025 Accredited Laboratory ARUN SOIL LAB PVT LTD
(NABL accredited lab) Geotech Investigation Report No. ASL 173E-2023

CLASSIFICATION OF SOIL

FOR COHESIVE SOIL FOR NON-COHESIVE SOIL


Plasticity Liquid Limit % Passing on IS Sieve 0.075
Soil Classification mm
Low Plastic <35
ML >50
Medium Plastic 35 to 50
SM 13-49
High Plastic >50
SM-SP 5-12
SP 1-4
ABBREVIATIONS
• CL - SILTY CLAY OF LOW PLASTICITY • ML - SANDY SILT

• CI - SILTY CLAY OF MEDIUM PLASTICITY • SM - SILTY SAND

• CH - SILTY CLAY OF HIGH PLASTICITY • SM-SP - POORLY GRADED SAND-SILT MIXTURE

• ML - CLAYEY SILT OF LOW PLASTICITY • SW/SP - WELL/POORLY GRADED SAND

• CL-ML - CLAYEY SILT OF LOW PLASTICITY • GSF - GENERAL SHEAR FAILURE

• MI - CLAYEY SILT OF MEDIUM PLASTICITY • LSF- LOCAL SHEAR FAILURE

• SC - CLAYEY SAND • ISF - INTERMEDIATE SHEAR FAILURE

• GL - GROUND LEVEL • BGL - BELOW GROUND LEVEL

ARUN SOIL LAB PVT. LTD.


(Geotech & Material Consultants for Civil Engineering Projects)
E-11, First Floor, Lekhraj Market-I, Indira Nagar, Lucknow- 226016
Phone: 2341943; 4001043; Mobile: 9415025566, 9415501637, 38
arunsoillab.asl@gmail.com; info@arunsoillab.com
Page 6 of 24
ISO/IEC 17025 Accredited Laboratory ARUN SOIL LAB PVT LTD
(NABL accredited lab) Geotech Investigation Report No. ASL 173E-2023

INTERPRETATION OF THE LAB TEST RESULTS

GENERAL NATURE OF SOIL STRATA


The results of lab tests and bore hole log charts of bore hole 1 indicate that the strata at the site is
found to comprise of both cohesive as well as non-cohesive soil.
The cohesive type soil comprises of clayey silt soil of low plasticity and compressibility belonging
to ‘CL-ML’, ‘ML’ group of IS classification and having 82 to 97 percent material finer than 75
micron.
However, the non-cohesive type soil is found to comprise of either sandy silt ‘ML’ type soil or
silty sand ‘SM’ type soil or poorly graded sand-silt mixture belonging to ‘SM-SP’ and ‘SP’ group
of IS classification and having 2 to 60 percent fines.
The results of classification tests indicate that the natural soil stratum present at the Site is found to
comprise of both fine-grained soils (clayey soil) and coarse-grained soils (sandy soil).

S.P.T. VALUES
The S.P.T. values obtained in the respective clayey layer region present as per bore-log charts
enclosed are found to range from 10 to 33 indicating ‘Stiff’ to ‘Hard’ consistency.
However, the S.P.T. values obtained in the respective sandy layer region present as per bore-log
charts enclosed are found to range from 15 to 89 indicating ‘Medium Dense’ to ‘Very Dense’
relative density.
The results of S.P.T. values indicate that the stratum at the Site is ‘Well’ to ‘Very Well’
compacted.

WATER TABLE
Water Table at the Site was observed at a depth from 21.00 metre below ground level on the day of
soil investigation during the Fourth week of May 2023. However, the existing water table may rise
in the post-monsoon period in general. Therefore, a water table at a depth of 0.00 metre below
ground level has been adopted for calculation purposes.

ARUN SOIL LAB PVT. LTD.


(Geotech & Material Consultants for Civil Engineering Projects)
E-11, First Floor, Lekhraj Market-I, Indira Nagar, Lucknow- 226016
Phone: 2341943; 4001043; Mobile: 9415025566, 9415501637, 38
arunsoillab.asl@gmail.com; info@arunsoillab.com
Page 7 of 24
ISO/IEC 17025 Accredited Laboratory ARUN SOIL LAB PVT LTD
(NABL accredited lab) Geotech Investigation Report No. ASL 173E-2023

HARMFUL SALTS TEST REPORT


Soil samples obtained from 0.00-0.50 meter, 1.00-1.45 meter and 1.45-1.90 meter depth below
ground level from 01 bore hole were tested for the presence of harmful salts like Carbonates,
Bicarbonates, Chlorides, Sulphates & pH test.

