You are on page 1of 19

Print Calculation Sheet

Isolated Footing Design(ACI 318-14) - Metric


Footing No. Group ID Foundation Geometry
- - Length Width Thickness
56 6 3.00m 3.00m 0.50m

Footing No. Footing Reinforcement Pedestal Reinforcement


- Bottom Reinforcement(Mz) Bottom Reinforcement(Mx) Top Reinforcement(Mz) Top Reinforcement(Mx) Main Steel Trans Steel
56 21 - 13 mm 22 - 13 mm 21 - 13 mm 21 - 13 mm N/A

Isolated Footing 56
1m

0.5 m

Elevation

X 1.5 m

0.5 m

0.7 m
3m
1.5 m

3m

Plan

Input Values

Footing Geometry

Design Type : Set Dimension


Minimum Footing Length - X(Fl) : 3000.00 mm
Minimum Footing Width - Z (Fw) : 3000.00 mm
Footing Thickness (Ft) : 500.00 mm
Eccentricity along X (Oxd) : 0.00 mm
Eccentricity along Z (Ozd) : 0.00 mm

Column Dimensions

Column Shape : Rectangular


Typesetting math: 65%

28-04-2024 12:50:49 1/19


Column Length - X (Dcol) : 0.50 m
Column Width - Z (Bcol) : 0.70 m

Pedestal

Include Pedestal : No
Pedestal Shape : N/A

Design Parameters

Concrete and Rebar Properties

Unit Weight of Concrete : 25.00 kN/m3


Strength of Concrete : 32.00 N/mm2
Yield Strength of Steel : 420.00 N/mm2
Minimum Bar Size : 13 mm
Maximum Bar Size : 25 mm
Top Footing Minimum Bar Size : 13 mm
Top Footing Maximum Bar Size : 25 mm
Pedestal Minimum Bar Size : 19 mm
Pedestal Maximum Bar Size : 32 mm
Minimum Bar Spacing : 80.00 mm
Maximum Bar Spacing : 300.00 mm
Pedestal Clear Cover (P, CL) : 50.00 mm
Bottom Footing Clear Cover (F, CL) : 75.00 mm

Soil Properties

Unit Weight : 18.00kN/m3

Base Value of Soil Bearing Capacity : 236.00kPa

Multiplying factor for soil bearing capacity for ultimate


: 2.00
loads

Soil Bearing Capacity Type : Gross Bearing Capacity

Soil Surcharge : 0.00kN/m2

Height of Soil above Footing : 1000.00mm

Type of Depth : Fixed Top

Bearing Capacity Input Method : Fixed Bearing Capacity

Minimum Percentage of Slab area in Contact for Service


: 0.00
Loads

Minimum Percentage of Slab area in Contact for Ultimate


: 0.00
Loads

Sliding and Overturning

Coefficient of Friction : 0.40


Factor of Safety Against Sliding : 1.50
Factor of Safety Against Overturning : 1.50

Global Settings

Top Reinforcement Option : Calculate only when foundation is subjected to uplift forces
Concrete Design Option : Net Pressure(Gross Pressure - Self Weight Pressure)
Top Reinforcement Factor : 1.00

------------------------------------------------------

Design Calculations
Typesetting math: 65%

28-04-2024 12:50:49 2/19


Footing Size

Initial Length (Lo) = 3.00 m


Initial Width (Wo) = 3.00 m

Load Combinations

Load Combination/s- Service Stress Level


Load Load Case Soil Self
Combination Load Combination Title Multiplier Bearing Weight Code
Number (a) Factor (b) Factor (c)
a - Value specified in the Load Multiplier table
b - Value specified in the Pile/Soil Bearing Capacity Factors table
c - Value specified in the Apply Self Weight and Dead Weight Factor table
101 1.0 DL 1.00 1.00 1.00 -
102 1.0 DL + 1 L 1.00 1.00 1.00 -
103 1.0 DL + 1 L 1.00 1.00 1.00 -
104 1.0 DL + 1.0 LR 1.00 1.00 1.00 -
105 1.0 DL + 0.75 L + 0.75 LR 1.00 1.00 1.00 -
106 1.0 DL + 0.75 L + 0.75 LR 1.00 1.00 1.00 -
107 1.0 DL + 0.6 W+X (+GCPI) 1.00 1.00 1.00 -
108 1.0 DL + 0.6 W+X (-GCPI) 1.00 1.00 1.00 -
109 1.0 DL + 0.6 W-X (+GCPI) 1.00 1.00 1.00 -
110 1.0 DL + 0.6 W-X (-GCPI) 1.00 1.00 1.00 -
111 1.0 DL + 0.6 W+Z (+GCPI) 1.00 1.00 1.00 -
112 1.0 DL + 0.6 W+Z (-GCPI) 1.00 1.00 1.00 -
113 1.0 DL + 0.6 W-Z (+GCPI) 1.00 1.00 1.00 -
114 1.0 DL + 0.6 W-Z (-GCPI) 1.00 1.00 1.00 -
115 1.05 DL + 0.7 E+X 1.00 1.00 1.00 -
116 1.05 DL + 0.7 E-X 1.00 1.00 1.00 -
117 1.05 DL + 0.7 E+Z 1.00 1.00 1.00 -
118 1.05 DL + 0.7 E-Z 1.00 1.00 1.00 -
119 1.0 DL + 0.45 W+X (+GCPI) + 0.75 L + 0.75 LR 1.00 1.00 1.00 -
120 1.0 DL + 0.45 W+X (-GCPI) + 0.75 L + 0.75 LR 1.00 1.00 1.00 -
121 1.0 DL + 0.45 W-X (+GCPI) + 0.75 L + 0.75 LR 1.00 1.00 1.00 -
122 1.0 DL + 0.45 W-X (-GCPI) + 0.75 L + 0.75 LR 1.00 1.00 1.00 -
123 1.0 DL + 0.45 W+Z (+GCPI) + 0.75 L + 0.75 LR 1.00 1.00 1.00 -
124 1.0 DL + 0.45 W+Z (-GCPI) + 0.75 L + 0.75 LR 1.00 1.00 1.00 -
125 1.0 DL + 0.45 W-Z (+GCPI) + 0.75 L + 0.75 LR 1.00 1.00 1.00 -
126 1.0 DL + 0.45 W-Z (-GCPI) + 0.75 L + 0.75 LR 1.00 1.00 1.00 -
127 1.026 DL + 0.525 E+X + 0.75 L + 0.75 LR 1.00 1.00 1.00 -
128 1.026 DL + 0.525 E-X + 0.75 L + 0.75 LR 1.00 1.00 1.00 -
129 1.026 DL + 0.525 E+Z + 0.75 L + 0.75 LR 1.00 1.00 1.00 -
130 1.026 DL + 0.525 E-Z + 0.75 L + 0.75 LR 1.00 1.00 1.00 -
131 0.6 DL + 0.6 W+X (+GCPI) 1.00 1.00 1.00 -
132 0.6 DL + 0.6 W+X (-GCPI) 1.00 1.00 1.00 -
133 0.6 DL + 0.6 W-X (+GCPI) 1.00 1.00 1.00 -
134 0.6 DL + 0.6 W-X (-GCPI) 1.00 1.00 1.00 -
135 0.6 DL + 0.6 W+Z (+GCPI) 1.00 1.00 1.00 -
136 0.6 DL + 0.6 W+Z (-GCPI) 1.00 1.00 1.00 -
137 0.6 DL + 0.6 W-Z (+GCPI) 1.00 1.00 1.00 -
138 0.6 DL + 0.6 W-Z (-GCPI) 1.00 1.00 1.00 -
139 0.55 DL + 0.7 E+X 1.00 1.00 1.00 -
140 0.55 DL + 0.7 E-X 1.00 1.00 1.00 -
141 0.55 DL + 0.7 E+Z 1.00 1.00 1.00 -
142 0.55 DL + 0.7 E-Z 1.00 1.00 1.00 -
143 1.0 DL + TLSS (+) 1.00 1.00 1.00 -
144 1.0 DL + TLSS (-) 1.00 1.00 1.00 -
145 1.0 DL + 1 L + TLSS (+) 1.00 1.00 1.00 -
146 1.0 DL + 1 L + TLSS (-) 1.00 1.00 1.00 -
147 1.0 DL + 1.0 LR + TLSS (+) 1.00 1.00 1.00 -
148 1.0 DL + 1.0 LR + TLSS (-) 1.00 1.00 1.00 -
149 1.0 DL + 0.75 L + 0.75 LR + TLSS (+) 1.00 1.00 1.00 -
150 1.0 DL + 0.75 L + 0.75 LR + TLSS (-) 1.00 1.00 1.00 -
151 1.0 DL + 0.5 L + 1.0 BL 1.00 1.00 1.00 -
152
Typesetting math: 65% 0.9 DL + 1.0 BL 1.00 1.00 1.00 -

