Professional Documents
Culture Documents
April, 2008
Contents
Exercises
Calculation of
Calculation of
- voltage drops
2. Nodal method
Characteristics:
- One nodal point has to be selected, where the voltage is known or set to a certain
value. This is the reference node, called “slack”. In most cases one of the feeding
nodes will be selected.
- Application for grids, where loads are connected to the nodal points (application for
transmission and distribution grids).
Determination of plus/minus-sign:
- Voltages from node to reference node “0” are positive ⇒ arrow pointing to the
reference node
Consumption Infeed
Active power P Plus Minus
Inductive reactive power QL Plus Minus
Capacitive reactive power QC Minus Plus
The derivation of the systems of equations is shown by means of the following example for a
distribution grid (figure 1).
The effective capacitances of lines (overhead lines or cables) will be neglected for short-
circuit calculations and load flow calculations in grids with nominal voltages smaller than or
equal to 110 kV. In this case the equivalent circuit diagram of a line consists only of the
effective impedance or of the effective admittance:
1 1
Y ik = = (1)
Z b ik Rik + j X ik
From figure 1 follows the equivalent circuit diagram in figure 2 with (n+1) nodal points. The
reference node (slack) is designated by “0”. The numbering of the other nodes is arbitrary.
The voltages are phase-to ground voltages.
The impedances of the infeeds and of the loads
Ui
Z= (2)
Ii
I ij = Y ij ⋅ ( U i − U j ) = −I ji (3)
For every nodal point we get the following equations, if we apply Kirchhoff’s current law:
n
I i + ∑ I ij = 0 i = 0,1, 2, 3 .... n (4)
j =0
j ≠i
n
I i = − ∑ Y ij ⋅ ( U i − U j ) (5)
j =0
j ≠i
n n
I i = −U i ⋅ ∑ Y ij + ∑ U j ⋅ Y ij ( ) (6)
j =0 j =0
j ≠i j ≠i
If we apply equation (6) for the equivalent circuit diagram in figure 2, then we get the
following system of equations:
I0 Y 00 Y 01 Y 02 0 Y 04 0 U0
I1 Y 10 Y 11 Y 12 0 0 0 U1
I2 Y 20 Y 21 Y 22 0 0 0 U2
= ⋅ (7)
I3 0 0 0 Y 33 Y 34 0 U3
I4 Y 40 0 0 Y 43 Y 44 Y 45 U 4
I5 0 0 0 0 Y 54 Y 55 U 5
For each element of the main diagonal we get the negative value of the sum of this line:
n
Y ii = − ∑ Y ij (8)
j =0
j ≠i
Y ij = Y ji (9)
- If there is between two nodal points a connection (line), so the admittance of this line
will be placed at the appropriate position in the matrix.
The determinant of the nodal admittance matrix is equal to zero, because the row sum is
zero too. This matrix is singular, which means there is no inverse matrix.
Hence the phase-to-ground voltages will be determined by means of the phase-to-ground
voltage at node “0” (reference node):
U i = U 0 + ∆U i0 (11)
n
After insertion of equation (11) in equation (7) we get (because of (Y ii + ∑Y
j =0
ij ) ⋅ U 0 = 0 ):
j ≠i
I1 Y 11 Y 12 0 0 0 ∆U10
I2 Y 21 Y 22 0 0 0 ∆U 20
I3 = 0 0 Y 33 Y 34 0 ⋅ ∆U 30 (12)
I4 0 0 Y 43 Y 44 Y 45 ∆U 40
I5 0 0 0 Y 54 Y 55 ∆U 50
(The first line and the first column of the original matrix have been eliminated.)
Equation (12) can be expressed by
i = Y ⋅ ∆u (13)
∆u = Y −1 ⋅ i = Z ⋅ i (14)
After inversion the impedance matrix is a fully occupied symmetrical matrix. All elements
have a negative sign.
Designation of the elements:
Zii driving point impedance (German: Kurzschlussimpedanz)
Zij transfer impedance (German: Transferimpedanz)
It is often advantageous to separate the complex values in real part and imaginary part.
Index w: real part or active component (German: Wirkanteil)
Index b: imaginary part or reactive component (German: Blindanteil)
Equation (12) is then as follows:
iw = G⋅ ∆uw − B⋅ ∆u b (17)
i b = B⋅ ∆uw + G⋅ ∆u b (18)
iw G − B ∆uw
= ⋅ (19)
ib B G ∆u b
The solve of equation (19) for the column vector of the voltages yields to
∆ uw R −X iw
= ⋅ (23)
∆ ub X R ib
First approach
Y b ij = Gb ij + jϖCb ij (24)
The current Ii0 is the sum of the shunt arm currents at node i:
Y i0 is the shunt admittance at nodal point i. Please note, that this admittance should not be
confused with the line impedance.