TABLE NO. 1

BORE DEPTH
CARBONATES BICARBONATES CHLORIDES SULPHATES
HOLE IN pH
% % % %
NO. METRES

0.00-0.50 NIL 0.168 0.026 NIL 7.49


1 1.00-1.45 NIL 0.151 0.026 NIL 7.52
1.45-1.90 NIL 0.134 0.030 NIL 7.55

Er. Anurag Kapoor


B.Tech. (Civil), M.Tech (Geotech)
PGDM (Finance), LM - IGS & IRC
VICE CHAIRMAN
ARUN SOIL LAB Pvt. Ltd.

ARUN SOIL LAB PVT. LTD.


(Geotech & Material Consultants for Civil Engineering Projects)
E-11, First Floor, Lekhraj Market-I, Indira Nagar, Lucknow- 226016
Phone: 2341943; 4001043; Mobile: 9415025566, 9415501637, 38
arunsoillab.asl@gmail.com; info@arunsoillab.com
Page 8 of 24
ISO/IEC 17025 Accredited Laboratory ARUN SOIL LAB PVT LTD
(NABL accredited lab) Geotech Investigation Report No. ASL 173E-2023

RECOMMENDATIONS FOR PROPOSED CONSTRUCTION OF FOUR-LANE


GREENFIELD AMRITSAR CONNECTIVITY FOR CONNECTION OF AMRITSAR
WITH DELHI-AMRITSAR-KATRA EXPRESSWAY FROM JUNCTION WITH NH-3
AND TARAN BYPASS NEAR MANNAWALA VILLAGE CH 70+950 TO JUNCTION
WITH NH-354 AJANALA ROAD NEAR HARSHA CHINA VILLAGE CH 99+020 (KM
70+950 TO KM 99+020 PF AMRITSAR CONNECTIVITY) ON EPC MODE UNDER
BHARATMALA PARIYOJNA IN THE STATE OF PUNJAB

BORED CAST IN-SITU CONCRETE PILE (CH 87+430 INTERCHANGE)


Pile
Load
Length Pile Safe Pile Safe Pile
Pile Capacity Depth of
Bore Hole Below Cut-off Capacity Capacity
Diametre of Pile fixity
Cut-off Length (compression) (Uplift)
(Lateral)
Level
(mm) (m) (m) (Tonnes) (Tonnes) (Tonnes) (m)
Fixed Head Fixed Head

0.50 8.14 1.16


8.00 41.11 20.34
9.50 67.59 27.10
12.50 78.47 46.40
14.00 95.81 57.51
BH-1 1000 2.00 39.55 7.66
17.00 196.73 82.52
24.50 391.37 173.94
26.00 457.17 196.86
27.00 478.87 212.90
28.00 501.45 229.55

0.20 10.20 0.59


7.70 51.64 24.27
9.20 87.24 32.50
12.20 97.33 56.00
13.70 118.70 69.51
BH-1 1200 2.30 63.54 8.86
16.70 254.64 99.74
24.20 502.31 209.81
26.00 596.19 243.09
27.00 622.21 262.61
28.00 649.30 282.86

ARUN SOIL LAB PVT. LTD.


(Geotech & Material Consultants for Civil Engineering Projects)
E-11, First Floor, Lekhraj Market-I, Indira Nagar, Lucknow- 226016
Phone: 2341943; 4001043; Mobile: 9415025566, 9415501637, 38
arunsoillab.asl@gmail.com; info@arunsoillab.com
Page 9 of 24
ISO/IEC 17025 Accredited Laboratory ARUN SOIL LAB PVT LTD
(NABL accredited lab) Geotech Investigation Report No. ASL 173E-2023

However, the Final Ultimate Bearing Capacity of the pile must be adopted only after performing
Pile Load Test on Test Pile constructed at the site as per IS: 2911 (Part- IV)-1985 and actual
design load requirements of the proposed structure.

NOTE: -
The above recommendations are based on the field investigation data results and the laboratory

tests results of the samples collected from the test locations and our experience in this regard. If the

actual sub-soil conditions during excavation for the foundations differ from that has been reported,

a reference should be made to us for suggestions.

Further, the recommendations are based on the assumptions as mentioned in the Report and the

designer of the Structure should take into consideration all the factors required as per codes. The

recommendations should be taken as guidelines for the designer.

Er. Anand Kumar Sonkar Er. Anurag Kapoor


B.Tech. (Civil), M.Tech (SDEE) B.Tech. (Civil), M.Tech (Geotech)
Sr. MANAGER [TECHNICAL] PGDM (Finance), LM - IGS & IRC
ARUN SOIL LAB Pvt. Ltd. VICE CHAIRMAN
ARUN SOIL LAB Pvt. Ltd.

ARUN SOIL LAB PVT. LTD.


(Geotech & Material Consultants for Civil Engineering Projects)
E-11, First Floor, Lekhraj Market-I, Indira Nagar, Lucknow- 226016
Phone: 2341943; 4001043; Mobile: 9415025566, 9415501637, 38
arunsoillab.asl@gmail.com; info@arunsoillab.com
Page 10 of 24
ISO/IEC 17025 Accredited Laboratory ARUN SOIL LAB PVT LTD
(NABL accredited lab) Geotech Investigation Report No. ASL 173E-2023

SITE PLAN/GOOGLE EARTH IMAGE

ARUN SOIL LAB PVT. LTD.


