SAUDI ARAMCO ID/PIEU - 14- May 2018 - REV. 2018.03.00 (Standards Cutoff -March 31, 2018) Rev. 2018.03.

Rev. 2018.03.00 31-Mar-18


SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Air Terminal Devices, Volume Damper and Duct Heaters
SAIC-K-4009 14-May-18 HVAC
Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ZULUF-TEMPORARY CONSTRUCTION FACILITY PROJECT- PK# 06 10-08643-0008 Al Yamama Company

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

A General
Schedule “Q”
A1 Delivered equipment and material shall be free of damage. Attachment IV
Section 5
B Air Terminal devices
All air system supply and return grilles shall be furnished in accordance
SAES-K-001
B1 with drawings and specifications, and mounted at locations shown on
Para 5.2.2
drawings.
Air Terminal devices shall be constructed of noncombustible material or of
NFPA 90A
B2 a material that has a maximum flame spread index of 25 and a maximum
Sect. 4.3.7.2
smoke developed index of 50
All materials in return air plenums shall be noncombustible
SAES-K-001
B3 or limited combustible and shall meet the requirements of
Para 4.8.12.12
Section 2.3.10 of NFPA 90A.
C Volume Dampers
Volume damper for sub-main and main-branch ducts takeoffs
shall be opposed blade type with blade linkages outside SAES-K-001
C1
the air stream and with a locking quadrant damper for Para 4.8.17.3
rectangular ducts.

Volume dampers at branch ducts shall be sheet metal butterfly type, using SAES-K-001
C2
pivot and rod with locking quadrant damper for rigid round ducts. Para 4.8.17.2

D Duct Heater (RVL Material)

SAES-K-001
D3 Electric Duct Heaters shall be equipped with an airflow switches
Para 4.4.4.5

Heating equipment / EDH shall be UL listed and selected for the type of SAES-K-001
D4
service required. Para.4.8.11

Heat pumps and air conditioners having duct heaters closer than 1.2 m (4
ft) to the heat pump or air conditioner shall have both the duct heater and
SAES-P-100
D5 heat pump or air conditioner identified as suitable for such installation and
Para 5.2
so marked.
(NFPA 70 Para 424.61)

Duct Heaters used with air conditioners or other air-cooling equipment that
could result in condensation of moisture shall be identified as suitable for SAES-P-100
D6
use with air conditioners Para 5.2
(NFPA 70 Para 424.62)

Saudi Aramco: Company General Use