The effective conductance Gb will be only considered in grids of nominal voltage greater than
or equal to 220 kV. If the effective conductance Gb is neglected, then current Ii0 is a
completely capacitive current.
In the sense of Kirchhoff’s current law the current Ii0 is a load current (consumer).
Equation (4) can be extended by this load current:
n
I i + I i0 + ∑ I ij = 0 i = 0,1, 2, 3 .... n (31)
j =0
j ≠i
From that follows that the column vector of the nodal point currents has to be extended.
These additional nodal point currents are designated by index 0. Equation (19) is now as
follows:
iw + iw 0 G − B ∆uw
= ⋅ (32)
ib + ib 0 B G ∆ub
Second approach
Another possibility is to put the shunt admittances into the admittance matrix. Then we have
only the consumer currents and feeder currents as nodal point currents (as did at the
beginning of this chapter, where the effective capacitances were neglected). The equivalent
circuit diagram is presented in figure 5. Compared with figure 2 the numbering of the nodes
has to be changed, because the zero bar of the positive-sequence system gets index “0”.
The zero bar of the positive-sequence system is the reference node. The voltage of the
reference node is
U0 = 0 (33)
U i = ∆U i0 (34)
I0 Y 00 Y 01 Y 02 Y 03 Y 04 Y 05 Y 06 0
I1 Y 10 Y 11 Y 12 Y 13 0 Y 15 0 U1
I2 Y 20 Y 21 Y 22 Y 23 0 0 0 U2
I3 = Y 30 Y 31 Y 32 Y 33 0 0 0 ⋅ U3 (35)
I4 Y 40 0 0 0 Y 44 Y 45 0 U4
I5 Y 50 Y 51 0 0 Y 54 Y 55 Y 56 U 5
I6 Y 60 0 0 0 0 Y 65 Y 66 U 6
The properties of this admittance matrix are the same as described for the admittance matrix
in equation (7). The admittance matrix is singular again.
Due to the fact that U0 = 0 and current I0 is not needed, column “0” can be neglected. So we
can reduce the admittance matrix by erasing column “0” and line “0” (same procedure as did
with equation (12))). Now we can invert the admittance matrix.
Shunt admittances can also represent fault admittances or/and constant consumer
admittances.
Equation (35) has to be separated into known (index B: German “bekannt”) and unknown
(index U: German “unbekannt”) values. In general we get:
i B Y BB Y BU u B
= ⋅ (36)
iU Y UB Y UU uU
If the loads in the grid are represented by load admittances, the unknown nodal point
currents are not existent and we get
iU = 0 (38)
If the phase-to-ground voltage at node “1” in the equivalent circuit diagram according to
figure 5 is known, then we get the desired sub matrices from equation (35).
Y 22 Y 23 0 0 0
Y 32 Y 33 0 0 0
Y UU = 0 0 Y 44 Y 45 0 (38)
0 0 Y 54 Y 55 0
0 0 0 Y 65 Y 66
Y 21
Y 31
Y UB = 0 (39)
Y 51
0
I2
I3
iU = I4 (40)
I5
I6
u B = U1
The separation into real part and imaginary part yields to:
−1
uw U G − BUU ⎡G − BUB uw B iw U ⎤
= − UU ⋅ ⎢ UB ⋅ − ⎥ (41)
ub U BUU GUU ⎣ BUB GUB ub B ib U ⎦
It is to be assumed, that a three-phase short circuit is a symmetrical load. For the calculation
we use the system of equations without consideration of the effective capacitances
(equations (14) and (15)). In case of a three-phase short-circuit without base load (pre-load)
exists only one “consumer” current. The related grid is shown in figure 6.
U i = U 0 + ∆U i0 = 0 (42)
∆U i0 = -U 0 (43)
- U 0 = Z ii ⋅ I i (44)
− U0
Ii = (45)
Z ii
The driving point impedance therefore is the resulting impedance (short-circuit impedance)
between infeed and fault location.