(Geotech & Material Consultants for Civil Engineering Projects)
E-11, First Floor, Lekhraj Market-I, Indira Nagar, Lucknow- 226016
Phone: 2341943; 4001043; Mobile: 9415025566, 9415501637, 38
arunsoillab.asl@gmail.com; info@arunsoillab.com
Page 11 of 24
ISO/IEC 17025 Accredited Laboratory ARUN SOIL LAB PVT LTD
(NABL accredited lab) Geotech Investigation Report No. ASL 173E-2023

SITE PHOTOGRAPHS

ARUN SOIL LAB PVT. LTD.


(Geotech & Material Consultants for Civil Engineering Projects)
E-11, First Floor, Lekhraj Market-I, Indira Nagar, Lucknow- 226016
Phone: 2341943; 4001043; Mobile: 9415025566, 9415501637, 38
arunsoillab.asl@gmail.com; info@arunsoillab.com
Page 12 of 24
ARUN SOIL LAB PRIVATE LIMITED PILE CALCULATION

SAFE LOAD CARRYING CAPACITY OF BORED CAST IN SITU PILES [AS PER IRC:78-2014 AND IS :2911(Part 1)]
ESTIMATION OF VERTICAL COMPRESSIVE AND UPLIFT LOAD CARRYING CAPACITY OF BORED CAST IN-SITU CONCRETE PILE
SUB SOIL INVESTIGATION FOR PROPOSED CONSTRUCTION OF FOUR-LANE GREENFIELD AMRITSAR CONNECTIVITY FOR CONNECTION OF AMRITSAR WITH DELHI-AMRITSAR-KATRA EXPRESSWAY
NAME OF THE PROJECT FROM JUNCTION WITH NH-3 AND TARAN BYPASS NEAR MANNAWALA VILLAGE CH 70+950 TO JUNCTION WITH NH-354 AJANALA ROAD NEAR HARSHA CHINA VILLAGE CH 99+020 (KM 70+950 TO KM
99+020 PF AMRITSAR CONNECTIVITY) ON EPC MODE UNDER BHARATMALA PARIYOJNA IN THE STATE OF PUNJAB
Pile Diameter (mm) 1000 Ground Water Table (m) 0.00 (Conservative side) FOS In Compression 2.50
Pile Cut off Length Below G.L(m)
BORE HOLE Average Void Factor (%) FOS In Uplift
2.00 10.00 2.50
Parameters of Pile Reduced Level of Borehole (m) 100.000 Critical Depth (Pd Level) 20.00 X Pile Diameter Grade of Concrete (M) 35
BH-1 Settlement (Assumed) 10.00 mm (1% of pile diameter) (Assumed)

Calculation sheet for Vertical Compressive and Uplift Load Carrying Capacity
Cumulative
Total Difference in
Pile Length Angle of Effective Effective Skin Self
Type of Soil RL of Layer RL of Layer Thickness of Submerged Ultimate End Factors for Skin Friction Weight of Ultimate shaft Total Ultimate pile Safe Pile Capacity Safe Pile Capacity
Layer no Below Cut- Cohesion Internal Bulk Density Overburden Overburden Bearing Capacity Factor friction in Weight of
Layer Top Bottom Layer Bulk Density Bearing Displaced Soil and resistance capacity (compression) (Uplift)
off Level Friction Pressure Pressure at pile layer pile
tip Capacity RCC

C Ø Pd Ru K Pdi tan δ Asi α W W' Rf Qu= Ru+ Rf Qus


(m) (m) (m) (m) Kg/cm2 ° (gms/cc) (kN/m3) (kN/m2) (kN/m2) Nc Nq Nγ (kN) (kN/m2) (m2) (kN) (kN) (kN) (kN) (kN) (Tonnes) (Tonnes)

1 CLAY 0.50 98.000 97.500 0.50 0.20 18 1.87 8.53 4.27 4.27 9 7.48 4.07 180.06 1.50 2.13 0.32 1.57 0.7 23.62 4.95 1.60 23.62 203.68 8.14 1.16

2 SAND 8.00 97.500 90.000 7.50 0.00 27 1.76 7.45 55.90 60.17 9 12.73 14.47 643.97 1.50 32.22 0.37 23.56 0.0 420.05 79.17 31.92 443.68 1087.64 41.11 20.34

3 SAND 9.50 90.000 88.500 1.50 0.00 29 1.91 8.92 13.39 73.55 9 18.14 19.34 1115.64 1.50 66.86 0.40 4.71 0.0 188.55 94.01 36.25 632.23 1747.86 67.59 27.10

