Isolated Footing 7
1.2 m
Elevation 0.2 m
X 0.55 m
0.45 m
Z
0.3 m
1.1
0.55
1.1 m
Plan
Input Values
Footing Geometry
Column Dimensions
Pedestal
Include Pedestal : No
Pedestal Shape : N/A
Design Parameters
Soil Properties
Global Settings
Top Reinforcement Option : Calculate only when foundation is subjected to uplift forces
Concrete Design Option : Net Pressure(Gross Pressure - Self Weight Pressure)
Design Calculations
Load Combinations
Moments are About the center of Column / Pedestal (does not include moments caused by lateral loads)
For the loads shown in this table, the sign convention is the same as that for JOINT LOADS in STAAD.Pro when global Y is the vertical axis.
Footing Size
2
m
(Service check is performed with footing thickness requirements from concrete check)
If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of negative pressure will be set to zero and the
pressure will be redistributed to remaining corners.
Stability Check
OTM
1.2 m
Sliding Force
Load
Along X- Along Z- Required About X- About Z- Required
Case Resultant
Direction Direction FOS Direction Direction FOS
No.
1 8.69 17.41 7.77 1.50 20.95 10.88 1.50
2 N/A N/A N/A 1.50 N/A N/A 1.50
3 4.16 65.14 4.16 1.50 79.03 2.70 1.50
Page 7 of
Load
Along X- Along Z- Required About X- About Z- Required
Case Resultant
Direction Direction FOS Direction Direction FOS
No.
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding X Direction
Critical Load Case for Sliding along X-Direction : 3
Governing Disturbing Force : 3.26 kN
Governing Restoring Force : 13.58 kN
Minimum Sliding Ratio for the Critical Load Case : 4.16
Critical Load Case for Overturning About X-Direction : 4
Governing Overturning Moment : 7.75 kNm
Governing Resisting Moment : 13.56 kNm
Minimum Overturning Ratio for the Critical Load Case : 1.75
Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding Z Direction
Critical Load Case for Sliding along Z-Direction : 4
Governing Disturbing Force : 5.26 kN
Governing Restoring Force : 12.32 kN
Minimum Sliding Ratio for the Critical Load Case : 2.34
Critical Load Case for Overturning About Z-Direction : 3
Governing Overturning Moment : -5.54 kNm
Governing Resisting Moment : : 14.94 kNm
Minimum Overturning Ratio for the Critical Load Case : 2.70
Critical Load Case And The Governing Factor Of Safety For Sliding Along Resultant Direction
Critical Load Case for Sliding along Resultant Direction : : 4
Governing Disturbing Force : 5.30 kN
Page 8 of
Gross
Factored Area of
Pressure at
Load Case / Pressure at Pressure at Pressure at Bearing footing in
bottom
Load top left top right bottom left Capacity Contact
right
Combination corner corner corner For with soil
corner
ID (kN/m2) (kN/m2) (kN/m2) Ultimate (Au)
(kN/m2)
Load Case (m2)
(kN/m2)
Actual Area in Contact for all ultimate load cases exceeds the minimum required. Hence Safe
Maximum Corner Pressure from all ultimate load cases is less than the allowable. Hence Safe
Moment Calculation
Page 9 of
X 0.55 m
0.26 m
Z
0.55
0.26 m
Plan
Shear Enhancement Factor (if considered) is applied to (Tc), as per IS456 -2000 Clause No 40 5.1 and Fig 24
Page 10 of
X 0.55 m
0.185 m 0.185 m
0.55
Plan
Shear Enhancement Factor (if considered) is applied to (Tc), as per IS456 -2000 Clause No 40 5.1 and Fig 24
Tv< Tc hence, safe
X 0.55 m
Z
0.07 m
0.55
Plan
Ks = = 1.00
Page 11 of
Shear Strength(Tc) = =
1250.00 kN/m2 Ks x
Tc = 1250.00 kN/m2
Reinforcement Calculation
Along X Axis
Along Z Axis
5 - 10 mm
Ø10 @ 300mm
5 - 10 mm
Ø10 @ 300mm
Crack Width Calculation (for Mz)
Modulus of Elasticity of Concrete(E c) = 25000000.00 kN/m2 Clause No. 6.2.3.1
X 0.55 m
Z
0.45 m
1.2 m
0.3 m
1.1
0.55
1.1 m
Plan 0.2 m
0.55 m
Elevation
BOTTOM 5 - 10
TOP N/A
Foundation
1.1 m 1.1 m 0.2 m N/A N/A 5 - 10 mm 5 - 10 mm
Plan