NOTES:

01. ALL EARTH FILLING BELOW FLOOR & TRENCH SHOULD BE


WELL COMPACTED SALT FREE FILL .
02. POLYTHENE SHEET TO BE PROVIDED OVER COMPACTED FILL
BEFORE PLACING ANY CONCRETE.
03. ALL TRENCH FLOORS, WALLS, & PLINTH FLOOR LEVEL
TO BE REINFORCED WITH A-393 MESH (BRC).
04. ALL ALUMINIUM LOUVERED DOORS SHOULD BE AS PER
DEWA's SPECIFICATION AND STANDARDS.
WALL 05. THE DOOR SHALL HAVE PAD LOCKING ARRANGEMENT TO SUIT
CHEQ'D PLATE DEWA's STANDARD PAD LOCK.
06. EACH CHEQURED PLATES AREA SHALL NOT
+ 0.15 SSFFL EXCEED 3600 SQ. CM.
07. ALL CHEQURED PLATES SHALL HAVE SUITABLE
LIFTING HOOKS/KEYS ARRANGEMENT.
08. ALL CHEQURED PLATES, COVERS TO BE MINIMUM 6 mm THICK,
CHANNEL HOT DIP GALVANISED SUITABLY STRENGTHENED IN CENTRE
TO AVOID ANY DEFLECTION. TRENCH COVERS, SIDE SUPPORTS
TO BE 40mm x 40mm MS ANGLE WITH 13 mm x 6 mm EDGE KERB.
PE
OPENING SLO 09. THE SHADED AREA SHOWS CHEQURED PLATE TO BE
PLACED OVER CHANNEL .
10. CHANNEL AREAS MARKED CHEQURED PLATES ARE NOT
TO BE PROVIDED.
P.C.C 11. ALL TRENCH TURNINGS, INTERSECTION SHALL HAVE A RADIUS OF
SECTION X-X 45 cm AT LOWER HALF DEPTH.
12. ALL INTERNAL WALL OF SUBSTATION SHALL BE PLASTERED AND
PAINTED WITH APPROVED WHITE EMULSION PAINT. THE
EXTERNAL SURFACE SHALL BE PLASTERED, PAINTED, TREATED
IN THE SAME MANNER AS THE EXTERNAL SURFACE OF
THE BUILDING .
13. THIS LAYOUT IS BASED ON THE EQUIPMENT PRESENTLY
DOOR AVAILABLE WITH US, YOU MIGHT BE ASKED TO CARRY OUT
SLIGHT MODIFICATION, SHOULD THE EQUIPMENT AVAILABLE
AT THE SAME TIME OF COMMISSIONING OF YOUR
13mm X6mm FLAT BAR 6 mm th HOT DIP GALVENISED
WELDED TO ANGLE CHEQUERED PLATE COVER SUBSTATION DIFFER .
FOR DETAILS REFER 14. THE WALLS EXPOSED TO TRAFFIC SHALL BE PROTECTED BY
DETAILS Z-Z FFL
10 cm Dia.1Mts. HIGH G.I. REMOVABLE PIPES PAINTED IN RED & WHITE.
CHEQ'D PLATE 15. THE ROOF SHALL BE RCC SLAB & SHALL BE PANTED WITH THE SAME
25mmX25mmX3mm PAINT OF THE INTERNAL WALLS.
ANGLE WELDED TO
CHEQUERED PLATE 16. THE FIXED ALU. LOUVERS SHALL BE OF THE SAME TYPE / DESIGN
COVER ON TWO SIDES AS THE ALU. LOUVRED DOORS.
60mmX60mmx6mm
EDGE ANGLE
17. FIRE FIGHTING / DETECTING SYSTEM OR ANY OTHER
SERVICES SHALL NOT BE INSTALLED INSIDE SUBSTATION ROOM.
T10 ANCHOR WELDED
TO ANGLE @300C/C 18. SUBSTAION FLOOR TO BE SAND CEMENT NET FINISHING ONLY.
19. CROSS CHECK THIS DRAWING WITH YOUR PROJECT DETAIL
DRAWING IN CASE OF ANY DISCREPANCIES. PLEASE INFORM US
DETAIL Z-Z (TYPICAL SECTION) WITH IN TWO WEEKS FOR REVISION (IF REQUIRED).
20. ALL INTERNAL WIRING WITHIN SUBSTATION ROOM SHALL BE
CONCEALED TYPE ENSURING FIRE SAFETY.
SECTION A-A ELECTRICAL DETAILS
SYMBOL DESCRIPTION MOUNTING HEIGHT
FROM F.F.L.
FLOURESCENT
TUBE 280CM/9'-2"
25 mm DIA LIFTING HOLE 4'-0 LONG
CHEQURED PLATE COVER S.P SWITCH 137CM/4'-6"

13A SWITCHED SOCKET 46CM/1'-6"


R.T.U.
MCB DISTRIBUTION
BOARD WITH
30 Amp SPN
150CM/5'-0"
ISOLATOR
UP TO
SWITCHGEAR (TO BE CONNECTED
0.60 OPENING AT TO CONSUMER LV DB)
CHANNEL BASE LEVEL

D1 = 305X275 ALL LOUVERED DOOR

DOOR DETAILS REF.


DETAIL OF LIFTING HOLE
(2 NO'S ON EACH
DrG No. P-DS/DOOR/01/96 "B"
CHEQURED PLATE) DrG No. P-DS/DOOR/02/96 "A"
NO PARKING SIGN IS TO BE PROVIDED
INFRONT OF S/S . DOOR (BY PARTY)
+ 0.15 SSFFL.

Rev. Description Date Sign.


X PCC KERB EXPO 2020
D1 COVER HEAVY DUTY
DUBAI, UNITED ARAB EMIRATES

8"THK BLOCK WORK


CABLES 2

X 30N/MM
PC CONCRETE

T T FLOOR AT 2M C/C
+ 0.00FFL.
PLAN POLYTHENE SHEET
Channel width
COMPACTED DESIGN BY ABD TITLE. 11-6.6/0.4kV S/STN. For bldg. for
EARTH
SECTION T-T DRAWN BY NASEER EMPOWER
APPROVED BY ON PLOT NO. 592-639
DATE 28-01-2019 AT MARSA DUBAI.( SS18580)
DRG.NO. REV.
SCALE: 1:75
SHEET NO: 1 OF 1 13240-2019