4 CLAY 12.50 88.500 85.500 3.00 0.30 17 2.06 10.40 31.19 104.74 9 7.12 3.53 812.17 1.50 89.15 0.31 9.42 0.7 583.22 123.70 41.45 1215.45 2027.62 78.47 46.40

5 CLAY 14.00 85.500 84.000 1.50 0.35 16 2.07 10.49 15.74 120.48 9 6.76 3.06 899.67 1.50 112.61 0.29 4.71 0.7 343.70 138.54 43.93 1559.15 2458.81 95.81 57.51

6 SAND 17.00 84.000 81.000 3.00 0.00 30 1.95 9.32 27.95 148.43 9 21.65 22.40 2606.00 1.50 134.45 0.41 9.42 0.0 787.34 168.23 51.67 2346.48 4952.49 196.73 82.52

7 SAND 24.50 81.000 73.500 7.50 0.00 33 1.97 9.51 71.35 148.43 9 36.82 35.19 4423.91 1.50 184.10 0.46 23.56 0.0 2999.63 242.45 69.86 5346.11 9770.02 391.37 173.94

8 SAND 26.00 73.500 72.000 1.50 0.00 34 1.99 9.71 14.56 148.43 9 43.95 41.06 5280.18 1.50 227.06 0.48 4.71 0.0 765.53 257.30 73.27 6111.64 11391.82 457.17 196.86

9 SAND 27.00 72.000 71.000 1.00 0.00 34 1.99 9.71 9.71 148.43 9 43.95 41.06 5280.18 1.50 239.19 0.48 3.14 0.0 537.63 267.19 75.53 6649.28 11929.45 478.87 212.90

10 SAND 28.00 71.000 70.000 1.00 0.00 34 1.99 9.71 9.71 148.43 9 43.95 41.06 5280.18 1.50 248.90 0.48 3.14 0.0 559.45 277.09 77.80 7208.73 12488.91 501.45 229.55

* Safe pile capacity in uplift = 70% of skin friction capacity + Self weight of pile

Page 13 of 24
ARUN SOIL LAB PRIVATE LIMITED PILE CALCULATION

SAFE LOAD CARRYING CAPACITY OF BORED CAST IN SITU PILES [AS PER IRC:78-2014 AND IS :2911(Part 1)]
ESTIMATION OF VERTICAL COMPRESSIVE AND UPLIFT LOAD CARRYING CAPACITY OF BORED CAST IN-SITU CONCRETE PILE
SUB SOIL INVESTIGATION FOR PROPOSED CONSTRUCTION OF FOUR-LANE GREENFIELD AMRITSAR CONNECTIVITY FOR CONNECTION OF AMRITSAR WITH DELHI-AMRITSAR-KATRA EXPRESSWAY
NAME OF THE PROJECT FROM JUNCTION WITH NH-3 AND TARAN BYPASS NEAR MANNAWALA VILLAGE CH 70+950 TO JUNCTION WITH NH-354 AJANALA ROAD NEAR HARSHA CHINA VILLAGE CH 99+020 (KM 70+950 TO KM
99+020 PF AMRITSAR CONNECTIVITY) ON EPC MODE UNDER BHARATMALA PARIYOJNA IN THE STATE OF PUNJAB
Pile Diameter (mm) 1200 Ground Water Table (m) 0.00 (Conservative side) FOS In Compression 2.50
Pile Cut off Length Below G.L(m)
BORE HOLE Average Void Factor (%) FOS In Uplift
2.30 10.00 2.50
Parameters of Pile Reduced Level of Borehole (m) 100.000 Critical Depth (Pd Level) 20.00 X Pile Diameter Grade of Concrete (M) 35
BH-1 Settlement (Assumed) 12.00 mm (1% of pile diameter) (Assumed)

Calculation sheet for Vertical Compressive and Uplift Load Carrying Capacity
Cumulative
Total Difference in
Pile Length Angle of Effective Effective Skin Self
Type of Soil RL of Layer RL of Layer Thickness of Submerged Ultimate End Factors for Skin Friction Weight of Ultimate shaft Total Ultimate pile Safe Pile Capacity Safe Pile Capacity
Layer no Below Cut- Cohesion Internal Bulk Density Overburden Overburden Bearing Capacity Factor friction in Weight of
Layer Top Bottom Layer Bulk Density Bearing Displaced Soil and resistance capacity (compression) (Uplift)
off Level Friction Pressure Pressure at pile layer pile
tip Capacity RCC

C Ø Pd Ru K Pdi tan δ Asi α W W' Rf Qu= Ru+ Rf Qus


(m) (m) (m) (m) Kg/cm2 ° (gms/cc) (kN/m3) (kN/m2) (kN/m2) Nc Nq Nγ (kN) (kN/m2) (m2) (kN) (kN) (kN) (kN) (kN) (Tonnes) (Tonnes)

