Professional Documents
Culture Documents
4.1 Introduction
-178-
Subsequent chapters provide the detailed properties, applications, failure modes,
and techniques used for evaluating and testing different insulating materials.
V
I (4.1)
R
.
R (4.2)
A
-179-
4.3 Areas of Insulation Application
There are four main areas where electrical insulation must be applied in
high voltage power equipment. These four areas can be classified as:
(i) Between the phase conductor (or coil) at high voltage and the earth (or
the grounded conductor). This is generally referred to as phase-to-earth
insulation.
(iii) Between the adjacent turns in a coil (or winding). This is known as
inter-turn insulation.
(iv) Between the coils (or windings) of the same phase when the phase
winding is made of several layers. This is known as inter-coil
insulation.
-180-
different conductors or the conductor and the earth. Transmission line
insulators, for example, are required to withstand the conductor weight
and forces created by wind, snow, rain, and to keep conductors at a
specified minimum distance from the tower structure under all weather
conditions.
(ii) Heat Transfer: Insulation materials help in the transfer of heat from the
current carrying conductor to the surroundings thereby keeping the
conductor temperature within safe limits. As an example, insulating oil
in an oil filled transformer provides the electrical insulation and the
heat transfer functions.
(iii) Arc Quenching: In circuit breakers, insulation materials help in the arc
extinction at current zero in order to successfully interrupt the high fault
currents. Oil, SF6 and air are used in circuit breakers for arc
interruption in addition to their function as electrical insulation.
4.5.1 DC resistivity
E
= (4.3)
J
-181-
where E is applied electric field (V/m) and J is current density in the material
(A/m2). can be calculated from measured value of the insulation resistance.
Alternatively, if and the geometry are known, insulation resistance can be
calculated. Insulation resistance is used as an indication of conduction behavior
of insulating materials in many practical applications such as in high potential or
hi-pot testing.
4.5.2 DC conductivity
-182-
filled with the insulating material under discussion, and Co is the capacitance for
the same parallel electrodes when these are separated by a vacuum. Generally, r
is not a fixed parameter but depends upon temperature, frequency and molecular
structure of the insulating material.
Eo = 4 q (4.5)
Eo E E E
P= = o o (4.6)
4 4 4 4 r
Eo
P = r 1 r 1
E
or (4.7)
4 r 4
-183-
D = E + 4P (4.8)
-184-
In addition to this orientational polarization, the applied electric field
exerts a force on each positive charge (be it a positive ion or even a nucleus of
an atom) and on each negative charge (negative ions and electrons) and thus
slightly displaces them along the field lines. Displacement polarization results
in all dielectrics, both polar and nonpolar.
-185-
But at higher frequencies, the duration of half cycle could be shorter than p.
Therefore in this case the dipoles cannot follow the change in the field
intensity. This results in reduction in polarization, which will ultimately
diminish to zero at a very high frequency. Fig. (4.2) illustrates variation of
polarization and hence complex permittivity as a function of frequency.
-186-
capacitive elements. Fig. (4.3) also shows the phasor diagram for the circuit
under the application of an AC voltage.
dielectric, then the capacitive component of the current is IC = jCpV, while the
resistive component of the current is IR = -jI tan , where is known as the loss
angle. Since loss angle is usually very small, IC I and, therefore, IR = -
jICtan. Hence, total current I = IR+IC can be expressed as:
CpV
Fig. (4.3). Parallel equivalent circuit (a) for an insulating material, and (b) its
phasor diagram.
where
-187-
tan is commonly known as the loss tangent or the dissipation factor and
sometimes as power factor of the dielectric. It is defined as the quotient of
active and reactive power loss in a dielectric. It is derived from Fig. (4.3) as
follows:
'r
tan = = (4.12)
o r r
1
tan = (4.13)
R p Cp
tan = Rs Cs (4.14)
For a fixed frequency, both series and parallel circuits hold good and one
circuit can be obtained from the other. However, the frequency dependence is
just the opposite in the two cases.
-188-
4.5.7 Power loss in a dielectric
Fig. (4.4). Series equivalent circuit (a) for an insulating material and (b) its
phasor diagram.
It is clear from eqn. (4.15) that the dielectric power losses are influenced
by applied voltage, dielectric permittivity and loss tangent. Sometimes, losses
also occur in a dielectric due to partial discharges in the insulation. In such a
case, the equivalent circuit of a dielectric needs to be modified to account for the
occurrence of partial discharges. Partial discharges are discussed elsewhere in
this book.
-189-
solid dielectric, it is called a flashover or a spark over. Usually spark over
causes a temporary failure whereas a puncture results in permanent failure of
the insulation. The breakdown voltage of an insulation system depends upon
the insulating material itself, the shape, size, surface smoothness and sometimes
the materials of the electrodes used, the distance between the electrodes, the type
and polarity of the applied voltage as well as the atmospheric and environmental
factors, etc. Therefore, it is essential that experimental conditions are specified
when reporting on the breakdown voltage of an insulation material. Breakdown
voltage is always given in peak values.
-190-
plate or other similar electrode systems are used to measure the dielectric
strength.
-191-
is also important. Sometimes, a material possesses excellent dielectric
properties, but cannot be used for electrical insulation applications if it does
not possess suitable non-electrical properties.
