Busbar Protection

Protection & Contrle / Application


08/02 1 05/02/03

Rev. A JM, September 2004

Without Busbar Protection

F1

F2

Argues
There are fewer faults on busbars than on other parts of the power system. No risk of dislocation of system due to accidental operation of busbar protection.
08/02 2 05/02/03
2

Without Busbar Protection

F1

F2

Drawbacks
Slow fault clearance. Busbar faults at F1 and F2 are cleared by remote time delayed protection on circuits feeding the faults: Time Delayed Overcurrent or Time Delayed Distance Protection
08/02 3 05/02/03
3

With Busbar Protection


BUSBAR ZONE F1

Fast clearance by breakers at the busbars

08/02 4 05/02/03

With Busbar Protection


BUSBAR ZONE F1 F2

Where busbars are sectionalised, Protection can limit the amount of system disruption for a busbar fault

08/02 5 05/02/03

With Busbar Protection


1/2
SS 1
87BB 87BB

SS 2

SS 3

21

21

08/02 6 05/02/03

With Busbar Protection


2/2
87BB 87BB

21

21

08/02 7 05/02/03

With No Busbar Protection


1/2

21

21

21

21

21

08/02 8 05/02/03

With No Busbar Protection


2/2

21

21

21

21

21

08/02 9 05/02/03

With Burbar protection


87BB 87BB

21

21

With No Burbar protection

21

21

21

21
08/02 1005/02/03

21
10

Busbar Faults Are Usually Permanent


Causes of Busbar Faults :
Falling debris Insulation failures Circuit breaker failures Current transformer failures Isolators switchs operated on load or outside their ratings Safety earths left connected

Therefore :
Circuit breakers should be tripped and locked out by busbar protection
08/02 1105/02/03
11

Busbar Protection must be :


RELIABLE
Failure to trip could cause widespread damage to the substation

STABLE False tripping can cause widespread interruption of supplies to customers / possible power system instability DISCRIMINATING Should trip the minimum number of breakers to clear the fault FAST To limit damage and possible power system instability

08/02 1205/02/03

12

Methods of Providing Busbar Protection


Frame to Earth (Leakage) Protection
>I

Insulation

Blocking Scheme Protection


>I >I >I >I >I

Differential Protection :

High Impedance Low Impedance

08/02 1305/02/03

13

Frame Leakage Protection


Protection & Contrle / Application
08/02 1405/02/03

Rev. A JM, September 2004

14

Frame Leakage Busbar Protection

>I

Insulation

08/02 1505/02/03

15

Frame Leakage Busbar Protection

>I

08/02 1605/02/03

16

Frame Leakage Busbar Protection

>I

08/02 1705/02/03

17

Frame Leakage Busbar Protection

>I

>I

08/02 1805/02/03

18

Frame Leakage Busbar Protection

Can detect only earth faults Switchgear must be insulated from earth (by standing on concrete plinth) Only one single earth conductor allowed on switchgear All cable glands must be insulated Switchgear sections must be insulated