If we strictly apply complex calculation right from the beginning and we define the voltage at
the reference node as positive real, than we get based on equations (43) and (23) the
following equations:
∆Ub i0 = 0 (47)
− U0 = Rii ⋅ Iw i − X ii ⋅ Ib i (48)
0 = X ii ⋅ Iw i + Rii ⋅ Ib i (49)
The short-circuit current can be calculated from equations (48) and (49):
− U0
Iw i + jIb i = (50)
Rii + jX ii
The load flow calculation will be done by means of equation (13). Symmetrical load
conditions are assumed. For constant consumer power first the nodal currents have to be
determined from the nodal apparent powers:
S i = U i ⋅ I *i (51)
S*i = U *i ⋅ I i (52)
-1
I i = U *i ⋅ S*i (53)
or in matrix notation 1
p uw − ub iw
= ⋅ (54)
q ub uw − i b
s = U ⋅ i* (55)
p u ub iw
= w ⋅ (56)
- q - ub uw i b
s* = U * ⋅ i (57)
−1
iw uw ub p
= ⋅ (58)
ib - ub uw −q
−1
i = U* ⋅ s* (59)
−1
U * ⋅ ∆u = U * ⋅ Z ⋅ U * ⋅ s* 2
(61)
U * ⋅ ∆u = Z ⋅ s* (62)
1
Assumption for the following equations (54) until (59): inductive reactive power: +jQ
2 * * −1 * *
Note: U ⋅ Z ⋅ U = Z , because U is a diagonal matrix. In case that U is fully occupied, this equation is not valid.
Equation (62) is non-linear because of the quadratic dependence on the voltage. Hence an
approximation method has to be applied, like
- Newton-Raphson approximation method
- Iteration, which means that the nodal currents will be calculated with approximated
voltages
Iteration
First iteration step For the first iteration step it is assumed, that at all nodal points we
have the same phase-to-ground voltage U0.
−1
∆u (1 ) = Z ⋅ U *(0 ) ⋅ s* (63)
u (1 ) = u 0 + ∆u (1 ) (64)
with
1 U0
. .
0
. .
n U0
U *(0 ) = (65)
1 U0
. .
0
. .
n U0
1 U0
. .
. .
n U0
u0 = (constant for all iteration steps) (66)
1 0
. .
. .
n 0
Result:
1 Uw1 1 Uw 1 Ub 1
. . . . .
. . . . .
n Uwn n Uw n Ub n
u (1) = ⇒ U *(1) = (67)
1 U b1 1 - Ub 1 Uw 1
. . . . .
. . . . .
n U bn n - Ub n Uw n
Second iteration −1
∆u (2 ) = Z ⋅ U *(1 ) ⋅ s* (68)
step
u (2 ) = u 0 + ∆u (2 ) (69)
Iteration step ν −1
∆u (ν ) = Z ⋅ U *(ν −1 ) ⋅ s* (70)
u (ν ) = u 0 + ∆u (ν ) (71)
The activel and reactive components of the nodal currents will be calculated according to
equation (58):
Pi ⋅ Uw i + Qi ⋅ Ub i
Iw i = 2 2
(73)
Uw i + Ub i
Pi ⋅ Ub i − Qi ⋅ Uw i
Ib i = 2 2
(74)
Uw i + Ub i
2.4 Exercises
Goal of this exercise: to get familiar with the method of the nodal approach.
Tasks:
1. Define the slack (reference node “0”). Calculate the line reactances (in this example it is
to be assumed, that the reactances are in the positive real axis ⇒ negligence of “j”)
3. Calculate the
- nodal point voltages (phase-to-ground voltages)
- branch currents
Solution:
1.
This matrix is singular. An inverse matrix can not be calculated. Hence the first line
and the first column will be erased. It remains a (3x3)-matrix.
0 1 2 3
0 -0,35 0,25 0,1 0
1 0,25 -0,375 0 0,125
Y=
2 0,1 0 -0,1 0
3 0 0,125 0 -0,125
1 2 3
1 -4 0 -4
Z=
2 0 -10 0
3 -4 0 -12
∆U10 − 4 0 −4 0
∆U20 = 0 − 10 0 ⋅ 300 (Z in Ω; I in A)
∆U30 − 4 0 − 12 250
∆U10 = −1000 V = −1 kV
∆U20 = −3000 V = −3 kV
∆U30 = −3000 V = −3 kV
110 kV
U0 =
3
U1 = U0 + ∆U10 = 62,5 kV
U2 = U0 + ∆U20 = 60,5 kV
U3 = U0 + ∆U30 = 60,5 kV
Given is the following grid. State for this grid the admittance matrix Y.
0 1 2 3 4
0 Y00 Y01 0 0 0
1 Y10 Y11 Y12 0 Y14
Y=
2 0 Y21 Y22 Y23 0
3 0 0 Y32 Y33 Y34
4 0 Y41 0 Y43 Y44
G -B
Y=
B G
Rij - X ij
Gij = 2 2
Bij = 2 2
Rij + X ij Rij + X ij
R X G B
[Ω] [Ω] [S] [S]
Grid 0 -1 0,035 0,353 0,28 -2,81
Cable 1-2 0,019 0,036 11,68 -21,62
Cable 1-4 0,048 0,090 4,67 -8,65
Cable 2-3 0,010 0,018 23,36 -43,25
Cable 3-4 0,015 0,027 15,57 -28,83
The calculation of the elements in the main diagonal includes the elements in the 1st row and
1st column.