-192-
For solid insulation materials, mechanical properties play a very
important role. For example, for use of glass or porcelain in making insulators
for overhead transmission and distribution lines, the mechanical strength under
compression and tension is very important. Similarly, for polymer insulations
applications in power cables and other equipment require suitable physical,
chemical, and mechanical properties. Tables (4.1) and (4.2) provide some
selected electrical and nonelectrical properties for glass, porcelain and several
commonly used polymers [3]. Further properties of some solid insulation
materials are provided in Tables (8.2) to (8.8) in chapter 8.
Table (4.1) Electrical and mechanical properties of glass and porcelain [3].
-193-
Table (4.2).
-194-
4.7 Classification of Insulating Materials
4.7.1 Gases
4.7.2 Vacuum
The absence of any solid, liquid and gas in the interelectrode gap space
results into a vacuum medium which has excellent insulating and arc quenching
-195-
properties. A true vacuum is very difficult to achieve and maintain and residual
gas pressure of the order of 10-9 to 10-12 bar may exist in vacuum insulated
equipment. In such equipment, electrode material, shape and surface finish,
residual gas pressure and contaminating particles are important factors which
influence the breakdown in a vacuum gap. Vacuum insulated switches and
circuit breakers are increasingly being used in power systems now.
4.7.3 Liquids
-196-
4.7.4 Solids
4.7.5 Composites
-197-
other under combined thermal, mechanical and electrical stresses over an
expected life of the equipment and have nearly equal dielectric constants.
Furthermore, the liquid insulant should not absorb any impurities from the solid
which may adversely affect its resistivity, dielectric strength, loss factor and
other properties.
There are several parameters which can significantly influence the useful
life of an insulation material. The most important of these parameters are briefly
summarized here.
4.8.1 Temperature
-198-
increase in the operating stress values. Thus, there is an influence of the applied
electric stress on the life expectancy of insulation materials.
-199-
important that a suitable insulation material is selected for a specific
application after considering all the relevant factors and it is operated while
keeping the thermal, electrical and environmental stresses within the
acceptable levels.
Fig. (4.6). Effect of ultraviolet radiation exposure time on the time to tracking
breakdown of three epoxy systems [4].
Example 4.1:
-200-
Solution
C 230
The dielectric constant r 2.3
C o 100
Example 4.2:
Solution
= 2 f = 377 rad/s
tan = 0.009
Cp = 230 pF
1
For a parallel network tan =
R p Cp
Therefore
1 1
Rp 1281.41 M
C p tan 377 230 *10 12 0.009
Example 4.3:
-201-
Solution
= o r tan
Therefore
1
1.447 *1010 m
Example 4.4:
Solution
tan = Rs Cs
Therefore
tan 0.009
103794.3
Rs =
C s 377 230 *10 12
Example 4.5:
-202-
Solution
A
o V 2 r tan 2
d V
Hs = o r tan
Ad d
Hs = o r E2 tan
Hs = 276.4 W/m3
Example 4.6:
Gap (mm) 1 2 3 4
-203-
Solution
x = 3 - 1 = 2 mm
v 175
Thus = 87.5 kV/mm is the required dielectric strength.
x 2
Example 4.7:
An XLPE cable has = 1017 m, and the radius of inner and outer
conductors are 1 and 2 cm, respectively. Find the insulation resistance of this
cable if cable length is (a) 1m, and (b) 1 km.
Solution
-204-
The insulation resistance, dR of the layer between x and dx can be
obtained from equation (4.2) by realizing that in this case.
dx
dR
2 x
x 2
x 2 dx 2
R dR n
x 1
2 x 1 x 2 1
1017
Thus, for = 1m, R= ln 2 1.103 * 1016
2 1
1.103 * 1016
and for = 1 km, R= ln 2 1.103 * 1013
1000
Example 4.8:
A coaxial cable has inner and outer conductor diameter of 5 and 7 can
respectively. The insulation material has a resistivity of 2*1010 m while it
relative permittivity is 3.5. Calculate: (i) dissipation factor, (ii) loss factor,
(iii) dielectric losses per meter of cable when energized at 100 kV, 60 Hz, and
(iv) insulation resistance of the cable.
Solution
1 1
(i) tan =
o r 2 f o r 2 * 60 * 8.854 *10 12 * 3.5 * 2 *1010
= 4.28*10-3
-205-
(ii) Loss factor = r tan = 3.5 * 4.28 * 10-3 = 1.5*10-2
V2
(iv) Since power in a resistor is given as PL =
R
V 2 1000002
Hence R = Insulation Resistance = 1.07 * 109 per m of
PL 9.34
cable length
b 2 * 1010 3.5
Alternatively R = ln ln 1.07 * 10 per m of cable
9
2 a 2 2.5
length and also
1 1
tan =
CR 2 * 60 * 5.79 *10 10 *1.07 *109
= 4.28 * 10-3
-206-
4.10 Questions / Problems
Q.4.1 Name the main electrical and non-electrical properties required for
use of an insulation material in high voltage cables.
-207-
Q.4.8 Should transformer oil possess a high or a low value of viscosity?
Should this material have a high or low value of specific heat
capacity? Give reasons for your answers.
(ii) tan
Q.4.10 A high voltage cable has a capacitance of 200 pF/m whereas its
insulation resistance is 104 Mm. If the cable length is 1 km, find
parallel equivalent circuit for this cable and calculate its loss tangent.
-208-
References
[1] N.H. Malik, A.A. Al-Arainy and M.I. Qureshi, "Electrical Insulation in
Power Systems", Maral Dekker Inc. New York, USA, 1997.
-209-