1 CLAY 0.20 97.700 97.500 0.20 0.20 18 1.87 8.53 1.71 1.71 9 7.48 4.07 241.55 1.50 0.85 0.32 0.75 0.7 10.87 2.85 0.92 10.87 252.42 10.20 0.59

2 SAND 7.70 97.500 90.000 7.50 0.00 27 1.76 7.45 55.90 57.61 9 12.73 14.47 902.65 1.50 29.66 0.37 28.27 0.0 464.02 109.73 44.58 474.89 1377.54 51.64 24.27

3 SAND 9.20 90.000 88.500 1.50 0.00 29 1.91 8.92 13.39 70.99 9 18.14 19.34 1573.52 1.50 64.30 0.40 5.65 0.0 217.60 131.10 50.81 692.48 2266.00 87.24 32.50

4 CLAY 12.20 88.500 85.500 3.00 0.30 17 2.06 10.40 31.19 102.18 9 7.12 3.53 1153.06 1.50 86.59 0.31 11.31 0.7 686.59 173.85 58.29 1379.07 2532.13 97.33 56.00

5 CLAY 13.70 85.500 84.000 1.50 0.35 16 2.07 10.49 15.74 117.92 9 6.76 3.06 1279.58 1.50 110.05 0.29 5.65 0.7 406.21 195.23 61.87 1785.29 3064.87 118.70 69.51

6 SAND 16.70 84.000 81.000 3.00 0.00 30 1.95 9.32 27.95 145.87 9 21.65 22.40 3713.57 1.50 131.89 0.41 11.31 0.0 926.82 237.98 73.01 2712.10 6425.67 254.64 99.74

7 SAND 24.20 81.000 73.500 7.50 0.00 33 1.97 9.51 71.35 145.87 9 36.82 35.19 6301.69 1.50 181.54 0.46 28.27 0.0 3549.51 344.86 99.20 6261.61 12563.31 502.31 209.81

8 SAND 26.00 73.500 71.700 1.80 0.00 34 1.99 9.71 17.48 145.87 9 43.95 41.06 7521.31 1.50 225.95 0.48 6.79 0.0 1097.01 370.51 105.09 7358.62 14879.93 596.19 243.09

9 SAND 27.00 71.700 70.700 1.00 0.00 34 1.99 9.71 9.71 145.87 9 43.95 41.06 7521.31 1.50 239.55 0.48 3.77 0.0 646.11 384.76 108.36 8004.73 15526.04 622.21 262.61

10 SAND 28.00 70.700 69.700 1.00 0.00 34 1.99 9.71 9.71 145.87 9 43.95 41.06 7521.31 1.50 249.25 0.48 3.77 0.0 672.30 399.01 111.63 8677.03 16198.34 649.30 282.86

* Safe pile capacity in uplift = 70% of skin friction capacity + Self weight of pile

Page 14 of 24
ARUN SOIL LAB PVT LTD
Lateral Load Capacity of Pile
[As per IS : 2911(Part 1/Sec 2)-2010, Second Revision and IRC : 78-2014]

SUB SOIL INVESTIGATION FOR PROPOSED CONSTRUCTION OF FOUR-LANE GREENFIELD AMRITSAR CONNECTIVITY FOR CONNECTION OF
AMRITSAR WITH DELHI-AMRITSAR-KATRA EXPRESSWAY FROM JUNCTION WITH NH-3 AND TARAN BYPASS NEAR MANNAWALA VILLAGE CH
Project Name
70+950 TO JUNCTION WITH NH-354 AJANALA ROAD NEAR HARSHA CHINA VILLAGE CH 99+020 (KM 70+950 TO KM 99+020 PF AMRITSAR
CONNECTIVITY) ON EPC MODE UNDER BHARATMALA PARIYOJNA IN THE STATE OF PUNJAB

Borehole : BH1 Water Table : 0.00

PILE DETAILS :
Diameter of Pile, ( D ) = 1000 mm
Existing Ground Level = - m
Pile Cut-off Level = 2.75 m
Maximum Liquefiable Level / Loose or Soft soil = 0
Minimum Length of Pile to be long pile = 28.00 m
Grade of Concrete (M) = M35
4
Moment of Inertia of Pile, (I) = 0.0491 m
Modulus of Elasticity of Pile, (E) = 29580.40 Mpa
Pile Legth Above Scour /Liquefiable Level, (L1) = 0 m

SOIL PARAMETERS :
SOIL TYPE(CLAY/SILT/SAND) SAND
2
Cohesion of Soil, ( c ) = 0.00 kg/cm
2
Unconfined compressive strength of Soil, (su) = 0.00 kg/cm
Modulus of subgrade reaction for cohesive soil, k1 = -
Average "N" value = 20