28-04-2024 12:50:49 3/19


Load Combination/s- Strength Level
Load Load Case Soil Self
Combination Load Combination Title Multiplier Bearing Weight Code
Number (a) Factor (b) Factor (c)
a - Value specified in the Load Multiplier table
b - Value specified in the Pile/Soil Bearing Capacity Factors table
c - Value specified in the Apply Self Weight and Dead Weight Factor table
201 1.4 DL 1.00 1.00 1.00 -
202 1.2 DL + 1.6 L + 0.5 LR 1.00 1.00 1.00 -
203 1.2 DL + 1.6 L + 0.5 LR 1.00 1.00 1.00 -
204 1.2 DL + 1.0 L + 1.6 LR 1.00 1.00 1.00 -
205 1.2 DL + 1.6 LR + 0.5 W+X (+GCPI) 1.00 1.00 1.00 -
206 1.2 DL + 1.6 LR + 0.5 W+X (-GCPI) 1.00 1.00 1.00 -
207 1.2 DL + 1.6 LR + 0.5 W-X (+GCPI) 1.00 1.00 1.00 -
208 1.2 DL + 1.6 LR + 0.5 W-X (-GCPI) 1.00 1.00 1.00 -
209 1.2 DL + 1.6 LR + 0.5 W+Z (+GCPI) 1.00 1.00 1.00 -
210 1.2 DL + 1.6 LR + 0.5 W+Z (-GCPI) 1.00 1.00 1.00 -
211 1.2 DL + 1.6 LR + 0.5 W-Z (+GCPI) 1.00 1.00 1.00 -
212 1.2 DL + 1.6 LR + 0.5 W-Z (-GCPI) 1.00 1.00 1.00 -
213 1.2 DL + 1.0 L + 0.5 LR + 1.0 W+X (+GCPI) 1.00 1.00 1.00 -
214 1.2 DL + 1.0 L + 0.5 LR + 1.0 W+X (-GCPI) 1.00 1.00 1.00 -
215 1.2 DL + 1.0 L + 0.5 LR + 1.0 W-X (+GCPI) 1.00 1.00 1.00 -
216 1.2 DL + 1.0 L + 0.5 LR + 1.0 W-X (-GCPI) 1.00 1.00 1.00 -
217 1.2 DL + 1.0 L + 0.5 LR + 1.0 W+Z (+GCPI) 1.00 1.00 1.00 -
218 1.2 DL + 1.0 L + 0.5 LR + 1.0 W+Z (-GCPI) 1.00 1.00 1.00 -
219 1.2 DL + 1.0 L + 0.5 LR + 1.0 W-Z (+GCPI) 1.00 1.00 1.00 -
220 1.2 DL + 1.0 L + 0.5 LR + 1.0 W-Z (-GCPI) 1.00 1.00 1.00 -
221 1.25 DL + 1.0 L + 1.0 E+X 1.00 1.00 1.00 -
222 1.25 DL + 1.0 L + 1.0 E-X 1.00 1.00 1.00 -
223 1.25 DL + 1.0 L + 1.0 E+Z 1.00 1.00 1.00 -
224 1.25 DL + 1.0 L + 1.0 E-Z 1.00 1.00 1.00 -
225 0.9 DL + 1.0 W+X (+GCPI) 1.00 1.00 1.00 -
226 0.9 DL + 1.0 W+X (-GCPI) 1.00 1.00 1.00 -
227 0.9 DL + 1.0 W-X (+GCPI) 1.00 1.00 1.00 -
228 0.9 DL + 1.0 W-X (-GCPI) 1.00 1.00 1.00 -
229 0.9 DL + 1.0 W+Z (+GCPI) 1.00 1.00 1.00 -
230 0.9 DL + 1.0 W+Z (-GCPI) 1.00 1.00 1.00 -
231 0.9 DL + 1.0 W-Z (+GCPI) 1.00 1.00 1.00 -
232 0.9 DL + 1.0 W-Z (-GCPI) 1.00 1.00 1.00 -
233 0.85 DL + 1.0 E+X 1.00 1.00 1.00 -
234 0.85 DL + 1.0 E-X 1.00 1.00 1.00 -
235 0.85 DL + 1.0 E+Z 1.00 1.00 1.00 -
236 0.85 DL + 1.0 E-Z 1.00 1.00 1.00 -
237 1.2 DL + 0.5 W+X (+GCPI) 1.00 1.00 1.00 -
238 1.2 DL + 0.5 W+X (-GCPI) 1.00 1.00 1.00 -
239 1.2 DL + 0.5 W-X (+GCPI) 1.00 1.00 1.00 -
240 1.2 DL + 0.5 W-X (-GCPI) 1.00 1.00 1.00 -
241 1.2 DL + 0.5 W+Z (+GCPI) 1.00 1.00 1.00 -
242 1.2 DL + 0.5 W+Z (-GCPI) 1.00 1.00 1.00 -
243 1.2 DL + 0.5 W-Z (+GCPI) 1.00 1.00 1.00 -
244 1.2 DL + 0.5 W-Z (-GCPI) 1.00 1.00 1.00 -
245 1.4 DL + 1.2 TLSS (+) 1.00 1.00 1.00 -
246 1.4 DL + 1.2 TLSS (-) 1.00 1.00 1.00 -
247 1.2 DL + 1.6 L + 0.5 LR + 1.2 TLSS (+) 1.00 1.00 1.00 -
248 1.2 DL + 1.6 L + 0.5 LR + 1.2 TLSS (-) 1.00 1.00 1.00 -
249 1.2 DL + 1.0 L + 1.6 LR + 1.2 TLSS (+) 1.00 1.00 1.00 -
250 1.2 DL + 1.0 L + 1.6 LR + 1.2 TLSS (-) 1.00 1.00 1.00 -
251 1.2 DL + 0.5 L + 1.0 BL 1.00 1.00 1.00 -
252 0.9 DL + 1.0 BL 1.00 1.00 1.00 -

