Preventive Maintenance Task List

1
Transformer oil type

Site: RIL, Hazira Rev:

Equipment Name: Dated:


Equipment No: Start Time:
Permit No: Closing Time:

Sr
Activities Status
No

1 Ensure that a valid work order and electrical work permit is prepared for the activity.
Take valid Electrical work permit from authorized authority before starting any PM
2
activity on the Transformer.
3 Prepare a scheme to isolate the transformer from both HT and LT side.
Ensure that transformer HT & LT side CB are open, locked and tagged out as per
3
corporate LOTO procedure.
Discharge the transformer from both LT & HT side before working; keep the
4
discharge rod connected to the trafo bus bars till the job is complete.
5 Clean trafo tank, radiator and other parts.
6 Clean trafo LT & HT bushing and check for physical damage and leakages.
7 Check Oil level in HT & LT Bushing.
8 Check arcing horns for uniformity in all phases and adjust gaps if required.
9 Check trafo for oil leakages and take remedial actions.
10 Check Oil level in conservator and OLTC tank and do the necessary top up.
11 Check relief vent diaphragms and replace if necessary.
12 Check silica gel in oil breather and replace or reactivate if necessary.
13 Do the paint work where ever required.
14 Check the status of all valves.
15 Operate radiator cut off valves and check if they are in operating condition.
Take oil samples for Oil test like BDV, DGA, Moisture content, Tan Delta,
16
Resistivity etc.
17 Do the control cable dressing where ever required.
18 Clean HV & LV WTI / OTI dirty gauge glasses
Check the following settings
HV WTI alarm & Trip
19
LV WTI Alarm& Trip
OTI Alarm & Trip
Do the following test by Simulation
HV WTI alarm & Trip
LV WTI Alarm& Trip
OTI Alarm & Trip
20
Buchholz Alarm & Trip
PRV Alarm & Trip
MOG Alarm & Trip
Oil Surge relay trip
21 Power Connections tightness
22 Check tightness of all HV bushing connections
23 Check tightness of all LV bushing connections
Preventive Maintenance Task List
1
Transformer oil type

Site: RIL, Hazira Rev:

24 Check tightness of all HV winding neutral bushing connections


25 Check all LV winding neutral bushing connections for tightness
Check all body and neutral earthing connections and apply grease for corrosion
26
prevention
OLTC Drive Mechanism Box
27 Clean drive mechanism box
28 Check all control wiring terminations for tightness.
29 Check DM motor connections for tightness.
30 Check and record DM motor insulation.
31 Check DM motor relay setting.
32 Check DM motor O/L relay setting.
33 Check DM gearbox for oil leakages and take remedial action.
34 Check oil level in gear box and do the top up as per manufacturer's recommendation.
35 Provide lubrication in drive mechanism as per manufacturer's recommendations
36 Operate the OLTC in manual mode in all steps
37 Operate OLTC in auto mode in all steps
38 Check panel indication lamps
39 Check Panel space heater and thermostat setting
40 Check panel illumination lamp
Transformer Marshalling Box
41 Clean Marshalling box
42 Check all control connections for tightness.
43 Check all aux AC & DC supplies.
44 Check all indication lamps
45 Check all relay and timer settings.
46 Check panel space heater and thermostat.
47 Check panel illumination.
RTCC Panel
48 Clean RTCC Panel
49 Check all connections for tightness.
50 Test all annunciations and alarms by simulation.
51 Check aux AC & DC supply.
52 Check AVR relay settings.
53 Operate the AVR relay in test mode.
54 Do manual raise & lower operation from panel.
55 Check panel indications lamps.
56 Check panel space heater and thermostat
57 Check panel illumination lamp
58 Check panel earthing.
Measurements
59 Measure trafo IR and PI value with a insulation tester if values are lower take
necessary steps
HV winding to Earth with 5 KV megger for winding > 6.6KV, 2.5 KV for winding <
6.6 to 1.1 KV
LV Winding to Earth with 500 V megger for winding < 1.1 KV
Preventive Maintenance Task List
1
Transformer oil type

Site: RIL, Hazira Rev:

HV Winding to LV Winding
60 Measure Neutral earthing pit resistance

Any Other Abnormality / Remark / Observation:-

Checked by:

Tkii Engineer: Ril Engineer: