Customer Name: MIRAS INTERNATION INVESTMENT

Project Name : Olayan Hospital

# Consultant Comments Cummins Reply


1 Cummins last agreed proposal with the contractor, consultant and user in the meeting dated 30 November 2022 is for total Gen-Sets rated power 4088kVA
/ 3270KW ESP achieved by the following proposal:-
•Qty: 1 X C2000D6 with rated power "2500kVA / 2000KW ESP", Derated site net output at site conditions 50⁰C & 635mASL is 2,411.25kVA / 1,929kW ESP.
Generator capacity submitted is not matching with
•Qty: 1 X C1250D6 with rated power "1588kVA / 1270KW ESP", Derated site net output at site conditions 50⁰C & 635mASL is 1,527kVA / 1,222kW ESP.
project contract documents.
The total Project Gen-Sets derated site net output Power is 3,151 KW / 3,938.25 kVA, the total loads are 2202 KW hence the Gen-Sets will be running @
70%.

2 Submit Sizing report at derating calculation 50C shown Attaching the last updated sizing report and Gen-Sets deration reports for the proposed Gen-Sets @ 50⁰C & 635mASL
genset net power as per engine derating -engine gross

power(KW) -fan power- ………. etc.


3 Cummins required air flow are as follows:-
Fresh air inlet required for the generator (CFM) In
•The C1250D6 cooling system air flow is 34.6 m3/sec (73,313.3 CFM) @ maximum cooling air flow static restriction 12.7 mmH2O with required combustion
coordination with the Mechanical Department to avoid
air flow rate is 110.4 m3/min (3,898.8 CFM).
any overheating or in efficient operation for the
•The C2000D6 cooling system air flow is 38.2 m3/sec (80,941.3 CFM) @ maximum cooling air flow static restriction 12.7 mmH2O with required combustion
generator.
air flow rate is 174 m3/min (6,144.8 CFM
4 Material list with brand and country of origin to be Attached.
submitted.

# Cummins Public
Date: 04 December 2022.
Subject: Deration Calculation Sheet.
Project: LTAC Rehabilitation Hospital.

“C2000 D6” Standby Power Genset

GENSET NET POWER AS PER ENGINE DERATION:


Engine: QSK60-G6

Engine Standby Power = 2180 KWm


Deration at 50 ⁰C and 635 mASL = 6 %
Engine Fan Power = 44 KWm
Alternator Efficiency = 96.2 %
Genset Net Power = {(Engine kW Deration%) – Fan Power} x Alt.Efficiency

Genset Net S Power = {(2180 x 0.945) – 44} x 0.962 = 1929 KWe


GENSET NET POWER AS PER ALTERNATOR DERATION

Alternator: PI734F

Power output at 400V: 2084 KW


Deration at 50 ⁰C & 635 mASL altitude: 6 %
Total power Output after Deration: 2084 x 0.94 = 1958.96 KWe

Total Genset Net Power After Deration @ 50 ⁰C and 635 mASL is = 1929 KWe ESP

Baher Adel Elbarbary


Application Engineer – Technical Specialist
Cummins Saudi Arabia Limited, (Riyadh Branch)
Loads Summary Report
Project - LTAC Rehabilitation Hospital
Comments -
Project Requirements

Frequency, Hz : 60.0 Generators Running in Parallel : 2

Duty : Standby Site Altitude, ft(m) : 2001(610)

Voltage : 220/380, Series Wye Site Temperature, °C : 50

Phase : 3 Max. Altr Temp Rise, °C : 150

Fuel : Diesel Project Voltage Distortion Limit, % :

Emissions : No Preference

Loads Summary List


*Note: Detailed Loads and Step Report available below

Running Starting Peak Dip Limits, % VTHD%


Step No. Load Name Quantity
kW kVA kW kVA kW kVA Vdip Fdip Limit

Step01 LOAD A (LIFE 1 86.08 107.6 86.08 107.6 None None 30.0 10.0 0.0
SAFETY) - H-DPBL-LS
FEEDER 2

Step01 LOAD B (CRITICAL ) - 1 41.52 51.9 41.52 51.9 None None 30.0 10.0 0.0
H-SGBL-NL5/EL5
FEEDER 3

Step Summary 64.0 80.0 64.0 80.0 None None 30.0 10.0 0.0

Step02 LOAD E - H-SGBL- 1 1134.96 1418.7 1134.96 1418.7 None None 30.0 10.0 0.0
NL3/EL3

Step Summary 567.0 709.0 567.0 709.0 None None 30.0 10.0 0.0

Step03 LOAD F - H-SGBL- 1 939.6 1174.5 1174.5 1468.12 None None 30.0 10.0 0.0
NL1/EL1

Step Summary 470.0 587.0 587.0 734.0 None None 30.0 10.0 0.0

Project
Running Max Starting Cumulative Step Cumulative Peak
VTHD%
Project Summary
kW kVA kW kVA kW kVA kW kVA Limit