Applied Loads on Top of Pedestal


Before consideration of self weight and load multiplier table

Moments are about the center of Column / Pedestal (does not include moments caused by lateral loads)
For the loads shown in this table, the sign convention is the same as that for JOINT LOADS in STAAD.Pro when global Y is the vertical axis.

Typesetting math: 65%

28-04-2024 12:50:49 4/19


Applied Loads from Column - Service Stress Level
Fy
(kN)
Fx Fz Mx Mz
Load Case Downwards is
(kN) (kN) (kNm) (kNm)
negative Upwards
is positive
101 11.06 -713.14 27.24 53.02 -3.54
102 9.75 -850.53 44.50 81.25 -2.25
103 9.75 -850.53 44.50 81.25 -2.25
104 10.98 -751.03 30.34 56.99 -3.44
105 10.02 -844.60 42.51 77.18 -2.49
106 10.02 -844.60 42.51 77.18 -2.49
107 19.61 -695.69 31.47 57.55 -14.65
108 15.71 -719.63 29.60 55.83 -9.50
109 3.41 -691.51 30.82 56.01 6.28
110 3.10 -716.38 29.09 54.64 6.78
111 12.73 -706.37 54.52 112.88 -6.35
112 11.39 -727.93 42.01 89.44 -4.32
113 14.03 -685.21 0.16 -6.95 -6.89
114 12.24 -713.96 6.14 10.37 -4.68
115 126.69 -776.54 31.79 63.85 -153.19
116 -103.47 -721.04 25.40 47.49 145.76
117 5.44 -812.52 135.19 305.41 1.74
118 17.79 -685.06 -77.99 -194.07 -9.17
119 16.44 -831.52 45.69 80.57 -10.83
120 13.51 -849.47 44.28 79.28 -6.97
121 4.29 -828.38 45.20 79.42 4.87
122 4.05 -847.03 43.90 78.39 5.24
123 11.27 -839.53 62.97 122.08 -4.60
124 10.27 -855.69 53.59 104.49 -3.08
125 12.25 -823.65 22.20 32.20 -5.01
126 10.91 -845.22 26.69 45.19 -3.35
127 96.62 -883.96 45.61 84.69 -114.69
128 -76.00 -842.33 40.82 72.42 109.52
129 5.68 -910.94 123.16 265.86 1.51
130 14.94 -815.34 -36.73 -108.75 -6.68
131 15.19 -410.44 20.58 36.34 -13.23
132 11.29 -434.37 18.70 34.62 -8.09
133 -1.01 -406.26 19.93 34.80 7.69
134 -1.32 -431.12 18.20 33.43 8.19
135 8.30 -421.12 43.62 91.68 -4.93
136 6.96 -442.67 31.12 68.23 -2.91
137 9.60 -399.95 -10.74 -28.16 -5.48
138 7.82 -428.71 -4.75 -10.84 -3.27
139 121.16 -419.97 18.17 37.34 -151.42
140 -109.00 -364.48 11.79 20.98 147.52
141 -0.09 -455.96 121.57 278.90 3.51
142 12.26 -328.49 -91.61 -220.58 -7.40
143 11.06 -713.14 27.24 53.02 -3.54
144 11.06 -713.14 27.24 53.02 -3.54
145 9.75 -850.53 44.50 81.25 -2.25
146 9.75 -850.53 44.50 81.25 -2.25
147 10.98 -751.03 30.34 56.99 -3.44
148 10.98 -751.03 30.34 56.99 -3.44
149 10.02 -844.60 42.51 77.18 -2.49
150 10.02 -844.60 42.51 77.18 -2.49
151 10.39 -782.00 34.74 66.84 -2.92
152 9.94 -641.99 23.39 47.42 -3.21