OTHER PARAMETERS :
3
Modulus of Subgrade Reaction for granular soil, (‫ח‬h) = 2.84 MN/m
3
Modulus of Subgrade Reaction for Cohesive Soil, (k1) = - MN/m
3
Modulus of horizontal subgrade reaction = - MN/m
K = [(k1*0.3/1.5*B)]
Stiffness Factor for P.C. Cohesive Soil, (R) = - m
Stiffness Factor for N.C.clay and NonCohesive Soil, (T) = 3.48 m
Embedded Pile Length (Le) = 28.00 m
Type of pile Behaviour Long
L1 / R or L1 / T = 0

DETERMINATION OF DEPTH OF FIXITY :


For Fixed Headed Pile : Lf / R or Lf / T = 2.20
Depth of Fixity for fixed headed pile, (Lffx) = 7.66 m
Depth of Fixity w.r.t. Pile Cap Bottom (Lffx = Lf + L1) = 7.66 m

Determination of Lateral Load Capacity :


Pile Head Deflection at Pile Cut-off Level, (δ) = 10 mm
Lateral Load Capacity for fixed headed pile, (Hfx) = 39.55 Tonnes
=

Lateral Load Capacity of Pile = 39.55 Tonnes

Page 15 of 24
ARUN SOIL LAB PVT LTD
Lateral Load Capacity of Pile
[As per IS : 2911(Part 1/Sec 2)-2010, Second Revision and IRC : 78-2014]

SUB SOIL INVESTIGATION FOR PROPOSED CONSTRUCTION OF FOUR-LANE GREENFIELD AMRITSAR CONNECTIVITY FOR CONNECTION OF
AMRITSAR WITH DELHI-AMRITSAR-KATRA EXPRESSWAY FROM JUNCTION WITH NH-3 AND TARAN BYPASS NEAR MANNAWALA VILLAGE CH
Project Name
70+950 TO JUNCTION WITH NH-354 AJANALA ROAD NEAR HARSHA CHINA VILLAGE CH 99+020 (KM 70+950 TO KM 99+020 PF AMRITSAR
CONNECTIVITY) ON EPC MODE UNDER BHARATMALA PARIYOJNA IN THE STATE OF PUNJAB

Borehole : BH1 Water Table : 0.00

PILE DETAILS :
Diameter of Pile, ( D ) = 1200 mm
Existing Ground Level = - m
Pile Cut-off Level = 2.75 m
Maximum Liquefiable Level / Loose or Soft soil = 0
Minimum Length of Pile to be long pile = 28.00 m
Grade of Concrete (M) = M35
4
Moment of Inertia of Pile, (I) = 0.1018 m
Modulus of Elasticity of Pile, (E) = 29580.40 Mpa
Pile Legth Above Scour /Liquefiable Level, (L1) = 0 m

SOIL PARAMETERS :
SOIL TYPE(CLAY/SILT/SAND) SAND
2
Cohesion of Soil, ( c ) = 0.00 kg/cm
2
Unconfined compressive strength of Soil, (su) = 0.00 kg/cm
Modulus of subgrade reaction for cohesive soil, k1 = -
Average "N" value = 20

OTHER PARAMETERS :
3
Modulus of Subgrade Reaction for granular soil, (‫ח‬h) = 2.84 MN/m
3
Modulus of Subgrade Reaction for Cohesive Soil, (k1) = - MN/m
3
Modulus of horizontal subgrade reaction = - MN/m
K = [(k1*0.3/1.5*B)]
Stiffness Factor for P.C. Cohesive Soil, (R) = - m
Stiffness Factor for N.C.clay and NonCohesive Soil, (T) = 4.03 m
Embedded Pile Length (Le) = 28.00 m
Type of pile Behaviour Long
L1 / R or L1 / T = 0

DETERMINATION OF DEPTH OF FIXITY :


For Fixed Headed Pile : Lf / R or Lf / T = 2.20
Depth of Fixity for fixed headed pile, (Lffx) = 8.86 m
Depth of Fixity w.r.t. Pile Cap Bottom (Lffx = Lf + L1) = 8.86 m

Determination of Lateral Load Capacity :


Pile Head Deflection at Pile Cut-off Level, (δ) = 12 mm
Lateral Load Capacity for fixed headed pile, (Hfx) = 63.54 Tonnes
=

Lateral Load Capacity of Pile = 63.54 Tonnes

Page 16 of 24
RESULT SHEET
NAME OF THE PROJECT FOUR-LANE GREENFIELD AMRITSAR CONNECTIVITY FOR CONNECTION OF AMRITSAR WITH DELHI-AMRITSAR-KATRA EXPRESSWAY
Client Name M/s D.P.S. Contractors Pvt. Ltd.
Bore Hole No. 1 Easting 489836.52 Depth of Water Level (m bgl) 21.00
Total depth of
35.00
Coordinate Northing 3507820.98 Commenced on ARUN SOIL LAB PVT. LTD.
Bore Hole (m) Elevation 100.000 Completed on
% Material Passing