1101.1 1376.3 587.2 734.1 1218.5 1523.2 0.0 0.0 0.0

*Note: Detailed Loads and Step Report available below

Notes: -
• The proposed Gen-Set models for LTAC Rehabilitation Hospital project are (Qty: 1 X C2000D6 with rated power
"2500kVA / 2000KW ESP" + Qty: 1 X C1250D6 with rated power "1588kVA / 1270KW ESP");
► "C2000D6" Gen-Set 400V 60Hz powered by engine "QSK60-G6" & alternator "Pl734F" winding 13 derated net out
power at Riyadh site conditions (635 mASL & 50°C) is 1,929kW / 2,411.25 kVA (Standby Rating).
► "C1250D6" Gen-Set 400V 60Hz powered by engine "KTA50-G3" & alternator "PI734B" winding 13 derated net out
power at Riyadh site conditions (635 mASL & 50°C) is 1,222kW / 1,527kVA (Standby Rating).
► Therefore, Total Project Gen-Sets Net Output Power: 3,151 KW / 3,938.25 kVA

► The Project Total Running Power: 2,202 KW.


► Each Gen-Set will run at 70% rated capacity.

Loads and Steps Detail Report 13-Nov-2022 Page 1


Loads and Steps Detail Report
Project - LTAC Rehabilitation Hospital
Comments -
Project Requirements

Frequency, Hz : 60.0 Generators Running in Parallel : 2

Duty : Standby Site Altitude, ft(m) : 2001(610)

Voltage : 220/380, Series Wye Site Temperature, °C : 50

Phase : 3 Max. Altr Temp Rise, °C : 150

Fuel : Diesel Project Voltage Distortion Limit, % :

Emissions : No Preference

Calculated Individual Generator Set Load Running and Peak Requirements

Running kW : 1101.1 Max. Step kW : 587.2 In Step 3 Cumulative Step kW : 1218.5

Running kVA : 1376.3 Max. Step kVA : 734.1 In Step 3 Cumulative Step kVA : 1523.2

Running PF : 0.8 Peak kW : None Cumulative Peak kW : None

Running NLL kVA : None Peak kVA : None Cumulative Peak kVA : None
Alternator kW : 1101.08

Step1

Calculated Individual Generator Set Step Load Requirements

Running kW : 64.0 Starting kW : 64.0 Cumulative Step kW : 64.0

Running kVA : 80.0 Starting kVA : 80.0 Cumulative Step kVA : 80.0

Running Amps : 243.0 Starting Non-linear kVA : 0.0

Running Non-linear kVA : 0.0

Alternator kW : 63.8

Voltage Distortion Limit for : 0


step

LOAD A (LIFE SAFETY) - H-DPBL-LS FEEDER 2 Three Phase Quantity : 1 In this Step

Category : User Defined

Running kW : 86.08 Starting kW : 86.08 Peak kW : None

Running kVA : 107.6 Starting kVA : 107.6 Peak kVA : None

Running PF : 0.8 Starting PF : 0.8 Cyclic : No

Running Amps : 155.49 Max. % Voltage Dip : 30.0 Max. % Frequency Dip : 10.0

Alternator kW : 86.08 Voltage : 400

LOAD B (CRITICAL ) - H-SGBL-NL5/EL5 FEEDER 3 Three Phase Quantity : 1 In this Step