Applied Loads from Column - Strength Level


Fy
(kN)
Fx Fz Mx Mz
Load Case Downwards is
(kN) (kN) (kNm) (kNm)
negative Upwards
is positive
201 15.48 -998.39 38.13 74.23 -4.95
202 11.14 -1094.54 61.85 110.79 -2.13
203 11.14 -1094.54 61.85 110.79 -2.13
Typesetting math: 65%

28-04-2024 12:50:49 5/19


Applied Loads from Column - Strength Level
Fy
(kN)
Fx Fz Mx Mz
Load Case Downwards is
(kN) (kN) (kNm) (kNm)
negative Upwards
is positive
204 11.84 -1053.79 54.91 98.22 -2.79
205 20.27 -901.86 41.18 73.76 -13.34
206 17.02 -921.80 39.62 72.33 -9.05
207 6.77 -898.37 40.64 72.47 4.10
208 6.51 -919.09 39.20 71.33 4.51
209 14.53 -910.76 60.38 119.87 -6.42
210 13.42 -928.72 49.96 100.33 -4.74
211 15.62 -893.12 15.08 20.01 -6.88
212 14.13 -917.08 20.07 34.44 -5.04
213 26.18 -983.03 58.55 101.39 -21.42
214 19.68 -1022.93 55.43 98.53 -12.85
215 -0.82 -976.06 57.47 98.82 13.45
216 -1.34 -1017.51 54.59 96.54 14.29
217 14.71 -1000.83 96.96 193.62 -7.59
218 12.47 -1036.75 76.12 154.54 -4.22
219 16.87 -965.55 6.36 -6.10 -8.49
220 13.90 -1013.48 16.34 22.77 -4.82
221 176.92 -1068.46 55.87 106.19 -216.66
222 -151.88 -989.17 46.74 82.83 210.40
223 3.70 -1119.86 203.58 451.28 4.66
224 21.34 -937.77 -100.97 -262.26 -10.93
225 24.21 -612.75 31.57 55.26 -21.70
226 17.70 -652.64 28.45 52.40 -13.13
227 -2.79 -605.78 30.49 52.70 13.17
228 -3.31 -647.22 27.61 50.41 14.01
229 12.73 -630.55 69.98 147.49 -7.86
230 10.50 -666.47 49.14 108.41 -4.49
231 14.90 -595.27 -20.62 -52.23 -8.77
232 11.93 -643.20 -10.64 -23.36 -5.09
233 173.80 -645.81 27.71 56.75 -216.54
234 -155.00 -566.52 18.59 33.39 210.52
235 0.58 -697.21 175.43 401.83 4.79
236 18.22 -515.12 -129.12 -311.70 -10.80
237 20.40 -841.23 36.21 67.40 -13.50
238 17.15 -861.17 34.65 65.96 -9.22
239 6.90 -837.74 35.67 66.11 3.93
240 6.64 -858.46 34.23 64.97 4.35
241 14.66 -850.13 55.42 113.51 -6.59
242 13.54 -868.09 45.00 93.97 -4.90
243 15.74 -832.49 10.12 13.65 -7.04
244 14.26 -856.45 15.11 28.08 -5.20
245 15.48 -998.39 38.13 74.23 -4.95
246 15.48 -998.39 38.13 74.23 -4.95
247 11.14 -1094.54 61.85 110.79 -2.13
248 11.14 -1094.54 61.85 110.79 -2.13
249 11.84 -1053.79 54.91 98.22 -2.79
250 11.84 -1053.79 54.91 98.22 -2.79
251 12.60 -924.62 40.19 77.44 -3.63
252 9.94 -641.99 23.39 47.42 -3.21

Reduction of force due to buoyancy = 44.11 kN

Effect due to adhesion = 0.00 kN

2
Area from initial length and width, Ao = Lo X W o = 9.00 m

Min. area required from bearing pressure, Amin = 7.78 m2

Note: Amin is an initial estimation considering self-weight, axial load and moment against factored bearing capacity.
Typesetting math: 65%

28-04-2024 12:50:49 6/19


Final Footing Size

Length (L2) = 3.00 m Governing Load Case : # 101


Width (W2) = 3.00 m Governing Load Case : # 101
Depth (D2) = 0.50 m
Depth is governed by Ultimate Load Case
(Service check is performed with footing thickness requirements from concrete check)

Area (A2) = 9.00 m2


Final Soil Height = 1.00 m
Weight of the footing + pedestal (if any) = 112.50 kN
Soil Weight On Top Of Footing = 155.69 kN

Gross Pressures at 4 Corners

Pressure Pressure Area of


Pressure Pressure Gross
at top at bottom
Load Case / at top left at bottom footing in Bearing
right right uplift (Au)
Combination corner left corner Capacity
corner corner 2
(kN/m2) (kN/m2) (m ) (kN/m2)
(kN/m2) (kN/m2)

118 153.6950 161.7246 58.1387 50.1091 0.00 236.0000

118 153.6950 161.7246 58.1387 50.1091 0.00 236.0000

129 57.9534 58.5455 204.0760 203.4839 0.00 236.0000

129 57.9534 58.5455 204.0760 203.4839 0.00 236.0000

If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of negative pressure will be set to zero and the pressure
will be redistributed to remaining corners.

Summary of Adjusted Gross Pressures at four Corners

Pressure at Pressure at Pressure at Pressure at Gross


top left top right bottom right bottom left Bearing
Load Case / corner corner corner corner Capacity
Combination (kN/m2) (kN/m2) (kN/m2) (kN/m2) (kN/m2)

118 153.6950 161.7246 58.1387 50.1091 236.0000

118 153.6950 161.7246 58.1387 50.1091 236.0000

129 57.9534 58.5455 204.0760 203.4839 236.0000

129 57.9534 58.5455 204.0760 203.4839 236.0000

Stability Check

Typesetting math: 65%

28-04-2024 12:50:49 7/19


1m
OTM

Sliding Force
.