SPT Value corrected

SPT Value corrected


Shear

Wet Bulk Density

Original Moisture
Type of Sample

Dry Bulk Density


due to overburden

IS group symbol

Specific Gravity
Atterberg Limits

due to dilatancy

Compression
IS Sieve

Type of Test
Characterisitics

Void Ratio
Silt Factor
SPT Value
Depth of Bore Reduced Level

Index
Cohesion

Angle of

Friction
Internal
Hole (Assumed)

4.750

2.000

0.425

0.075
LL PL PI

metre metre N N' N" (mm) (mm) (mm) (mm) % % % (gms/cc) % (gms/cc) (G) (e) (Kg/sqcm) (Ø) (Cc) CD/UU
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

0.00 - 0.50 100.000 - 99.500 DS - - - 100 100 100 97 - 26 19 7 CL-ML - - - - - - - -

1.00 - 1.45 99.000 - 98.550 UD - - - 98 95 92 90 - 26 19 7 CL-ML 1.87 16.90 1.60 2.64 0.650 0.2 18 - UU
1.45 - 1.90 98.550 - 98.100 SPT 10 - - - -

2.50 - 2.95 97.500 - 97.050 UD - - - 100 100 100 26 - NON-PLASTIC SM 1.74 13.70 1.53 2.56 0.673 0 27 - CD
2.95 - 3.40 97.050 - 96.600 SPT 15 17.33 17.33 - -

4.00 - 4.45 96.000 - 95.550 UD - - - 100 100 100 22 - NON-PLASTIC SM - - - - - - - - CD


4.45 - 4.90 95.550 - 95.100 SPT 19 19.63 19.63 - -

5.50 - 5.95 94.500 - 94.050 UD - - - 100 100 99 18 - NON-PLASTIC SM 1.79 15.50 1.55 - - - - - CD
5.95 - 6.40 94.050 - 93.600 SPT 22 20.78 20.78 - -

7.00 - 7.45 93.000 - 92.550 UD - - - 100 100 99 16 - NON-PLASTIC SM - - - - - - - - CD


7.45 - 7.90 92.550 - 92.100 SPT 24 20.98 20.98 -

8.50 - 8.95 91.500 - 91.050 UD - - - 100 100 99 14 - NON-PLASTIC SM - - - - - - - - CD


8.95 - 9.40 91.050 - 90.600 SPT 30 24.48 24.48 - -

10.00 - 10.45 90.000 - 89.550 UD - - - 100 100 100 14 - NON-PLASTIC SM 1.91 17.80 1.62 2.57 0.586 0 29 - CD
10.45 - 10.90 89.550 - 89.100 SPT 36 27.42 27.42 - -
-
11.50 - 11.95 88.500 - 88.050 UD - - - 90 87 85 82 - 34 25 9 ML 2.06 22.70 1.68 2.67 0.589 0.30 17 - UU
11.95 - 12.40 88.050 - 87.600 SPT 22 - - -
-
13.00 - 13.45 87.000 - 86.550 UD - - 92 89 86 85 - 34 25 9 ML - - - - - - - - UU
13.45 - 13.90 86.550 - 86.100 SPT 27 - - - -

14.50 - 14.95 85.500 - 85.050 UD - - - 93 90 88 86 - 34 25 9 ML 2.07 21.30 1.71 2.67 0.561 0.35 16 - UU
14.95 - 15.40 85.050 - 84.600 SPT 33 - - -

16.00 - 16.45 84.000 - 83.550 UD - - - 100 100 100 55 - NON-PLASTIC ML 1.95 18.60 1.64 2.59 0.579 0 30 - CD
16.45 - 16.90 83.550 - 83.100 SPT 38 22.79 22.79 - -

17.50 - 17.95 82.500 - 82.050 UD - - - 100 100 100 60 - NON-PLASTIC ML - - - - - - - - CD


17.95 - 18.40 82.050 - 81.600 SPT 39 22.28 22.28 - -

Page 17 of 24
RESULT SHEET
NAME OF THE PROJECT FOUR-LANE GREENFIELD AMRITSAR CONNECTIVITY FOR CONNECTION OF AMRITSAR WITH DELHI-AMRITSAR-KATRA EXPRESSWAY
Client Name M/s D.P.S. Contractors Pvt. Ltd.
Bore Hole No. 1 Easting 489836.52 Depth of Water Level (m bgl) 21.00
Total depth of
35.00
Coordinate Northing 3507820.98 Commenced on ARUN SOIL LAB PVT. LTD.
Bore Hole (m) Elevation 100.000 Completed on
% Material Passing