Goal of this exercise: to get an idea of the range of magnitude of earth fault current
The earth fault current has to be calculated according to the method of symmetrical
components:
Calculation of impedances
Solution
Z1Q =
(110 kV )2 = 6 ,05 Ω
110-kV-grid
2000 MVA
6,05 Ω
ü 2 = 110 Z1Q = = 0,05 Ω
110
X1Q = 0,995 ⋅ Z1Q = 0,0498 Ω
R1Q = 0,1 ⋅ X1Q = 0,0049 Ω
Z1T = 0,1 ⋅
(10,5 kV )2 = 0,551 Ω
20 MVA
R1T = 0,01 ⋅
(10,5 kV )2 = 0,055 Ω
20 MVA
2 2
X1T = Z1T − R1T = 0,548 Ω
X 0T = 0,95 ⋅ X1T = 0,521 Ω (Z0m is there included)
Cable 1 1
R1K = ⋅ 0,0967 Ω/km ⋅ 10 km = 0,48 Ω
2
1
X1K = ⋅ 0,179 Ω/km ⋅ 10 km = 0,9 Ω
2
C1K = 2 ⋅ 0,456 µF/km ⋅ 10 km = 9,12 µF
Zero-sequence system
Positive-sequence system
Negative-sequence system
1 1
ZC = = −
= − j 2792 Ω
jωC j 314s ⋅ 1,14 µF
1
1 1
ZC = = −
= − j 559 Ω
jωC j 314s 1 ⋅ 5,7 µF
I 0 = I1 = I 2
U 0 + U1 + U 2 = 3 Z F ⋅ I 0
This means, the symmetrical component networks have to be connected in series at fault
location.
In the next step we can simplify the three equivalent circuit diagrams.
Zero-sequence system
Due to the very large values of the impedances of the capacitances we can neglect the
impedances of cable 1 and cable 4 and get the parallel connection of the four capacitances:
1 1
ZC = = = − j 279 Ω
jωC j 314s ⋅ (2 ⋅ 4,56 µF + 2 ⋅ 1,14 µF )
−1
Positive-sequence system
Negative-sequence system
It is to be seen, that
- the shunt impedance in the positive sequence system is equivalent to the effective
capacitance
- the positive current is not flowing over the effective capacitance, because the
impedance in the parallel branch is smaller
- the impedance in the negative sequence system is very small and can therefore be
neglected
Due to the fact, that the voltage in negative-sequence system is negligible we can assume,
that U0 = U1
10 kV
I0 = = j 0,02069 kA ≈ j 21 A (completely capacitive current)
3 ⋅ (− j 279 Ω )
ICE = 3 ⋅ I0 = j63 A
10 kV
Verification: ICE = 3 ⋅ ϖ ⋅ CE ⋅ UY = 3 ⋅ 314 s −1 ⋅ 11,4 µF ⋅ = 62 A
3
10 kV
U0 ≈ −
3
10 kV
U1 ≈
3
U2 ≈ 0
10 kV 10 kV
Ua = U0 + U1 + U2 = − + +0 =0
3 3
10 kV 10 kV
U b = U0 + a 2U1 + aU2 = − + a2 +0
3 3
(
Ub = a2 − 1 )10 kV
3
= ja 3⋅
10 kV
3
= ja10 kV
10 kV 10 kV
U c = U0 + aU1 + a 2U2 = − +a +0
3 3
(
Uc = a − 1 )10 kV
3
= − ja 2
3⋅
10 kV
3
= − ja210 kV
10 kV
δ= = 3
10 kV
3
3. Mesh-current method
Characteristics:
- Definition of meshes, which include supply voltages, grid impedances and load
impedances
- Voltage drops over the grid impedances and load impedances are included in the
meshes
- If the load impedances are not constant (as usual in transmission grids or
distribution grids), then the impedance matrix has to be changed after each
iteration step ⇒ the application of the mesh-current method for transmission grids
and distribution grids is disadvantageous
Application:
1. Definition of a “tree”, which connects all the nodes of the equivalent circuit.
Each node must be reached only on one route by the “tree”.
2. The branches of the equivalent circuit, which are not part of the “tree” are called
independent branches.
f = z − k +1 (75)
5. Impedance matrix
o Main diagonal
The value of each main diagonal element is the sum of the impedances of
the corresponding mesh.