Frictional Force 0.5 m

Factor of safety against


- Factor of safety against sliding
overturning

Load
Along X- Along Z- Required About X- About Z- Required
Case Resultant
Direction Direction FOS Direction Direction FOS
No.
101 33.90 13.76 12.75 1.50 21.10 155.04 1.50
102 44.07 9.66 9.44 1.50 15.57 226.18 1.50
103 44.07 9.66 9.44 1.50 15.57 226.18 1.50
104 35.52 12.86 12.09 1.50 20.27 163.86 1.50
105 42.66 10.06 9.79 1.50 16.29 213.58 1.50
106 42.66 10.06 9.79 1.50 16.29 213.58 1.50
107 18.76 11.69 9.92 1.50 18.83 56.42 1.50
108 24.03 12.75 11.27 1.50 20.04 81.54 1.50
109 107.37 11.88 11.81 1.50 19.23 300.42 1.50
110 121.35 12.93 12.86 1.50 20.39 269.78 1.50
111 29.25 6.83 6.65 1.50 9.96 109.82 1.50
112 33.44 9.06 8.75 1.50 12.93 142.55 1.50
113 25.93 2342.44 25.93 1.50 198.44 98.09 1.50
114 30.64 61.06 27.39 1.50 104.66 130.20 1.50
115 3.16 12.59 3.06 1.50 18.82 6.93 1.50
116 3.65 14.88 3.55 1.50 23.55 7.18 1.50
117 76.27 3.07 3.06 1.50 4.17 1593.90 1.50
118 20.44 4.66 4.55 1.50 5.85 75.48 1.50
119 25.69 9.24 8.70 1.50 15.31 83.15 1.50
120 31.79 9.70 9.28 1.50 15.88 117.33 1.50
121 98.23 9.31 9.27 1.50 15.47 579.59 1.50
122 105.73 9.76 9.72 1.50 16.01 499.45 1.50
123 37.74 6.76 6.65 1.50 10.39 155.85 1.50
124 42.07 8.06 7.92 1.50 12.34 197.08 1.50
125 34.22 18.88 16.53 1.50 36.30 141.16 1.50
126 39.20 16.03 14.83 1.50 27.40 182.07 1.50
127 4.59 9.72 4.15 1.50 15.46 10.20 1.50
128 5.61 10.45 4.94 1.50 17.23 10.84 1.50
129 79.97 3.69 3.68 1.50 5.20 1277.96 1.50
130 27.83 11.32 10.49 1.50 12.27 110.18 1.50
131 16.71 12.33 9.92 1.50 20.41 45.70 1.50
132 23.34 14.08 12.06 1.50 22.46 71.92 1.50
133 249.03 12.65 12.64 1.50 21.12 115.33 1.50
134 197.99 14.40 14.36 1.50 23.11 110.98 1.50

Typesetting math: 65%


135 31.09 5.92 5.81 1.50 8.53 106.56 1.50

28-04-2024 12:50:49 8/19


Factor of safety against
- Factor of safety against sliding
overturning

Load
Along X- Along Z- Required About X- About Z- Required
Case Resultant
Direction Direction FOS Direction Direction FOS
No.
136 38.30 8.57 8.36 1.50 11.94 156.50 1.50
137 25.99 23.24 17.33 1.50 27.92 91.08 1.50
138 33.39 54.97 28.54 1.50 74.12 136.39 1.50

139 2.13 14.18 2.10 1.50 20.81 4.56 1.50

140 2.16 19.98 2.15 1.50 32.85 4.37 1.50

141 2927.37 2.24 2.24 1.50 3.00 286.67 1.50


142 18.03 2.41 2.39 1.50 3.11 61.25 1.50
143 33.90 13.76 12.75 1.50 21.10 155.04 1.50
144 33.90 13.76 12.75 1.50 21.10 155.04 1.50
145 44.07 9.66 9.44 1.50 15.57 226.18 1.50
146 44.07 9.66 9.44 1.50 15.57 226.18 1.50
147 35.52 12.86 12.09 1.50 20.27 163.86 1.50
148 35.52 12.86 12.09 1.50 20.27 163.86 1.50
149 42.66 10.06 9.79 1.50 16.29 213.58 1.50
150 42.66 10.06 9.79 1.50 16.29 213.58 1.50
151 38.73 11.58 11.10 1.50 17.92 185.95 1.50
152 34.87 14.81 13.63 1.50 21.98 158.82 1.50

Critical Load Case And The Governing Factor Of Safety For Overturning And Sliding - X Direction

Critical Load Case for Sliding along X-Direction : 139


Governing Disturbing Force : 121.16 kN
Governing Restoring Force : 257.62 kN
Minimum Sliding Ratio for the Critical Load Case : 2.13
Critical Load Case for Overturning about X-Direction : 141
Governing Overturning Moment : 339.68 kNm
Governing Resisting Moment : 1020.04 kNm
Minimum Overturning Ratio for the Critical Load Case : 3.00

Critical Load Case And The Governing Factor Of Safety For Overturning And Sliding - Z Direction

Critical Load Case for Sliding along Z-Direction : 141


Governing Disturbing Force : 121.57 kN
Governing Restoring Force : 272.01 kN
Minimum Sliding Ratio for the Critical Load Case : 2.24
Critical Load Case for Overturning about Z-Direction : 140
Governing Overturning Moment : 202.02 kNm
Governing Resisting Moment : 882.82 kNm
Minimum Overturning Ratio for the Critical Load Case : 4.37
Critical Load Case And The Governing Factor Of Safety For Sliding Along Resultant Direction
Critical Load Case for Sliding along Resultant Direction : 139
Governing Disturbing Force : 122.52 kN
Governing Restoring Force : 257.62 kN
Minimum Sliding Ratio for the Critical Load Case : 2.10

Ultimate Gross Pressures


The base pressures reported in this table and the area of footing in contact include the effect of buoyancy (if any).