08/02 1905/02/03

19

Frame Leakage Busbar Protection Neutral Check


False Operation because induced loop

>I

>I

08/02 2005/02/03

No operation prevents from false trip

20

Frame Leakage Busbar Protection Neutral Check

>I

>I

08/02 2105/02/03

21

Frame Leakage Busbar Protection Neutral Check

>I

>I

08/02 2205/02/03

22

Blocking Scheme Protection


Protection & Contrle / Application
08/02 2305/02/03

Rev. A JM, September 2004

23

Blocking Scheme Busbar Protection

>I

>I

>I

>I

>I

08/02 2405/02/03

24

Blocking Scheme Busbar Protection

>I

>I

>I

>I

>I

08/02 2505/02/03

25

Blocking Scheme Busbar Protection

>I

>I

>I

>I

>I

08/02 2605/02/03

26

High Impedance Protection


Protection & Contrle / Application
08/02 2705/02/03

Rev. A JM, September 2004

27

Single Bus Substation

08/02 2805/02/03

28

Single Bus Substation

P1

S1

P1

S1

P1

S1

P2

S2

P2

S2

P2

S2

08/02 2905/02/03

29

Single Bus Substation

08/02 3005/02/03

30

Single Bus Substation

08/02 3105/02/03

31

Single Bus Substation

08/02 3205/02/03

32

Double Bus Substation

08/02 3305/02/03

33

Isolator Auxiliary Switches Current switching


Bus A Bus B

P1 S1 P2 S2 P1 S1 P1 S1 P1 S1 P2 S2 P1 S1

P2

S2

P2

S2

P2

S2

a b

Current

08/02 3405/02/03

34

Isolator Auxiliary Switches Current switching


Bus A Bus B

Current a b

08/02 3505/02/03

35

Isolator Auxiliary Switches Current switching


Bus A Bus B

a b

Current

08/02 3605/02/03

36

Isolator Auxiliary Switches Current switching


Bus A Bus B

a b

Current

08/02 3705/02/03

37

Isolator Auxiliary Switches Current switching


Bus A Bus B

a b

Current

08/02 3805/02/03

38

Isolator Auxiliary Switches Current switching


Bus A Bus B

a b

Current

08/02 3905/02/03

39

Isolator Auxiliary Switches Tripping switching


Bus A Bus B

Tripping a b a Current b

08/02 4005/02/03

40

Interposing CT are not acceptable


Main CT must be identical Current switching via auxilliary relay is not acceptable. Requirement of number of position contact (Disconnector switch) is high

08/02 4105/02/03

41

Isolator Auxiliary Switches Current switching


Bus A Bus B

a Current b

08/02 4205/02/03

42

Isolator Auxiliary Switches Current switching


Bus A Bus B Bus A Bus B

Current

a b

Current

a b

08/02 4305/02/03

43

Isolator Auxiliary Switches On Load Transfer


Bus A Bus B

a Current b

08/02 4405/02/03

44

Isolator Auxiliary Switches On Load Transfer


Bus A Bus B

a Current b

08/02 4505/02/03

45

Isolator Auxiliary Switches On Load Transfer


Bus A Bus B

a Current b

08/02 4605/02/03

46

Isolator Auxiliary Switches On Load Transfer


Bus A Bus B

a Current b

08/02 4705/02/03

47

Isolator Auxiliary Switches On Load Transfer


Bus A Bus B

Current a b

08/02 4805/02/03

48

Isolator Auxiliary Switches On Load Transfer


Bus A Bus B

a Current b

08/02 4905/02/03

49

Isolator Auxiliary Switches On Load Transfer


Bus A Bus B

a Current b

08/02 5005/02/03

50

Isolator Auxiliary Switches Check Zone


Bus A Bus B

Trip Bus A
Zone A Zone B
08/02 5105/02/03

Trip Bus B
51

Isolator Auxiliary Switches Check Zone


Bus A Bus B

Trip Bus A False Tripping

Current switching failure


Zone A Zone B

08/02 5205/02/03

Trip Bus B
52

Isolator Auxiliary Switches Check Zone


Bus A Bus B

Trip Bus A
Zone A Zone B

Check Zone
08/02 5305/02/03
53

Trip Bus B

Isolator Auxiliary Switches Check Zone


Bus A Bus B

Trip Bus A
Zone A Zone B
08/02 5405/02/03

Trip Bus B
54

Isolator Auxiliary Switches Check Zone


Bus A Bus B

Trip Bus A Check Zone


08/02 5505/02/03

Trip Bus B
55

One Breaker and a Half Substation

08/02 5605/02/03

56

S1

P1

S2

P2

Bus A
P1 S1 P2 S2 P2 S2 P1 S1

Bus B

08/02 5705/02/03

57

Bus A

Bus B

08/02 5805/02/03

58

Bus A

Bus B

08/02 5905/02/03

59

Bus A

Bus B

08/02 6005/02/03

60

Bus A

Bus B

08/02 6105/02/03

61

Bus A

Bus B

08/02 6205/02/03

62

Bus A
P1 S1 P2 S2 P2 S2 P1 S1

Bus B

P1 S1

P2 S2

P2 S2

P1 S1

08/02 6305/02/03

63