SPT Value corrected

SPT Value corrected


Shear

Wet Bulk Density

Original Moisture
Type of Sample

Dry Bulk Density


due to overburden

IS group symbol

Specific Gravity
Atterberg Limits

due to dilatancy

Compression
IS Sieve

Type of Test
Characterisitics

Void Ratio
Silt Factor
SPT Value
Depth of Bore Reduced Level

Index
Cohesion

Angle of

Friction
Internal
Hole (Assumed)

4.750

2.000

0.425

0.075
LL PL PI

metre metre N N' N" (mm) (mm) (mm) (mm) % % % (gms/cc) % (gms/cc) (G) (e) (Kg/sqcm) (Ø) (Cc) CD/UU
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

19.00 - 19.45 81.000 - 80.550 UD - - - 100 100 100 26 - NON-PLASTIC SM 1.97 18.90 1.66 2.59 0.560 0 33 - CD
19.45 - 19.90 80.550 - 80.100 SPT 51 27.73 27.73 - -

20.50 - 20.95 79.500 - 79.050 UD - - - 100 100 99 14 - NON-PLASTIC SM - - - - - - - - CD


20.95 - 21.40 79.050 - 78.600 SPT 43 32.91 23.96 - -

22.00 - 22.45 78.000 - 77.550 UD - - - 100 100 98 11 - NON-PLASTIC SM-SP 1.96 19.70 1.64 2.6 0.585 0 33 - CD
22.45 - 22.90 77.550 - 77.100 SPT 52 38.53 26.77 - -

23.50 - 23.95 76.500 - 76.050 UD - - - 100 100 98 9 - NON-PLASTIC SM-SP - - - - - - - - CD


23.95 - 24.40 76.050 - 75.600 SPT 60 43.19 29.10 -

25.00 - 25.45 75.000 - 74.550 UD - - - 100 100 96 7 - NON-PLASTIC SM-SP - - - - - - - - CD


25.45 - 25.90 74.550 - 74.100 SPT 69 48.29 31.65 - -

26.50 - 26.95 73.500 - 73.050 UD - - - 100 100 95 4 - NON-PLASTIC SP 1.99 17.60 1.69 2.61 0.544 0 34 - CD
26.95 - 27.40 73.050 - 72.600 SPT 75 50.91 32.96 - -

28.00 - 28.45 72.000 - 71.550 UD - - - 100 100 92 4 - NON-PLASTIC SP - - - - - - - - CD


28.45 - 28.90 71.550 - 71.100 SPT 77 50.89 32.95 -

29.50 - 29.95 70.500 - 70.050 UD - - - 100 100 94 3 - NON-PLASTIC SP - - - - - - - - CD


29.95 - 30.40 70.050 - 69.600 SPT 76 48.94 31.97 -

31.00 - 31.45 69.000 - 68.550 UD - - - 100 100 92 2 - NON-PLASTIC SP - - - - - - - - CD


31.45 - 31.90 68.550 - 68.100 SPT 82 51.49 33.25 -

32.50 - 32.95 67.500 - 67.050 UD - - - 100 100 93 4 - NON-PLASTIC SP 1.99 16.50 1.71 2.61 0.526 0 34 - CD
32.95 - 33.40 67.050 - 66.600 SPT 85 51.90 33.45 - -

34.00 - 34.45 66.000 - 65.550 UD - - - 100 100 92 4 - NON-PLASTIC SP - - - - - - - - CD


34.45 - 34.90 65.550 - 65.100 SPT 89 53.03 34.02 - -

34.90 - 35.00 65.100 - 65.000 DS - - - 100 100 91 3 - NON-PLASTIC SP - - - - - - - - -

Page 18 of 24
Page 19 of 24
ISO/IEC: 17025-2017 accredited lab Triaxial / Direct Shear Graphs

ARUN SOIL LAB PRIVATE LIMITED


Geotech & Material Testing Consultant
(Civil Engineering Projects)

Page 20 of 24
ISO/IEC: 17025-2017 accredited lab Triaxial / Direct Shear Graphs

ARUN SOIL LAB PRIVATE LIMITED


Geotech & Material Testing Consultant
(Civil Engineering Projects)

Page 21 of 24
ISO/IEC: 17025-2017 accredited lab Triaxial / Direct Shear Graphs

ARUN SOIL LAB PRIVATE LIMITED


Geotech & Material Testing Consultant
(Civil Engineering Projects)

Page 22 of 24
ISO/IEC: 17025-2017 accredited lab Triaxial / Direct Shear Graphs

ARUN SOIL LAB PRIVATE LIMITED


Geotech & Material Testing Consultant
(Civil Engineering Projects)

Page 23 of 24
ISO/IEC: 17025-2017 accredited lab Consolidation Test Graphs

ARUN SOIL LAB PRIVATE LIMITED


Geotech & Material Testing Consultant
(Civil Engineering Projects)

Page 24 of 24