Load Case / Pressure at Pressure at Pressure at Pressure at Gross Area of


Load top left top right bottom bottom left Factored footing in
Typesetting math: 65% Combination Bearing Contact

28-04-2024 12:50:49 9/19


ID corner corner right corner corner Capacity with soil
(kN/m2) (kN/m2) (kN/m2) (kN/m2) For (Au)
2
Ultimate (m )
Load Case
(kN/m2)

201 112.2773 117.9194 159.3828 153.7407 472.0000 9.00

202 113.3091 116.7334 179.7177 176.2935 472.0000 9.00

203 113.3091 116.7334 179.7177 176.2935 472.0000 9.00

204 112.1212 115.9938 171.8495 167.9768 472.0000 9.00

205 98.9214 109.3545 151.2867 140.8536 472.0000 9.00

206 102.9430 110.7494 151.6981 143.8917 472.0000 9.00

207 104.2546 103.9385 145.1792 145.4954 472.0000 9.00

208 107.0922 106.5326 146.9466 147.5062 472.0000 9.00

209 89.7038 95.7879 162.4825 156.3984 472.0000 9.00

210 97.6975 102.7847 158.4801 153.3929 472.0000 9.00

211 114.7476 121.2745 133.5189 126.9920 472.0000 9.00

212 114.2212 119.6006 139.3701 133.9907 472.0000 9.00

213 97.4163 112.7537 170.8303 155.4929 472.0000 9.00

214 105.4596 115.5435 171.6529 161.5690 472.0000 9.00

215 108.0829 101.9216 158.6152 164.7764 472.0000 9.00

216 113.7580 107.1098 162.1500 168.7982 472.0000 9.00

217 78.9812 85.6205 193.2218 186.5825 472.0000 9.00

218 94.9685 99.6141 185.2171 180.5714 472.0000 9.00

219 129.0687 136.5937 135.2947 127.7697 472.0000 9.00

220 128.0160 133.2459 146.9971 141.7671 472.0000 9.00

221 46.0037 181.6155 241.2266 105.6148 472.0000 9.00

222 174.8364 47.5744 94.7751 222.0371 472.0000 9.00

223 27.0465 25.7957 271.6065 272.8573 472.0000 9.00

224 193.7936 203.3942 64.3952 54.7946 472.0000 9.00

225 69.6805 84.7031 116.2813 101.2587 472.0000 9.00

226 77.7238 87.4928 117.1039 107.3349 472.0000 9.00

227 80.3470 73.8710 104.0662 110.5423 472.0000 9.00

228 86.0222 79.0592 107.6010 114.5640 472.0000 9.00

229 51.2453 57.5698 138.6728 132.3483 472.0000 9.00

230 67.2326 71.5634 130.6681 126.3373 472.0000 9.00

231 101.3329 108.5430 80.7457 73.5355 472.0000 9.00

232 100.2801 105.1952 92.4481 87.5329 472.0000 9.00

233 13.5333 148.3957 179.7751 44.9127 472.0000 9.00

234 142.3660 14.3547 33.3237 161.3350 472.0000 9.00

235 0.0000 0.0000 210.3324 212.3974 472.0000 8.72

236 161.3222 170.2715 2.8954 0.0000 472.0000 8.89

237 94.0996 104.6334 142.6351 132.1012 472.0000 9.00

238 98.1212 106.0283 143.0464 135.1393 472.0000 9.00

239 99.4328 99.2174 136.5275 136.7430 472.0000 9.00

240 102.2704 101.8115 138.2949 138.7539 472.0000 9.00

241 84.8820 91.0668 153.8308 147.6460 472.0000 9.00

242 92.8757 98.0636 149.8285 144.6405 472.0000 9.00

243 109.9258 116.5534 124.8673 118.2396 472.0000 9.00

244 109.3994 114.8795 130.7185 125.2383 472.0000 9.00

245 112.2773 117.9194 159.3828 153.7407 472.0000 9.00

246 112.2773 117.9194 159.3828 153.7407 472.0000 9.00

Typesetting math: 65% 247 113.3091 116.7334 179.7177 176.2935 472.0000 9.00

28-04-2024 12:50:49 10/19


248 113.3091 116.7334 179.7177 176.2935 472.0000 9.00

249 112.1212 115.9938 171.8495 167.9768 472.0000 9.00

250 112.1212 115.9938 171.8495 167.9768 472.0000 9.00

251 103.7524 108.1654 151.5154 147.1024 472.0000 9.00

252 81.2758 84.9112 111.1836 107.5483 472.0000 9.00

Minimum Required Contact Area for Ultimate Loads : 0.00 m2

Actual Area in Contact for all ultimate load cases exceeds the minimum required. Hence Safe

Gross Bearing Capacity for Ultimate Loads : 472.00 kN/m2

Maximum Corner Pressure from all ultimate load cases is less than the allowable. Hence Safe

Shear Calculation

Punching Shear Check

X 1.5 m

Z
0.205 m
1.5 m

Plan
Total Footing Depth, D = 0.50m
Calculated Effective Depth, d = D - Ccover - 1 * db = 0.41 m
For rectangular column, = Bcol / Dcol = 1.40

Effective depth, d, increased until 0.75XVc Punching Shear Force

Punching Shear Force, Vu = 1638.88kN, Load Case # 223

From ACI Cl. 22.6.5.2, bo for column= = 4.05 m

Table 22.6.5.2, (b), Vc1 = = 3899.03 kN

Table 22.6.5.2, (c), Vc2 = = 4760.27 kN

Table 22.6.5.2, (a), Vc3 = = 3116.53 kN

Punching shear strength, Vc = 0.75 X minimum of (Vc1, Vc2, Vc3) = 2337.40 kN


0.75 X Vc > Vu hence, OK

One-Way Shear in XY Plane

(Shear Plane Parallel to Global X Axis)

Typesetting math: 65%

28-04-2024 12:50:49 11/19


X 1.5 m

0.74 m
Z

1.5 m
0.74 m

Plan
From ACI Cl. 22.5.5.1, Vc = = 1171.16 kN

Distance of critical section from top left corner


along Z, DZ = = 2.26 m

Check that 0.75 X Vc > Vux where Vux is the shear force for the critical load cases at a distance d from the face of the column caused by bending about the X axis.

From above calculations, 0.75 X Vc = 878.37 kN

Critical load case for Vux is # 223 = 483.79 kN

0.75 X Vc > Vux hence, OK

One-Way Shear in YZ Plane

(Shear Plane Parallel to Global Z Axis)

X 1.5 m

0.84 m 0.84 m
1.5 m

Plan
From ACI Cl. 22.5.5.1, Vc = = 1171.16 kN

Distance of critical section from top left corner along


X, DX = = 2.16 m

Check that 0.75 X Vc > Vuz where Vuz is the shear force for the critical load cases at a distance d from the face of the column caused by bending about the Z axis.