Category : User Defined

Running kW : 41.52 Starting kW : 41.52 Peak kW : None

Running kVA : 51.9 Starting kVA : 51.9 Peak kVA : None

Running PF : 0.8 Starting PF : 0.8 Cyclic : No

Loads and Steps Detail Report 13-Nov-2022 Page 2


Running Amps : 75.0 Max. % Voltage Dip : 30.0 Max. % Frequency Dip : 10.0

Alternator kW : 41.52 Voltage : 400

Step2

Calculated Individual Generator Set Step Load Requirements

Running kW : 567.0 Starting kW : 567.0 Cumulative Step kW : 631.0

Running kVA : 709.0 Starting kVA : 709.0 Cumulative Step kVA : 789.0

Running Amps : 2158.0 Starting Non-linear kVA : 0.0

Running Non-linear kVA : 0.0

Alternator kW : 567.48

Voltage Distortion Limit for : 0


step

LOAD E - H-SGBL-NL3/EL3 Three Phase Quantity : 1 In this Step

Category : User Defined

Running kW : 1134.96 Starting kW : 1134.96 Peak kW : None

Running kVA : 1418.7 Starting kVA : 1418.7 Peak kVA : None

Running PF : 0.8 Starting PF : 0.8 Cyclic : No

Running Amps : 2050.14 Max. % Voltage Dip : 30.0 Max. % Frequency Dip : 10.0

Alternator kW : 1134.96 Voltage : 400

Step3

Calculated Individual Generator Set Step Load Requirements

Running kW : 470.0 Starting kW : 587.0 Cumulative Step kW : 1219.0

Running kVA : 587.0 Starting kVA : 734.0 Cumulative Step kVA : 1523.0

Running Amps : 1787.0 Starting Non-linear kVA : 0.0

Running Non-linear kVA : 0.0

Alternator kW : 469.8

Voltage Distortion Limit for : 0


step

LOAD F - H-SGBL-NL1/EL1 Three Phase Quantity : 1 In this Step

Category : User Defined

Running kW : 939.6 Starting kW : 1174.5 Peak kW : None

Running kVA : 1174.5 Starting kVA : 1468.12 Peak kVA : None

Running PF : 0.8 Starting PF : 0.8 Cyclic : No

Running Amps : 1697.25 Max. % Voltage Dip : 30.0 Max. % Frequency Dip : 10.0

Alternator kW : 939.6 Voltage : 400

Loads and Steps Detail Report 13-Nov-2022 Page 3


Cummins Saudi Arabia LLC Ref: PD-MAZ-12-06-22

1. BILL OF QUANTITIES

2. COMPLIANCE STATEMENT

3. GENERATOR DATA SHEETS

4. PRODUCT CERTIFICATES

5. PREVOIUS APPROVALS

6. REFERENCES LIST
Origin and Plant Specification

BOP- C1250D6 (Open Type) -1270KW, 1588 KVA Standby:

Item Description Qty.

1 CPG Diesel Engine Generator model (C1250D6) rated @ ISO Conditions: 1

1588 KVA/1270 KW STANDBY POWER

1400 KVA/1120 KW PRIME POWER at 400/230 V, 3phase, 4 wire, 0.8 Power factor, 60
Hz & 1800rpm

Each Generator Set Will Include:

Engine – Cummins 1

Jacket Water Heater. 1

Alternator – Stamford (Cummins). 1

Basic Base frame with integral Anti-Vibration Mountings and Lifting Points 1

Alternator (400/230 V, 60Hz. 1800rpm) 1

Alternator Heater. 1

Battery Charger 1

Set mounted Power Command 3.3 Control Panel 1

Skid Mounted Radiator Suitable for 50C Ambient Temperature 1

Lead Acid Batteries w/tray, & cables. 1

Startup & Commissioning 1

Transportation to site 1

Exhaust Silencer with Flexible 1

This Genset with Cummins UK Origin


Item Description Qty.

1 CPG Diesel Engine Generator model (C2000D6) rated @ ISO Conditions: 1

2500 KVA/2000 KW STANDBY POWER

2281 KVA/1825 KW PRIME POWER at 400/230 V, 3phase, 4 wire, 0.8 Power factor, 60
Hz & 1800rpm

Each Generator Set Will Include:

Engine – Cummins 1

Jacket Water Heater. 1

Alternator – Stamford (Cummins). 1

Basic Base frame with integral Anti-Vibration Mountings and Lifting Points 1

Alternator (400/230 V, 60Hz. 1800rpm) 1

Alternator Heater. 1

Battery Charger 1

Set mounted Power Command 3.3 Control Panel 1

Skid Mounted Radiator Suitable for 50C Ambient Temperature 1

Lead Acid Batteries w/tray, & cables. 1

Startup & Commissioning 1

Transportation to site 1

Exhaust Silencer with Flexible 1

This Genset with Cummins UK Origin


Origin and Plant Specification

BOP- C1250D6 (Open Type) -1270KW, 1588 KVA Standby:

Item Description Qty. Origin

1 CPG Diesel Engine Generator model (C1250D6) rated @ ISO 1 Complete Genset Model
Conditions: C1500D6 / Cummins UK

1588 KVA/1270 KW STANDBY POWER

1400 KVA/1120 KW PRIME POWER at 400/230 V, 3phase, 4


wire, 0.8 Power factor, 60 Hz & 1800rpm

Each Generator Set Will Include:

Engine – Cummins 1 Cummins India

Alternator – Stamford (Cummins). 1 Stamford Europe/India/

Depends on availability

Battery Charger 1 Cummins Europe/India


/USA

Depends on availability

Set mounted Power Command 3.3 Control Panel 1 Cummins Singapore/ USA

Lead Acid Batteries w/tray, & cables. 1 Part of the Genset

This Genset with Cummins UK Origin


BOP- C2000D6 (Open Type) -2000 KW, 2500 KVA Standby:

Item Description Qty. Origin

1 CPG Diesel Engine Generator model (C2000D6) rated @ ISO 1 Complete Genset Model
Conditions: C1500D6 / Cummins UK

2500 KVA/2000 KW STANDBY POWER

2281 KVA/1825 KW PRIME POWER at 400/230 V, 3phase, 4


wire, 0.8 Power factor, 60 Hz & 1800rpm

Each Generator Set Will Include:

Engine – Cummins 1 Cummins UK

Alternator – Stamford (Cummins). 1 Stamford Europe/India

Depends on availability

Battery Charger 1 Cummins Europe/India


/USA

Depends on availability

Set mounted Power Command 3.3 Control Panel 1 Cummins Singapore/ USA

Lead Acid Batteries w/tray, & cables. 1 Part of the Genset

This Genset with Cummins UK Origin