- positive sign, if the meshes have the same direction when passing the
impedance
- negative sign, if the meshes have opposite direction when passing the
impedance
6. The mesh voltage will get a positive sign, if the mesh current direction and the
direction of the voltage are opposite.
According to these regulations the impedance matrix and the voltage vector must be
constituted.
uM = Z M ⋅ iM (76)
Exercise
Load flow calculation by means of mesh-current method
R’1 X’1
[Ω/km] [Ω/km]
NYY-0 3x(1x400) 0,051 0,086
NYY 3x70/35 0,271 0,082
Table 1: Impedances of the cable
Tasks:
⎜ ⎟
⎝ 0,724 ⎠
X Q = 0,995 ⋅ ZQ = 1,89 mΩ
RQ = 0,1 ⋅ X Q = 0,19 mΩ
2
Transformer U (0,724 kV)2
ZT = ukr ⋅ rT = 0,06 ⋅ = 12,58 mΩ
SrT 2,5 MVA
2
U (0,724 kV)2
RT = uRr ⋅ rT = 0,008 ⋅ = 1,68 mΩ
SrT 2,5 MVA
(12,58 mΩ )2 − (1,68 mΩ )2
2 2
XT = ZT − RT = = 12,47 mΩ
10,5
ü= = 14,50
0,724
l K1 25 m Ω
Cable RK1 = ⋅ R1′ = ⋅ 0,051 = 0,212 mΩ
nK1 6 km
l K1 25 m Ω
X K1 = ⋅ X1′ = ⋅ 0,086 = 0,358 mΩ
nK1 6 km
100 m Ω
RK2 = ⋅ 0,051 = 1,70 mΩ
3 km
100 m Ω
X K1 = ⋅ 0,086 = 2,87 mΩ
3 km
50 m Ω
RK3 = ⋅ 0,271 = 13,55 mΩ
1 km
50 m Ω
X K3 = ⋅ 0,082 = 4,10 mΩ
1 km
(0,69 kV ) = 0,635 Ω
2 2
Loads U
Z A1 = n =
SA1 0,75 MVA
Z A2 =
(0,69 kV )2 = 0,952 Ω
0,5 MVA
Z A3 =
(0,69 kV )2 = 4,761 Ω
0,1 MVA
Equivalent circuit
′ U nQ 1 10 kV 1
U Q = ⋅ = ⋅ = 398,2 V
3 ü 3 14,5
branches z=6
nodes k=4
System of equations
uM = Z M ⋅ iM
′
U Q Z Q + Z T + Z C1 + Z A1 − Z A1 0 I M1
0 = − Z A1 Z C2 + Z A2 + Z A1 − Z A2 ⋅ I M2
0 0 − Z A2 Z C3 + Z A3 + Z A2 I M3
u Mb XM RM i Mw
= ⋅
u Mw RM − XM i Mb
′ ′
Assumption: U Q =U Qw + j0 (completely real)
0 IM1w
0 IM2w
0 X RM I
= M ⋅ M3w
′
U Qw RM − XM IM1b
0 IM2b
0 IM3b
X Q + X T + X C1 + X A1 − X A1 0 R Q + R T + R C1 + R A1 − R A1 0
− X A1 X C 2 + X A 2 + X A1 − X A2 − R A1 R C 2 + R A 2 + R A1 − R A2
0 − X A2 X C3 + X A3 + X A2 0 − R A2 R C3 + R A3 + R A2
R Q + R T + R C1 + R A1 − R A1 0 − (X Q + X T + X C1 + X A1 ) X A1 0
− R A1 R C 2 + R A 2 + R A1 − R A2 X A1 − (X C 2 + X A 2 + X A 1 ) X A2
0 − R A2 R C3 + R A 3 + R A 2 0 X A2 − (X C 3 + X A 3 + X A 2 )
ZM [1,1] = 291,8 mΩ
ZM [2,2] = 781,7 mΩ
ZM [3,3] = 3362,9 mΩ
ZM [1,4] = 572,9 mΩ
ZM [2,5] = 1382,1 mΩ
ZM [3,6] = 4631,9 mΩ
−1
i M = Z M ⋅ uM = Y M ⋅ uM
I A1 = I M1 − I M2
I A2 = I M2 − I M3
I A3 = I M3 = 81 A
∆Uw = R ⋅ Iw − X ⋅ I b
∆U b = X ⋅ Iw + R ⋅ Ib
The voltage drops ∆U have to be calculated for all the three “sections” in the equivalent
circuit.
′
UA = U Q − ∆U