From above calculations, 0.75 X Vc = 878.37 kN

Critical load case for Vuz is # 221 = 424.67 kN

0.75 X Vc > Vuz hence, OK

Flexure About Z-Axis

Typesetting math: 65%

28-04-2024 12:50:49 12/19


Design For Bottom Reinforcement Parallel to X Axis

21 - 13 mm

Calculate the flexural reinforcement along the X direction of the footing. Find the area of steel required.

Critical Load Case # 221

The strength values of steel and concrete used in the formulae are in Mpa

Bars parallel to X Direction are placed at bottom


Effective Depth d = 0.41 m
Factor from ACI Cl. 22.2.2.4.3 =
= 0.82

From ACI318-2011 Appendix B 8.4.2, = = 0.03116

Maximum Reinforcement Ratio corresponding to εt


= 0.005 = = = 0.01986

From ACI Cl. 7.6.1.1, = = 0.00180

From Ref.1, Eq. 3.8.4a, constant m = = 15.44

Calculate reinforcement ratio for critical load case

Design for flexure about Z axis is performed at the face


of the column at a distance from top left corner of = 1.75 m
footing, Dx =

Ultimate moment = = 393.00 kNm

Nominal moment capacity required, Mn = = 436.67 kNm

(Based on effective depth) Required = = 0.00214

(Based on gross depth) x d / Depth = 0.00174


Since ρ < ρmin, select ρ= ρmin ρmin Governs
Area of Steel Required, As = = 2699.96 mm2
Note - "Area of Steel required" reported here is the larger value between the calculated area of steel and minimum steel required as per code stipulations
Selected bar Size = 13 mm
Minimum spacing allowed (Smin) = 80.00mm
Selected spacing (S) = 141.87mm
Smin<= S <= Smax and selected bar size < selected maximum bar size
The reinforcement is accepted.
According to ACI 318 Clause No- 24.3.2
Max spacing for Cracking Consideration = 192.39mm

Safe for Cracking Aspect.


Typesetting math: 65%

28-04-2024 12:50:49 13/19


Based on spacing reinforcement increment; provided reinforcement is

13 mm @ 140mm o.c.

Required development length for bars = = 0.45 m

Available development length for bars,DL = = 1.18 m

Size of bar Used as


Reinforcement 13 mm Area of one bar = 129.00 mm2

Number of bars required, Nbar = = 21

Because the number of bars is rounded up, make sure new reinforcement ratio < ρmax

Total reinforcement area, As_total = Nbar X (Area of one bar) = 2708.99 mm2
d= D - Ccover - 0.5 X (dia. of = 0.41 m
one bar)

Reinforcement ratio, = = 0.00222

From ACI Cl. 25.2.1, minimum req'd clear distance between bars
Cd = max (Diameter of one bar, 1.0" (25.4mm), Min. User Spacing) = 80.00mm
Provided Steel Area / Required Steel Area = 1.00

Design For Top Reinforcement Parallel to X Axis

First load case to be in pure/partial uplift # 235

Calculate the flexural reinforcement for Mz. Find the area of steel required

The strength values of steel and concrete used in the formulae are in ksi

Bars parallel to X Direction are placed at bottom


Effective Depth d = 15.98 m

Factor from ACI Cl. 22.2.2.4.3 = 0.82


=
From ACI318-2011 Appendix B 8.4.2, = = 0.03116
Maximum Reinforcement Ratio corresponding to εt = 0.005
= = = 0.01986

From ACI Cl. 7.6.1.1, = = 0.00180


From Ref. 1, Eq. 3.8.4a, constant m = = 15.44

Calculate reinforcement ratio for critical load case

Design for flexure about Z axis is performed at the


face of the column at a distance from top left = 1.75 m
corner of footing, Dx =

Ultimate moment = = 71.48 kNm

Nominal moment capacity required, Mn = = 79.42 kNm

(Based on effective depth)Required = = 0.000384

(Based on gross depth) x d / Depth =


Since ρ < ρmin, select ρ= ρmin ρmin Governs

Area of Steel Required, As = = 2699.96 mm2


Note - "Area of Steel required" reported here is the
larger value between the calculated area of steel
and minimum steel required as per code stipulations
Total reinforcement area, As_total = Nbar X (Area of one bar) = 2708.99 mm2
Provided Steel Area / Required Steel Area = 1.00

Selected bar Size = mm


Minimum spacing allowed (Smin) =

Typesetting math: 65% Selected spacing (S) =

28-04-2024 12:50:49 14/19


Smin<= S <= Smax and selected bar size < selected maximum bar size
The reinforcement is accepted.
According to ACI 318 Clause No- 24.3.2
Max spacing for Cracking Consideration = 192.39mm

Safe for Cracking Aspect.

Based on spacing reinforcement increment; provided reinforcement is

mm @ o.c.

Flexure About X-Axis

Design For Bottom Reinforcement Parallel to Z Axis

22 - 13 mm

Calculate the flexural reinforcement along the Z direction of the footing. Find the area of steel required.

Critical Load Case # 223

The strength values of steel and concrete used in the formulae are in Mpa

Bars parallel to X Direction are placed at bottom


Effective Depth d = 0.41 m
Factor from ACI Cl. 22.2.2.4.3 =
= 0.82

From ACI318-2011 Appendix B 8.4.2, = = 0.03116

Maximum Reinforcement Ratio corresponding to εt


= 0.005 = = = 0.01986

From ACI Cl. 7.6.1.1, = = 0.00180

From Ref.1, Eq. 3.8.4a, constant m = = 15.44

Calculate reinforcement ratio ρ for critical load case

Design for flexure about X axis is performed


at the face of the column at a distance from 0.5 ×L ±0.5 × Bcol+Ozd = 1.85 m
top left corner of footing, Dz =
Ultimate moment = Mu|x = Dx = 428.32 kNm
Nominal moment capacity required, Mn = MuΦ = 475.91 kNm
(Based on effective depth) Required ρ = 1m 1- 1-2×m×Mnfy× bw×d2 = 0.00233
(Based on gross depth) ρ x d / Depth = 0.00190
Typesetting math: 65% Since ρmin < ρ < ρmax OK

28-04-2024 12:50:49 15/19


Area of Steel Required, As = ρ × bw × d = 2842.55 mm2
Note - "Area of Steel required" reported here is the larger value between the calculated area of steel and minimum steel required as per code stipulations
Selected Bar Size = 13 mm
Minimum spacing allowed (Smin) = 80.00mm
Selected spacing (S) = 135.11mm
Smin<= S <= Smax and selected bar size < selected maximum bar size
The reinforcement is accepted.

Max spacing for Cracking Consideration = 192.39mm

Safe for Cracking Aspect.

Based on spacing reinforcement increment; provided reinforcement is

13 mm @ 135mm o.c.

Required development length for bars = db × fy2.1 ×λ×fc' = 0.45 m


Available development length for bars, DL
0.5 × L- Dcol- Ccover = 1.08 m
=
Size of bar Used as
=
Reinforcement 13 mm Area of one bar 129.00 mm2
Number of bars required, Nbar= AsAbar = 22

Because the number of bars is rounded up, make sure new reinforcement ratio < ρmax

Total reinforcement area, As_total = Nbar X (Area of one bar) = 2837.99 mm2
d= D - Ccover - 1.5 X (dia. of 0.41 m
=
one bar)
Reinforcement ratio, ρ = As_totald × bw = 0.00233
From ACI Cl. 25.2.1, minimum req'd clear distance between bars
Cd = max (Diameter of one bar, 1.0" (25.4mm), Min. User Spacing) = 80.00mm
Provided Steel Area / Required Steel Area = 1.00

Bending moment for uplift cases will be calculated based solely on selfweight, soil depth and surcharge loading.

As the footing size has already been determined based on all servicebility load cases, and design moment calculation is based on selfweight, soil depth and surcharge
only, top reinforcement value for all pure uplift load cases will be the same.

Design For Top Reinforcement Parallel to Z Axis

Top reinforcement is calculated based on self weight of footing and soil

Calculate the flexural reinforcement for Mx. Find the area of steel required

The strength values of steel and concrete used in the formulae are in ksi

Bars parallel to X Direction are placed at bottom


Effective Depth d = 15.98 m
Factor β1 from ACI Cl. 22.2.2.4.3 = = 0.82
From ACI318-2011 Appendix B 8.4.2, ρbal = = 0.03116
Maximum Reinforcement Ratio corresponding to εt = 0.005
= 0.01986
= ρmax =
From ACI Cl. 7.6.1.1, ρmin = = 0.00180
From Ref. 1, Eq. 3.8.4a, constant m = fy0.85 × fc' = 15.44

Calculate reinforcement ratio ρ for critical load case

Design for flexure about X axis is performed at the face of


the column at a distance from top left corner of footing, = 0.5 × L ± Bcol+ Oxd = 1.85 m
Dx
Ultimate moment, = Mu|z = Dz = 60.50 kNm
Nominal moment capacity required, Mn = MuΦ = 67.22 kNm
(Based on effective depth) Required ρ = 1m 1- 1-2×m×Mnfy× bw×d2 = 0.00032
(Based on gross depth)ρ x d / Depth = 0.00032
Since ρ < ρmin, select ρ= ρmin ρmin Governs

Typesetting math: 65% Area of Steel Required, As = ρ × bw × d = 2699.96 mm2

28-04-2024 12:50:49 16/19


Note - "Area of Steel required" reported here is the larger
value between the calculated area of steel and minimum
steel required as per code stipulations
Total reinforcement area, As_total = Nbar X (Area of one bar) = 2708.99 mm2
Provided Steel Area / Required Steel Area = 1.00

Selected bar Size = 13 mm


Minimum spacing allowed (Smin) = mm
Selected spacing (S) = 141.87mm
Smin<= S <= Smax and selected bar size < selected maximum bar size
The reinforcement is accepted.
According to ACI 318 Clause No- 24.3.2
Max spacing for Cracking Consideration = 192.39mm

Safe for Cracking Aspect.

Based on spacing reinforcement increment; provided reinforcement is

13 mm @ 140mm o.c.

Material Take Off


Footing Reinforcement

Direction Size Number Total Length (m) Weight (kg)

Along Z on Bottom
13 mm 22 62.70 62.33
Face

Along X on Bottom
13 mm 21 59.85 59.50
Face

Along Z on Top
13 mm 21 59.85 59.50
Face

Along X on Top
13 mm 21 59.85 59.50
Face

Total Reinforcement Weight : 240.82 kg

Concrete

3
- Length (m) Width (m) Thickness (m) Volume (m )

Footing 3.00 3.00 0.50 4.50

Pedestal 0.00 0.00 0.00 0.00

Total Concrete Volume : 4.50 m3

Formwork

Footing : 6.00 m2

Pedestal : 0.00 m2

Total : 6.00 m2

Soil Excavation

Pit Depth : 1.50 m


Pit Slope (a : b) : 1 : 1 (Assumed)
Side Distance, s : 0 (Assumed)
Excavation Volume : 31.50 m3

Backfill Volume : 27.00 m3

Typesetting math: 65%

28-04-2024 12:50:49 17/19


X X

Z Z

21 - 13 mm

21 - 13 mm


Typesetting math: 65% 

28-04-2024 12:50:49 18/19


19/19

X 1.5 m
Z
1m
0.5 m
0.7 m
3m
1.5 m

3m
0.5 m

28-04-2024 12:50:49
Plan
1.5 m
Elevation
BOTTOM 21 - 13 mm

TOP 21 - 13 mm
Dimensions (m) Reinforcement
L B D AstX(T) AstZ(T) AstX(B) AstZ(B)
Foundation
1.5 m

3m 3m 0.5 m 21 - 13 mm 21 - 13 mm 22 - 13 mm 21 - 13 mm
l b h Main Reinforcement Trans Reinforcement
TOP 21 - 13 mm Pedestal
N/A N/A N/A N/A N/A
BOTTOM 22 - 13 mm
Plan

Typesetting math: 65%


You might also like